ATTACHMENT #1

PHOTOGRAPH

DOCUMENTATION

Admin hallway painted cement-like ceiling tile has visible mold growth

Admin hallway ceiling plenum duct insulation has visible surface mold growth

Admin hallway ceiling air supply vent has visible surface mold growth

Admin hallway ceiling plenum pipe insulation has visible

Admin hallway painted cement-like ceiling tile has

Admin h a l l wa y ceiling plenum pipe insulation has visible

Admin hallway ceiling plenum pipe insulation has visible surface mold growth

Office 7 ceiling plenum was relatively clean and dry

Admin hallway ceiling plenum- back of ceiling tile has mold/debris present

Women restroom painted cement-like ceiling tile has visible mold growth

Admin hallway ceiling plenum- back of ceiling tile has mold/debris present

Women’s restroom painted cement-like ceiling tile has

Women’s restroom ceiling air vent has visible particulate and mold growth

Room 41 main floor larva room food prep creates dust that lands on surfaces and provides a food source for mold growth

Women restroom painted cement-like ceiling plenum has heavy particulate on top of the ceiling tile

Room 41 painted cement-like ceiling tile has imbedded mold growth that did not wipe off.

Men’s restroom painted cement-like ceiling tile has visible Room 41 metal ducts are rusted mold growth

Room 41 ceiling plenum space –top of ceiling tile was wet and has microbial growth

Room 41 ceiling plenum space –pipe is un-insulated and corroded

Room 41 ceiling plenum space –top of ceiling tile has debris build-up.

Room 41 ceiling plenum space –un-insulated pipe has microbial growth

Room 41 ceiling plenum space –top of ceiling tile has debris build-up.

Room 41 ceiling plenum space –un-insulated pipe has microbial growth and condensation on the surface.

Room 41 ceiling plenum space insulated duct has

Room 3 ERF ceiling plenum space has apparent rodent droppings

Room 3 ERF ceiling tile metal tracking and painted cement-like ceiling tile has visible surface mold growth.

Room 3 ERF outside Room 1 Knock Down Room has mold on lower painted cinder block wall

Room 3 ERF ceiling plenum space has apparent rodent droppings

Room 1 Knock-Down Room has embedded mold growth on painted vinyl wall panels

Room 1 Knock-Down Room has embedded mold growth on painted vinyl wall panels

Room 1 Knock-Down Room upper wall area-embedded mold growth on painted vinyl wall panels

Room 41 ceiling plenum space has mold on insulated piping

Room 3 ERF ceiling has visible mold

Condensation drain line from wash room is draining onto Boiler Room floor instead of being routed to a floor drain

The lower wallboard wall of the Boiler Room was found wet and has mold growth behind the vinyl base cove and slightly above.

Water damage is occurring as a result of a condensation line draining onto the Boiler Room floor

The lower wall of the Boiler Room was wet and mold growth was found behind the vinyl base cover

Metal Ducting insulated duct un-insulated pipe Air register plenum space Ceiling tile

Room #41 Admin hallway

Ceiling tile

Women’s

Restroom

Ceiling/wall

Knock down room

Mold on walls

Air register

Boiler room ERF Room#3