POLE WIRE C.B. LOAD LOAD C.B. WIRE POLE

NO. SIZE AMP/P TOTAL TYPE A B TYPE TOTAL AMP/P SIZE NO.

1A 14 20/1 Kitchen outlets 1000 A 2000 A 1000 Outlets and lights 15/1 14 2A

1B 14 20/1 Kitchen outlets 1000 A 2000 A 1000 Outlets and lights 15/1 14 2B

3A 14 20/1 Clothes washer 1000 A 2000 A 1000 Outlets and lights 15/1 14 4

3B 14 20/1 Bath Outlets 1000 A 2000 A 1000 Outlets and lights 15/1 14 6

5 14 20/1 Kitchen DC 1000 C 2000 A 1000 Outlets and lights 15/1 14 8

7 14 15/1 Dryer 1000 A 2000 A 1000 Refrigerator 15/1 14 10

9 14 15/1 Furnace 1000 B 2000 C 1000 Smoke detectors 15/1 14 12

11 14 15/1 Outlets and lights 1000 A 1000 C 14

13 C C 16

15 C C 18

17 C C 20

19 C C 22

21 C C 24

23 C C 26

25 C C 28

27 C C 30

29 C C 32

31 C C 34

33 C C 36

35 C C 38

37 C C 40

CONNECTED LOAD PER PHASE VA 8000 7000

CONNECTED LOAD PER PHASE A 67 58 Sled Springs Bunkhouse One

LOAD SUMMARY CONN. DEMAND DEMAND DATE: 6/5/2014

VA FACTOR VA VOLTS: 120/240V,1PH,3W PANEL

TYPE "A": RECEPTACLES (FIRST 10KVA) 10000.00 100% 10000.00 MAIN C.B.: 100A

TYPE "A": RECEPTACLES (OVER 10KVA) 2000.00 50% 1000.00 BUS: 100 AMP A

TYPE "B": NON-CONTINUOUS LOADS 1000.00 100% 1000.00 POLES: 12

TYPE "C": CONTINUOUS LOADS 2000 125% 2500 MOUNTING: Recessed

TOTAL DEMAND LOAD VA 15000 14500 AIC RATING:

TOTAL DEMAND LOAD AMPS 60 SUBFEED C.B: NA

REV 8/30/07

Enter data in non green areas only

MINIMUM SERVICE SIZE 75.52 AMPS

LOCATION:

LOAD VA

1 14 20/1 Kitchen outlets 1000 A 2000 A 1000 Bathroom 20/1 14 2

3 14 20/1 Kitchen outlets 1000 A 2000 B 1000 Furnace 15/1 14 4

5A 14 20/1 Clothes washer 1000 A 2000 A 1000 Bedroom 15/1 14 6

5B 14 20/1 Dosing tank pump 1000 B 2000 A 1000 Bedroom 15/1 14 8

7 14 20/1 Kitchen DC 1000 C 2000 A 1000 Dryer 15/1 14 10A

9 14 15/1 Range 1000 A 2000 A 1000 Refrigerator 15/1 14 10B

11A 14 15/1 Range 1000 A 2000 C 1000 Smoke detectors 15/1 14 12A

11B 14 15/1 Bedroom 1000 A 2000 A 1000 Bedroom 15/1 14 12B

13 C C 14

15 C C 16

17 C C 18

19 C C 20

21 C C 22

23 C C 24

25 C C 26

27 C C 28

29 C C 30

31 C C 32

33 C C 34

35 C C 36

37 C C 38

CONNECTED LOAD PER PHASE VA 8000 8000

CONNECTED LOAD PER PHASE A 67 67 Sled Springs Bunkhouse Two

LOAD SUMMARY CONN. DEMAND DEMAND DATE: 6/5/2014

VA FACTOR VA VOLTS: 120/240V,1PH,3W PANEL

TYPE "A": RECEPTACLES (FIRST 10KVA) 10000.00 100% 10000.00 MAIN C.B.: 100A

TYPE "A": RECEPTACLES (OVER 10KVA) 2000.00 50% 1000.00 BUS: 100 AMP A

TYPE "B": NON-CONTINUOUS LOADS 2000.00 100% 2000.00 POLES: 12

TYPE "C": CONTINUOUS LOADS 2000 125% 2500 MOUNTING: Recessed

TOTAL DEMAND LOAD VA 16000 15500 AIC RATING:

TOTAL DEMAND LOAD AMPS 65 SUBFEED C.B: NA

REV 8/30/07

Enter data in non green areas only

MINIMUM SERVICE SIZE 80.73 AMPS

1 12 20/1 Meeting Room and Exterior Lights 1000 C 2000 C 1000 Bed, Bath, Storage, Kitchen Lights 20/1 12 2

3 12 20/1 Meeting Room Outlets 1000 C 2000 C 1000 Kitchen Outlets 20/1 12 4

5 12 20/1 Kitchen Outlets 1000 C 2000 C 1000 Bed, Bath Outlets 20/1 12 6

7 12 20/1 Range Hood 1000 C 2000 C 1000 Not Used? 20/1 12 8

9 12 20/1 Spare 1000 C 2000 C 1000 Spare 20/1 12 10

11 10 30/1 Not Used C 1000 C 1000 Spare 20/1 12 12

13 10 Not Used C 1000 C 1000 Spare 20/1 12 14

15 -- -- Blank C C Blank -- -- 16

17 -- -- Blank C C Blank -- -- 18

19 C C 20

21 C C 22

23 C C 24

25 C C 26

27 C C 28

29 C C 30

31 C C 32

33 C C 34

35 C C 36

37 C C 38

39 C C 40

41 C C 42

CONNECTED LOAD PER PHASE VA 7000 5000

CONNECTED LOAD PER PHASE A 58 42 Sled Springs Mess Hall

LOAD SUMMARY CONN. DEMAND DEMAND DATE: 6/5/2014

VA FACTOR VA VOLTS: 120/240V,1PH,3W PANEL

TYPE "A": RECEPTACLES (FIRST 10KVA) 100% MAIN C.B.: 100A

TYPE "A": RECEPTACLES (OVER 10KVA) 50% BUS: 100 AMP A

TYPE "B": NON-CONTINUOUS LOADS 100% POLES: 18

TYPE "C": CONTINUOUS LOADS 12000 125% 15000 MOUNTING: Recessed

TOTAL DEMAND LOAD VA 12000 15000 AIC RATING: 22,000

TOTAL DEMAND LOAD AMPS 63 SUBFEED C.B: NA

REV 8/30/07

Enter data in non green areas only

MINIMUM SERVICE SIZE 78.13 AMPS

1 100 Main C 1000 A 1000 Outlets and lights 20/1 12 2

3 Main C 1000 A 1000 Outlets and lights 20/1 12 4

5 Blank C 1000 A 1000 Outlets and lights 20/1 12 6

7 Blank C 1000 A 1000 Outlets and lights 20/1 12 8

9 Blank C 1000 A 1000 Outlets and lights 20/1 12 10

11 Blank C 1000 A 1000 Outlets and lights 20/1 12 12

13 Blank C C Blank 14

15 Blank C C Blank 16

17 Blank C C Blank 18

19 Blank C C Blank 20

21 C C 22

23 C C 24

25 C C 26

27 C C 28

29 C C 30

31 C C 32

33 C C 34

35 C C 36

37 C C 38

39 C C 40

41 C C 42

CONNECTED LOAD PER PHASE VA 3000 3000

CONNECTED LOAD PER PHASE A 25 25 Sled Springs Old Bunkhouse

LOAD SUMMARY CONN. DEMAND DEMAND DATE: 6/5/2014

VA FACTOR VA VOLTS: 120/240V,1PH,3W PANEL

TYPE "A": RECEPTACLES (FIRST 10KVA) 6000.00 100% 6000.00 MAIN C.B.: 100A

TYPE "A": RECEPTACLES (OVER 10KVA) 50% BUS: 100 AMP A

TYPE "B": NON-CONTINUOUS LOADS 100% POLES: 20

TYPE "C": CONTINUOUS LOADS 125% MOUNTING: Recessed

TOTAL DEMAND LOAD VA 6000 6000 AIC RATING:

TOTAL DEMAND LOAD AMPS 25 SUBFEED C.B: NA

REV 8/30/07

Enter data in non green areas only

MINIMUM SERVICE SIZE 31.25 AMPS

1 12 20/1 Main Lights 1000 A 2000 A 1000 Outlets 20/1 12 2

3 Blank C C Blank 4

5 Blank C C Blank 6

7 Blank C C Blank 8

9 Blank C C Blank 10

11 Blank C C Blank 12

13 Blank C C Blank 14

15 Blank C C Blank 16

17 Blank C C Blank 18

19 Blank C C Blank 20

21 C C 22

23 C C 24

25 C C 26

27 C C 28

29 C C 30

31 C C 32

33 C C 34

35 C C 36

37 C C 38

39 C C 40

41 C C 42

CONNECTED LOAD PER PHASE VA 2000

CONNECTED LOAD PER PHASE A 17 Sled Springs PT Room

LOAD SUMMARY CONN. DEMAND DEMAND DATE: 6/5/2014

VA FACTOR VA VOLTS: 120/240V,1PH,3W PANEL

TYPE "A": RECEPTACLES (FIRST 10KVA) 2000.00 100% 2000.00 MAIN C.B.: 100A

TYPE "A": RECEPTACLES (OVER 10KVA) 50% BUS: 100 AMP A

TYPE "B": NON-CONTINUOUS LOADS 100% POLES: 20

TYPE "C": CONTINUOUS LOADS 125% MOUNTING: Surface

TOTAL DEMAND LOAD VA 2000 2000 AIC RATING:

TOTAL DEMAND LOAD AMPS 8 SUBFEED C.B: NA

REV 8/30/07

Enter data in non green areas only

MINIMUM SERVICE SIZE 10.42 AMPS

1 12 20/1 Main Lights 1000 C 2000 A 1000 Office 2 Outlets 20/1 12 2

3 12 20/1 Office 1 Outlets 1000 A 2000 A 1000 Office 1 Outlets 20/1 12 4

5 12 20/1 Office 1 Outlets 1000 A 2000 A 1000 East Wall Shop Outlets 20/1 12 6

7 20/1 Spare 1000 A 2000 A 1000 North Wall Shop Outlets 20/1 12 8

9 Blank C C Blank 10

11 Blank C C Blank 12

13 Blank C C Blank 14

15 Blank C C Blank 16

17 Blank C C Blank 18

19 Blank C C Blank 20

21 C C 22

23 C C 24

25 C C 26

27 C C 28

29 C C 30

31 C C 32

33 C C 34

35 C C 36

37 C C 38

39 C C 40

41 C C 42

CONNECTED LOAD PER PHASE VA 4000 4000

CONNECTED LOAD PER PHASE A 33 33 Sled Springs Warehouse

LOAD SUMMARY CONN. DEMAND DEMAND DATE: 6/5/2014

VA FACTOR VA VOLTS: 120/240V,1PH,3W PANEL

TYPE "A": RECEPTACLES (FIRST 10KVA) 7000.00 100% 7000.00 MAIN C.B.: 100A

TYPE "A": RECEPTACLES (OVER 10KVA) 50% BUS: 100 AMP A

TYPE "B": NON-CONTINUOUS LOADS 100% POLES: 20

TYPE "C": CONTINUOUS LOADS 1000 125% 1250 MOUNTING: Recessed

TOTAL DEMAND LOAD VA 8000 8250 AIC RATING: 22,000

TOTAL DEMAND LOAD AMPS 34 SUBFEED C.B: NA

REV 8/30/07

Enter data in non green areas only

MINIMUM SERVICE SIZE 42.97 AMPS

BunkhouseOneMasterPanel
BunkhouseTwoMasterPanel
MessHallMasterPanel
OldBunkhouseMasterPanel
PTRoomMasterPanel
WarehouseMasterPanel

File details come from the government source that posted it. Updated .