Addendum Three.pdf
PDF 861 KB Posted
- Solicitation number
- RFB 785 2700000170 4
- Issued by
- Nelson County, Kentucky
About this file
This is Addendum Three to an Invitation to Bid (RFB-103-27) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for emergency flood repair work at Green River Campground in Campbellsville, Kentucky. The addendum, dated October 30, 2026, establishes binding changes to the original specifications and drawings dated September 15, 2026. Final technical questions must be submitted by 12:00 PM EST on November 4, 2026, with a final addendum to be issued on that same date if needed. The project is identified as Engineering File No. 670-CC2Q-GR10-00 and C/S Project No. 2512.
The addendum includes general provisions allowing contractors to stay on-site in RVs or camping vehicles at a cost of $30.00 per night per campsite, with contractors responsible for their own trash, sanitary waste removal, electrical, and water supply. One bathhouse will remain open for shower use, which contractors must clean and maintain. Regarding specifications and drawings, the addendum permits an alternative to the originally specified 3-inch I.P.S. DR11 HDPE water mains, allowing instead 2-inch SDR 21 PVC piping that meets ASTM D2241 and NSF/ANSI 61 standards for potable water, with detailed requirements for joints, fittings, valves, and installation procedures. Additional revisions include modifications to detail 2 on sheet C503 related to water system thrust blocking details.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2700000170_4_SO_FORM.PDF | ||
| Final_RFB_785_2700000170_1_SO_FORM.PDF | ||
| Final_RFB_785_2700000170_3_SO_FORM.PDF | ||
| Addendum Two.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-103-27
FOR: Emergency Flood Repair Green River Campground Department of Parks Campbellsville, Kentucky
DATE: October 30, 2026
RFB-785-2700000170
ADDENDUM NO. Three (3)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-103-27 For: Emergency Flood Repair Green River Campground Department of Parks Campbellsville, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
Green River Campground Emergency Flood Repair Engineering File No. 670-CC2Q-GR10-00 C/S Project No. 2512
RFB 103-27
2026.10.30
Addendum No. 03 _ The original specifications and drawings dated RTA 09/15/2026 for the above referenced project are amended as noted in this Addendum.
Receipt of this Addendum shall be acknowledged by inserting its number in the space provided on the Official Bid Document for RFB 103-27.
GENERAL
1) Due to the bid date moving in Addendum 02: Final questions are due by 12:00 PM EST, November 04, 2026. After this time, no other questions will be answered that are technical. If needed, the final addendum will be issued November 04, 2026.
2) Contractors may stay on site in RVs or other camping vehicles. Contractors will be responsible for their own trash and sanitary waste removal as the campsites do not have sanitary connections. Contractors will also be responsible for their own electrical and water during the work. One bathhouse will be kept open for use. Use of the bathhouse for showering only is acceptable, however, the General Contractor will be responsible for cleaning and maintaining the facility. The cost is $30.00 per night per campsite.
SPECIFICATIONS
3) None
DRAWINGS
1) Sheet C500, C501, C502, C503 – As an alternative to 3” I.P.S. DR11 HDPE, water mains may be 2” SDR 21 PVC, ASTM D2241, NSF/ANSI 61 listed for potable water. Joints shall be integral bell with elastomeric gasket per ASTM D3139, gaskets per ASTM F477. Fittings shall be ASTM D2467 (Schedule 80 socket), with solvent cement per ASTM D2564, NSF/ANSI 61 listed for potable water. Primer shall be ASTM F656, NSF/ANSI 61 listed. Joining procedure shall be ASTM D2855 (two-step method with primer and cement). Valves must be 2" mechanical joint gate valves certified to “meet applicable requirements of C509/C515. Valves must be connected to pipe with mechanical joint transition gasket (IPS × DI) and restraining mechanical joint gland for IPS-OD PVC. Transitions to HDPE service lines must be by threaded service saddle adapter to compression couplings with stainless steel inserts inside HDPE for stiffener.
2) Sheet C503 – Drawing Revision to detail 2/C503. See detail for full assembly modification.
END of ADDENDUM
WWW.CLOTFELTER-SAMOKAR.COM
C
LO
TF
EL
TE
R -S
AM
O
KA
R
REVISION HISTORY OF THIS DRAWING
GREEN RIVER CAMPGROUND EMERGENCY
FLOOD REPAIR
DRAWING NO.
KDM
09/15/2026
228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE
DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
RTA
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
670-CC2Q-GR10-00
S T A
T E O F KENT UCK
Y
P R
O
F E S S IO NA L ENG IN
EE
R20203
L I C E N S E D
JOSEPH E.
MATESEVAC
09/15/2026
Paducah, KY Office 2301 McCracken Blvd, Paducah, KY 42001
270-443-1995 / BFWengineers.com
Copyright © 2024 / Bacon Farmer Workman Engineering & Testing, Inc.
JEM
09/15/2026
WATER SYSTEM DETAILS
C503
THRUST / LBS. OF PRESSURETYPICAL THRUST BLOCKING DETAILS
PLAN OF 90° BEND
PLAN OF TEE
INSPECTOR PRIOR TO BACKFILLING.
THE CURRENT ADDITION OF THE AWWA C-105.
PORTLAND CEMENT CONCRETE, 2500 PSI, MINIMUM.
THRUST BLOCKS SHALL BE CONSTRUCTED WITH CLASS "B"
BLOCKING SHALL BE POURED AFTER THE POLYETHYLENE WRAP IS
WRAPPED WITH A POLYETHYLENE MATERIAL, 8-MIL. INSTALLED TO
USE ADDITIONAL CONCRETE AS REQUIRED FOR OVER EXCAVATION.
THRUST BLOCKS TO BE PLACED AGAINST UNDISTURBED EARTH.
BLOCKING SHALL BE INSPECTED BY THE DESIGN ENGINEER'S
ALL DUCTILE IRON PIPE, FITTINGS AND VALVES SHALL BE
PLAN OF CROSS
OR 22 1/2° BEND
PLAN OF 45°
IN PLACE.
NOTES:
ELEVATION
DEAD END ORPIPE SIZE 1/4" BEND
4"
16"
12"
10"
8"
6"
TEE
1/16" BEND 1/8" BEND
TYPICAL THRUST BLOCKING DETAILS (WATER)
UNDISTURBED EARTH
POLYETHYLENE
WRAP (TYP.)
WATER
MAIN (TYP.)
CONC. THRUST
BLOCKING (TYP.)
UNDISTURBED EARTH
WATER
MAIN (TYP.)
CONC. THRUST
BLOCKING (TYP.)
POLYETHYLENE
WRAP (TYP.)
UNDISTURBED EARTH
CONC. THRUST
BLOCKING (TYP.)
POLYETHYLENE
WRAP (TYP.)
ADHESIVE TAPE
(DUCT TAPE) TYP.
CONC. THRUST
BLOCKING (TYP.)
UNDISTURBED EARTH
POLYETHYLENE
WRAP (TYP.)
WATER
MAIN (TYP.)
WATER
MAIN (TYP.)
POLYETHYLENE
WRAP (TYP.)
CONC. THRUST
BLOCKING (TYP.)
SCALE: N.T.S.4
5' -0
" M
AX
MIN.
' M
IN
' M
AX
2'-0"
VA
R
IE
S
D
IA
6"
PI
PE
WHEN FINAL SURFACE
INCLUDES TOPSOIL AND GRASS
IN LANDSCAPED AREAS, USE
COMPACTED EARTH BACKFILL
TO 92% STANDARD PROCTOR.
SEE NOTE 3 FOR TRENCH
SECTION THROUGH ROCK.
UTILITY PIPE
COMPACTED DGA TO
95% STANDARD
PROCTOR
#9M
LIMESTONE
WHEN FINAL SURFACE IS
PAVEMENT USE CONTROLLED
LOW-STRENGTH MATERIAL
(FLOWABLE FILL)
IMPROVED SURFACE
IMPROVED SURFACES: MATCH
EXISTING. FOR ASPHALT, MATCH
EXISTING OR PATCH WITH MIN 6"
PC CONCRETE
FINAL SURFACE IN GRASS
AREAS, MIN. 6" TOPSOIL,
SEED, FERTILIZE, MULCH
AND PROTECT
UNIMPROVED SURFACE
INSTALL CONTINUOUS
TRACER WIRE
UNDISTURBED SOIL
UNDISTURBED SOILUTILITY PIPE
FINISHED GRADE
UTILITY LOCATION
TAPE
EXCAVATED
MATERIAL
SLOPE TO CONFORM TO
O.S.H.A. REQUIREMENTS.
UNDISTURBED SOIL
UNDISTURBED SOIL
UTILITY PIPE
UTILITY TRENCH DETAILS FOR FORCED SYSTEM
UNDISTURBED SOIL
SCALE: N.T.S.5
EXISTING GRADE
SEWER MAIN
WATER MAIN
1/2 PIPE LENGTH1/2 PIPE LENGTH
18" MINIMUM
WATER MAIN CROSSING SEWER
SCALE: N.T.S.3
NOTE:
1. CONCRETE PADS SHALL BE CONSTRUCTED AROUND ALL MAIN LINE.
2. CONCRETE PADS SHALL BE CLASS "A" TYPE PORTLAND CEMENT
CONCRETE WITH A WOOD FLOAT FINISH TOOLED EDGE.
3. THE VALVE BOX SHALL NOT TRANSMIT SHOCK OR STRESS TO THE VALVE.
CONCRETE VALVE
BLOCKING
8-MIL POLYETHYLENE
WRAP
RESILIENT SEAT
GATE VALVE (SEE
SPECS.)
2 PIECE CAST IRON VALVE
BOX (SEE SPECS.)
CAST IRON
COVER MARKED
"WATER" ON LID
18" SQUARE CONC. PAD
(FOR UNPAVED AREAS)
" M
IN
. C
O
VE
R
6" M
IN
VALVE DIA. + 12" MIN.
TYPICAL GATE VALVE AND BOX COLLAR
4"
WATER MAIN
#12 GAUGE COPPER WIRE
8" COPPER GROUND ROD
WIRE
CONNECTOR
SCALE: N.T.S.1
WATER MAINS SHALL BE BURIED A MINIMUM OF 36" BELOW GRADE
MEASURED FROM FINISHED GRADE TO THE TOP OUTSIDE OF PIPE.
PROPOSED
GRADE
CAST IRON MANHOLE
FRAME & LID
8"
#57 CRUSHED
STONE BASE
" M
IN
1'-0"
1'-0"
BRICK OR BLOCK
4'-0" DIA.
EARTH FILL
EARTH FILL
4" HOSE BIBB W/ VACUUM
BREAKER TAPPED TO BOTTOM
PART OF WATER MAIN
6'' PERFORATED PVC PIPE W/ END CAP.
BACKFILLED W/ #57 TO SUBGRADE AND WRAP
WITH NON/WOVEN FILTER FABRIC. INSTALL AT
1% SLOPE AND EXTEND LENGTH TO
DAYLIGHT TO DRAIN.
6 SCALE: N.T.S.
DRAIN VAULT FOR WATER MAIN
PRECAST CONCRETE MANHOLE
WITH "DOG-HOUSE" OPENINGS
FOR WATER MAIN. MANHOLE
SHALL REST UPON BRICK OR
BLOCK BASE AND SHALL NOT
CONTACT WATER MAIN
PRECAST
CONCRETE
LID
NO LEAD BRASS VACUUM
BREAKER
" M
IN
. 3
6" M
AX
#57 LIMESTONE
1" WATER LINE
2 SCALE: 1"=1'
LEAD-FREE, FREEZE PROOF "POTABLE" HYDRANT
ZURN WILKINS 700 XL DUAL CHECK
VALVE BACKFLOW PREVENTER OR
EQUIVALENT WITH THREADED
ADAPTERS AS REQUIRED
1" FORD CURB STOP VALVE OR
EQUIVALENT WITH THREADED
ADAPTERS AS REQUIRED
FORD TYPE A MODULAR METER PIT COVE
(FRAME AND LID COMBINED) 18" LID ON
18" METER PIT TILE OR EQUIVALVENT
MIN 6" x 6" x 4' Ø PRE-CAST
CONCRETE RING
DRAIN HOLE
FROST LINE
M
IN
1" STANDPIPE
HYDRANT CONNECTION PIECE
NO-LEAD 3/4” Any Flow® FROST-PROOF
YARD HYDRANT PART# AFNL7503
MIN. 3-FEET BURY DEPTH, 1" STANDPIPE
AND 3/4" HOSE THREADED OUTLET
REVISED DETAIL 2 10/29/26
| Addendum Three |
| Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings. |
| END OF ADDENDUM |
Addendum 03