QUESTIONS AND ANSWERS AG-1681-S-17-0036 08/04/2017

1. Specifications call out for Room Signs? Is that just the Bathrooms?

Just the bathrooms, mens/womens visitor area and the locker room is unisex

2. Area 102c Vestibule/Ramp is shaded a different color and the finish schedule call for a walk off matt is this correct? If yes do you have a specification?

A walk off mat is correct attached is the Tech Data sheet, Tweed Brown is the color.

This is acceptable or an approved equal.

1. What is the flooring in the base bid? The finish schedule calls for Conference room Carpet and kitchen/break VCT. The plans don’t show how much VCT?

No exact dimensions, but it would be just to replace the existing tile with VCT in the kitchen/break room. It is just in front of the cabinets and refrigerator. See attached picture. Approximate area would be 10’ x 4’ (40 SF).

May 2015 • www.matsinc.com • 1.800.MATS.INC

Mats Inc. Technical Data for Supreme Nop

Product Description Material 100% solution-dyed UV stabilized polypropylene fibers

Backing Eco Di elephant back high density rubber

Roll Sizes 6'7" x approximately 101'8”; 13'2" x approximately 101'8”

Custom Sizes 6'7" x custom lengths up to 101'8”; 13'2" x custom lengths up to 101'8”

Technical Specifications Test Requirement Supreme Nop

Product Dimensions

Pile height ISO 1776 In inches 3/16"

Total height ISO 1776 In inches 7/16"

Pile weight ISO 8543 In ounces per square yard 42.8 oz/sq yd

Total weight ISO 8543 In ounces per square yard 73 oz/sq yd

Safety

Surface flammability ASTM D2859

CPSC FF 1-70

Test specimen must be greater than 1" in at least 7 of 8 specimens tested

Passes

Performance

Static electrical propensity

EN 1815 Antistatic: less than 2 kilovolts (kV) < 2 kV

Color Fastness

To light ISO 105 B02 1 = considerable change; 6 = negligible or no change

≥ 6

To water ISO 105 E01 1 = considerable change; 6 = negligible or no change

To shampoo BS 1006 1 = considerable change; 6 = negligible or no change

To rubbing wet and dry ISO 105 x 12 1 = considerable change; 6 = negligible or no change

Wet: 4 - 5; Dry: 4 -

LEED

MR Credit 4 LEED-NC v. 3 For 1 - 2 points: $ value of all materials = min. average 10% recycled content

15% recycled (post-consumer)

IEQ Credit 4.1 LEED-NC v. 3 For 1 point: low-emitting adhesive with a VOC of 50 g/L or less for indoor carpet adhesive

Multi-Bond VOC: 0 g/L

IEQ Credit 4.3 LEED-NC v. 3 For 1 point: low-emitting flooring per GreenLabelPlus or FloorScore™

GreenLabelPlus certified

IEQ Credit 5 LEED-NC v. 3 For 1 point: semi-permanently installed entrance system at least ten feet in length and maintained on a weekly basis by a contracted service organization

Supreme Nop is designed for semi-permanent installation.

QUESTIONS AND ANSWERS AG-1681-S-17-0036 080317