This Addendum No. 1 pertains to a design change notification for an Invitation to Bid (RFB-171-26) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for the replacement of building automation systems at General Butler State Resort Park in Carrollton, Kentucky. The project involves the replacement of temperature control and HVAC systems across multiple buildings including the Main Lodge, Conference Center, Wood Wing Guest Building, and Woodland Business Building. The original bid date of January 22, 2026, has been moved to January 30, 2026, at 1:30 P.M. Eastern Time, with call-in information remaining unchanged. The addendum provides clarification on scope exclusions through redline markups on project drawings and specifications, utilizing 60% transparent red shaded boxes to indicate work, equipment, and systems explicitly excluded from the contract scope that shall not be priced or carried as alternates.
The addendum emphasizes that all work outside the 60% transparent red shaded boxes remains part of the Contract Documents and that contractors are responsible for reviewing all redline changes not marked as excluded scope and incorporating them into their bids accordingly. The document includes comprehensive mechanical and electrical schedules, control diagrams, and installation details for HVAC equipment including water source heat pumps, rooftop units, split systems, furnaces, boilers, cooling towers, and related controls integrated into a new Building Automation System (BAS) to be connected to an existing Kentucky State Parks cloud-based server. All other requirements of the drawings, specifications, and previously issued addenda remain unchanged and in full force, with bidders required to review all sheets in Addendum No. 1 to ensure proper interpretation of the revised scope and pricing exclusions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2600000302_2_SO_FORM.PDF | ||
| Final_RFB_785_2600000302_1_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-171-26
FOR: Replace Building Automation Systems General Butler State Resort Park Department of Parks Carrollton, Kentucky
DATE: January 22, 2026
RFB-785-2600000302
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
Item 2: Official Bid Date has been moved to January 30, 2026, at 1:30 P.M. Eastern Time. Call in Information will remain the same.
END OF ADDENDUM
Invitation to Bid No. RFB-171-26 For: Replace Building Automation Systems General Butler State Resort Park Department of Parks Carrollton, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
Addendum #1 Summary:
Dear Bidders, This addendum is issued to clarify the intent of the redline mark-ups included in Addendum No. 1 Drawings for the General Butler – TCC Replacement project .
The redline mark-ups shown on the drawings are provided for coordination and scope clarification purposes only.
Please note the following key guidance when preparing pricing:
1. Redline Mark-Ups (General):
Redline revisions identify changes, clarifications, or areas of review relative to the previously issued documents. Contractors shall review all redline notes, callouts, and revisions on each affected sheet to understand the revised intent of the design.
2. 60% Transparent Red Boxes – Not in Scope:
Any work, keynotes, equipment, piping, ductwork, controls, devices, or systems enclosed within 60% transparent red shaded boxes is explicitly excluded from the project scope.
o Items shown within these shaded areas are not required, o Shall not be included in bids, and o Shall not be priced or carried as alternates.
3. Scope Outside Red Shaded Areas:
All work outside of the 60% transparent red shaded boxes remains part of the Contract Documents unless otherwise noted. Contractors are responsible for incorporating all applicable redline changes that are not shaded as excluded scope.
4. No Change to Remaining Contract Requirements:
Except as clarified above, all other requirements of the drawings, specifications, and previously issued addenda remain unchanged and in full force.
Bidders are responsible for reviewing all sheets included in Addendum No. 1 to ensure proper interpretation of the revised scope and pricing exclusions.
Should there be any questions regarding the intent of the redline mark-ups or shaded exclusions, submit requests for clarification in accordance with the Instructions to Bidders.
Sincerely, Gary Hagan , PE
HVAC HYDRONIC SYMBOLS AND ABBREVIATIONS
PIPING SYMBOLS
- GATE SOLENOID ACTUATED
VALVE
- CHECK VALVE
- TRIPLE DUTY VALVE
- THREE WAY AUTOMATIC
CONTROL VALVE
- THREE WAY SOLENOID
ACTUATED VALVE
- AUTOMATIC AIR VENT.
- MANUAL AIR VENT.
- SPHERICAL RUBBER
VIBRATION ISOLATOR
- STEEL FLEXIBLE CONNECTOR
- SUCTION DIFFUSER
TDV
AAV
MAV
- HEAT TRACE WITH JACKET FOR
EXTERIOR PIPING LINES
- FLOW SWITCH
HT
FS
AABC ASSOCIATED AIR BALANCE COUNCIL
ABV ABOVE
ACT ACOUSTICAL CEILING TILE
AD ACCESS DOOR
ADDT'L ADDITIONAL
AFF ABOVE FINISHED FLOOR
AMB AMBIENT
AUX CD AUXILIARY CONDENSATE
BOD BOTTOM OF DUCT
BPD BAROMETRIC OR BACKPRESSURE DAMPER
BFP BACKFLOW PREVENTOR
BHP BRAKE HORSEPOWER
BOP BOTTOM OF PIPE
BOS BOTTOM OF STEEL
BTUH BRITISH THERMAL UNITS PER HOUR
CA COMBUSTION AIR
CAD CEILING AIR DIFFUSER
CAL COMBUSTION AIR LOUVER
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CONC CONCRETE
COND CONDENSING
CONN CONNECT
CONT CONTINUATION
CSR CEILING SUPPLY REGISTER
CO2 CARBON DIOXIDE SENSOR
CPVC CHLORINDATED POLY VINYL CHLORIDE
DB DRY BULB
dB DECIBEL
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DIFF DIFFERENCE
DISC SW DISCONNECT SWITCH
DN DOWN
DP DEW POINT
DWG DRAWING
DTL DETAIL
DX DIRECT EXPANSION
EA EXHAUST AIR
EAL EXHAUST AIR LOUVER
EAR EXHAUST AIR REGISTER
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
ELEV ELEVATION
EMS ENERGY MANAGEMENT SYSTEM
EEA EXISTING EXHAUST AIR (GRILLE)
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ERA EXISTING RETURN AIR (GRILLE/DIFFUSER)
ESA EXISTING SUPPLY AIR (GRILLE/DIFFUSER)
ESP EXTERNAL STATIC PRESSURE
EXIST EXISTING
FD FIRE DAMPER
FLR FLOOR
FPM FEET PER MINUTE
FRR FLOOR RETURN REGISTER
FSR FLOOR SUPPLY REGISTER
F&I FURNISHED & INSTALLED
FRPM FAN REVOLUTIONS PER MINUTE.
GA GAUGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
H HUMIDISTAT, RELATIVE HUMIDITY SENSOR
HEPA HIGH EFFICIENCY PARTICULATE AIR FILTER
HP HORSEPOWER
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LB POUND
LBG LINEAR BAR GRILLE
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MD MANUAL DAMPER
MFGR MANUFACTURER
MIN MINIMUM
NG NATURAL GAS
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OA OUTSIDE AIR
OAL OUTDOOR AIR LOUVER
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OF OVERFLOW
OPNG OPENING
ORIG ORIGINAL
ΔP PRESSURE DIFFERENCE
PC PLUMBING CONTRACTOR
PROVIDEFURNISH & INSTALL
QTY QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RAR RETURN AIR REGISTER
RBF ROUTE BELOW FLOOR
RAF ROUTE ABOVE FLOOR
RAC ROUTE ABOVE CEILING
REF REFER/REFERENCE
RLINES REFRIGERANT LINES
REV ROOF EXHAUST VENTILATOR
SA SUPPLY AIR
SAR SUPPLY AIR REGISTER
SC SHADING COEFFICIENT
SD SPLITTER DAMPER
SD SMOKE DAMPER
M EXTERNAL STATIC PRESSURE
SMACNA
SHEET METAL & AIR CONDITIONING
CONTRACTORS NATIONAL ASSOC.
SPEC SPECIFICATION
ST SOUND TRAP
SQ FT SQUARE FEET
SQ IN SQUARE INCHES
STN SECTION
T THERMOSTAT
Ts TEMPERATURE SENSOR
TCC
TEMPERATURE CONTROL
CONTRACTOR
ΔT TEMPERATURE DIFFERENCE
TAG TRANSFER AIR GRILLE
TOS TOP OF STEEL
TV TURNING VANE
TYP TYPICAL
T&P TEMPERATURE AND PRESSURE
UG UNDERGROUND
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
VTR VENT THROUGH ROOF
WB WET BULB
WG WATER GAUGE
WRG WALL RETURN AIR GRILLE
WRR WALL RETURN AIR REGISTER
WSR WALL SUPPLY REGISTER
AAV AUTOMATIC AIR VENT
BD BLOW-DOWN PIPING
BFP BOILER FEED PUMP
BFV BUTTERFLY VALVE
CDWR CONDENSER WATER RETURN
CDWS CONDENSER WATER SUPPLY
CHR CHILLED/HOT WATER RETURN
CHS CHILLED/HOT WATER SUPPLY
CHWP CHILLED/HOT WATER PUMP
CDR CONDENSATE RETURN
CTR COOLING TOWER RETURN
CTS COOLING TOWER SUPPLY
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
EWT ENTERING WATER TEMPERATURE
FT HD FEET HEAD
FS FLOW SWITCH
FW FEEDWATER
FWP FEED WATER PUMP
F&T FLOAT AND THERMOSTATIC
GLY GLYCOL
GV GATE VALVE
HPS HIGH PRESSURE STEAM
HW HOT WATER
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
LWT LEAVING WATER TEMPERATURE
MPS MEDIUM PRESSURE STEAM
MV MOTORIZED VALVE
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPSH NET POSITIVE SUCTION HEAD
OS&Y OUTSIDE SCREW & YOLK
PRV PRESSURE REDUCING VALVE
PSIA POUNDS/SQUARE INCH - ABSOLUTE
PSIG POUNDS/SQUARE INCH - GAUGE
PVC POLYVINYL CHLORIDE
RED REDUCER
TDH TOTAL DYNAMIC HEAD
TOL THREAD-O-LET
TXV THERMAL EXPANSION VALVE
VB VACUUM BREAKER
WC WATER CHILLER
ZV ZONE VALVE
• SYMBOLS USED BUT NOT LISTED HERE SHALL BE DEFINED ELSEWHERE IN THE BID DOCUMENTS. IF NOT, CONTACT THE
ENGINEER FOR CLARIFICATION PRIOR TO BID OPENING.
• LIST OF ABBREVIATIONS, ACRONYMS, AND SYMBOLS IS A STANDARD LIST. NOT ALL SYMBOLS ARE USED ON THIS PROJECT.
NOTE:
THERMOSTAT
CONNECT NEW MATERIAL TO EXISTING
MATERIAL
SUPPLY / OUTSIDE AIR DUCT UP
SUPPLY / OUTSIDE AIR DUCT DOWN.
RETURN AIR DUCT UP.
RETURN AIR DUCT DOWN.
EXHAUST / COMBUSTION AIR DUCT UP.
EXHAUST / COMBUSTION AIR DUCT DUCT
DOWN.
DUCT OFFSET UP OR DOWN WITH TWO
SMOOTH RADIUS FITTINGS.
MANUAL VOLUME DAMPER (OPPOSED
BLADE)
- BRANCH DUCT TAKE-OFF WITH
BALANCING DAMPER; REFER TO DETAILS
HEREIN FOR FITTING REQUIREMENTS.
- CEILING AIR DIFFUSER
- EXHAUST AIR GRILLE
- LINEAR SLOT DIFFUSER
(SUPPLY OR RETURN)
- FIRE DAMPER - (VERTICAL OR
HORIZONTAL). INCLUDE DUCT ACCESS
DOOR & CEILING/WALL ACCESS DOOR.
- FIRE / SMOKE COMBINATION DAMPER -
(VERTICAL OR HORIZONTAL). INCLUDE
DUCT ACCESS DOOR & CEILING/WALL
ACCESS DOOR.
- MOTOR OPERATED DAMPER - LOCATE IN
ACCESSIBLE LOCATION. WHERE
INSTALLED BEHIND DRYWALL, PROVIDE
ACCESS DOOR IN CEILING/WALL.
- CONDENSATE DRAIN PIPING; USE
SANITARY WASTE FITTING. (45° WYES;
DO NOT USE 90° ELLS OR TEES)
- PIPE UP
- PIPE DOWN
CD
DUCTWORK AND ACCESSORIES
ELBOW WITH TURNING VANES
• SYMBOLS USED BUT NOT LISTED HERE SHALL BE DEFINED ELSEWHERE IN THE BID DOCUMENTS. IF NOT, CONTACT THE
ENGINEER FOR CLARIFICATION PRIOR TO BID OPENING.
• LIST OF ABBREVIATIONS, ACRONYMS, AND SYMBOLS IS A STANDARD LIST. NOT ALL SYMBOLS ARE USED ON THIS PROJECT.
NOTE:
PIPING ABBREVIATIONS
HVAC AIRSIDE SYMBOLS AND ABBREVIATIONS
DUCTWORK AND ACCESSORIES ABBREVIATIONS
T
- RETURN AIR GRILLE
- PRESSURE RELIEF VALVE
A. WHERE PIPING, DUCTWORK, ETC. IS SHOWN TO BE REMOVED, IT APPLIES
ONLY TO LINES SERVING FIXTURES, SUPPLIES, RETURNS, OUTLETS,
EQUIPMENT, ETC. WHICH ARE TO BE REMOVED. DO NOT DISCONNECT ANY
MAINS OR BRANCH LINES SERVING ITEMS WHICH ARE TO REMAIN.
B. CARE SHOULD BE TAKEN BY ALL CONTRACTORS TO AVOID DAMAGING OR
DISTURBING EXISTING CONSTRUCTION WHICH IS INDICATED TO REMAIN.
CONTRACTORS SHALL BE RESPONSIBLE FOR MAKING ANY REPAIRS
NECESSARY TO RECTIFY DAMAGE AND RESTORE EXISTING
CONSTRUCTION TO UNDAMAGED STATE UPON COMPLETION OF WORK AT
NO EXPENSE TO THE OWNER.
C. ALL CONTRACTORS SHALL THOROUGHLY FAMILIARIZE THEMSELVES WITH
ALL ARCHITECTURAL DRAWINGS AND DETAILS PRIOR TO BEGINNING
CONSTRUCTION FOR COORDINATION OF ALL DEMOLITION WORK FOR EACH
RESPECTIVE TRADE.
D. PRIOR TO BEGINNING DEMOLITION WORK, EACH TRADE SHALL BE
RESPONSIBLE FOR OBTAINING ALL NECESSARY PERMITS AS REQUIRED BY
LOCAL AND STATE AUTHORITIES, CODES AND ORDINANCES.
E. ALL CONTRACTORS SHALL REFER TO NEW CONSTRUCTION DRAWINGS
AND SPECIFICATIONS PRIOR TO BEGINNING DEMOLITION WORK FOR
COORDINATION WITH SAME.
F. UNLESS NOTED OTHERWISE, SHOWN OR SPECIFIED, ALL MATERIALS AND
EQUIPMENT REMOVED OR DEMOLISHED (EXCEPT THAT WHICH IS TO BE
SALVAGED OR RELOCATED) AS DIRECTED BY DRAWINGS AND
SPECIFICATIONS, SHALL BECOME THE PROPERTY OF THE CONTRACTOR
AND SHALL BE LEGALLY DISPOSED OF.
G. ALL PIPING, ETC. WHICH IS REQUIRED TO BE CUT SHALL BE CUT FLUSH
WITH FINISHED FLOORS/WALLS. ALL CUTTING AND PATCHING OF EXISTING
FLOORS/WALLS SHALL BE BY EACH CONTRACTOR.
H. CONTRACTOR SHALL GIVE A MINIMUM NOTICE OF 48 HOURS TO GENERAL
CONTRACTOR AND OWNER PRIOR TO SHUT-DOWN OF ANY EXISTING
UTILITIES, PIPING SYSTEMS, ETC.
I. CONTRACTOR SHALL VISIT SITE PRIOR TO SUBMITTING BID TO CONFIRM
EXISTING CONDITIONS INDICATED. CONTRACTOR SHALL INCLUDE ALL
REQUIRED DEMOLITION.
J. THE FOLLOWING LIST OF ITEMS SHALL BE TURNED OVER TO THE OWNER
WHEN REMOVED FROM SERVICE: VALVE AND DAMPER ACTUATORS,
TRANSDUCERS, CONTROL PANELS, CONTROL MODULES, AND POWER
TRANSFORMERS.
GENERAL DEMOLITION NOTES
- BALL VALVE
- GLOBE VALVE
- GLOBE VALVE WITH
OUTSIDE SCREW & YOKE
- GATE VALVE
- GATE VALVE WITH
OUTSIDE SCREW & YOKE
- GATE AUTOMATIC
CONTROL VALVE
- PIPING WITH
DIRECTION OF FLOW
- PIPING DOWN
- PIPING UP
- BUTTERFLY VALVE -
PIPES 2 1/2" AND LARGER
- BUTTERFLY AUTOMATIC
CONTROL VALVE
- BUTTERFLY SOLENOID
ACTUATED VALVE
FS
FD
DN
UP
M
ALL EXISTING HVAC EQUIPMENT TO REMAIN SHALL BE PRE-TESTED.
REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
AABC REPORTS SHALL BE PROVIDED FOR EXISTING EQUIPMENT,
EACH AIR TERMINAL UNIT, WATER PRESSURE RATES, AIR PRESSURE
RATES, AIRFLOW RATES, AND WATER FLOW RATES FOR EACH
TERMINAL UNIT/AHU.
UPON COMPLETION OF NEW WORK, EACH SYSTEM SHALL BE
RETESTED AND ANY DEVIATIONS FROM DESIGN OR ORIGINAL VALUES
SHALL BE NOTED. WHERE POSSIBLE PROVIDE RECOMMENDATIONS
TO CORRECT DEVIATIONS
EXISTING AIR DISTRIBUTION DRAWINGS WILL BE PROVIDED FOR TAB
CONTRACTORS USE.
TEST & BALANCE NOTES
LIMIT OF DEMOLITION
A. ENGINEERS WILL MAKE PERIODIC VISITS DURING CONSTRUCTION TO REVIEW INSTALLATION COMPLIANCE WITH
DRAWINGS, DETAILS, AND SPECIFICATIONS. ANY DEVIATIONS FROM THE DRAWINGS, DETAILS, AND SPECIFICATIONS
SHALL BE CORRECTED AT NO ADDITIONAL COST AND NO ADDITIONAL TIME TO THE CONSTRUCTION SCHEDULE. THE
ENGINEER WILL NOT INDICATE ALL LOCATIONS OF THE DEVIATIONS, IT IS THE CONTRACTOR’S RESPONSIBILITY TO
INSTALL THE SYSTEMS IN COMPLIANCE WITH THE DRAWINGS, DETAILS, AND SPECIFICATIONS. THE CONTRACTOR
SHALL CORRECT ALL DEVIATIONS, EVEN IF THEY ARE NOT SPECIFICALLY INDICATED IN FIELD REPORTS AND/OR
PUNCH LISTS.
B. HVAC CONTRACTOR SHALL COORDINATE DUCT, DIFFUSERS, REGISTERS AND GRILLES WITH LIGHT FIXTURE AND
SPRINKLER HEAD LOCATIONS.
C. CONTRACTOR SHALL COORDINATE ROUTING OF DUCTWORK WITH ALL OTHER TRADES PRIOR TO COMMENCING
INSTALLATION.
D. CONTRACTORS SHALL COORDINATE NEW/RE-WORKED DUCTWORK WITH EXISTING BEAMS, JOISTS, ETC. TO AVOID
CONFLICTS. ADJUST DUCT ROUTING AS REQUIRED TO ACCOMMODATE EXISTING STRUCTURAL CONDITIONS.
E. ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS, CEILINGS, AND FLOORS TO BE FIRESTOPPED. ALL
PENETRATIONS THROUGH NON-FIRE RATED FLOORS SHALL BE FIRESTOPPED IN ACCORDANCE WITH LOCATION
CODES.
F. FLEXIBLE DUCT TO BE A MAXIMUM OF 5'-0" IN LENGTH UNLESS OTHERWISE NOTED. CRIMPING OF FLEXIBLE DUCT
WILL NOT BE ACCEPTED.
G. ALL DIFFUSERS, REGISTERS, AND GRILLES SHALL BE FURNISHED WITH OPPOSED BLADE DAMPERS UNLESS
OTHERWISE NOTED. SURFACE MOUNTED CEILING DIFFUSERS SHALL BE PROVIDED WITH FULLY INSULATED BACKING.
H. ALL DUCTS PENETRATING FIRE RATED WALLS, CEILINGS, ETC. TO HAVE FIRE DAMPERS AND ACCESS DOORS.
REFERENCE HVAC SPECIFICATIONS.
I. THE MECHANICAL CONTRACTOR SHALL PROVIDE STARTERS FOR ALL HVAC EQUIPMENT. THE ELECTRICAL
CONTRACTOR SHALL MOUNT AND CONNECT STARTERS.
J. ALL DUCT CONNECTIONS TO AIR HANDLING EQUIPMENT (FANS, ETC.) SHALL HAVE NEOPRENE FLEXIBLE
CONNECTIONS FURNISHED AND INSTALLED COMPLETE BY THE MECHANICAL CONTRACTOR.
K. ALL 90 DEGREE ELBOWS SHALL BE INSTALLED WITH TURNING VANES; UNLESS OTHERWISE NOTED. THIS INCLUDES
VERTICAL AND SINGLE LINE ELBOWS ON THE FLOOR PLANS WHERE TURNING VANES ARE NOT SHOWN.
L. ALL EXHAUST DISCHARGES AND GAS FLUES WHERE INDICATED SHALL BE LOCATED A MINIMUM OF 10'-0" AWAY FROM
OUTSIDE AND COMBUSTION AIR INTAKES UNLESS LOCAL AND STATE CODES MANDATE ADDITIONAL DISTANCE.
M. CONTRACTOR SHALL VERIFY ELECTRICAL CHARACTERISTICS OF ALL MECHANICAL EQUIPMENT WITH THE
ELECTRICAL CONTRACTOR PRIOR TO PLACING EQUIPMENT ON ORDER.
N. WHERE WALL TYPE LOUVERS ARE INDICATED, MECHANICAL CONTRACTOR SHALL SEAL WATER-TIGHT ALL AROUND
LOUVER WITH SILICON CAULKING. CONTRACTOR SHALL COORDINATE PAINTING REQUIREMENTS FOR LOUVERS
WITH GENERAL CONTRACTOR PRIOR TO SUBMITTING BID.
O. EACH CONTRACTOR SHALL SEAL ALL EXTERIOR WALL PENETRATIONS IN WATER-TIGHT MANNER. CONTRACTOR
SHALL INSTALL PIPE SLEEVES IN ALL EXTERIOR WALL/FOUNDATION PENETRATIONS. CUTTING AND SLEEVING FOR
INSTALLATION SHALL BE COORDINATED WITH GENERAL CONTRACTOR AND ARCHITECT PRIOR TO COMMENCING
WORK.
P. INSTALL BALANCING DAMPERS IN ALL BRANCH DUCTS (SA/RA/OA/EA SYSTEMS). BALANCING DAMPERS SHALL BE
INSTALLED WITH INSULATION STANDOFFS AND LOCKING QUADRANTS FOR BALANCING.
Q. THERMOSTATS, TEMPERATURE SENSORS, TRANSFORMERS AND LOW VOLTAGE WIRING SHALL BE FURNISHED AND
INSTALLED BY THE TEMPERATURE CONTROLS CONTRACTOR. THERMOSTATS/SENSORS TO BE MOUNTED AT 44" AFF
TO CENTER OF DEVICE.
R. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST INTERNATIONAL ENERGY CONSERVATION CODE, NATIONAL
ELECTRIC CODE, NFPA, ALL LOCAL AND STATE CODES.
S. ELECTRICAL CONTRACTOR SHALL VISIT AND EXAMINE THE SITE PRIOR TO SUBMITTING BID TO BECOME FAMILIAR
WITH EXISTING CONDITIONS. NO ALLOWANCE SHALL BE MADE FOR EXISTING CONDITIONS NOT KNOWN TO THE
CONTRACTOR.
T. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FEES, PERMITS AND LICENSES FOR THE COMPLETE
INSTALLATION OF HIS WORK. DRAWINGS ARE DIAGRAMMATIC REPRESENTATION OF THE WORK AND INDICATES
GENERAL ARRANGEMENT. SEE ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS.
U. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK
NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF
THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER.
V. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEERS PRIOR TO PURCHASING AND INSTALLING ANY EQUIPMENT.
W. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONED
DRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.
X. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE
CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS NEEDED.
Y. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE
NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE
REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES
OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT
SHALL APPLY.
Z. FOR BRANCH CIRCUIT REQUIRING A NEUTRAL CONDUCTOR, A DEDICATED NEUTRAL CONDUCTOR SHALL BE
PROVIDED.
AA. INSTALL EQUIPMENT, MATERIALS, ETC., IN STRICT ACCORD WITH MANUFACTURERS' RECOMMENDATIONS AND
DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEERS
PRIOR TO INSTALLATION FOR CLARIFICATION.
AB. COORDINATE EXACT PHASING OF ALL WORK WITH GENERAL CONTRACTOR.
AC. ELECTRICAL CONTRACTOR SHALL VERIFY EXACT MOUNTING LOCATION AND CONNECTION REQUIREMENTS OF ALL
PLUMBING/MECHANICAL EQUIPMENT WITH PLUMBING/MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
AD. CONDUCTORS SHALL BE COPPER RATED NOT LESS THAN 600VOLTS, MINIMUM WIRE SIZE SHALL BE #12 AWG, TYPE
THHN OR THWN UNLESS OTHERWISE NOTED.
AE. E.C SHALL PROVIDE A TYPED LEDGER/CIRCUIT DIRECTORY IN PANELBOARD INDICATING TYPE OF LOAD AND
LOCATION FOR EACH BRANCH CIRCUIT BREAKER. PROVIDE ENGRAVED PHENOLIC NAMEPLATES FOR ALL
PANELBOARDS & DISCONNECT SWITCHES, UNLESS OTHERWISE NOTED.
AF. DISCONNECT SWITCHES, STARTERS, AND ASSOCAITED ELECTRICAL EQUIPMENT SERVING HVAC UNITS SHALL BE
MOUNTED ON WALLS OR PROVIDED WITH INDIVIDUAL STRUCTURAL SUPPORTS. ELECTRICAL EQUIPMENT SHALL
NOT BE MOUNTED DIRECTLY ON EQUIPMENT. ALL STRUCTURAL SUPPORTS FOR ELECTRICAL EQUIPMENT SHALL BE
PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL INCLUDE DESIGN FOR
ALL STRUCTURAL SUPPORT.
AG. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM
SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL
BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION
ON THE SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE ENGINEER.
AH. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC., FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THE
RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A
DEVIATION, WHETHER APPROVED BY THE ENGINEERS OR NOT, SHALL BE THE RESPONSIBILITY OF THE PURCHASER.
AI. ALL EXPOSED EQUIPMENT, MATERIALS, WIRING AND CABLING INSTALLED IN AIR-PLENUMS SHALL BE
"PLENUM-RATED".
AJ. FOR THE PURPOSES OF THESE DOCUMENTS, THE TERM "PROVIDE" SHALL BE INTERPRETED BY THE CONTRACTOR
AS "FURNISH AND INSTALL THE SPECIFIED SCOPE OF WORK, INCLUDING THE SUPPLY OF ALL MATERIALS AND
EQUIPMENT AS WELL AS THE COMPLETE INSTALLATION AND INTEGRATION INTO THIS PROJECT AND SHALL BE MADE
READY FOR ITS INTENDED USE.
AK. ELECTRICAL CONTRACTOR SHALL PROVIDE LAMICOID LABEL FOR ALL CONTROL PANELS, STARTERS, DISCONNECT
SWITCHES FOR HVAC UNITS AS WELL AS ON THE HVAC UNITS ASSOCIATED WITH THIS PROJECT INDICATING PANEL
FED FROM, CIRCUIT NUMBER AND BREAKER SIZE.
AL. NO MORE THAN THREE (3) PHASE CONDUCTORS SHALL BE COMBINED PER CONDUIT WITHOUT DERATING PER NEC.
ALL CONDUCTORS ARE COPPER.
AM. AMPACITY OF CONDUCTORS ARE SIZED BASED UPON NEC TABLE 310.16 USING 75 DEGREE COLUMN. CONTRACTOR
SHALL USE 60 DEGREE COLUMN FOR EQUIPMENT MARKED FOR USE WITH 60 DEGREE.
AN. VOLTAGE DROP SHALL BE CALCULATED PER NEC FOR CONDUCTORS EXCEEDING 50'-0" ON 120 VOLT AND 100'-0" ON
277 VOLT BRANCH CIRCUITS AND FEEDERS. ADJUST CONDUCTOR SIZE TO MEET NEC REQUIREMENTS.
AO. CONDUIT LISTED IS THE MINIMUM EMT SIZE ALLOWED BY NEC FOR THW/THHN INSULATED WIRE.
AP. EC SHALL COORDINATE WITH THE TCC FOR ALL 120V REQUIREMENTS TO CONTROLS AND INSTRUMENTATION FIELD
DEVICES AND EQUIPMENT PRIOR TO BID. EC SHALL PROVIDE ALL 120V CONNECTIONS AS NEEDED FROM EXISTING
120V CIRCUIT SERVING DEVICES BEING REPLACED OR FROM THE NEAREST CIRCUIT AVAILABLE. PRIOR TO
CONNECTING TO EXISTING CIRCUIT, EC SHALL MEASURE EXISTING CIRCUIT LOAD TO VERIFY THE ADDITIONAL LOAD
WILL NOT EXCEED 15A CONNECTED.
GENERAL PROJECT NOTES
ME010
MECHANICAL & ELECTRICAL INFORMATION
11/15/2025
10/10/202511/15/2025
WATER SOURCE HEAT PUMP SCHEDULE
MARK TONS
AIRFLOW FAN
GPM
WPD
(FT HD)
HEATING (WATER)
VOLTAGE MCA MOCP REMARKSSA
CFM
RA
CFM
OA
CFM
ESP
IN WG
FAN
SPEED
HP OR
HIGH
STATIC
OPTION
EAT °F
SENSIBLE
(MBH)
TOTAL
(MBH)
LAT °F
HEAT REJ
(MBH)
EAT °F MBH
LAT
°F
HEAT ABS
(MBH)
AC-2 20 8,000 6,000 2,000 2 1537 7.5 HP 60 17.6 79 203.3 257.4 58 307.1 55 195 77 136 208/3Ø/60 86.23 A 110 A 2, 3, 5, 6, 10, 11
GENERAL NOTES:
A. ESP DOES NOT INCLUDE INTERNAL PRESSURE LOSSES FOR COIL, FILTER OR CABINET CONFIGURATION
B. MOTORS ARE TO BE ECM WITH A MINIMUM OF 3 SPEED SETTINGS; UNLESS OTHERWISE SPECIFICALLY NOTED.
C. CAPACITIES INDICATED BASED ON 80°F EWT FOR COOLING, BASED ON 65°F EWT FOR HEATING.
D. FLEX HOSE KIT SIZE SHALL MATCH PIPE SIZE ON FLOOR PLANS. PROVIDE A CONCENTRIC REDUCER TO WSHP CONNECTION SIZE.
E. PROVIDE WITH SOUND ATTENUATION REDUCTION PACKAGE INCLUDING COMPRESSOR DISCHARGE MUFFLER, VIBRATION ISOLATION TO COMPRESSOR, WATER REFRIGERANT COIL, INSULATED COMPRESSOR ENCLOSURE AND UNIT BASE STIFFENERS.
F. LOW VOLTAGE TERMINAL STRIP FOR BAS CONTROL.
G. UNITS 7.5 TONS AND LARGER SHALL BE EQUIPED WITH DUAL COMPRESSORS AND CAPACITY MODULATION STRATEGY THAT ALLOWS OPERATION AT 20% CAPACITY.
H. BASIS OF DESIGN: TRANE. ADDITIONAL MFGRS TO BE VERIFIED BY MC: JCI, TRANE, BOSCH, DAIKIN
I. REFERENCE SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
J. WARRANTY: 3 YEAR PARTS AND LABOR. 5 YEAR COMPRESSOR.
K. EXISTING CONDENSER LOOP IS 40% PROPYLENE GLYCOL WITH 90°F EWT IN COOLING AND 45°F EWT IN HEATING.
REMARKS:
1. HORIZONTAL SUSPENDED UNIT; REFER TO FLOOR PLAN FOR DISCHARGE/INLET CONFIGURATION.
2. FLOOR SET VERTICAL UNIT; REFER TO FLOOR PLAN FOR DISCHARGE/INLET CONFIGURATION.
3. LINE SIZE SOLENOID VALVE, SLOW CLOSING, FAST OPENING.
4. END OF RUN UNIT; PROVIDE LINE SIZE THREE WAY SOLENOID VALVE.
5. UNIT SHALL BE PROVIDED WITH HOT GAS REHEAT SYSTEM FOR DEHUMIDIFICATION. HUMIDITY SENSORS SHALL BE LOCATED IN RETURN DUCTWORK FOR DEHUMIDIFICATION CONTROL.
6. WHERE VARIOUS LEAVING/RETURN AIR CONFIGURATIONS ARE REQUIRED. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO COORDINATE CONFIGURATION WITH ROOM LAYOUT.
7. DCV WITH CO2; REFER TO CONTROL DIAGRAM FOR MORE INFORMATION.
8. NOT USED
9. OA PROVIDED AT ROOM NEUTRAL FROM DOAU.
10. OA IS AMBIENT OUTDOOR AIR.
11. PROVIDE PREMIUIM EFFICIENCY MOTOR AND VFD DRIVE FOR FAN.
SCH2078
AIRSIDE INSULATION SCHEDULE
SYSTEM LOCATION INSULATED MATERIAL THICKNESS
INSTALLED
R-VALUE
INSULATION
JACKET
VAPOR
BARRIER
REMARKS
HVAC AIR SIDE:
SUPPLY AIR (50°F TO 65°F) INDOOR YES MINERAL FIBER 1" 4 FSK YES
SUPPLY AIR (50°F TO 65°F)
OUTDOOR
(ZONE 1 - 4)
YES ELASTOMERIC FOAM 3" 8 MTL YES
SUPPLY AIR (68°F & ABOVE)
OUTDOOR
(ZONE 1 - 4)
YES ELASTOMERIC FOAM 3" 8 MTL NO
RETURN AIR INDOOR YES MINERAL FIBER 1" 4 FSK NO
RETURN AIR
OUTDOOR
(ZONE 1 - 4)
YES ELASTOMERIC FOAM 3" 8 MTL NO
EXHAUST AIR INDOOR
YES,
SEE NOTE 4
MINERAL FIBER 1" 4 FSK NO 4
EXHAUST AIR OUTDOOR NO - - - - -
KITCHEN / GREASE EXHAUST ALL YES
FIRE-PROOF PRODUCT RATED;
ASTM E2336
FSK NO
MAKE-UP AIR (68°F to 105°F) INDOOR YES MINERAL FIBER 3" 6 FSK NO
MAKE-UP AIR (95°F & ABOVE) OUTDOOR YES ELASTOMERIC FOAM 3" 8 MTL NO
OUTSIDE AIR (AMBIENT) ALL YES MINERAL FIBER 1" 4 FSK NO
COMBUSTION AIR ALL YES MINERAL FIBER 1" 4 FSK NO 5
HVAC FLUID SIDE:
CONDENSATE LINES YES CLOSED CELL ELASTOMERIC 1/2" NONE YES 5
R.LINES - 1-1/4" AND SMALLER INDOOR YES CLOSED CELL ELASTOMERIC 1" NONE NO 3
R.LINES - 1-1/4" AND SMALLER OUTDOOR YES CLOSED CELL ELASTOMERIC 1" PVC YES
GENERAL NOTES:
A. REFERENCE FLOOR PLAN AND DRAWING DETAILS FOR SPECIAL CONDITIONS.
B. JACKET:
ASJ = ALL SERVICE JACKET
FSK = FOIL SCRIM KRAFT
MTL= METAL LAMINATE WITH FACTORY APPLIED ADHESIVE
LMN = FACTORY APPLIED EMBOSSED WHITE LAMINATE
C. INSULATION INSTALLED OUTDOORS SHALL BE PROVIDED WITH A WEATHER PROOF JACKET.
D. INSULATION THICKNESS IS BASED ON 1.0 PCF.
E. INSTALLED R-VALUE IS THE INSULATION REQUIREMENT AFTER COMPRESSION IN FIELD.
F. THIS SCHEDULE DOES NOT APPLY TO DOUBLE WALL DUCTWORK. REFER TO KEY NOTES OR DUCT MATERIAL SCHEDULE FOR DOUBLE WALL INSULATION REQUIREMENTS.
H. REFERENCE SPECIFICATION FOR ADDITIONAL REQUIREMENTS
REMARKS:
1. ATTIC SPACES ARE UNCONDITIONED AND VENTILATED SPACES THAT ARE OUTSIDE THE INSULATED PERIMETER OF THE BUILDING.
2. COAT WITH ANTI-MICROBIAL SEALANT. SEALANT SHALL ALSO BIND LOOSE FIBERS.
3. WHERE DUCT PENETRATES WALL, INSULATION CAN BE REDUCED TO 1" THICKNESS.
4. AT EXTERIOR WALLS/ROOF PENETRATIONS, EXHAUST AIR DUCTS SHALL BE EXTERNALLY INSULATED FOR THE FIRST (15) FIFTEEN FEET.
5. INSULATION IS REQUIRED FOR METAL DUCT/PIPE AND IS NOT REQUIRED ON PVC, CPVC, OR FABRIC DUCT.
SCH2040
SPLIT SYSTEM FURNACE SCHEDULE
(D/X COOLING WITH INDIRECT GAS FIRED HEAT)
MARK
FURNACE (FAC) CONDENSING UNIT
REMARKS
CFM COOLING FAN HEATING
VOLTAGE MCA MOCP MBH VOLTAGE MCA MOCP
SA RA OA
SENSIBLE
(MBH)
TOTAL (MBH) EAT LAT ESP HP FRPM MBH IN MBH OUT EAT LAT
GF-1A / CU-1A 900 725 175 22 34 79 / 66 55 / 55 0.8 1 1075 120 113.4 58 100 120/1Ø/60 14.1 15 36 208/3Ø/60 16.6 25 ALL
GF-1B / CU-1B 900 725 175 22 34 79 / 66 55 / 55 0.8 1 1075 120 113.4 58 100 120/1Ø/60 14.1 15 36 208/3Ø/60 16.6 25 ALL
GENERAL NOTES: ALL OUTDOOR AND INDOOR COMPONENTS TO BE OF THE SAME MANUFACTURERS. FURNISH UNITS WITH THE FOLLOWING.
A. MC SHALL SIZE R.LINES AND PROVIDE ALL ACCESSORIES REQUIRED BY MANUFACTURER TO MEET SCHEDULED CAPACITES WITH EXTENDED REFRIGERANT PIPE LENGTHS. R.LINE LOSS TO BE ADDED TO CAPACITY SCHEDULED.
B. INDOOR UNIT SHALL BE FURNISHED WITH THE FOLLOWING:
1. ELECTRICTRONIC IGNITION PILOT
2. AGA APPROVAL AND RATING
3. 100% SAFETY SHUT-OFF
4. FAN LIMIT CONTROL
5. FAN PRESSURE LOSS DOES NOT INCLUDE COOLING COIL AND FILTER PRESSURE LOSSES. MC SHALL CONSULT MFGR TO OBTAIN A FAN THAT WILL MEET THE TOTAL STATIC PRESSUREOF THE SYSTEM AT MEDIUM SPEED.
6. INDOOR FAN MOTOR RELAYS AND NECESSARY INTERLOCKING CONTROLS FOR OUTDOOR AND INDOOR OPERATION
7. UL LISTED COMPONENTS AND REFRIGERANT.
8. NONFERROUS DRAIN PAN AND CONNECTION.
9. INSULATED CABINET AND BAKED ENAMEL EXTERIOR FINNISH.
C. OUTDOOR UNIT SHALL BE FURNISHED WITH THE FOLLOWING:
1. WEATHERPROOF BAKED ENAMEL HOUSING WITH TOP DISCHARGE.
2. UL LISTED ELECTRICAL IN NEMA ENCLOSURE AND FACTORY WIRED UNITS RATED IN ACCORDANCE WITH AHRI 210, 340.
3. FACTORY ASSEMBLED AND TESTED HERMETIC COMPRESSOR. CONDENSER COIL. CONTROLS, AND CABINET RATED IN ACCORDANCE WITH AHRI STANDARD 210, 340, AND 270.
5. UNITS TO HAVE HIGH/LOW PRESSURE SWITCHES, ANTI-SHORT CYCLING DEVICE AND OVERLOAD PROTECTION.
6. LIQUID/SUCTION LINE SERVICE VALVES.
7. REFRIGERANT TO BE FACTORY TESTED AND CHARGED.
8. UNIT TO OPERATE AT PLUS/MINUS TEN PERCENT (+10%) OF RATED VOLTAGE.
9. SEER NOT LESS THAN 13
10. CONDENSER HAIL GUARDS
D. WARRANTY:
1. FURNACE: 10 YEAR HEAT EXCHANGER WARRANTY, 3 YEAR ON CONTROL BOARD,1 YEAR PARTS AND LABOR.
2. CONDENSING UNIT: 5 YEAR COMPRESSOR,1 YEAR PARTS AND LABOR.
E. DESIGN BASIS: TRANE. ADDITIONAL MFGRS TO BE VERFIED BY MC: CARRIER, YORK
F. REFERENCE SPECIFICATION FOR ADDITIONAL REQUIREMENTS
REMARKS:
1. VERTICAL AHU CONFIGURATION.
2. ECM MOTOR.
3. SIDE OR BOTTOM RETURN AIR DUCT CONNECTION COLLAR.
4. ONE INCH (1") DISPOSABLE FILTER & FILTER RACK. UPON COMPLETION OF THE PROJECT, CLEAN FILTERS SHALL BE INSTALLED.
5. CU WITH LOW AMBIENT COOLING TO 0°F.
6. PROVIDE TWINNING KIT.
SCH2056
HYDRONIC INSULATION SCHEDULE
SYSTEM LOCATION PIPE SIZE INSULATED MATERIAL THICKNESS
CONDUCTIVITY BTU
IN/ (H SF °F)
JACKET
VAPOR
BARRIER
HWS/HWR (105°F TO 200°F) INDOOR
1/2" TO 1-1/4" YES PREFORMED PIPE WRAP 1-1/2" 0.25-0.29 FSK NO
1-1/2" TO 8" YES PREFORMED PIPE WRAP 2" 0.25-0.29 FSK NO
HWS/HWR (105°F TO 200°F) OUTDOOR
1/2" TO 1-1/4" YES ELASTOMERIC WRAP 2" 0.25-0.29 ALUM NO
1-1/2" TO 8" YES ELASTOMERIC WRAP 2-1/2" 0.25-0.29 ALUM NO
CDS/CDR (45°F TO 105°F) GLYCOL FILLED ALL SIZES NO -- -- -- -- --
GENERAL NOTES:
A. REFERENCE SPECIFICATION FOR ADDITIONAL INSULATION REQUIREMENTS. REFERENCE FLOOR PLAN AND DRAWING DETAILS FOR SPECIAL CONDITIONS.
B. JACKET:
ASJ = ALL SERVICE JACKET
FSK = FOIL SCRIM KRAFT
MTL= METAL LAMINATE WITH FACTORY APPLIED ADHESIVE
LMN = FACTORY APPLIED EMBOSSED WHITE LAMINATE
C. INSULATION INSTALLED OUTDOORS SHALL BE PROVIDED WITH A WEATHER PROOF JACKET.
D. CHEMICAL TREATMENT PIPING AND MAKE UP WATER PIPING SHALL BE INSULATED TO MATCH THE SYSTEM INSULATION REQUIREMENTS HEREIN.
E. HYDRONIC SPECIALITIES, TANKS, AND EQUIPMENT ARE TO BE INSULATED TO MATCH THE SYSTEM INSULATION REQUIREMENTS HEREIN.
G. REFERENCE SPECIFICATION FOR ADDITIONAL REQUIREMENTS
REMARKS:
1. XXX
SCH2041
DUCT SILENCER SCHEDULE
MARK
BASIS OF
DESIGN
SYSTEM TYPE
FACE DIMENSIONS
(W X H)
OVERALL
LENGTH
CFM VELOCITY FPM PD
INSERTION LOSS (OCTAVE BAND) dB
REMARKS
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
ST-2 S SUPPLY AIR RECT 48"X16" 36 INCH 8000 1500 0.82 5 9 15 30 37 35 27 17 ALL
GENERAL NOTES:
A. DESIGN BASIS: IAC ACOUSTICS. ADDITIONAL MFGRS TO BE VERFIED BY MC: PRICE, RUSKIN
REMARKS:
1. RECTANGULAR INLET, RECTANGULAR OUTLET DUCT CONNECTIONS.
2. 22 GAUGE GALVANIZED SHEET METAL CASING WITH MASTIC FILLED SEAMS.
4. FIELD VERIFY HEIGHT AND FIT IN SHOP DRAWINGS COORDINATION PRIOR TO ORDERING SILENCERS.
5. RECTANGULAR DUCT FLANGE CONNECTIONS.
SCH2021
AIR DISTRIBUTION SCHEDULE
MARK
NECK / NOMINAL
SIZE
FACE SIZE CFM RANGE
MAX PD
(IN WG)
NOISE LEVEL
(NC / FPM)
STYLE MFR / MODEL
S-1 6"Ø
24" X 24"
0-99 H: 0.24
V: 0.043
H: --
V: NC-16
4 CONE PRICE / SCDA
S-2 8"Ø 100-249 H: 0.063
V: 0.104
H: NC-17
V: NC-27
S-3 10"Ø 250-399 H: 0.075
V: 0.122
H: NC-20
V: NC-29
S-4 12"Ø 400-599 H: 0.086
V: 0.141
H: NC-22
V: NC-31
S-5 14"Ø 600-899 H: 0.128
V: 0.209
H: NC-28
V: NC-35
R-1 / E-1 10"Ø 12" X 12" 0-300 0.013 300
CEILING EGG CRATE
WITH FRAME
PRICE / 80
SERIES
R-2 / E-2 12"Ø 24" X 12" 301-500 0.013 300
R-3 / E-3 14"Ø 24" X 24" 501-1000 0.013 300
R-4 / E-4 16"Ø TO 18"Ø 24" X 48" 1001-2000 0.013 300
R-5 / E-5 10" X 6" 10" X 6" 0-99 0.035 300
FIXED BLADE
45 DEG.
DEFLECTION 3/4"
BLADE SPACING
PRICE / 630
SERIES
R-6 / E-6 16" X 8" 16" X 8" 100-249 0.035 300
R-7 / E-7 18" X 12" 18" X 12" 250-399 0.035 300
R-8 / E-8 28" X 14" 28" X 14" 400-599 0.035 300
R-9 / E-9 40" X 18" 40" X 18" 1000-2000 0.062 400
GENERAL NOTES:
A. MANUFACTURER AND MODEL NUMBER LISTED IS BASIS OF DESIGN. PROVIDE PRODUCT WITH EQUAL PERFORMANCE AND SIZE.
B. COORDINATE MOUNTING TYPE WITH CEILING PLANS PRIOR TO ORDERING; REFER TO ARCHITECTURAL DRAWINGS.
C. ALL TYPES AND SIZES MAY NOT APPLY.
D. SYMBOL INDICATED ON DRAWING MAY NOT DEPICT ACTUAL SIZE; GRAPHICS MAY BE SHOWN LARGER FOR CLARITY ONLY.
E. NOISE LEVEL: "H" DENOTES DATA WITH HORIZONTAL THROW PATTERN. "V" DENOTES DATA WITH VERTICAL THROW PATTERN.
F. MANUFACTURERS: NAILOR, TITUS, TUTTLE & BAILEY, PRICE.
DIFFUSERS:
F. WHITE BAKED ENAMEL FINISH.
G. OPPOSED BLADE DAMPER ADJUSTABLE THROUGH THE FACE OF OUTLET.
H. SLOT DIFFUSERS MAY REQUIRE FIELD FABRICATED PLENUMS TO FIT; REFERENCE FLOOR PLAN FOR KEY NOTES WHERE FACTORY OR FIELD PLENUMS
ARE REQUIRED.
I. PROVIDE INSULATION BACKING FOR DIFFUSERS; INSULATION R-VALUE TO MATCH SYSTEM TYPE ON INSULATION SCHEDULE.
RETURN/EXHAUST AIR:
J. ALL GRILLES TO BE FURNISHED WITH BORDER/FRAME.
K. ALL GRILLES TO BE STEEL CONSTRUCTION, WHITE BAKED ENAMEL FINISH, WITH 1/2" X 1/2" EGG-CRATE GRID SPACING & 45 DEGREE DEFLECTION.
SCH2020
ME020
MECHANICAL SCHEDULES10/10/2025
10/10/2025
CONDENSATE DRAIN DETAIL
SCALE: NONE
UNION CLEANOUT:
FOR PVC CD, USE DIVERSITECH A/C EASY TEE
FOR COPPER CD, USE THREADED CAP;
REFER TO PIPE MATERIAL SCHEDULE FOR MATERIAL
TYPES ALLOWED ON EACH SYSTEM
FULL SIZE OF DRAIN
CONNECTION
PLUMBING HUB DRAIN; REFER
TO PLUMBING DRAWINGS FOR
LOCATION
MIN. 2" AIR
GAP
P-TRAP
2 IN. MIN.
COOLING COIL DRAIN
PAN
NOTE:
MC TO FURNISH ONE PORTABLE DRAIN GUN WITH TAPERED
FITTING TEE ON 3/8" TO 3/4" DRAIN OPENING. INCLUDE TWO
CO2 CARTRIDGES FOR EACH CONDENSATE TRAP ON
PROJECT.
2 IN. MIN.
DTL2083
1/8" SLOPE PER 12"
RETURN
SUPPLY
W
OG
C O
IL
WSHP HOSE KIT DETAIL
SCALE: NONE
FULL PORT BALL
VALVE WITH
MEMORY STOP
Y STRAINER WITH BLOW DOWN
VALVE WITH HOSE CONNECTION
REFER TO
SPECIFICATIONS FOR
PIPING MATERIAL
FSWT
UNION
FSWT
UNION
2 WAY AUTOMATIC
TEMPERATURE
CONTROL VALVE (60
PSIG CLOSE OFF
PRESSURE)
TEMPERATURE AND
PRESSURE GAUGE
WELLS (TYPICAL)
MEASURFLO WITH
TEMPERATURE AND
PRESSURE GAUGE
WELLS
DTL2186
DETAIL "A"
DETAIL "A"
REFRIGERANT LINE/CONDUIT PIPE PORTAL CURB DETAIL
SCALE: NONE
ABS PIPE PORTAL
COVER
GASKETED FASTENERS
MINIMUM TWO PER SIDE
STAINLESS CLAMP
FASTENERS
APPROXIMATELY 8"
O.C.
PIPE PORTAL
CURB BY M.C.
RIGID INSULATION
ROOF SHEATHING
WOOD FRAMING
LOOSE BATT
INSULATION
SUPPORT PIPES FROM STRUCTURE
PIPE PORTAL CAP
WATER CUT-OFF
MASTIC
FASTEN PER
ARCHITECTS
REQUIREMENTS
SINGLE PLY ROOF
MEMBRANE
LAP SEALANT
HOT AIR WELD
BONDING ADHESIVE
BASE MEMBRANE ATTACHMENT
REQUIRED FOR ROOF SYSTEM
ROOFING CONTRACTOR TO FLASH
AND COUNTERFLASH ALL ROOF
PENETRATIONS; COORDINATE
WITH G.C PRIOR TO SUBMITTING
BID
SNAP CAP
TO LOCK
NOTE:
MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL PIPE CURB; SIMILAR TO
PORTALS PLUS PIPE CURB OR EQUAL. COORDINATE SIZE OF CURB WITH ELECTRICAL
CONTRACTOR SO AS TO PROVIDE ADEQUATE CLEARANCE FOR REFRIGERANT LINES
AND CONDUIT.
DTL2124
FINISHED FLOOR
FURNACE
COOLING
COIL
VERTICAL GAS FURNACE WITH COOLING COIL DETAIL
SCALE: NONE
EXTEND REFRIGERANT LINES
AND CONNECT TO
CONDENSING UNIT COIL ON
ROOF
COOLING COIL
CONDENSATE DRAIN TRAP
CONDENSATE DRAIN
LINE; SPILL TO EXISTING
FLOOR DRAIN IN ROOM
1" THICK
NEOPRENE
VIBRATION
ISOLATORS
SUPPLY AIR DUCT;
PROVIDE TRANSITION
FROM UNIT TO DUCT SIZE
ON FLOOR PLANS
NEOPRENE FLEXIBLE
CONNECTOR
FLUE AND VENT;
TERMINATE WITH
CONCENTRIC VENT
KIT AT ROOF. REFER
TO VENT DETAIL
HORIZONTAL FILTER
HOUSING WITH RACK AND
DOOR GASKETS MCDANIELS
OR EQUAL
DTL2109
BLOWER
ACCESS
SUPPLY
AIR
VERTICAL WATER SOURCE HEAT PUMP DETAIL
SCALE: NONE
NEOPRENE FLEX
CONNECTION
EXISTING HOUSEKEEPING
PAD. INCREASE EXISTING
PAD DIMENSIONS TO BE 3"
LARGER THAN NEW UNIT,
ON ALL SIDES.
ELECTRICAL
CONNECTION
COMPRESSOR / CONTROL
ACCESS
CONDENSATE DRAIN LINE
CONNECTION. WITH
P-TRAP REFER TO FLOOR
PLAN FOR DRAIN LINE
ROUTING ISOLATOR
RETURN AIR PLENUM OR
DUCTWORK
FILTER HOUSING WITH
RACK AND DOOR GASKETS
"MCDANIEL ACG" OR
EQUAL
FLOAT SWITCH
AUXILIARY DRAIN PAN
SUPPLY/RETURN HOSE KIT
WITH SHUT-OFF VALVES
SW/RW
DTL2106
TWINNED FURNACE WITH COOLING COIL DETAIL
SCALE: NONE
TOP
SIDE
BOTTOM
FRONT
2'-10
2'-0
2'-01
2'-41
1'-11 4"
1'-8
1 12 2
4 4
3 3
1 1
2 2
0'-11
0'-1 4"
1'-63
1'-2 " 1'-01
FURNACE DRAIN
0'-43
1. FURNACE
2. COOLING COIL
3. RETURN OPENING
4. FLUE IN / OUT
5. REFRIGERANT LINE CONNECTIONS
6. COOLING COIL DRAIN
7. FURNACE DRAIN
INSTALLED WEIGHT: 160 LBS. FURNACE
65 LBS. COOLING COIL
FURNACE
COOLING COIL
TOP / BOTTOM
SIDE FRONT
2'-01
2'-2
1'-73 " 1'-103
1'-91
2'-0 2"
FURNACE / COOLING COIL
TWINNED CONFIGURATION
FURNACE
COOLING
COIL
CONDENSATE DRAIN
LINE; SPILL TO
EXISTING FLOOR
DRAIN IN ROOM
(AC-2)
AIR CONDITIONING UNIT AC-2 DETAIL
SCALE: NONE
6'-2
1'-6"
2'-0"
3'-0"
2'-0"
2'-7 2"
0'-1"
5'-8"
2'-3
0'-2 2"
0'-4 4"
1'-0
1'-11 2"
1-1/2" WATER OUT
3/4" DRAIN
1-1/2" WATER IN
1. TOP OPENINGS 15-5/8" X 15-7/8"
2. RETURN OPENING 74-1/2" X 38-7/8"
3. CONTROL PANEL
2'-71 " 1'-63
0'-11
EXISTING HOUSEKEEPING
PAD. INCREASE EXISTING
PAD DIMENSIONS TO BE 3"
LARGER THAN NEW UNIT,
ON ALL SIDES.
MASONRY WALL RA GRILLE INSTALLATION DETAIL
SCALE: NONE
EXISTING SPLIT FACE
MASONRY BLOCK
WALL
2" X 8" X 3
16" WALL WELDED TUBE
STEEL TO FRAME OPENING.
PAINT TO MATCH LOBBY DOOR /
WINDOW FRAMES
RIGID RECTANGULAR DUCT.
RA GRILL SHALL BE MOUNTED
TO TUBE STEEL FRAME USING
SCREW FASTENERS.
PAINT TO MATCH LOBBY DOOR
/ WINDOW FRAMES
BOTTOM COURSE OF
MASONRY BLOCK
WALL SHALL REMAIN
EXISTING SLAB FLOOR
1" INTERNAL LINER WITH
ANTI-MICROBIAL COATING
PROVIDE PLASTIC OR STEEL
BLOCKING TO SUPPORT
FREE END OF DUCT
90 DEGREE MITRED ELBOW WITH
TURNING VANES
NOTE:
MASONRY BLOCK WALL SHALL BE CUT TO PRECISE WELDED FRAME SIZE. NO SAW
OVER CUTTING ON CORRIDOR SIDE OF WALL IS ALLOWED. FRAME SHALL BE
INSTALLED WITH 1/16" TOLERANCE CLEARANCE.
INSTALLATION SHALL BE OF SIMILAR APPEARANCE TO TRANSFER GRILLE INSTALLED
BELOW THE WINDOW IN THE LOBBY.
PAINT CUT EDGES OF MASONRY OPENING TO MATCH WALL COLOR.
PROVIDE DUCT STRAP AND
FASTEN TO WALL
FRAME SHALL BE
FASTENED TO MASONRY
BLOCK WALL WITH (5) 1/2"
SLEEVE ANCHORS PER
SIDE
ME030
MECHANICAL DETAILS10/10/2025
10/10/2025
11/15/2025
11/15/2025 hcien Text Box
AC-2
hcien Text Box AC-1,3,4,5,6,7,8,9 existing hose kits and circuit setters remain.
hcien Text Box
CT-1
MSB
FACP PU2-A/B
DWH-1/2
PU1-A/B
B-1/2
CUH-1
CUH-1
IU-X
64"X14" (E) SA
"X
E
"X
E
36"X10" (E
) SA
24"X8" (E
) SA
36"X10" (E
) SA
36"X10" (E
) SA
24"X8" (E
) SA
24"X8" (E
) SA
18"X10" (E) OA
C U
H -1
RHC
4" CDWR
3" CDWS
2" HWS
3" HWR
4" CDWR
3" CDWS
2-1/2" HWS
3" HWR
4" CDWR
3" CDWS
2-1/2" HWS
2-1/2" HWR
2" CDWR
4" CDWS
3" HWS
1" HWR
2" CDWR
4" CDWS
3" HWS
1" HWR
2" CDWR
4" CDWS
3" HWS
3/4" HWR
3/4" HWS/R
4" CDWR
1-1/4" HWS
3" HWR
3" CDWR
3" CDWS
2" HWS
2" HWR
CDW
R CDW
S
HW
S HW
RCDW
R
CDW
S
HW
S
HW
R
C D
W R
C D
W
SH
W S
H W
R
CDWR
CDWS
HWS
HWR
C D
W R
C D
W
SH
W S
H W
R
CDWR
CDWS HWS
HWR
C D
W R H W
S H
W R
CDWR HWS
HWR
2-1/2" CDWS/R UP
1" HWS/R UP
2-1/2" CDWS/R UP
2-1/2" HWS/R UP
30X12" (E
18"X12" (E
30X12" (E) SA UP
18"X12" (E) SA UP
36"X12" (E) SA UP (AC-3)
36"X12" (E) SA
"X
(E
S A
"X
(E
S A
S T
ST
12"X10"
(E) OA
"X
(E
S A
15"X10" (E) SA
26"X10" (E) SA
"X
(E
S A
"X
(E
S A
"X
(E
S A
15"X10" (E) SA
15"X10" (E) SA
15"X10" (E) SA
18"X12" (E) SA
12"X12" (E) SA
15"X10" (E) SA
46"X16" SA UP
(AC-2)
HOOD MUA
HOOD MUA HOOD EXHAUST
HOOD
EXHAUST
UP TO EF-1
HOOD MUA
10"x10" (E
) SA
(E) OAL
30"X12"
525 CFM
(E) OAL
54"X12"
975 CFM
ROOM IS A RETURN
AIR PLENUM
ROOM IS A RETURN
AIR PLENUM
ROOM IS A RETURN
AIR PLENUM
ROOM IS A RETURN
AIR PLENUM
30"X42" OAL
2,800 CFM
18"X18" (E) OA
10"X12" (E) OA TO AC-6
8"X12" (E) OA TO AC-7
25"X12" RA UP
(AC-2)
24"X24" OAL
2,110 CFM
FCU
FCU
FTR FTR
16"X12" EA UP
HOOD MUA
HOOD EA
AC-6
AC-7
AC-9
CT-1
VF-1
FAN COIL
PU-4A
(SERVES VF-1)
T
T
T
T
AC-1
AC-6
AC-7
AC-5
64"X18" SA
64"X14" SA
EF-4
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
534 ESA
ERA
1200 ERA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
EEA
EEA
EEA
EEA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
ESA
M
M M
M
T
T
T
AC-1 TCCP
Ds
T
T
T
T
AC-2
RHC
BAS-1
HPWLS, HHWS, & VF-1
TCCP'S
AC-9
TCCP
AC-5
TCCP
AC-6 TCCP
AC-7 TCCP
M
M
1 1
1. EXISTING EQUIPMENT TO BE REMOVED. PERFORM PRE-TEST ON EQUIPMENT PRIOR TO
REMOVAL. MEASURE AIR FLOW AND STATIC PRESSURES ON THE UNIT (OA, SA, RA)
2. EXISTING THERMOSTAT TO BE REMOVED AND REPLACED WITH NEW. EXISTING BACKBOX,
CONDUIT, AND RACEWAYS SHALL REMAIN UNLESS NOTED OTHERWISE. (TYPICAL)
3. HALF-TONE INDICATES EXISTING TO REMAIN. (TYPICAL)
4. REMOVE TO EXTENT SHOWN. (TYPICAL)
5. SOUND TRAP TO BE REMOVED AND REPLACED WITH NEW.
6. CUT PIPING FOR REMOVAL OF UNIT. PREPARE PIPES FOR RECONNECTION.
7. EXISTING TEMPERATURE CONTROL PANEL (TCCP), BACKPLATE, WIRING, CONDUIT, AND
RELAYS TO BE REMOVED AND REPLACED WITH NEW. EXISTING 120V POWER SHALL REMAIN.
8. MC SHALL REMOVE EXISTING MANUAL / MOTORIZED DAMPER AND REPLACE WITH NEW.
9. EXISTING SYSTEM SHALL BE TESTED AND REPORT SUBMITTED FOR TOTAL BUILDING AIR
BALANCE STUDY.
10. EXISTING DUCT SMOKE DETECTOR TO BE REMOVED AND REPLACED WITH NEW.
11. NOT USED.
12. EXISTING FRONT END BAS SYSTEM SHALL BE REMOVED COMPLETE. EXISTING 120V POWER
SUPPLY TO REMAIN AND BE REUSED. NOT USED.
13. MC SHALL REMOVE EXISTING MANUAL / MOTORIZED DAMPER COMPLETE. CONDUIT, WIRING, BACK-BOX AND POWER SHALL BE REMOVED BACK TO TCCP AND/OR POWER PANEL.
14. REMOVE ABANDONED PIPING BACK TO MAIN AND CAP.
15. EXISTING RACEWAY TO BE ABANDONED IN PLACE.
16. TCC SHALL REMOVE EXISTING CONTROL WIRING WHERE INIDICATED.
17. TCC SHALL INSTALL NEW WIRELESS THERMOSTAT IN EXISTING LOCATION.
18. NOT USED.
19. THE MC SHALL REMOVE AND INTALL NEW TCC FURNISHED MOTORIZED CONTROL VALVES FOR
HEATING COIL. THE TCC SHALL COORDINATE WITH THE EC WHERE CONDUIT AND BACK
BOXES ARE REQUIRED. THE TCC SHALL INTEGRATE THE HEATING COIL EQUIPMENT INTO THE
BAS. REFER TO THE CONTROLS DRAWINGS.
20. EXISTING SCREWS ATTACHING OA DUCT TO AHU SHALL BE REMOVED. MC SHALL INSTALL
FLOOR MOUNTED DUCT SUPPORT OR SUSPEND FROM STRUCTURE ABOVE. LATERAL
BRACING SHALL BE PROVIDED TO PREVENT SWAYING. REFER TO SPECIFCATIONS.
21. CAP EXISTING DUCT / PIPE.
22. PROVIDE NEW EQUIPMENT. REFER TO DETAILS.
23. INDICATES MANUFACTURER REQUIRED SERVICE CLEARANCE. MC SHALL INSTALL EQUIPMENT
TO MEET MANUFACTURER REQUIRED SERVICE CLEARANCE. (TYPICAL)
24. SUPPORT WITH RUBBER BLOCKS AND CHANNEL SUPPORTS, DURABLOK OR EQUAL.
SUPPORTS SHALL BE INSTALLED AT EVERY 6'-0" AND AT EACH CHANGE IN DIRECTION.
25. NOT USED.
26. NEW SOUND TRAP. REFER TO SCHEDULE.
27. PROVIDE COPPER CONDENSATE TRAP AND EXTEND CONDENSATE DRAIN PIPE AND SPILL TO
EXISTING FLOOR DRAIN. REFER TO CONDENSATE TRAP DETAIL. (TYPICAL)
28. EXTEND SW / RW TO WSHP AND CONNECT WITH HOSE KIT. REFER TO WSHP HOSE KIT DETAIL.
(TYPICAL)
29. CONNECT WSHP SUPPLY CONNECTION TO DUCT MAIN WITH BEVELED TAP.
30. INSTALL NEW 24V LOW LEAKAGE (GASKETED) MOTOR OPERATED DAMPER AND MANUAL
BALANCING DAMPER. CONNECT DAMPER TO UNIT CONTROLLER.
31. TCC TO REMOVE AND REPLACE EXISTING THERMOSTAT WITH NEW. PROVIDE NEW WIRING
FOR BAS CONTROL.. (TYPICAL)
32. PROVIDE NEW TCCP AND CONTROLS COMPONENTS FOR INTEGRATION INTO NEW BAS
SYSTEM. REFER TO CONTROL DIAGRAMS.
33. MC SHALL INSTALL NEW DUCT MOUNTED SMOKE DETECTOR, FURNISHED BY EC.
34. ALL NEW SA/RA DUCT SHALL BE INSULATED. REFER TO DUCT INSULATION SCHEDULE FOR
REQUIREMENTS.
35. INTEGRATE INTO EXISTING KENTUCKY STATE PARKS CLOUD BASED SERVER. PROVIDE NEW
BACNET ROUTER.
HVAC KEY NOTES:
ELECTRICAL KEY NOTES:
1. DISCONNECT EXISTING 120V CIRCUIT SERVING EXISTING TEMPERATURE CONTROLS
PANEL/EQUIPMENT SCHEDULED TO BE REMOVED. INTERECEPT AND EXTEND EXISTING
CIRCUIT AS REQUIRED AND TERMINATE TO NEW PANEL/EQUIPMENT. WHERE EXISTING 120V
IS NOT AVAILABLE, EXTEND TO NEAREST 120V CIRCUIT - PRIOR TO CONNECTING TO
EXISTING CIRCUIT, ELECTRICAL CONTRACTOR SHALL MEASURE EXISTING CIRCUIT LOAD
TO VERIFY THE ADDITIONAL LOAD WILL NOT EXCEED 15A CONNECTED.
2. REMOVE EXISTING CONDUIT AND WIRING SERVING EQUIPMENT BEING REPLACED
COMPLETELY BACK TO SOURCE.
3. PROVIDE NEW FEEDER (3) #2 PHASE CONDUCTORS, (1) #6 GROUND, IN 1-1/4” CONDUIT
FROM NEW CIRCUIT BREAKER IN THE SWITCHBOARD 'MSB' LOCATED IN MECHANICAL ROOM
G19 TO NEW DISCONNECT SWITCH SERVING AC-2 AND FROM DISCONNECT SWITCH TO NEW
AC-2 UNIT. FINAL CONNECTION TO THE UNIT SHALL BE FLEXIBLE CONDUIT FOR REDUCED
VIBRATION. CONTRACTOR SHALL FIELD VERIFY BEST ROUTING PATH FOR FEEDER PRIOR
TO BID. RE-WORK EXISTING CEILINGS AS NEEDED TO INSTALL FEEDER.
4. EXISTING CIRCUIT BREAKER PREVIOUSLY SERVING AC-2 IN PANEL ‘KDP 2’ SHALL BE
TURNED OFF AND SHALL BE RE-LABELED AS “SPARE”.
5. PROVIDE NEW 110A/3P HACR TYPE CIRCUIT BREAKER IN EXISTING SQUARE D, QED
SWITCHBOARD 'MSB'. NEW CIRCUIT BREAKER SHALL BE COMPATIBLE WITH THE EXISTING
EQUIPMENT. KAIC RATING SHALL MATCH EXISTING.
6. REMOVE EXISTING DISCONNECT SWITCH SERVING HVAC UNIT BEING REPLACED.
7. EC SHALL INSTALL MC FURNISHED VFD. FIELD VERIFY BEST MOUNTING LOCATION.
DISCONNECT SWITCH SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION AND WITHIN LINE
OF SIGHT OF THE UNIT. NEC CLEARANCES SHALL BE MAINTAINED.
8. DISCONNECT DUCT SMOKE DETECTOR AND REMOVE FIRE ALARM CONNECTION REFER TO
NEW WORK PLANS FOR ADDITIONAL REQUIREMENTS. NEW DUCT SMOKE DETECTOR SHALL
BE FURNISHED AND CONNECTED TO THE EXISTING FIRE ALARM SYSTEM BY THE
ELECTRICAL CONTRACTOR. EC SHALL PROVIDE CONDUIT AND WIRING AND ENSURE
COMPATIBILITY WITH EXISTING SYSTEM. ALL WORK SHALL BE PERFORMED BY A NICET
CERTIFIED TECHNICIAN THAT IS APPROVED BY THE EXISTING FIRE ALARM SYSTEM
MANUFACTURER TO WORK ON THEIR SYSTEM. DUCT SMOKE DETECTOR SHALL ALARM AND
SHUT-DOWN UNIT UPON DETECTION OF SMOKE. COORDINATE INSTALLATION OF DUCT
SMOKE DETECTOR AND ASSOCIATED WORK AMONGST TRADES PRIOR TO START OF WORK.
NOTE: SOME NOTES DO NOT APPLY TO THIS SHEET AND ARE NOT USED.
T
PTAC
PTAC
EXISTING
RACEWAY
EXISTING
WIRING
EXISTING
ACCESS
PANEL
WIRING FROM
ADJACENT
GUEST ROOM
WIRING TO
ADJACENT
GUEST ROOM
17 16
A. PROVIDE NEW TCCP AND CONTROLS COMPONENTS FOR WOODLAND
BUSINESS BUILDING FAN COIL UNITS (QTY 2) AND ERV UNIT (QTY 1) (UNITS
ADDED UNDER A SEPARATE CONTRACT). DISCONNECT EXISTING 120V
CIRCUIT SERVING EXISTING TEMPERATURE CONTROLS PANEL/EQUIPMENT
SCHEDULED TO BE REMOVED. INTERECEPT AND EXTEND EXISTING CIRCUIT
AS REQUIRED AND TERMINATE TO NEW PANEL/EQUIPMENT. WHERE EXISTING
120V IS NOT AVAILABLE, EXTEND TO NEAREST 120V CIRCUIT - PRIOR TO
CONNECTING TO EXISTING CIRCUIT, ELECTRICAL CONTRACTOR SHALL
MEASURE EXISTING CIRCUIT LOAD TO VERIFY THE ADDITIONAL LOAD WILL
NOT EXCEED 15A CONNECTED.
WOODLAND BUSINESS BLDG NOTES:
KEYPLAN
CONFERENCE CENTER
MAIN LODGE
WOOD WING GUEST BUILDING
(NOT SHOWN IN PLANS)
G U
E S
T R
M S
GUEST RMS
G U
ES
T
R M
S
WOODLAND BUSINESS BUILDING
(NOT SHOWN IN PLANS)
SCALE: 1/8" = 1'-0"
NORTH
ME100
ML
MAIN LODGE BASEMENT FLOOR PLAN - MECH & ELEC
SCALE: 1/4" = 1'-0"
COUNT INCLUDES MAIN LODGE (SHOWN) AND
WOOD WING GUEST BUILDING (NOT SHOWN)
10/10/2025
10/10/2025
11/15/2025
11/15/2025 hcien Callout Inspect existing Control Valve. Replace as necessary for proper control should valve be in disrepair.
hcien Text Box hcien Text Box hcien Text Box hcien Text Box hcien Callout Temp and Humidity Sensors Only. BAS Front end should monitor and have graphic for each lodge room.
hcien Callout 33 Rooms in Wood Wing hcien Callout Above Ceiling hcien Callout New IT Room and location of ALC Main Server hcien Rectangle hcien Callout Mount Condenser for Mini-Split on outside wall provided with decorative cover.
Electrical Circuit shall be ran and held tight on outside wall of Cooling Tower Room, and fed through existing sleeves. Circuit shall fed from nearby electrical Switchboard MSB. Provide a 208V 30A/2P Breaker hcien Arrow hcien Line hcien Line hcien Line hcien Ellipse hcien Text Box hcien Text Box
AC-4
CU FOR
WALK-INS
COOL/FREEZ
EF-1
CU-X
CUH-1
CUH-1
CUH-1
CUH-1
CU-3
CU-2
CU-1
WFC-2
WFC-1
WFC-2
WFC-3
16"X36" (E
46"X16" (E
24"X18" (E) SA
36"X24" (E)
T
T T
T
2-1/2" CDWS/R DOWN
1" HWS/R DOWN
46"X26" (E
12"x12" (E ) O
A TO AC-8
M
M
M
ST
36"X12" (E) SA DOWN
30X12" (E) SA DN
18"X12" (E) SA DN
40"X20" RA OPENING IN SHAFT
FOR RETURN AIR PATH BACK TO
UNIT
T
C D
W R
C D
W S
H W
S H
W R
ROOM IS A RETURN
AIR PLENUM
18"X24" OAL
900 CFM
14"X14" (E) OA DUCT
AC-4
TCCP
FCU
FCU
FTR FTR
T
AC-3 TCCP
AC-3 36"X24"
T
FLAT ROOF
ESA
ESA
ERA
ESA
ESA
M
DS
AC-3
T
AC-3 TCCP
AC-4
TCCP
T T
T
T
19 19
1. EXISTING EQUIPMENT TO BE REMOVED. PERFORM PRE-TEST ON EQUIPMENT PRIOR TO
REMOVAL. MEASURE AIR FLOW AND STATIC PRESSURES ON THE UNIT (OA, SA, RA)
2. EXISTING THERMOSTAT TO BE REMOVED AND REPLACED WITH NEW. EXISTING BACKBOX,
CONDUIT, AND RACEWAYS SHALL REMAIN UNLESS NOTED OTHERWISE. (TYPICAL)
3. HALF-TONE INDICATES EXISTING TO REMAIN. (TYPICAL)
4. REMOVE TO EXTENT SHOWN. (TYPICAL)
5. SOUND TRAP TO BE REMOVED AND REPLACED WITH NEW.
6. CUT PIPING FOR REMOVAL OF UNIT. PREPARE PIPES FOR RECONNECTION.
7. EXISTING TEMPERATURE CONTROL PANEL (TCCP), BACKPLATE, WIRING, CONDUIT, AND
RELAYS TO BE REMOVED AND REPLACED WITH NEW. EXISTING 120V POWER SHALL REMAIN.
8. MC SHALL REMOVE EXISTING MANUAL / MOTORIZED DAMPER AND REPLACE WITH NEW.
9. EXISTING SYSTEM SHALL BE TESTED AND REPORT SUBMITTED FOR TOTAL BUILDING AIR
BALANCE STUDY.
10. EXISTING DUCT SMOKE DETECTOR TO BE REMOVED AND REPLACED WITH NEW.
11. NOT USED.
12. EXISTING FRONT END BAS SYSTEM SHALL BE REMOVED COMPLETE. EXISTING 120V POWER
SUPPLY TO REMAIN AND BE REUSED. NOT USED.
13. MC SHALL REMOVE EXISTING MANUAL / MOTORIZED DAMPER COMPLETE. CONDUIT, WIRING, BACK-BOX AND POWER SHALL BE REMOVED BACK TO TCCP AND/OR POWER PANEL.
14. REMOVE ABANDONED PIPING BACK TO MAIN AND CAP.
15. EXISTING RACEWAY TO BE ABANDONED IN PLACE.
16. TCC SHALL REMOVE EXISTING CONTROL WIRING WHERE INIDICATED.
17. TCC SHALL INSTALL NEW WIRELESS THERMOSTAT IN EXISTING LOCATION.
18. NOT USED.
19. THE MC SHALL REMOVE AND INTALL NEW TCC FURNISHED MOTORIZED CONTROL VALVES FOR
HEATING COIL. THE TCC SHALL COORDINATE WITH THE EC WHERE CONDUIT AND BACK
BOXES ARE REQUIRED. THE TCC SHALL INTEGRATE THE HEATING COIL EQUIPMENT INTO THE
BAS. REFER TO THE CONTROLS DRAWINGS.
20. EXISTING SCREWS ATTACHING OA DUCT TO AHU SHALL BE REMOVED. MC SHALL INSTALL
FLOOR MOUNTED DUCT SUPPORT OR SUSPEND FROM STRUCTURE ABOVE. LATERAL
BRACING SHALL BE PROVIDED TO PREVENT SWAYING. REFER TO SPECIFCATIONS.
21. CAP EXISTING DUCT / PIPE.
22. PROVIDE NEW EQUIPMENT. REFER TO DETAILS.
23. INDICATES MANUFACTURER REQUIRED SERVICE CLEARANCE. MC SHALL INSTALL EQUIPMENT
TO MEET MANUFACTURER REQUIRED SERVICE CLEARANCE. (TYPICAL)
24. SUPPORT WITH RUBBER BLOCKS AND CHANNEL SUPPORTS, DURABLOK OR EQUAL.
SUPPORTS SHALL BE INSTALLED AT EVERY 6'-0" AND AT EACH CHANGE IN DIRECTION.
25. NOT USED.
26. NEW SOUND TRAP. REFER TO SCHEDULE.
27. PROVIDE COPPER CONDENSATE TRAP AND EXTEND CONDENSATE DRAIN PIPE AND SPILL TO
EXISTING FLOOR DRAIN. REFER TO CONDENSATE TRAP DETAIL. (TYPICAL)
28. EXTEND SW / RW TO WSHP AND CONNECT WITH HOSE KIT. REFER TO WSHP HOSE KIT DETAIL.
(TYPICAL)
29. CONNECT WSHP SUPPLY CONNECTION TO DUCT MAIN WITH BEVELED TAP.
30. INSTALL NEW 24V LOW LEAKAGE (GASKETED) MOTOR OPERATED DAMPER AND MANUAL
BALANCING DAMPER. CONNECT DAMPER TO UNIT CONTROLLER.
31. TCC TO REMOVE AND REPLACE EXISTING THERMOSTAT WITH NEW. PROVIDE NEW WIRING
FOR BAS CONTROL.. (TYPICAL)
32. PROVIDE NEW TCCP AND CONTROLS COMPONENTS FOR INTEGRATION INTO NEW BAS
SYSTEM. REFER TO CONTROL DIAGRAMS.
33. MC SHALL INSTALL NEW DUCT MOUNTED SMOKE DETECTOR, FURNISHED BY EC.
34. ALL NEW SA/RA DUCT SHALL BE INSULATED. REFER TO DUCT INSULATION SCHEDULE FOR
REQUIREMENTS.
35. INTEGRATE INTO EXISTING KENTUCKY STATE PARKS CLOUD BASED SERVER. PROVIDE NEW
BACNET ROUTER.
HVAC KEY NOTES:
ELECTRICAL KEY NOTES:
1. DISCONNECT EXISTING 120V CIRCUIT SERVING EXISTING TEMPERATURE CONTROLS
PANEL/EQUIPMENT SCHEDULED TO BE REMOVED. INTERECEPT AND EXTEND EXISTING
CIRCUIT AS REQUIRED AND TERMINATE TO NEW PANEL/EQUIPMENT. WHERE EXISTING 120V
IS NOT AVAILABLE, EXTEND TO NEAREST 120V CIRCUIT - PRIOR TO CONNECTING TO
EXISTING CIRCUIT, ELECTRICAL CONTRACTOR SHALL MEASURE EXISTING CIRCUIT LOAD
TO VERIFY THE ADDITIONAL LOAD WILL NOT EXCEED 15A CONNECTED.
2. REMOVE EXISTING CONDUIT AND WIRING SERVING EQUIPMENT BEING REPLACED
COMPLETELY BACK TO SOURCE.
3. PROVIDE NEW FEEDER (3) #2 PHASE CONDUCTORS, (1) #6 GROUND, IN 1-1/4” CONDUIT
FROM NEW CIRCUIT BREAKER IN THE SWITCHBOARD 'MSB' LOCATED IN MECHANICAL ROOM
G19 TO NEW DISCONNECT SWITCH SERVING AC-2 AND FROM DISCONNECT SWITCH TO NEW
AC-2 UNIT. FINAL CONNECTION TO THE UNIT SHALL BE FLEXIBLE CONDUIT FOR REDUCED
VIBRATION. CONTRACTOR SHALL FIELD VERIFY BEST ROUTING PATH FOR FEEDER PRIOR
TO BID. RE-WORK EXISTING CEILINGS AS NEEDED TO INSTALL FEEDER.
4. EXISTING CIRCUIT BREAKER PREVIOUSLY SERVING AC-2 IN PANEL ‘KDP 2’ SHALL BE
TURNED OFF AND SHALL BE RE-LABELED AS “SPARE”.
5. PROVIDE NEW 110A/3P HACR TYPE CIRCUIT BREAKER IN EXISTING SQUARE D, QED
SWITCHBOARD 'MSB'. NEW CIRCUIT BREAKER SHALL BE COMPATIBLE WITH THE EXISTING
EQUIPMENT. KAIC RATING SHALL MATCH EXISTING.
6. REMOVE EXISTING DISCONNECT SWITCH SERVING HVAC UNIT BEING REPLACED.
7. EC SHALL INSTALL MC FURNISHED VFD.