Attachment 3 Solicitation No.: AG-0261-S-16-0043
W.H.
M
W.H.
M
J
JJ
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
EXISTING METERMAIN TO REMAIN WITH SERVICE,
FEEDER, AND GROUNDING
EXISTING LOAD CENTER/ PANELBOARD TO REMAIN
WITH BREAKERS AND SOME LOADS, SEE PANEL A
SCHEDULE AND NOTES
EXISTING TELECOMMUNICATIONS JUNCTION BOX TO
REMAIN
REMOVE FLUSH MOUNTED LOAD CENTER/
PANELBOARD, REPAIR WALL EXCEPT PANELING
REPAIR OR REPLACEMENT AT THIS LOCATION BY
OTHERS WHICH MAY OCCUR DURING OR AFTER THIS
CONTRACT
SAFETY SWITCH TO REMAIN, SEE FURNACE PHOTO
JUNCTION BOX TO REMAIN AND BE REUSED
REMOVE BUZZER AND RELATED EQUIPMENT
REMOVE SMOKE ALARM
SPEAKER TO REMAIN, INCLUDING ALL RELATED
CABLING FROM THE BUILDING NEXT DOOR
EXHAUST FAN/LIGHT COMBINATION, REPAIR CEILING
TO FIT NEW EXHAUST FAN
EXISTING SURFACE MOUNTED FLUORESCENT
LUMINAIRE TO REMAIN
EXISTNG LUMINAIRE TO REMAIN: SURFACE AND
WALL MOUNT
REMOVE AND SALVAGE FOR REUSE, SURFACE
MOUNTED FLUORESCENT LUMINAIRE
REMOVE LUMINAIRE: SURFACE AND WALL MOUNT
REMOVE SWITCH
REMOVE RECEPTACLE
REMOVE DATA OUTLET, 2 OR MORE PORTS
REMOVE TELEPHONE OUTLET
ELECTRIC WATER HEATER, 120 VAC, 1.5KW, CORD
AND PLUG CONNECTED, TO REMAIN
INTAKE VENT TO REMAIN
EXHAUST VENT TO REMAIN
WALL CONSTRUCTION: WOOD SLATS, WIRE AND
PLASTER OVER STUDS, MAY ALSO HAVE GLUED ON
PANELING
WALL CONSTRUCTION: VARIES, PLASTER,
SHEETROCK, PANELING OR A COMBINATION OVER
BRICK, OFTEN GLUED
WALL CONSTRUCTION: SHEETROCK OVER STUDS,
MAY ALSO HAVE GLUED ON PANELING
S
P
EXISTING DEVICE BOX EMBEDDED IN THE BRICK TO
REMAIN, TO BE REWIRED AND NEW LUMINAIRE
INSTALLED
REMOVE SURFACE MOUNTED CONDUIT OR
WIREMOLD AND REPAIR MOUNTING HOLES IN BRICK,
PANELING, OR, PLASTER AND SHEETROCK FINISHES
REMOVE SURFACE MOUNTED CONDUIT OR
WIREMOLD GOING UP WALL FROM REMOVED DEVICE
AND REPAIR MOUNTING HOLES IN BRICK, PANELING,
OR, PLASTER AND SHEETROCK FINISHES
SWITCH IS SURFACE MOUNTED LOW ON WALL IN
WIREMOLD THAT FEEDS RECEPTACLES BEING
REMOVED
KEYED FIXTURE WITH SWITCH AND RECEPTACLE
BELOW (2 GANG BOX, SURFACE MOUNT FED FROM
ABOVE IN MC CABLE TO BE REMOVED
BATH FAN WITH BUILT IN LIGHT TO BE REMOVED,
CEILING TO BE REPAIRED TO FIT REPLACEMENT FAN,
THE SEPARATE LIGHT TO REMAIN SHALL HAVE A
NEW 6-INCH ROUND FROSTED, UV-STABILIZED
ACRYLIC OR LEXAN GLOBE INSTALLED
TWO RECEPTACLES IN A DOUBLE GANG RECESSED
BOX, BOX CANNOT BE REUSED AS HEIGHT DOES NOT
MEET ACCESSIBILITY STANDARDS.
REMOVE TIMER SWITCH IN THE SAME BOX FOR THE
PORCH LUMINAIRE
REMOVE RECESSED LOAD CENTER, BRANCH
CIRCUITS AND FEEDER, WOOD PANELING
REPLACEMENT BY OTHERS AND MAY NOT HAPPEN
DURING CONTRACT
FURNACE WIRING AND DISCONNECT TO REMAIN,
REPLACE CIRCUIT, SEE PHOTO
AC CONDENSING UNIT TO REMAIN WITH LOW
VOLTAGE CONTROL LINES, LINE VOLTAGE LINES
SHALL BE REMOVED AND REPLACED, SEE PHOTO
EXISTING ATTIC ACCESS, SIZE IS NOT SHOWN
CORRECTLY ON DRAWINGS, THE SMALLEST IS
21"x12" WHILE THE LARGEST IS 25"x12.75", IT IS
ALLOWED TO REMAKE ANY ACCESS LARGER
TWO RECEPTACLES IN A DOUBLE GANG BOX,
CONDUIT AND BOX MAY REMAIN FOR REUSE
THERMOSTAT AND LOW VOLTAGE WIRE TO FURNACE
AND AC UNIT TO REMAIN
CONDUIT TO REMAIN, REWORK BUILDING ENTRY
LOCATION, SEE PHOTO
SPEAKER AND RELATED WIRING TO REMAIN, FED
FROM OTHER BUILDING
INDICATES ENTIRE ROOM OR HALL HAS PANELING
ON THE WALLS, IF WITH AN ARROW POINTING TO A
WALL THEN JUST THAT WALL IS PANELED
EXPOSED DAMAGED CEILING TILE TO BE REPAIRED
BY OTHERS
S
P
S
NOTE: REWORK THE GROUNDING ELECTRODE CONDUCTOR (GEC)
TO THE INTERIOR METAL WATER SERVICE (LIKELY PROVIDED
NOW THROUGH THE INTERIOR PANEL TO BE REMOVED). THE GEC
SHALL BE ROUTED TO ENTER BUILDING NEAR AC CONDENSER
CONDUIT TO PROVIDE PROTECTION AND HIDE THE CONDUCTOR.
BUZZER WITH COVER
OFF
REPLACE GLOBE PER
NOTES
SPACE FOR FUTURE
UPS
COMMUNICATIONS GENERAL NOTES
1. DATA AND VOICE HORIZONTAL CABLING AND OUTLETS SHALL ALL BE REMOVED. DATA FIBER
OPTIC AND VOICE BACKBONE CABLES SHALL REMAIN INCLUDING CONNECTIONS.
2. SEE SPECIFICATIONS FOR NEW REQUIREMENTS, INCLUDING GROUNDING AS NOTED IN SECTION
270526.
3. DOCUMENT THE EXISTING PATCH PANEL PHONE OR VOICE CONNECTION SETUP TO HELP THE
FOREST SERVICE IN RECONNECTING PHONE LINES. TO PROPER LOCATIONS. THIS PATCH PANEL
WILL SERVE AS CONNECTION TO EXISTING PHONE OR VOICE BACKBONE ONLY.
DOCUMENTATION MAY BE ON BUILDING FLOOR PLAN OR SIMPLY NOTING LEGIBLY (HAND
WRITING ALLOWED) ON 8.1x11 SHEETS OF PAPER FOR EACH PATCH PANEL PORT.
3.1. INDICATE IF PORT USED OR UNUSED. IF UNUSED NO OTHER DOCUMENTATION NEEDED.
3.2. INDICATE IF PORT IS VOICE OR DATA. IF DATA, NO OTHER DOCUMENTATION REMOVE
CONNECTION.
3.3. INDICATE THE ROOM NUMBER SERVED (SEE RECEPTACLE PLAN FOR ROOM NUMBERS) AND
WHICH WALL THE WORK AREA PORT WAS ON (NORTH, SOUTH, EAST, OR WEST) . IF TWO
WORK AREA VOICE PORTS ARE ON THE SAME WALL, ADD A SECOND DIRECTION SUCH AS:
PORT 24-USED-VOICE-ROOM 15-NORTH WALL-EAST OUTLET.
3.4. DOCUMENT EVERY PATCH CABLES PORT-TO-PORT CONNECTION SUCH AS: PATCH CABLE
PORT 24 TO HUB 5, OR PATCH CABLE PORT 7 TO PORT 29.
3.5. WHERE THE PORT IS DIRECTLY CONNECTED TO THE PUNCH DOWN BLOCKS, DETERMINE
AND PERMANENTLY RECORD THE 4 DIGIT EXTENSION DIRECTLY ON THE PATCH PANEL
ABOVE THE PORT.
3.6. PROVIDE 2 COPIES OF THE DOCUMENTATION TEMPORARILY MOUNTED TO WALL IN
COMMUNICATIONS CLOSET AND A 3RD COPY PROVIDED TO THE CONTRACTING OFFICER.
4. PRESERVE ALL COMMUNICATIONS WIRING FROM PATCH PANEL TO THE PUNCH DOWN BLOCKS
AND ALL COMMUNICATIONS WIRING COMING INTO THE BUILDING AND LANDING IN LIU OR PUNCH
DOWN BLOCKS. IF ANY EXTERNAL WIRING TERMINATES DIRECTLY IN THE PATCH PANEL, IT
SHALL REMAIN.
5. AFTER DOCUMENTATION, SALVAGE ALL PATCH CORDS FOR REUSE BY OTHERS. FIBER OPTIC
PATCH CORD FORM THE LIU TO THE HUB SHALL REMAIN CONNECTED.
6. AFTER DOCUMENTATION, REMOVE ALL INTERIOR WIRING FROM PATCH PANEL TO WORK AREA
OUTLETS.
7. REARRANGE EQUIPMENT ADDING NEW EQUIPMENT AS CALLED FOR. CONNECT NEW WORK
AREA OUTLETS AND DOCUMENT AS PER SPECIFICATIONS LEAVING EXCESS CABLE BEHIND OR
TO THE SIDES OF THE RACK IN A VERTICAL CABLE MANAGER.
8. PROVIDE ADDITIONAL PATCH CABLES PER SPECIFICATIONS.
9. FINAL PATCHING/ACTIVATING PORTS AND ADDING PHONE LINES SHALL BE DONE BY OTHERS.
EXISTING METERMAIN TO REMAIN WITH SERVICE,
FEEDER, AND GROUNDING
EXISTING LOAD CENTER/ PANELBOARD TO REMAIN
WITH BREAKERS AND SOME LOADS, SEE PANEL A
SCHEDULE AND NOTES
EXISTING TELECOMMUNICATIONS JUNCTION BOX TO
REMAIN
SAFETY SWITCH TO REMAIN, SEE FURNACE PHOTO
NON-METALLIC SURFACE RACEWAY, PANDUIT
PAN-WAY T-45 SERIES WITH DIVIDER (INSTALL
COMMUNICATIONS IN LARGER CHANNEL)
INDICATES CONNECTION INTO WALL FOR
CONCEALED CIRCUIT FEED WHERE HOLLOW WALL
INDICATED, SOLID WALLS SHALL HAVE SURFACE
RACEWAY FEEDS FROM CEILING, AND IN ROOM 1
WEST WALL FEED SHALL BE CONCEALED IN THE
CABINET, SEE INSTALLATION NOTES
FAN - CEILING, OF TYPE SPECIFIED (SEE LIGHT
SCHEDULE)
SPEAKER TO REMAIN, INCLUDING ALL RELATED
CABLING FROM THE BUILDING NEXT DOOR
SMOKE ALARM, KIDDE I12040
CARBON MONOXIDE/SMOKE COMBINATION ALARM,
KIDDE KN-COSM-IBA
SALVAGED FLUORESCENT LUMINAIRE, TYPE "X":
SURFACE MOUNT
EXISTING FLUORESCENT LUMINAIRE TO REMAIN,
REWIRE
LUMINAIRE, TYPE "X": SURFACE AND WALL MOUNT
LUMINAIRE TO REMAIN: SURFACE AND WALL MOUNT
PIR OCCUPANCY SENSOR, CEILING MOUNTED, LINE
VOLTAGE, SMALL MOTION DETECTION, SET FOR 20
MINUTES AND WALK THROUGH, EXCEPT FOR HALL
SET FOR WALK THROUGH ONLY, AND BATHROOM
SET FOR 5 MINUTES AND WALKTHROUGH
PHOTO CONTROL, 120 VAC, WITH ADJUSTABLE
SHUTTER, WEATHER RESISTANT
SINGLE POLE
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX OR TYPE SHOWN MOUNT
ABOVE COUNTER TOP FOR COUNTER ACCESS
RECEPTACLE, GFCI PROTECTION PROVIDE BY
EXISTING BREAKER
WEATHER RESISTANT RECEPTACLE WITH GFCI
PROTECTION PROVIDED BY BREAKER AND WEATHER
PROOF COVER
RECEPTACLE, TWO DUPLEX IN A SINGLE DEVICE BOX
THE UPSTREAM ONE IS SURGE PROTECTED TYPE,
MOUNT FOR UNOBSTRUCTED ACCESS FOR RACK
MOUNTED EQUIPMENT
DATA OUTLET, TWO PORTS SEE SPECIFICATIONS
X-#
CIRCUIT TAG: "X" INDICATES PANEL, AND "#" IS THE
CIRCUIT NUMBER
BRANCH CIRCUIT: o - INDICATES GROUND, LONG LINE
- "NUETRAL" OR "GROUNDED CONDUCTOR" AND THE
SHORT LINE - "HOT" OR "LINE" CONDUCTORS
##" INDICATES UNUSUAL MOUNTING HEIGHT
a, b, c, ...
SMALL LETTERS INDICATE CONTROLLING DEVICES
AND CORRESPONDING CONTROLLED LUMINAIRES
INTAKE VENT TO REMAIN
EXHAUST VENT TO REMAIN
WALL CONSTRUCTION: WOOD SLATS, WIRE AND
PLASTER OVER STUDS, MAY ALSO HAVE GLUED ON
PANELING
WALL CONSTRUCTION: VARIES, PLASTER,
SHEETROCK, PANELING OR A COMBINATION OVER
BRICK, OFTEN GLUED
WALL CONSTRUCTION: SHEETROCK OVER STUDS,
MAY ALSO HAVE GLUED ON PANELING
S
C
M
S
A-1,3
A-2
A-4
A-12A-10
A-14
A-16
A-18
A-20
A-22
A-24
A-26
A-2
A-2
A-2
A-2
A-2
A-2
A-8
A-4
A-4
A-6
A-6
A-8
A-10
A-10
A-10
A-10
A-12
A-12
A-12
A-12
A-14
A-14
A-14
A-14
A-14
A-22
A-22
A-22
A-22
A-24 A-24
A-24
A-24 A-24
A-26
A-26
A-26
A-26
A-26 i i f f g g d d b a a a a
S1
F e
B
S
A A
M
P
P
M
M
M
S
S
S
C
B
S c
S c
M
M
M
M
M
S h
S h
S1A A k
S
TYPE DESCRIPTION MANUFACTURER MODEL # LAMPS MOUNTING
Qty
NOTES:
A DECORATIVE EXTERIOR WALL INCON LIGHTING 30211 9LED LED INCLUDED SURFACE/WALL 4
MOUNT TO EXISTING BOX WITH NEW CIRCUIT, SEE INSTALLATION NOTES
B CLOSE TO CEILING INCON LIGHTING 16111 13LED LED INCLUDED SURFACE/CEILING 2
P
KEYLESS LAMP HOLDER WITH
PULL CHAIN
ANY 13 WATT CFL SURFACE/CEILING 2
REUSE THE LAMP FROM THE TELECOMMUNICATIONS REMOVED LIGHT, THE OTHER LAMP
SHALL BE NEW
F EXHAUST FAN MARLEY 8060ES NOT APPLICABLE FLUSH/CEILING 1
REPLACES EXISTING FAN, REPAIR CEILING AS NEEDED, CONNECT TO DUCT TO EXTERIOR
S1 WALL PACK EXISTING SALVAGED EXISTING SURFACE/WALL 2
USE FIXTURE AS SPLICE BOX, DRILL HOLE THROUGH BRICK OR MORTAR FOR CIRCUIT FROM
ATTIC TO MOUNT AT LOCATION INDICATED, SEE PHOTOS
S2 1X4 FLUORESCENT EXISTING SALVAGED EXISTING SURFACE/CEILING 4
TOTAL 15
TYPE: EXISTING SQUARE D [QO-TYPE, 200 AMP, 30 CIRCUIT]
120/240 VAC
1 PHASE
FEEDER: EXISTING FROM 200 AMP METER MAIN
GROUNDING: #4 CU GRD TO WATER PIPES AND GROUND ROD OR
CONCRETE ENCASED ELECTRODE, SEE SPECIFICATIONS
CKT LOAD DESCRIPTION WATTS BREAKER AWG
LOAD (WATTS)
AWG BREAKER WATTS LOAD DESCRIPTION CKT
A B
AC CONDENSER
40 EX. 8
3760 12 20 EX 1260 RECEPTACLES-SOUTH WING SOUTH ROOM 2
3 2500 3040 12 20 EX 540 RECETPACLES-SOUTHWINGNORTHWEST ROOM WEST WALL 4
5 FURNACE 1500 QO120 12 1860 12 20 EX 360 RECEPTACLES-SOUTHWING NORTHWEST ROOM EAST COUNTER TOP 6
7 YARD GATE 1500 20 EX EX 1860 12 20 GFCI EX 360 RECEPTACLES-EXTERIOR AND BATHROOM 8
9 LIGHTS-NORTHWING QO115 14 900 12 20 EX 900 RECEPTACLES-MAIN AREA SOUTHWEST ROOM 10
11 LIGHTS-MAIN AREA QO115 14 900 12 QO120 900 RECEPTACLES-MAIN AREA SOUTHEAST ROOM 12
13 LIGHTS-SOUTHWING QO115 14 1080 12 QO120 1080 RECEPTACLES-MAIN AREA NORTHWEST ROOM 14
15 LIGHTS-EXTERIOR QO115 14 1500 12 QO120 1500 RECEPTACLES-TELECOM CLOSET 16
ALARM CIRCUIT (SMOKE AND CO)
Q0115 14 1500 12 QO120 1500 RECEPTACLE-WATER HEATER 18
19 1500 12 QO120 1500 RECEPTACLE-COUNTER ABOVE WATER HEATER 20
21 900 12 QO120 900 RECEPTACLES-MAIN AREA NORTHEAST ROOM 22
23 1080 12 QO120 1080 RECETPACLES-NORTHWING SOUTH ROOM 24
25 1080 12 QO120 1080 RECETPACLES-NORTHWING NORTH ROOM 26
27 #### 28
29 #### 30
CODE CALCULATED TOTAL LOAD (WATTS): LOAD PER PHASE: (WATTS)
11080 9880
A-13
A-5
A-13
A-13
A-13
A-13
A-11
A-9
A-9
A-11
A-11
A-11
A-11
A-11