COMMON WORK RESULTS FOR ELECTRICAL 260500-1

GENERAL SPECIFICATIONS

USDA FOREST SERVICE, R4

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Electrical equipment coordination and installation.

2. Grout.

3. Common electrical installation requirements.

1.2 SUBMITTALS

A. Product Data:

1. For any substitutions for equipment referred to by name in Division 26 specifications or the drawings.

1.3 QUALITY ASSURANCE

A. The installation shall conform to the 2014 Edition of the National Electrical Code (NFPA

70) and to the requirements specified herein.

B. The Contractor shall perform all work necessary and required to accomplish the task as detailed on the drawings and discussed in the installation notes. All work shall be done by a state licensed electrician.

1.4 MEASUREMENT AND PAYMENT

A. The work in this section, including all Division 27 Communications and incidentals in other electrical sections, shall be measured and paid for by the following method as shown in the Schedule of Items:

1. Electrical System - Lump Sum including full compensation for all demolition and installation labor, materials, and incidentals necessary to complete the work as shown on the drawings including all wiring, trenching, bedding, backfill, and all other incidentals necessary for a functional system.

PART 2 - PRODUCTS

2.1 PRODUCTS REFERRED TO BY NAME

A. The materials referred to by trade name, make, or catalog number on the drawings shall be regarded as establishing a minimum standard of quality; substitutions of equal or greater quality can be made by submitting a data sheet of the proposed substituted item to the Contracting Officer, for approval.

Attachment 2 Solicitation No.: AG-0261-S-16-0043

COMMON WORK RESULTS FOR ELECTRICAL 260500-2

2.2 GROUT

A. Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout, noncorrosive, nonstaining, mixed with water to consistency suitable for application and a 30-minute working time.

PART 3 - EXECUTION

3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

3.2 RACEWAY AND SIMILAR PENETRATIONS (NON-FIRE RATED, NOT

SLEEVED)

A. Masonry Walls: Core-drilled holes.

1. Fill oversized holes around conduits and sleeves with grout to within 1/4-inch (6 mm).

B. Stick-built and Similar Interior-Wall Penetrations (Finished Areas): Repair wall to within 1/8-inch (3 mm) to match the surrounding wall finish.

1. Allow for a small gap or flexible fill to allow expansion and contraction to minimize cracking.

C. Stick-built and Similar Interior-Wall Penetrations (Unfinished Areas): Repair wall to within 1/4-inch (6 mm).

1. Allow for a small gap to allow for expansion and contraction.

D. Aboveground, Exterior-Wall Penetrations: Seal exterior opening around the raceway or cable, using a flexible, waterproofing, joint sealant appropriate for size, depth, and color to closely match the surrounding surface. Finish interior openings, filling opening and matching the exiting surface with appropriate materials and finish quality for the space.

END OF SECTION 260500

May 2016

Attachment 2

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-1

USDA FOREST SERVICE, R4

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Building wires and cables rated 2000 V and less.

2. Connectors, splices, and terminations rated 2000 V and less.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 CONDUCTORS AND CABLES

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Conductors: Copper, complying with NEMA WC 70/ICEA S-95-658.

1. Conductor Insulation: Comply with NEMA WC 70/ICEA S-95-658.

C. Cable: Comply with NEMA WC 70/ICEA S-95-658 for metal-clad cable, Type MC with ground wire.

2.2 CONNECTORS AND SPLICES

A. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

PART 3 - EXECUTION

3.1 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS

AND WIRING METHODS

A. Feeders and Branch Circuits: Type THHN-2-THWN-2 or XHHW-2, single conductors in raceway; and Metal-clad cable, Type MC as allowed in drawings and Section 260533 "Raceways and Boxes for Electrical Systems".

Attachment 2

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519-2

3.2 INSTALLATION OF CONDUCTORS AND CABLES

A. Conceal cables in finished walls, ceilings, and floors unless otherwise indicated.

B. Complete raceway installation between conductor and cable termination points according to Section 260533 "Raceways and Boxes for Electrical Systems" prior to pulling conductors and cables.

C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

3.3 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B.

B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches (150 mm) of slack.

END OF SECTION 260519

May 2016

Attachment 2

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes grounding and bonding systems and equipment.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 SYSTEM DESCRIPTION

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with UL 467 for grounding and bonding materials and equipment.

2.2 CONDUCTORS

A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.

B. Bare Copper Conductors:

1. Solid Conductors: ASTM B 3.

2. Stranded Conductors: ASTM B 8.

2.3 CONNECTORS

A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected.

B. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.

C. Cable-to-Cable Connectors: Compression type, copper or copper alloy.

D. Ground Rod Clamps: Mechanical type, copper or copper alloy, terminal with hex head bolt.

E. Water Pipe Clamps:

Attachment 2

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526-2

1. Mechanical type, two pieces with zinc-plated bolts.

a. Material: Tin-plated aluminum.

2.4 GROUNDING ELECTRODES

A. Ground Rods: Copper-clad steel; 3/4 inch by 10 feet (19 mm by 3 m).

PART 3 - EXECUTION

3.1 APPLICATIONS

A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No. 6 AWG and larger unless otherwise indicated.

B. Underground Grounding Conductors: Bury at least 12 inches (300 mm) below grade.

3.2 GROUNDING AT THE SERVICE

A. Equipment grounding conductors and grounding electrode conductors shall be connected to the ground bus. Install a main bonding jumper between the neutral and ground buses.

3.3 EQUIPMENT GROUNDING

A. Install insulated equipment grounding conductors with all feeders and branch circuits.

3.4 INSTALLATION

A. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.

B. Ground Rods: Drive rods until tops are 2 inches (50 mm) below finished floor or final grade unless otherwise indicated.

1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating if any.

C. Grounding and Bonding for Piping:

1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes; use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.

END OF SECTION 260526

May 2016

Attachment 2

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Metal conduits, tubing, and fittings.

2. Metal wireways and auxiliary gutters.

3. Surface raceways.

4. Boxes, enclosures, and cabinets.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 METAL CONDUITS, TUBING, AND FITTINGS

A. Listing and Labeling: Metal conduits, tubing, and fittings shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. EMT: Comply with ANSI C80.3 and UL 797.

C. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360.

D. Fittings for Metal Conduit: Comply with NEMA FB 1 and UL 514B.

2.2 METAL WIREWAYS AND AUXILIARY GUTTERS

A. Description: Sheet metal, complying with UL 870 and NEMA 250, Type 1 unless otherwise indicated, and sized according to NFPA 70.

B. Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.

C. Wireway Covers: Screw-cover type unless otherwise indicated.

D. Finish: Manufacturer's standard enamel finish.

2.3 SURFACE RACEWAYS

Attachment 2

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-2

A. Listing and Labeling: Surface raceways shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Products: Subject to compliance with requirements, provide raceways indicated on the drawings, or submit a substitution request for consideration from one of the following manufacturers:

1. Hubbell Incorporated; Wiring Device-Kellems.

2. MonoSystems, Inc.

3. Panduit Corp.

4. Wiremold / Legrand.

C. Surface Nonmetallic Raceways: Two- or three-piece construction, complying with UL 5A, and manufactured of rigid PVC with texture and color selected by Contracting Officer from manufacturer's standard colors. Product shall comply with UL 94 V-0 requirements for self-extinguishing characteristics.

2.4 BOXES, ENCLOSURES, AND CABINETS

A. General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets installed in wet locations shall be listed for use in wet locations.

B. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.

C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, aluminum, Type FD, with gasketed cover.

D. Nonmetallic Outlet and Device Boxes: Comply with NEMA OS 2 and UL 514C.

E. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.

F. Box extensions used to accommodate new building finishes shall be of same material as recessed box.

PART 3 - EXECUTION

3.1 RACEWAY APPLICATION

A. Outdoors: Apply raceway products as specified below unless otherwise indicated:

1. Exposed Conduit, Aboveground: EMT with UL listed raintight compression fittings.

2. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.

3. Boxes and Enclosures, Aboveground: NEMA 250, Type 3R.

B. Indoors: Apply raceway products as specified below unless otherwise indicated:

1. Exposed, Not Subject to Physical Damage: See drawings.

2. Concealed in Ceilings and Interior Walls and Partitions: EMT or approved cable.

3. Boxes and Enclosures: NEMA 250, Type 1.

Attachment 2

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-3

C. Raceway Fittings: Compatible with raceways and suitable for use and location.

1. Flexible Conduit: Use only fittings listed for use with flexible conduit. Comply with

NEMA FB 2.20.

D. Install surface raceways only where indicated on Drawings.

3.2 INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except where requirements on Drawings or in this article are stricter. Comply with NECA 102 for aluminum conduits. Comply with NFPA 70 limitations for types of raceways allowed in specific occupancies and number of floors.

B. Keep raceways at least 6 inches (150 mm) away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping.

C. Complete raceway installation before starting conductor installation.

D. Conceal conduit and EMT within finished walls and ceilings unless otherwise indicated.

Install conduits parallel or perpendicular to building lines.

E. Install raceways square to the enclosure and terminate at enclosures with locknuts. Install locknuts hand tight plus 1/4 turn more.

F. Cut conduit perpendicular to the length. For conduits 2-inch (53-mm) trade size and larger, use roll cutter or a guide to make cut straight and perpendicular to the length.

G. Surface Raceways:

1. Install surface raceway with a minimum 2-inch (50-mm) radius control at bend points.

2. Secure surface raceway with screws or other anchor-type devices at intervals not exceeding 48 inches (1200 mm) and with no less than two supports per straight raceway section. Support surface raceway according to manufacturer's written instructions.

H. Flexible Conduit Connections: Comply with NEMA RV 3. Use a maximum of 36 inches (915 mm) of flexible conduit for equipment subject to vibration, noise transmission, or movement; and for transformers and motors.

I. Mount boxes at heights indicated on Drawings. If mounting heights of boxes are not individually indicated, give priority to ADA requirements. Install boxes with height measured to center of box unless otherwise indicated.

J. Recessed Boxes in Walls: Saw-cut opening for box and install box flush with surface of wall.

K. Boxes in Masonry Walls: Prepare surfaces to provide a flat surface for a raintight connection between box and cover plate or supported equipment and box.

L. Fasten junction and pull boxes to or support from building structure. Do not support boxes by conduits.

Attachment 2

RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533-4

END OF SECTION 260533

May 2016

Attachment 2

LIGHTING CONTROL DEVICES 260923-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 260923 - LIGHTING CONTROL DEVICES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Photoelectric switches.

2. Indoor occupancy sensors.

1.2 SUBMITTALS

A. Product Data: For each type of product.

B. Operation and Maintenance Data: For each type of lighting control device to include in emergency, operation, and maintenance manuals.

1.3 COORDINATION

A. Coordinate layout and installation of ceiling-mounted devices with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, smoke detectors, fire-suppression system, and partition assemblies.

1.4 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 OUTDOOR PHOTOELECTRIC SWITCHES

A. Description: Solid state, with contacts rated for 1800 VA, to operate connected load, complying with UL 773.

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. Light-Level Monitoring Range: 1.5 to 10 fc (16.14 to 108 lux), with an adjustment for turn-on and turn-off levels within that range.

3. Time Delay: Thirty-second minimum, to prevent false operation.

2.2 INDOOR OCCUPANCY SENSORS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

Attachment 2

LIGHTING CONTROL DEVICES 260923-2

1. Bryant Electric.

2. Cooper Industries, Inc.

3. Hubbell Building Automation, Inc.

4. Leviton Manufacturing Co., Inc.

5. Lightolier Controls.

6. Lithonia Lighting; Acuity Brands Lighting, Inc.

7. Lutron Electronics Co., Inc.

8. NSi Industries LLC; TORK Products.

9. RAB Lighting.

10. Sensor Switch, Inc.

11. Square D.

12. Watt Stopper.

B. General Requirements for Sensors: Ceiling-mounted, line voltage, solid-state indoor occupancy sensors.

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. Operation: Unless otherwise indicated, turn lights on when coverage area is occupied, and turn them off when unoccupied; with a time delay for turning lights off, adjustable over a minimum range of 1 to 20 minutes, with concurrent walk through function.

a. Time-Delay and Sensitivity Adjustments: Recessed and concealed behind hinged door.

3. Indicator: Digital display, to show when motion is detected during testing and normal operation of sensor.

C. PIR Type: Ceiling mounted; detect occupants in coverage area by their heat and movement.

1. Detector Sensitivity: Detect occurrences of 6-inch- (150-mm-) minimum movement of any portion of a human body that presents a target of not less than 36

sq. in. (232 sq. cm).

2. Detection Coverage (Room): Detect occupancy anywhere in a circular area of 1000

sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.

PART 3 - EXECUTION

3.1 SENSOR INSTALLATION

A. Coordinate layout and installation of ceiling-mounted devices with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, smoke detectors, fire-suppression systems, and partition assemblies.

B. Install and aim sensors in locations to achieve not less than 90 percent coverage of areas indicated. Do not exceed coverage limits specified in manufacturer's written instructions.

Attachment 2

LIGHTING CONTROL DEVICES 260923-3

3.2 ADJUSTING

A. Occupancy Adjustments:

1. For occupancy and motion sensors, verify operation at outer limits of detector range. Set time delay to suit Owner's operations.

END OF SECTION 260923

May 2016

Attachment 2

WIRING DEVICES 262726-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 262726 - WIRING DEVICES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Receptacles and associated device plates.

2. Receptacles with integral surge-suppression units.

3. Weather-resistant receptacles.

4. Snap switches.

1.2 DEFINITIONS

A. Pigtail: Short lead used to connect a device to a branch-circuit conductor.

B. TVSS: Transient voltage surge suppressor.

1.3 SUBMITTALS

A. Operation and Maintenance Data: For wiring devices to include in all manufacturers' packing-label warnings and instruction manuals that include labeling conditions.

1.4 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers' Names: Shortened versions (shown in parentheses) of the following manufacturers' names are used in other Part 2 articles:

1. Cooper Wiring Devices; Division of Cooper Industries, Inc. (Cooper).

2. Hubbell Incorporated; Wiring Device-Kellems (Hubbell).

3. Leviton Mfg. Company Inc. (Leviton).

4. Pass & Seymour/Legrand (Pass & Seymour).

B. Source Limitations: Obtain each type of wiring device and associated wall plate from single source from single manufacturer.

2.2 GENERAL WIRING-DEVICE REQUIREMENTS

Attachment 2

WIRING DEVICES 262726-2

A. Wiring Devices, Components, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Comply with NFPA 70.

C. Devices that are manufactured for use with modular plug-in connectors may be substituted under the following conditions:

1. Connectors shall comply with UL 2459 and shall be made with stranding building wire.

2. Devices shall comply with the requirements in this Section.

2.3 STRAIGHT-BLADE RECEPTACLES

A. Convenience Receptacles, 125 V, 20 A: Comply with NEMA WD 1, NEMA WD 6 Configuration 5-20R, UL 498, and FS W-C-596.

1. Products: Subject to compliance with requirements, provide one of the following:

a. Cooper; CR5362 (duplex).

b. Hubbell; HBL5352 (duplex).

c. Leviton; 5352 (duplex).

d. Pass & Seymour; 5362 (duplex).

2. Weather Resistant rated receptacles:

a. Hubbell; HBL5352WR (duplex).

2.4 GFCI RECEPTACLES

A. GFCI protection to be provided by an existing circuit breaker.

2.5 TVSS RECEPTACLES

A. General Description: Comply with NEMA WD 1, NEMA WD 6, UL 498, UL 1449, and FS W-C-596, with integral TVSS in line to ground, line to neutral, and neutral to ground.

1. TVSS Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 400 V and minimum single transient pulse energy dissipation of 240 J, according to IEEE C62.41.2 and IEEE C62.45.

2. Active TVSS Indication: Visual and audible, with light visible in face of device to indicate device is "active" or "no longer in service."

B. Duplex TVSS Convenience Receptacles:

1. Products: Subject to compliance with requirements, provide one of the following:

a. Cooper; 5362BLS.

b. Hubbell; HBL5362SA.

c. Leviton; 5380.

d. Pass & Seymour; 5362BLSP.

Attachment 2

WIRING DEVICES 262726-3

2. Description: Straight blade, 125 V, 20 A; NEMA WD 6 Configuration 5-20R.

2.6 TOGGLE SWITCHES

A. Comply with NEMA WD 1, UL 20, and FS W-S-896.

B. Switches, 120/277 V, 20 A:

1. Products: Subject to compliance with requirements, provide one of the following:

a. Single Pole:

1) Cooper; AH1221.

2) Hubbell; HBL1221.

3) Leviton; 1221-2.

4) Pass & Seymour; CSB20AC1.

2.7 WALL PLATES

A. Single and combination types shall match corresponding wiring devices.

1. Plate-Securing Screws: Metal with head color to match plate finish.

2. Material for Finished Spaces: 0.035-inch- (1-mm-) thick, satin-finished, Type 302 stainless steel.

3. Material for Unfinished Spaces: Galvanized steel.

B. Wet-Location, Weatherproof Cover Plates: NEMA 250, complying with Type 3R, extra duty, weather-resistant, die-cast aluminum or thermoplastic with lockable cover.

2.8 FINISHES

A. Device Color:

1. Wiring Devices Connected to Normal Power System: White unless otherwise indicated or required by NFPA 70 or device listing.

2. TVSS Devices: Blue.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with NECA 1, including mounting heights listed in that standard for accessibility, unless otherwise indicated.

B. Coordination with Other Trades:

1. Keep outlet boxes free of plaster, drywall joint compound, mortar, cement, concrete, dust, paint, and other material that may contaminate the raceway system, conductors, and cables.

2. Install wiring devices after all wall preparation, including painting, is complete.

C. Conductors:

Attachment 2

WIRING DEVICES 262726-4

1. Strip insulation evenly around the conductor using tools designed for the purpose.

Avoid scoring or nicking of solid wire or cutting strands from stranded wire.

2. The length of free conductors at outlets for devices shall meet provisions of NFPA 70, Article 300, without pigtails.

D. Device Installation:

1. Connect devices to branch circuits using pigtails that are not less than 6 inches (152

mm) in length.

2. When there is a choice, use side wiring with binding-head screw terminals. Wrap solid conductor tightly clockwise, two-thirds to three-fourths of the way around terminal screw.

3. Use a torque screwdriver when a torque is recommended or required by manufacturer.

4. Tighten unused terminal screws on the device.

5. When mounting into metal boxes, remove the fiber or plastic washers used to hold device-mounting screws in yokes, allowing metal-to-metal contact.

E. Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.

END OF SECTION 262726

May 2016

Attachment 2

COMMON WORK RESULTS FOR COMMUNICATIONS 270500-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 270500 - COMMON WORK RESULTS FOR COMMUNICATIONS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Communications equipment coordination and installation.

2. Grout.

3. Common communications installation requirements.

1.2 DEFINITIONS

A. BICSI: Building Industry Consulting Service International.

B. RCDD: Registered Communications Distribution Designer.

1.3 SUBMITTALS

A. Qualification Data: Submit qualifications and certification of installing contractor and key employees.

B. Product Data: For any substitutions for equipment referred to by name in Division 27 specifications or the drawings.

C. As-Built Drawings & Operation And Maintenance Manuals: As called for in the article by the same name.

1.4 QUALITY ASSURANCE

A. A single manufactures product shall be provided for horizontal cable wiring, fiber optic cable and connectors for all systems.

1. Installer's Qualifications must include equipment manufacturers (copper cable) certification for product installation and at least 5 years of successful installation experience with projects utilizing telecommunication-wiring work similar to that required for this project.

2. Personnel must be certified to install all wiring, terminations, and equipment, CAT 6 (or better). Certification from BICSI level TE-350 or equivalent manufactures certification for installation work is the acceptable standard.

B. General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-B.1, when tested according to test procedures of this standard.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

Attachment 2

COMMON WORK RESULTS FOR COMMUNICATIONS 270500-2

D. Telecommunications Pathways and Spaces: Comply with TIA/EIA-569-A.

E. Grounding: Comply with ANSI-J-STD-607-A.

1.5 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 PRODUCTS REFERRED TO BY NAME

A. The materials referred to by trade name, make, or catalog number on the drawings shall be regarded as establishing a minimum standard of quality; substitutions of equal or greater quality can be made by submitting a data sheet of the proposed substituted item to the Contracting Officer, for approval.

PART 3 - EXECUTION

3.1 COMMON REQUIREMENTS FOR COMMUNICATIONS INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both communications equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

3.2 AS-BUILT DRAWINGS & OPERATION AND MAINTENANCE MANUALS

A. Keep one copy of record drawings, other than working drawings, on the site at all times during construction, and note all changes and corrections made during the construction period.

B. Upon installations completion, prepare “Cabling Administration Drawings” and post in each Communications Room. These drawings are called for in other sections of Division 27.

C. Supply Electrical Operation and Maintenance Manuals. Label the front cover of the manuals with the following information: The name of the project, the General Contractor, the Electrical Contractor, the date of construction, and contract number.

1. Hard copy manuals: 8-1/2" x 11" size in hard cover, loose leaf, 3-ring binder.

Accordion fold drawings to 8-1/2" x 11" size. Provide an index and tabs for listing contents. Arrange contents in order of their appearance in the specifications.

Attachment 2

COMMON WORK RESULTS FOR COMMUNICATIONS 270500-3

a. Provide: One copy in communications room, plus one for permanent record.

2. Electronic manual: Same information and electronic format as the hard copy with information in Adobe PDF format. The “Cabling Administration Drawings” shall also be provided in AutoCAD “dwg” format, in the same scale as the Government provided construction drawings.

a. Provide the Contracting Officer with two CD’s, DVD’s, or thumb drives compatible with standard computers running Windows 7.

3. Include the following information as part of the operation and maintenance manuals:

a. Required Data:

1) “Cabling Administration Drawings.”

2) Test and inspection reports.

3) Diagrams, catalog data, parts lists, manufacturer's installation, operating and maintenance instruction manuals for all equipment and fixtures.

b. List major equipment with the names, addresses and telephone numbers of the equipment representative providing factory trained service personnel.

4. The Government will provide CAD drawing files on DVD or CD to the contractor for creating “Cabling Administration Drawings.”

END OF SECTION 270500

May 2016

Attachment 2

GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS 270526-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 270526 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Grounding conductors.

2. Grounding connectors.

3. Grounding busbars.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 CONDUCTORS

A. Insulated Conductors: Stranded copper wire, green or green with yellow stripe insulation, insulated for 600 V, and complying with UL 83.

2.2 GROUNDING BUSBARS

A. Rack and Cabinet Grounding Busbars: Rectangular bars of hard-drawn solid copper, accepting conductors ranging from No. 14 to No. 8 AWG, NRTL listed as complying with UL 467, and complying with J-STD-607-A. Predrilling shall be with holes for use with lugs specified in this Section.

1. Cabinet-Mounted Busbar: Terminal block, with stainless-steel or copper-plated hardware for attachment to the cabinet.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Grounding and Bonding Conductors:

1. Install in the straightest and shortest route between the origination and termination point, and no longer than required. The bend radius shall not be smaller than eight times the diameter of the conductor. No one bend may exceed 90 degrees.

2. Install without splices.

3. Support at not more than 36-inch (900-mm) intervals.

Attachment 2

GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS 270526-2

3.2 CONNECTIONS

A. Install and bond grounding busbar in the telecommunications area, to the grounding electrode system with No. 8 AWG insulated conductor at the intersystem bonding connection.

B. Bond metallic equipment in a telecommunications equipment area to the grounding busbar in that area, using equipment grounding conductors not smaller than No. 10 AWG.

C. Stacking of conductors under a single bolt is not permitted when connecting to busbars.

D. Shielded Cable: Bond the shield of shielded cable to the TGB in communications rooms and spaces. Comply with TIA/EIA-568-B.1 and TIA/EIA-568-B.2 when grounding screened, balanced, twisted-pair cables.

E. Rack- and Cabinet-Mounted Equipment: Bond powered equipment chassis to the cabinet or rack grounding bar. Power connection shall comply with NFPA 70; the equipment grounding conductor in the power cord of cord- and plug-connected equipment shall be considered as a supplement to bonding requirements in this Section.

END OF SECTION 270526

May 2016

Attachment 2

PATHWAYS FOR COMMUNICATIONS SYSTEMS 270528-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 270528 - PATHWAYS FOR COMMUNICATIONS SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Nonmetallic conduits and fittings.

2. Optical-fiber-cable pathways and fittings.

3. Surface pathways.

4. Lacing bars, spools, D-Rings and J-Hooks

5. Boxes, enclosures, and cabinets.

6. Handholes and boxes for exterior underground cabling.

1.2 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 SURFACE PATHWAYS

A. See drawings for requirements.

2.2 D-RINGS AND D-HOOKS

A. Cable Support: NRTL labeled for support of Category 6 cabling, designed to prevent degradation of cable performance and pinch points that could damage cable.

1. Support brackets with cable tie slots for fastening cable ties to brackets.

2. Lacing bars, spools, J-hooks, and D-rings.

3. Straps and other devices.

B. Shall provide adequate strength for twice the applied load minimum.

C. Where installed over 12 inches (300 mm) center to center they shall provide a minimum of 1 inch, flat or almost flat surface for cable support.

D. If metal, they shall be galvanized steel, paint powder coated, or aluminum with clear anodized finish.

2.3 BOXES, ENCLOSURES, AND CABINETS

A. Refer to the article by the same name in 260533 – “Raceways and Boxes for Electrical Systems.”

Attachment 2

PATHWAYS FOR COMMUNICATIONS SYSTEMS 270528-2

PART 3 - EXECUTION

3.1 PATHWAY APPLICATION

A. Indoors: Apply pathway products as specified below unless otherwise indicated:

1. Concealed in Attic: D-rings or J-hooks to keep conductors out of insulation.

2. Concealed in Interior Walls and Partitions: Fished, without other support.

3. Boxes and Enclosures: NEMA 250 Type 1.

B. Install surface pathways only where indicated on Drawings.

3.2 INSTALLATION

A. Comply with NECA 1, NECA 101, and TIA-569-B for installation requirements except where requirements on Drawings or in this article are stricter.

B. Unless otherwise permitted or prohibited, comply with requirements in Section 260533 "Raceway and Boxes for Electrical Systems."

C. Cables shall not be laid upon attic joists, duct work and other similar items.

D. Separation from EMI Sources:

1. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches (127 mm).

2. Cross all power wiring at 90 degrees where possible.

E. Surface Pathways:

1. Install surface pathway for surface telecommunications outlet boxes only where indicated on Drawings.

2. Install surface pathway with a minimum 2-inch (50-mm) radius control at bend points.

3. Secure surface pathway with screws or other anchor-type devices at intervals not exceeding 48 inches (1200 mm) and with no less than two supports per straight pathway section. Support surface pathway according to manufacturer's written instructions.

F. D-Rings and J-Hook Pathways:

1. For each pathway where allowed in supporting horizontal cabling leaving or entering a main cable tray pathway or other pathway:

a. Install the first support to support cabling within 12 inches (300 mm) of the last pathway support.

b. Twelve or fewer 4-pair cables or equivalent: Install supports so that cables span a maximum of 60 inches (1520 mm).

c. More than twelve 4-pair cables or equivalent: Install supports so that cables span a maximum of 30 inches (760 mm).

END OF SECTION 270528

Attachment 2

PATHWAYS FOR COMMUNICATIONS SYSTEMS 270528-3

COMMUNICATIONS EQUIPMENT ROOM FITTINGS 271100-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 271100 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Cable management for equipment frames.

1.2 DEFINITIONS

A. LAN: Local area network.

1.3 SUBMITTALS

A. Product Data: For each type of product.

1.4 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated or comparable product by one of the following:

1. ADC.

2. Belden Inc.

3. Berk-Tek Company.

4. Cooper B-Line.

5. Emerson Network Power Connectivity Solutions.

6. General Cable Company.

7. Hubbell Premise Wiring.

8. Leviton Commercial Networks Division.

9. Middle Atlantic Products, Inc.

10. Ortronics, Inc.

11. Panduit Corp.

12. Siemon Co. (The).

13. Tyco Electronics Corporation; AMP NETCONNECT.

2.2 CABLE MANAGEMENT FOR EXISITNG EQUIPMENT FRAME

Attachment 2

COMMUNICATIONS EQUIPMENT ROOM FITTINGS 271100-2

A. General Frame Requirements:

1. Module Dimension: Width compatible with EIA 310-D standard, 19-inch (480-

mm) panel mounting.

2. Finish: Manufacturer's standard, baked-polyester powder coat.

B. Cable Management for Equipment Frames:

1. Horizontal cable managers shall be TE Connectivity (AMP NETCONNECT) Horizontal 2U management panel, single sided, 5.5” deep 1933532-1 and double sided, 5.5” deep front and rear 1933533-1, or equal.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with NECA 1.

B. Bundle, lace, and train conductors and cables to terminal points without exceeding manufacturer's limitations on bending radii. Install lacing bars and distribution spools.

END OF SECTION 271100

May 2016

Attachment 2

COMMUNICATIONS COPPER NETWORK CABLING 271200-1

CARSON WHTIE HOUSE ELECTRICAL REMODEL AND REPAIRS

SECTION 271200 - COMMUNICATIONS COPPER NETWORK CABLING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. UTP cable.

2. Cable connecting hardware, patch panels, and cross-connects.

3. Telecommunications outlet/connectors.

4. Cabling and cabling system identification products.

B. Horizontal Cabling Description:

1. Horizontal cable and its connecting hardware provide the means of transporting signals between the telecommunications outlet/connector and the horizontal cross-connect located in the communications equipment room. This cabling and its connecting hardware are called a "permanent link," a term that is used in the testing protocols.

a. Two telecommunications outlet/connectors shall be installed for each work area outlet unless otherwise specified on the drawings.

b. Bridged taps and splices shall not be installed in the horizontal cabling.

2. A work area outlet includes the components that extend from the telecommunications outlet/connectors to the station equipment.

C. Patch Cords: Are provided under this contract in quantities called for herein.

D. Electronic Network Devices and UPS: Network routers and similar equipment, and any UPS are not provided in this contract.

1.2 DEFINITIONS

A. BICSI: Building Industry Consulting Service International.

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

C. EMI: Electromagnetic interference.

D. IDC: Insulation displacement connector.

E. LAN: Local area network.

F. Outlet/Connectors: A connecting device in the work area on which horizontal cable or outlet cable terminates.

G. RCDD: Registered Communications Distribution Designer.

Attachment 2

COMMUNICATIONS COPPER NETWORK CABLING 271200-2

H. UTP: Unshielded twisted pair.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

1.4 QUALITY ASSURANCE

A. General Performance: Horizontal cabling system shall comply with transmission standards in TIA/EIA-568-B.1, when tested according to test procedures of this standard.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

1.5 MEASUREMENT AND PAYMENT

A. No separate measurement or payment will be made for work specified in this section. All work will be included in other items listed in the Schedule of Items.

PART 2 - PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. The cable chosen for project shall be from one manufacturer for the entire project. Use a single manufacturer and the same product where two or more units of the same class or equipment are required.

B. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated within this section or comparable product by one of the following:

1. Preapproved:

a. Berk-Tek; a Nexans company.

b. General Cable Technologies Corporation.

c. Legrand Ortronics.

d. Leviton Commercial Networks Division.

e. Tyco Electronics/AMP NETCONNECT; Tyco International Ltd.

2. Not preapproved:

a. ADC.

b. American Technology Systems Industries, Inc.

c. Belden CDT Inc.; Electronics Division.

d. CommScope, Inc.

e. Draka USA.

f. Dynacom Corporation.

g. Genesis Cable Products; Honeywell International, Inc.

h. Hubbell Premise Wiring.

i. KRONE Incorporated.

Attachment 2

COMMUNICATIONS COPPER NETWORK CABLING 271200-3

j. Mohawk; a division of Belden CDT.

k. Molex Premise Networks; a division of Molex, Inc.

l. Nordex/CDT; a subsidiary of Cable Design Technologies.

m. Panduit Corp.

n. Siemon Co. (The).

o. Superior Essex Inc.

p. SYSTIMAX Solutions; a CommScope Inc. brand.

q. 3M Communication Markets Division.

2.2 GENERAL

A. Performance Rating: Category 6 exceeding TIA/EIA-568-B.2-1 Category 6 and ISO/IEC 11801 Class E performance requirements on all parameters.

1. Comply with all of the performance requirements for current and proposed applications such as Gigabit Ethernet (1000BASE-Tx), 10/100BASE-Tx, token ring, 155 Mbps ATM, 100 Mbps TP-PMD, ISDN, analog and digital video and analog and digital voice (VoIP).

2. Cable performance shall be independently verified and characterized to 600 MHz.

Listed and labeled by an NRTL acceptable to authorities having jurisdiction as complying with UL 444 and NFPA 70.

3. Comply with ICEA S-90-661 for mechanical properties.

2.3 UTP CABLE

A. Jacketing: Thermoplastic, lead free.

B. Horizontal Cable: 100-ohm, four-pair UTP, 23 AWG, unshielded.

1. Horizontal cable may be AMP NETCONNECT part number 219560-X, or 219567- X where X denotes color.

2.4 UTP CABLE HARDWARE

A. General Requirements for Cable Connecting Hardware: Comply with TIA/EIA-568-B.2, IDC type, with modules designed for punch-down caps or tools. Cables shall be terminated with connecting hardware of same category or higher.

1. Patch Panel: Modular panels housing multiple-numbered jack units with IDC-type connectors at each jack for permanent termination of pair groups of installed cables.

a. Number of Jacks per Field: One for each four-pair UTP cable indicated.

b. Fill all ports integral with connector bodies, including plugs and jacks.

2. Jacks and Jack Assemblies: Modular, color-coded, eight-position modular receptacle units with integral IDC-type terminals.

a. Number of Jacks per Field: One for each four-pair UTP cable indicated.

Attachment 2

COMMUNICATIONS COPPER NETWORK CABLING 271200-4

B. Rack Or Cabinet Mounted Patch Panels (Distribution Frame): Standard SL Series Patch configured with 6-port modules with individually replaceable jacks. Patch panels shall terminate the building cabling on 110-style insulation displacement connectors.

1. Modules shall accept 9mm and 12mm labels (included) as well as color-coded icons to indicate its function.

2. Patch panels shall be Listed.

3. AMP NETCONNECT: Description Height Width Part Numbers

a. 48-Port 2U 19.0” 1933328-1

b. -X denotes packaging: -1 = loaded, -2 = unloaded, jacks bagged

C. Jacks and Jack Assemblies: Modular, SL (slim profile) Series, color-coded, eight-position modular receptacle units with integral IDC-type terminals.

1. Modular jacks shall be unkeyed, unshielded, 4-pair, RJ-45. Modular jacks shall terminate using 110-style pc board connectors, color-coded for both T568A and T568B wiring. The 110-style insulation displacement connectors shall be capable of terminating 22-24 AWG solid or 24 AWG stranded conductors.

2. The insulation displacement contacts shall be paired, with additional space between pairs, to improve crosstalk performance. Modular jacks shall utilize a secondary PC board, separate from the signal path, for crosstalk compensation.

3. Jacks shall be terminated with a non impact compression tool that terminates and cuts all 8 conductor with one action. Impact termination devices are not acceptable.

4. Each modular jack shall be provided with a bend-limiting strain relief. The strain relief shall provide cylindrical support to limit the bend radius at the point of termination. Each jack shall incorporate an integral, hinged dust cover. Modular jacks shall be UL Listed.

5. Modular Jack Housing and 110 Connecting Blocks – Polyphenylene oxide, 94V-0 rated

a. Contacts – Beryllium copper, plated with 1.27μm (50μin) thick gold in localized area and 3.81μm (150μin) minimum thick matte tin in solder area over 1.27 μm (50 μin) minimum thick nickel under plate Insulation Displacement Contacts – Phosphorous bronze, plated with 3.81μm (150μin) minimum thick matte tin-lead over 1.27μm (50μin) minimum thick nickel under plate Integral Dust Cover – Polycarbonate

1) Modular Jack – 750 mating cycles Voltage – -40° – 70°C (-40° – 158°F) – 150VAC max.

2) 110 Contacts – 200 terminations Operating Temperature – -40° – 70°C (-40° – 158°F) - 150VAC max.

3) Pull Force – 20lbs (89N)

b. Shield – Copper zinc alloy 260, pre-plated with bright nickel Strain Relief – Polycarbonate

6. Modular jacks may be AMP NETCONNECT part number 1375055-X, 1375187- X, 1375188-1 or 1479552-1 where X denotes color.

Attachment 2

COMMUNICATIONS COPPER NETWORK CABLING 271200-5

D. Non Impact CAT 6 RJ-45 Jack Termination Tool

1. The termination tool and jacks shall allow easily wire lacing, depress the handle, seat each wire in its proper location, and cut them to length with one operation

2. The compression tool shall have an integrated lacing fixture which maintains pair-twist right up to termination, allowing consistent terminations every time for better network performance.

3. Provide the non impact AMP NETCONNECT SL Series Termination Tool (p/n:

1725150-1) or approved equal.

E. Patch Cords: Factory-made, unshielded, slim line, four-pair, type CMR cables in 36-inch (900 mm) and 18-inch (450-mm) lengths; terminated with eight-position modular plug at each end.

1. Provide 24 minimum of each size.

2. Constructed using modular plugs with 50μm gold-plated contacts, and wired to the

T568B or T568A wiring pattern.

3. Provide all-in-one, "snagless" plug/boot design for connections to patch panels with minimum interjack distance.

a. Boots that are wider than front width dimension are not acceptable.

b. Slip over jackets will not be allowed.

4. Cable assemblies may be AMP NETCONNECT part number 1933116-X, 1933117-X, 1933118-X, 1933119-X, 1933120-X, 1933121-X, 1933122-X, 933123-X, 1933124-X (X denotes length). or approved equal.

2.5 TELECOMMUNICATIONS OUTLET/CONNECTORS

A. Jacks: modular as called for in article “UTP Cable Hardware.”

B. Workstation Outlets: Two-port-connector assemblies mounted in single faceplate.

C. Faceplates shall be constructed utilizing single gang, staggered 4-port faceplates.

1. Accommodate self-adhesive labels and icon holes.

2. With "leveling" screw holes which allow the faceplate to be adjusted for better placement over outlet boxes.

3. Plastic Faceplate: High-impact plastic. White color. For use with snap-in jacks accommodating any combination of UTP, optical fiber, and coaxial work area cords.

4. Legend: Snap-in, clear-label covers and machine-printed paper inserts.

D. The 110 Connect faceplates may be AMP NETCONNECT part number(s) 83935-X, 83936-X, 557691-X, 558055-X or 558088-X where X denotes color.

2.6 IDENTIFICATION PRODUCTS

A. Comply with TIA/EIA-606-A and UL 969 for a system of labeling materials, including label stocks, laminating adhesives, and inks used by label printers.

Attachment 2

COMMUNICATIONS COPPER NETWORK CABLING 271200-6

PART 3 - EXECUTION

3.1 GENERAL INSTALLATION

A. 110-Style Jacks: Terminate using EIA/TIA/ANSI 568A color designation wire connections.

568-A COLOR CODE

Pin 1 white/green Pin2 green/white Pin3 white/orange Pin4 blue/white Pin5 white/blue Pin6 orange/white Pin7 white/brown Pin8 brown/white

B. Horizontal Cabling, Typical: Install 2 cables to each data jack location, one for data and one for voice.

3.2 INSTALLATION OF CABLES

A. Comply with NECA 1.

B. General Requirements for Cabling:

1. Comply with TIA/EIA-568-B.1.

2. Comply with BICSI ITSIM, Ch. 6, "Cable Termination Practices."

3. Install 110-style IDC termination hardware unless otherwise indicated.

4. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, cross-connects, and patch panels.

Exceptions will be shown on drawings.

5. Cables may not be spliced.

6. Secure and support cables at intervals not exceeding 30 inches (760 mm) and not more than 6 inches (150 mm) from cabinets, boxes, fittings, outlets, racks, frames, Attachment 2

COMMUNICATIONS COPPER NETWORK CABLING…