Addendum One .pdf
PDF 187 KB Posted
- Attached to
- RFB-243-24 DJJ Chiller Replacement NDC
- Solicitation number
- RFB 785 2500000094 2
- Issued by
- Cumberland County, Kentucky
About this file
This is Addendum One to an Invitation to Bid (RFB-243-24) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for the Department for Juvenile Justice. The project involves chiller replacement at the Northern Youth Development Center located at 15600 Turner Road in Crittenden, Kentucky (Kenton County). The original bid date has been moved to September 13, 2024 at 1:30 P.M. Eastern Time. Bidders must conform to the changes outlined in this addendum, which become binding upon the contract to be issued. Additional specifications and drawings will be distributed by Lynn Imaging and must be incorporated into all bids submitted.
The addendum establishes two primary modifications to the contract documents. Item One requires that the DDC Control System (Specification 230923) reuse the existing control system without upgrades, with all new mechanical equipment configured to include BacNet Communication Interface modules to communicate with the existing system using its current protocol. Item Two adds detailed specifications for steel pipe and fittings to the Hydronic Piping specification (Specification 232113), including requirements for ASTM A 53/A 53M black steel pipe with plain ends, Victaulic grooved mechanical-joint fittings and couplings, and wrought-steel fittings with ASTM A 234/A 234M specifications and ASTM B16.5 flanges with butt welding end connections and raised face facings.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2500000094_2_SO_FORM.PDF | ||
| Final_RFB_785_2500000094_1_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-243-24
FOR: Chiller Replacement Northern Youth Development Center Department for Juvenile Justice Crittenden, Kentucky
DATE: September 5, 2024
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
Item 2: Official Bid date has moved to September 13, 2024 @ 1:30 P.M. Eastern Time
END OF ADDENDUM
Invitation to Bid No. RFB-243-24 For: Chiller Replacement Northern Youth Development Center Department for Juvenile Justice Crittenden, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
E-TECH CONSULTANTS, PLLC
Consulting Engineers
378 Park Avenue Lexington, KY 40502 Ph: (859) 254-4200
PROJECT: RFB-543-24
Project #523-CB5B-NK15-00
DJJ – NORTHERN YDC CHILLER REPLACEMENT
15600 Turner Road
Kenton County, Crittenden, KY 41030
ADDENDUM ITEMS
The following items shall be included in the Contract Documents for this Project.
ITEM NO. ONE (1)
SPECIFICATION 230923 – DDC CONTROL SYSTEM
- Refer to Specification, Paragraph 2.0 Communication o The intent of this specification is to reuse the existing control system and not provide upgrade of the system, but to communicate with the new mechanical equipment in the existing communication protocol. All new equipment are to have BacNet Communication Interface modules.
Attachments: None Drawings: None
ITEM NO. TWO (2)
SPECIFICATION 232113 – HYDRONIC PIPING
- Refer to Specification, Paragraph 2.1 Chilled Water & Boiler Hot Water Piping:
o Add the following to this Specification and to the Contract Documents in its entirety, including related drawings:
▪ B. STEEL PIPE AND FITTINGS
• Steel Pipe: ASTM A 53/A 53M, black steel with plain ends;
welded and seamless, Grade B, and wall thickness as indicated in "Piping Applications" Article.
• Grooved Mechanical-Joint Fittings and Couplings: Victaulic
• Wrought-Steel Fittings and Wrought Cast and Forged Flanges and Flanged Fittings: ASTM A 234/A 234M, wall thickness to match adjoining pipe; ASTM B16.5 including bolts, nuts, and gaskets of the following material group, end connections, and facings:
o 1. Material Group: 1.1 o End Connections: Butt welding o Facings: Raised face
Attachments: None Drawings: None
END