Text version
MALHEUR NATIONAL FOREST
BLUE MOUNTAIN RANGER DISTRICT
BLUE MOUNTAIN WORK CENTER
WASTEWATER TREATMENT
Index to Plans
Description
DRAWINGS FOR PROPOSED
TITLE SHEET
NOTES
SITE PLAN
WASTEWATER TREATMENT LAYOUT
Page #
WASTEWATER TREATMENT DETAILS
PIPING DETAILS
ESTIMATE OF QUANTITIES
SEPTIC TANK DETAILS
MISC. DETAILS
FOREST SERVICE
U.S. DEPARTMENT OF AGRICULTURE
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
BMWC WASTEWATER TREATMENT
ESTIMATE OF QUANTITIES
ABBREVIATIONS GENERAL CIVIL NOTESDESIGN NOTES
U.S. DEPARTMENT OF AGRICULTURE
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
BMWC WASTEWATER SYSTEM
NOTES
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
BMWC WASTEWATER SYSTEM
SITE PLAN
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
BMWC WASTEWATER TREATMENT SYSTEM
SEPTIC TANK DETAILS
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
PIPING DETAILS
AdvanTex AX100 System
Individual Vent System
Air Inlet
(see detail sheet)
AX100 Filter Pod
Vent Fan Assembly
Recirculation Tank
30"DIA. PVC Access Riser with
Recirculating Ball Valve
(MM4FRP)
30"DIA. PVC Access Riser with
Duplex Pumping Package Unit
1.5"DIA. Transport Pipe
4"DIA. Filtrate Return Line
Discharge
Influent
Expected Flows
Expected Influent Quality Grease & Oil: 20 mg/L BOD: 150 mg/L TSS: 40 mg/L TKN: 65 mg/L
Typical Effluent Quality BOD: < 20 mg/L TSS: < 20 mg/L TN: < 25 mg/L *
Recirculation Tank is typically sized to equal 80% of peak flow.
* Non Nitrogen Sensitive Applications
Design Notes
2,500 gpd 5,000 gpd
Q Q ave.
peak
Consult with Orenco Systems, Inc. for applications where expected influent quality and/or targeted treatment goals vary from those stated above.
For engineer drawing and information contact Orenco Systems, Inc.
For instructions on maximizing nitrogen reduction, contact Orenco Systems Engineering.
General Notes
FOREST SERVICE
U.S. DEPARTMENT OF AGRICULTURE
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
ADVANTEX SAMPLE LAYOUT
È
AdvanTex AX100 System
Ventilation Details
FOREST SERVICE
U.S. DEPARTMENT OF AGRICULTURE
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
WASTEWATER TREATMENT DETAILS
PACIFIC NORTHWEST REGION
MAL-949
BLUE MOUNTAIN RANGER DISTRICT
NATIONAL FOREST
MALHEUR
MISCELLANEOUS DETAILS
| 1 |
| 2 |
| 3 |
| 4 |
| 5 |
| 6 |
| 7 |
| 8 |
| 9 |
File details come from the government source that posted it. Updated .