Addendum One.pdf
PDF 747 KB Posted
- Attached to
- RFB-21-24 KCTCS Upgrade Life Safety Somerset CC
- Solicitation number
- RFB 785 2400000012 2
- Issued by
- Ohio County, Kentucky
About this file
This is Addendum One to an Invitation to Bid (RFB-21-24) issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for an Upgrade Life Safety Bid Package #1 at KCTCS Somerset Community & Technical College in Somerset, Kentucky. The project, designated RFB-785-2400000012 with KFI Project Number 22-0864.00, involves comprehensive fire detection and alarm system upgrades across multiple buildings, including the replacement of fire alarm control panels (FACP), initiation devices such as smoke and heat detectors, annunciator panels, flow and tamper switches, speaker/strobe devices, and related infrastructure. The addendum, dated August 9, 2023, modifies specifications and drawings to clarify installation requirements, device quantities, system interconnections, and contractor responsibilities. Key clarifications address the retention of existing tamper switches integral to valves with new addressable modules for interface, the inclusion of Category 6 cabling for IP dialer connections, voice evacuation system installation in Building 1 only with speaker/strobe provisions for future expansion in other buildings, and the interconnection of fire alarm panels using existing campus fiber network infrastructure with the Building 1 South Campus panel serving as the master station.
The addendum establishes that the contractor is responsible for preparing and submitting documentation for State Fire Marshall approval, with Notifier designated as the basis of design system manufacturer. Contractor responsibilities include replacing ceiling tiles and drywall damaged during construction, with KCTCS responsible for asbestos testing and abatement on existing sprinkler piping. The site will remain occupied during installation, requiring coordination with school personnel to minimize disruption to classes. The contractor must work with the owner and KFI Engineers to establish a detailed phasing and construction schedule, as no published schedule is provided. Flow tests conducted by KFI Engineers are to be utilized rather than contractor-performed tests. The contractor bears responsibility for HBC plan review fees. Existing fire alarm system components, including all devices and cabling, will be replaced with new installations, except for tamper switches integral to valves and existing raceways and backboxes, which are to remain and be reused as appropriate.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2400000012_1_SO_FORM.PDF | ||
| Final_RFB_785_2400000012_2_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-21-24
FOR: Upgrade Life Safety Bid Package #1 KCTCS- Somerset Community & Technical College Somerset, Kentucky
DATE: August 9, 2023
RFB-785-2400000012
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-21-24 For: Upgrade Life Safety Bid Package #1 KCTCS- Somerset Community & Technical College Somerset, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
ADDENDUM
Page 1 of 4 Find a way.
Date: August 8, 2023
Project: RFB-21-24 KCTCS – Upgrade Life Safety – Bid Package #1
KFI Project Number: 22-0864.00
Addendum Number: 01
THIS ADDENDUM IS A CONTRACT DOCUMENT AND MAY APPLY TO ANY OR ALL CONTRACTS AND SUBCONTRACTS UNLESS OTHERWISE SPECIFIED HEREIN OR SHOWN ON THE ATTACHED DRAWINGS (IF ANY). ALL WORK REQUIRED BY THIS ADDENDUM SHALL BE IN COMPLETE ACCORD WITH THE CONTRACT DOCUMENTS AND SUBSEQUENT ADDENDA THERETO. THE ITEMS LISTED IN THIS ADDENDUM ARE NOT IN ANY ORDER IN REGARD TO THE DRAWINGS OR THE SPECIFICATIONS. ALL CONTRACTORS ARE CAUTIONED TO EXAMINE EACH AND EVERY ITEM OF THIS ADDENDUM.
THE FOLLOWING CHANGES OR CLARIFICATIONS TO THE PLANS & SPECIFICATIONS SHALL BE INCLUDED AS PART OF THE CONTRACT DOCUMENT
SPECIFICATION CHANGES:
1. Section Number: 28 46 00 FIRE DETECTION AND ALARM
a. Replace section 28 46 00 in it’s entirety with attached specification section
PLAN SHEET CHANGES:
1. FA000 – FIRE ALARM GENERAL NOTES - SITE PLAN – SYMBOLS
a. Add symbol and definition for ‘FAAP’
2. S1-FA110 - BUILDING 1 FIRE ALARM DEMOLITION - LEVEL 1
a. Revised quantities of existing flow and tamper switches to be removed. Revised keynote 4.
3. S1-FA210 - BUILDING 1 FIRE ALARM - LEVEL 1
a. Clarified quantity of flow and tamper switches to be installed. Added Keynote E13.
4. S5-FA110 - BUILDING 5 FIRE ALARM DEMOLITION - LEVEL 1
a. Revised quantity of existing heat detectors to be removed.
5. S5-FA210 - BUILDING 5 FIRE ALARM - LEVEL 1
a. Revised quantity of heat detectors to be installed.
CONTRACTOR QUESTIONS (Responses in Blue)
1. Building 1 drawing S1-FA110. Keynote 4. Need clarification on what is to be removed. The building currently has 3 flow switches and 5 tamper switches. 3 of these tamper switches are internal to the valve and would require replacing the entire valve.
a. All (3) flow switches to be replaced with new. (2) Tamper switches to be replaced with new.
(3) existing tamper switches integral to the valve to remain and interfaced with new fire alarm system. Provide addressable modules as required to interface with new system. Refer to revised Addendum 1 drawings.
2. Building 1 drawing S1-FA210. Keynote E12. Need clarification on purpose of Cat6 cable from new fire panel to existing port (is this for Starlink dialer?)?
a. Yes – the Cat6 data connection is to allow for IP dialer.
Page 2 of 4 Find a way.
3. Building 1 drawing S1-FA210. Please define FAAP notation on drawing. Currently not in legend.
a. FAAP is to indicate Fire Alarm Annunciator Panel. Symbol legend to be revised in Addendum
1 Drawings.
4. Building 2 drawing S2-FA210. Keynote E12. Need clarification on purpose of Cat6 cable from new fire panel to existing port (is this for Starlink dialer?)?
a. Yes – the Cat6 data connection is to allow for IP dialer.
5. Building 2 drawing S2-FA210 – Wall mount speaker strobe light is indicated on drawings. Please clarify if the building is to have audio voice system?
a. Voice system to be included in Building 1 only. Provide speaker/strobe devices throughout to allow ability for future voice system.
6. Building 4 drawing S4-FA210 - Keynote E12. Need clarification on purpose of Cat6 cable from new fire panel to existing port (is this for Starlink dialer?)?
a. Yes – the Cat6 data connection is to allow for IP dialer.
7. Building 4 drawing S4-FA210- Wall mount speaker strobe light is indicated on drawings. Please clarify if the building is to have an audio voice system?
a. Voice system to be included in Building 1 only. Provide speaker/strobe devices throughout to allow ability for future voice system.
8. Building 4 drawing S4-FA210- Keynote E9. Are fire control panels required to be interconnected?
a. Fire alarm panels are to be interconnected using the existing campus fiber network. FACP in Building 1 of South Campus is to serve as the master station for the South Campus.
9. Building 5 drawing S5-FA110-Keynote 2. Drawing shows 3 smoke detectors in diesel garage when there are currently 5 heat detectors instead of smoke detectors in diesel garage. Clarification needed on what to remove and install.
a. Existing devices to be replaced 1-for-1. All (5) heat detectors to be replaced with new. Refer to revised Addendum 1 Drawings for clarification.
10. Building 5 drawing S5-FA210- Wall mount speaker strobe light is indicated on drawings. Please clarify if the building is to have an audio voice system?
a. Voice system to be included in Building 1 only. Provide speaker/strobe devices throughout to allow ability for future voice system.
11. Stoner Building drawing Sto-FA210- Wall mount speaker strobe light is indicated on drawings. Please clarify if the building is to have an audio voice system?
a. Stoner building is not to receive an audio voice system. Provide speaker/strobe devices throughout to allow ability for future voice system.
12. Will there be a Ceiling tile replacement allowance and unit price, The ACT Ceiling Tiles are old some are damaged wet and stained there are several rooms within the buildings that the ceiling Tiles have absorbed moisture and sagging unable to salvage and reuse the affected tiles.
a. Contractor to replace all tiles damaged by construction.
13. Will there be a Dry Wall Allowance for replacement of ceilings and Unit price? There will be a few areas Rooms within the building of Hard D W ceiling that will need to be removed to install the sprinkler systems and Drywall replaced including Paint.
a. Contractor responsible for repairing and painting all ceilings damaged during construction.
14. Have the Buildings been tested for Asbestos on the Existing Limited area Sprinkler piping that is to be removed?
Page 3 of 4 Find a way.
a. KCTCS will test and abate all asbestos found or suspected. There will be a document that addresses this issue dealt with during pre-construction meeting.
15. The Diesel Shop has two water stubs in the floor. The domestic is connected to the larger 6'' or 8'' floor stub. Will this Domestic connection remain on the Fire Line or will the domestic be re-piped to the domestic floor stub?
a. Domestic connection will remain.
16. Can a set of as-built water utility site drawings be provided for the Diesel shop and Stoner?
a. All site utility plans available will be provided to the successful bidder.
17. Will the Design Team provide Fire Alarm Inspection Reports so that the FA contractor can confirm the location of all FA devices?
a. The Fire Alarm Inspection Reports will be provided to the successful bidder.
18. Will a Sprinkler Flow test be required for Diesel shop and Stoner Building?
a. No. Flow tests conducted by KFI Engineers are to be utilized.
19. Will Contractor be responsible for the HBC plan review fees?
a. Yes
20. Will there be a published more detailed Project Phasing schedule per Building outlining the allotted time for each building?
a. No. The awarded contractor will be responsible for working with the owner and KFI to determine a complete phasing and construction schedule.
21. Will any of the spaces be Occupied during the installation of the sprinkler and FA?
a. Yes. The awarded contractor will have to work with school personnel to complete the work without disruption to classes.
22. Will the furnishings remain in each space during construction?
a. To be determined during construction. Contractor to assume the rooms will contain furnishings.
23. Following is the block question in regards to the “Fire Alarm Annunciator Panel”. There is a line from the new “Fire Alarm control Panel” to that Annunciator Panel, however, there is nothing in the Spec that states what type of connection is needed and what information the Annunciator Panel is needing via that connection (see diagram following)…
a. The drawing # FA301 shows the following Riser Diagram (see attached diagram). At the top of that diagram, it shows a line to "TO EXISTING FIRE ALARM CIRCUITS/DEVICES AND ZONES".
i. Please provide details as to what specifically these Zones are and the type and manufacturer of the devices that must be connected.
1. Existing annunciation devices (horn/strobes) to be replaced with new devices. Existing zoning to remain.
2. Existing initiation devices (smoke detectors, etc.) to be replaced with new devices. Existing zoning to remain.
ii. Is there a specific "FA System" (eg: Simplex, Siemens, etc.) that must be connected to the new FA Control Panel?
1. Existing system to be replaced with new. New Fire Alarm Control panel is not to be interfaced with existing panels. Basis of design for new system is Notifier.
iii. What components of the existing FA circuit/System are you wanting to keep?
Page 4 of 4 Find a way.
1. All devices and cabling of the existing fire alarm system will be replaced with new, except existing tamper switches integral to valves. These are to be interfaced with new system using addressable fire alarm relays and new cabling to new FACP. Existing raceway and backboxes for annunciators and initiation devices to remain. New cabling to be provided throughout.
b. For "shut down" of the RTUs, is a contact closure per RTU adequate for FA shutdown? If so, do these contacts already exist?
i. One contact closure per RTU is adequate. Existing contact closures are to be replaced with new and interfaced with new fire alarm system with addressable auxiliary relays. Contractor to verify all quantities and locations of existing contact closures.
24. The drawings are not KY State Fire Marshall approved.
a. Do you expect the FA contractor to provide detailed drawings and engineering time for the
State submittal/approval process?
i. Yes. FA contractor shall be responsible for preparing and submitting documentation required for approval from the State Fire Marshall.
b. Does the customer have a preferred FA Manufacturer (Simplex, Siemens, etc.)?
i. Basis of design system manufacturer is Notifier.
END OF ADDENDUM
E100
DETAIL NUMBER
SHEET NUMBER
GENERAL
ELECTRICAL KEYED NOTE NUMBER
INDICATES ALL DEVICES UNDER ONE COVERPLATE
RACEWAY SYSTEMS
CONDUIT CONCEALED IN WALL OR CEILING
CONDUIT CONCEALED IN / UNDER FLOOR
CONDUIT RUN EXPOSED
CONDUIT TRANSITION UP
CONDUIT TRANSITION DOWN
JUNCTION BOXJ
JUNCTION BOX - FLOOR MOUNTEDJ
JUNCTION BOX - WALL MOUNTEDJ
PULL BOXB
P
MAN HOLEH
M
HAND HOLEH
H
FLOOR
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
SECURITY SYSTEMS
CCTV CAMERA (1D UNLESS NOTED OTHERWISE)
13'-0" /
CEILING
CAMERA
LEGEND
180 - 180 DEGREE VIEW RANGE
270 - 270 DEGREE VIEW RANGE
360 - 360 DEGREE VIEW RANGE
PTZ - PAN, TILT, ZOOM
WALL MOUNTED SECURITY DEVICES
CR SEE BELOW
WALL
SECURITY
LEGEND
AI - INTERCOM
CR - CARD READER
DC - DOOR CONTACT
EL - ELECTRIC LOCK
ES - ELECTRIC STRIKE
GB - GLASS BREAK DETECTOR
KB/F - KNOX BOX
KP - KEY PAD
KS - KEYED SWITCH
LM - LATCH MONITOR
LD - LOCKDOWN STROBE
ML - MAGNETIC LOCK
PB - PANIC BUTTON
REX - REQUEST TO EXIT
RR - REMOTE DOOR RELEASE
VI - VIDEO INTERCOM STATION
XP - EXIT PUSHBUTTON
XS - EXIT SENSOR
48" 42"
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
48" 48"
VERIFY
VERIFY
VERIFY
VERIFY
6" ABOVE DOOR
ABOVE
COUNTER
48" 48"
VERIFY
SECURITY DEVICES DE SEE BELOW
SECURITY
LEGEND
DE - DELAYED EGRESS
LA - LOCAL ALARM
MD - MOTION DETECTOR
CEILING
CEILING
CEILING
VERIFYAC ACCESS CONTROL EQUIPMENT / PANEL
PUSHBUTTON - SINGLE 48"
PUSHBUTTON - DOUBLE 48"
BUZZER 90"
BELL 90"
S
FIRE ALARM SYSTEMS
MANUAL STATION 48"
WALL MOUNTED HORN 80"
F
CEILING MOUNTED HORNF
F
WALL MOUNTED STROBE LIGHT 80"F
CEILING
CEILING MOUNTED STROBE LIGHTF CEILING
WALL MOUNTED HORN AND STROBE LIGHT 80"F
CEILING MOUNTED HORN AND STROBE LIGHT CEILINGF
WALL MOUNTED SPEAKER 80"F
CEILING MOUNTED SPEAKERF CEILING
WALL MOUNTED SPEAKER AND STROBE LIGHT 80"F
CEILING MOUNTED SPEAKER AND STROBE LIGHT CEILINGF
WALL MOUNTED SPEAKER AND STROBE LIGHT
WITH MESSAGE BOARD
80"F MB
CEILING MOUNTED SPEAKER AND STROBE
LIGHT WITH MESSAGE BOARDF MB CEILING
WALL MOUNTED CHIME AND STROBE LIGHT 80"F
WALL MOUNTED BELL 80"F
WALL MOUNTED REMOTE RESET FOR DUCT
DETECTOR
48"F RS
FIRE ALARM DEVICEF SEE BELOW
FIRE
ALARM
LEGEND
F/S - FIRE / SMOKE DAMPER
H - HEAT DETECTOR
H/S - HEAT / SMOKE DETECTOR
IR - INFRARED SENSOR
MD - MAGNETIC DOOR HOLDER
R - INTELLIGENT CONTROL RELAY MODULE
S - SMOKE DETECTOR
SD - SMOKE DAMPER
SR - SMOKE DETECTOR WITH RELAY
SS - FIRE SUPRESSION SYSTEM
48"
CEILING
CEILING
VERIFY
VERIFY
VERIFY
CEILING
VERIFY
CEILING
VERIFY
BEAM DETECTOR TRANSMITTER VERIFYF T
BEAM DETECTOR RECEIVER VERIFYF R
FLOW SWITCH VERIFYF FS
FLOW SWITCH VERIFYF TS
FACP
FIRE ALARM CONTROL PANEL - SURFACE MOUNT TOP 72"
FAA FIRE ALARM CONTROL - FLUSH MOUNT MAX TOP 72"
VCA FIRE ALARM VOICE COMMAND
ANNUNCIATOR - SEMI-FLUSH MOUNT
MAX TOP 72"
FAAP FIRE ALARM ANNUNCIATOR PANEL VERIFY
ABBREVIATIONS
& AND
@ AT
℄ CENTERLINE
° DEGREE (S)
Ø PHASE OR ROUND
# POUND OR NUMBER
AFCI ARC FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
APP ALARM ANNUNCIATOR PANEL
AL ALUMINUM
AMP AMPERE
APPROX APPROXIMATE
ARCH ARCHITECT/ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
BAS BUILDING AUTOMATION SYSTEM
BOT BOTTOM
C CONDUIT
CAB CABINET
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CLG CEILING
C/T CURRENT TRANSFORMER
D DEPTH
DIV DIVISION
DWG DRAWING
EA EACH
EM EMERGENCY
ELEV ELEVATOR
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXT EXTERIOR
FAA FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
GC GENERAL CONTRACTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
G/GND GROUND
GMB GROUNDING MAIN BUS BAR
H HEIGHT
HP HORSE POWER
HZ HERTZ
INT INTERIOR
JB JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPS
KW KILOWATT
L LENGTH
LF LINEAL FOOT
LS LIFE SAFETY
LV LOW VOLTAGE
LFC LIQUID TIGHT FLEXIBLE CONDUIT
L/LT LIGHT
LTS LIGHTS
LTG LIGHTING
MATV MASTER ANTENNA TELEVISION
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MEZZ MEZZININE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MS MOTOR STARTER
MSP MOTOR STARTER PANEL
MSS MOTOR STARTER SWITCH
N/A NOT APPLICABLE
NL NIGHT LIGHT
N.T.S NOT TO SCALE
PF POWER FACTOR
PIV POST INDICATOR VALVE
PNL PANEL
PVC POLYVINYL CHLORIDE
R/RECEPT RECEPTACLE
RM ROOM
SCHED SCHEDULE
SECT SECTION
S/D SMOKE DAMPER
SF SQUARE FOOT
SHT SHEET
SM SURFACE MOUNTED
SP SUMP PUMP
SPEC SPECIFICATIONS
STD STANDARD
SUSP SUSPENDED
SW SWITCH
SW. BD SWITCHBOARD
SW. GR SWITCHGEAR
TEL TELEPHONE
TERM TERMINAL
TGMB TELECOMMUNICATION GROUNDING
MAIN BUS BAR
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
V VOLTAGE
VA VOLT AMPERE
W WATT (S)
W WIDTH
W/ WITH UNIT
WG WIRE GUARD
WP WEATHERPROOF
XFRM TRANSFORMER
JUNCTION BOX (NOMINAL TRADE SIZE) SCHEDULE
J-BOX TRADE SIZE J-BOX ACTUAL SIZE
MINIMUM VOLUME
(PER NEC 314.16A)
1-GANG 4" x 3" x 2-1/8" 21.0 CUBIC INCHES
2-GANG 4-11/16" x 4-11/16" x 3-1/2" 42.0 CUBIC INCHES
3-GANG 8-5/8" x 4-1/2" x 3-1/2" 63.0 CUBIC INCHES
4-GANG 10-7/16" x 4-1/2" x 3-1/2" 84.0 CUBIC INCHES
5-GANG 12-1/4" x 4-1/2" x 3-1/2" 105.0 CUBIC INCHES
6-GANG 14-1/16" x 4-1/2" x 3-1/2" 126.0 CUBIC INCHES
4" SQUARE x 1-1/4"D 4" x 4" x 1-1/4" 18.0 CUBIC INCHES
4" SQUARE x 1-1/2"D 4" x 4" x 1-1/2" 21.0 CUBIC INCHES
4" SQUARE x 2-1/8"D 4" x 4" x 2-1/8" 30.3 CUBIC INCHES
4-11/16" SQUARE x 1-1/4"D 4-11/16" x 4-11/16" x 1-1/4" 25.5 CUBIC INCHES
4-11/16" SQUARE x 1-1/2"D 4-11/16" x 4-11/16" x 1-1/2" 29.5 CUBIC INCHES
4-11/16" SQUARE x 2-1/8"D 4-11/16" x 4-11/16" x 2-1/8" 42.0 CUBIC INCHES
CONDUIT ROUTING AND SEPARATION
GROUP A
277V, 480V ELECTRONIC DIMMER
CONTROL, LIGHTING,
SWITCHED POWER SOURCES & HIGH
CURRENT SOURCES
(120V, 40A OR GREATER)
120V, 20A POWER SERVICE
A
B
C
D
B C D
ADJACENT 6" [152 mm] 12" [305 mm] 12" [305 mm]
- - 12" [305 mm] 6" [152 mm]
- - ADJACENT 6" [152 mm]
- - - ADJACENT
36" [914 mm] 12" [305 mm] 6" [152 mm] 12" [305 mm]
12" [305 mm] 6" [152 mm] ADJACENT 6" [152 mm]
24" [610 mm] 12" [305 mm] 6" [152 mm] 12" [305 mm]ALL OTHER POWER SOURCES
GENERAL FIRE ALARM DEMOLITION NOTES
A. DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE NOT INTENDED TO INDICATE ALL DEVICES
OR CONDITIONS ASSOCIATED WITH DEMOLITION. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO FIELD VERIFY ACTUAL CONDITIONS INVOLVED IN THE DEMOLITION
AND SUBSEQUENT RECONSTRUCTION REQUIRED TO COMPLETE THE ELECTRICAL
INSTALLATION.
B. SEE ARCHITECTURAL/GENERAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF
DEMOLITION.
C. CIRCUIT CONTINUITY SHALL BE MAINTAINED TO ELECTRICAL LIGHTING, DEVICES, AND
EQUIPMENT REMAINING, BUT AFFECTED BY DEMOLITION. PROVIDE NEW CONDUIT AND
WIRING AS NECESSARY TO MAINTAIN CONTINUITY TO EXISTING EQUIPMENT AND DEVICES.
FIELD VERIFICATION OF BRANCH CIRCUIT CONFIGURATION SHALL BE THE RESPONSIBILITY
OF THE ELECTRICAL CONTRACTOR.
D. IN AREAS OF DEMOLITION, REMOVE ASSOCIATED JUNCTION BOXES, SUPPORTS, CONDUIT
AND WIRING TO THE POINT OF ORIGIN FOR LIGHTING, DEVICES AND EQUIPMENT NOT
BEING REUSED.
E. FOR CIRCUITS/HOMERUNS WITH ONLY A PORTION DEMOLISHED, REMOVE CONDUIT AND
CONDUCTORS BACK TO THE NEAREST JUNCTION BOX FEEDING CIRCUITS BUT MAINTAIN
POWER TO EQUIPMENT AND RECEPTACLES THAT WILL REMAIN AFTER DEMOLITION OR
REQUIRE POWER DURING DEMOLITION AND CONSTRUCTION.
F. FOR CIRCUITS/HOMERUNS WITH ALL DEVICES DEMOLISHED, REMOVE CONDUIT AND
CONDUCTORS BACK TO THE PANELBOARD SERVING CIRCUIT(S).
G. DASHED ELECTRICAL DEVICES INDICATE DEVICES THAT ARE TO BE DEMOLISHED.
SOLID/BOLD LINED ELECTRICAL DEVICES INDICATE DEVICES THAT ARE NEW.
SCREENED/LIGHT LINED ELECTRICAL DEVICES INDICATE DEVICES THAT ARE EXISTING TO
REMAIN AND ARE SHOWN FOR REFERENCE ONLY.
H. WALLS, CEILINGS, AND GENERAL MATERIALS SHALL BE DEMOLISHED BY
GENERAL/DEMOLITION CONTRACTOR. DEMOLISH ELECTRICAL LUMINAIRES, DEVICES, AND
EQUIPMENT PRIOR TO REMOVAL OF WALLS AND CEILINGS. RELOCATE SYSTEMS AS
INDICATED ON DRAWINGS OR AS REQUIRED FOR INSTALLATION OF NEW WALLS OR
CEILINGS. COORDINATE WITH STRUCTURAL INSTALLATION, ARCHITECTURAL,
MECHANICAL, AND OTHER TRADES. PROVIDE TEMPORARY LIGHTING AND POWER FOR
ELECTRICAL ITEMS IN THE VARIOUS AREAS OF CONSTRUCTION.
I. LUMINAIRES THAT ARE DESIGNATED FOR REUSE SHALL BE CLEANED AND REINSTALLED.
J. EXISTING CONDUIT HOLES OR SLEEVES INSTALLED IN CONCRETE FLOORS OR WALLS
THAT ARE ABANDONED AFTER DEMOLITION SHALL HAVE CONDUIT REMOVED AND HOLES
FILLED AND PATCHED. PROVIDE PATCHING AND PAINTING AS REQUIRED. SEE
ARCHITECTURAL TYPICAL DETAIL.
K. COORDINATE THE DEMOLITION OF LUMINAIRES, DEVICES, AND EQUIPMENT WITH OTHER
CONTRACTORS. DEMOLISH POWER, FIRE ALARM, ELECTRICAL CONTROLS, AND
INSTRUMENTATION WIRING OF EQUIPMENT BEING DEMOLISHED. RELOCATE, EXTEND, AND
RECONNECT POWER, FIRE ALARM, ELECTRICAL CONTROLS, AND INSTRUMENTATION
WIRING OF EQUIPMENT BEING RELOCATED. COORDINATE REMOVAL AND RELOCATION OF
POWER AND CONTROLS OF MECHANICAL EQUIPMENT WITH RESPECTIVE CONTRACTORS.
L. VERIFY EXISTING CONDITIONS BEFORE COMMENCING DEMOLITION OF AN AREA. WHERE
NEEDED DURING CONSTRUCTION FOR PHASING, TEMPORARILY RECONNECT CIRCUITS
AND DEVICES AFTER DEMOLITION UNTIL PERMANENT INSTALLATION IS COMPLETED.
DEMOLISH AFTER INSTALLATION IS COMPLETED.
M. COORDINATE DEMOLITION OF EXISTING WALLS, CEILINGS AND FLOORS WITH DEMOLITION
CONTRACTOR.
N. SEAL OPENINGS IN BOXES AND ENCLOSURES THAT HAVE CONDUIT REMOVED AND
OPENINGS THAT ARE NOT REUSED. PROVIDE BLANK COVER PLATES ON ALL JUNCTION
BOXES AND ENCLOSURES THAT HAVE DEVICES DEMOLISHED BUT BOXES ARE EXISTING
TO REMAIN.
O. PROVIDE MULTI-POLE CIRCUIT BREAKER(S) OR REPLACE WIRING WITH DEDICATED
NEUTRALS WHERE EXISTING MULTI-WIRE CIRCUITS ARE MODIFIED.
P. DEMOLISH ALL ELECTRICAL DEVICES AND BOXES AS NECESSARY WHERE NEW WALL
CONSTRUCTION WILL INTERSECT AN EXISTING WALL.
Q. DEMOLISH ALL EQUIPMENT IN A MANNER THAT WILL NOT DESTROY OR DAMAGE
EQUIPMENT OR DEVICES THAT ARE TO BE SALVAGED, EXISTING TO REMAIN, OR BE
RELOCATED.
R. REPLACE ALL CONDUITS AND RACEWAYS THAT ARE DAMAGED DURING CONSTRUCTION.
S. DEMOLISH OR RELOCATE LIGHTING CONTROLS, EXIT SIGNAGE, AND ACCESS CONTROLS
AS NECESSARY TO ACCOMMODATE NEW DOOR CONFIGURATIONS.
T. PROVIDE CONDUIT AND COMMUNICATIONS/DATA CABLING AS NECESSARY FOR A
COMPLETE CABLING SYSTEM TO DEVICE LOCATIONS EXISTING TO REMAIN AFTER
DEMOLITION.
U. DO NOT REUSE MATERIALS (CONDUIT, CABLING, WIRING, DEVICES, SUPPORTS,
EQUIPMENT, ETC...) UNLESS SPECIFICALLY INDICATED OR APPROVED BY THE ENGINEER.
ALL CONDUIT, PATHWAYS, AND WIRING SHALL BE NEW UNLESS SPECIFICALLY INDICATED
AS "EXISTING TO REMAIN" OR "EXISTING TO BE REUSED".
V. DUE TO DEMOLITION AND REMODELING, ELECTRICAL CONTRACTOR SHALL CONSIDER
MINOR CIRCUIT MODIFICATIONS AND REROUTING AS INCLUDED IN THE SCOPE. MAJOR
CONCEALED CONDITIONS IN WHICH THE CONTRACTOR COULD NOT ANTICIPATE THE
EFFORT LEVEL REQUIRED SHALL BE BROUGHT PROMPTLY TO THE ENGINEER’S
ATTENTION. IF THE CONTRACTOR WILL REQUEST A CHANGE IN THE CONTRACT AMOUNT
OR CONTRACT TIME DUE TO CONDITION, THEN THE CONTRACTOR SHALL SUBMIT DIGITAL
PHOTOGRAPHS OF THE EXISTING CONDITIONS WITH A PROPOSED RESOLUTION. FAILURE
TO DO SO IMPLIES THE CONTRACTOR HAS ASSUMED THE WORK EFFORT TO BE INCLUDED
IN THEIR BID. ENGINEER WILL PROMPTLY REVIEW INFORMATION AND MAKE
RECOMMENDATIONS TO THE OWNER IN AN ATTEMPT TO MAINTAIN CONSTRUCTION
SCHEDULE.
GENERAL FIRE ALARM PLAN NOTES
A. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE REQUIREMENTS OF THE LATEST
ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE, STATE, COUNTY, MUNICIPAL AND
FEDERAL LAWS AND ORDINANCES GOVERNING THE PROJECT. IF THE PLANS AND
SPECIFICATIONS ARE IN DIRECT CONFLICT WITH SUCH CODES, LAWS OR ORDINANCES,
NOTIFY THE ENGINEER OF CONFLICT IN WRITING PRIOR TO MAKING CHANGES FROM
PLANS AND/OR SPECIFICATIONS. WORK SHALL BE PERFORMED UNDER THE SUPERVISION
OF A LICENSED MASTER ELECTRICIAN, LICENSED IN THE STATE IN WHICH THE WORK WILL
OCCUR.
B. BRANCH CIRCUIT CONDUITS, JUNCTION BOXES AND CONNECTIONS ARE NOT SHOWN.
PROVIDE COMPLETE RACEWAY SYSTEM AND CONDUCTORS AS REQUIRED FOR THE
INDICATED CIRCUITRY.
C. ALTHOUGH FEEDER AND BRANCH CIRCUIT WIRING AND CONDUIT ARE NOT SPECIFICALLY
SHOWN, PROVIDE A COMPLETE FEEDER AND BRANCH CIRCUIT WIRING SYSTEM.
D. HOMERUN CIRCUITS SHALL BE 0.75 INCH CONDUIT, 2#12, 1#12 GROUND MINIMUM TO A
20A/1P CIRCUIT BREAKER IN DESIGNATED PANEL. THE NUMBERS SHOWN AT EACH
DEVICE/HOMERUN REPRESENT BRANCH CIRCUIT NUMBER(S) IN PANELBOARD.
E. EXTERIOR LUMINAIRE/DEVICE CIRCUITS SHALL BE 0.75 INCH CONDUIT, 2#10, 1#10 GROUND
MINIMUM TO 20A/1P CIRCUIT BREAKER IN DESIGNATED PANEL. THE NUMBERS SHOWN AT
EACH DEVICE REPRESENT BRANCH CIRCUIT NUMBER(S) IN PANELBOARD.
F. ALL CONDUIT AND WIRING SIZES SHOWN ARE MINIMUMS, DEPENDING ON EXACT ROUTING,
PROVIDE LARGER AS REQUIRED FOR VOLTAGE DROP, AMBIENT TEMPERATURE, OR
OTHER DERATING.
G. WIRE AND RACEWAY SIZES INDICATED ON HOMERUNS/CIRCUITS SHALL BE CONTINUOUS
FOR ENTIRE LENGTH.
H. A MAXIMUM OF THREE CIRCUITS SHALL BE INSTALLED IN A CONDUIT.
I. PROVIDE DEDICATED NEUTRAL FOR EACH SINGLE PHASE CIRCUIT.
J. RACEWAYS SHALL BE LIMITED TO SIX CURRENT CARRYING CONDUCTORS (THREE PHASE
AND THREE NEUTRALS) AND GROUNDING CONDUCTOR.
K. CONDUCTORS MUST BE DERATED PER THE NATIONAL ELECTRICAL CODE WHEN MORE
THAN THREE CURRENT CARRYING CONDUCTORS ARE RUN IN THE SAME RACEWAY.
L. INSTALL WIRING CONCEALED IN RACEWAYS AND CONCEAL RACEWAYS IN WALLS, FLOORS,
AND CEILINGS. NO SURFACE RACEWAYS SHALL BE INSTALLED ON NEW FINISHED WALLS.
M. CABLING THAT IS NOT IN CONDUIT AND IS LOCATED IN AIR HANDLING PLENUM SHALL BE
PLENUM RATED. REFER TO MECHANICAL PLANS FOR PLENUM AREAS.
N. DO NOT INSTALL ELECTRICAL EQUIPMENT THAT PHYSICALLY INTERFERES WITH
SERVICING OF MECHANICAL EQUIPMENT.
O. ELECTRICAL CONDUITS, WIRING, BOXES, ETC. SHALL NOT PENETRATE STAIR ENCLOSURE
UNLESS THEY ARE FEEDING DEVICES LOCATED WITHIN THE STAIR ENCLOSURE.
P. PROVIDE ELECTRICAL OUTLET PLATE GASKET SEALS AT RECEPTACLES, SWITCHES,
OTHER ELECTRICAL BOXES ON EXTERIOR WALLS AND INTERIOR WALLS BETWEEN
CONDITIONED AND UNCONDITIONED SPACES.
Q. PROVIDE UNIVERSAL BLANK PLUGS ON SPARE CONDUITS SIZED FOR CONDUIT.
R. SEAL CONDUITS AT THE LAST STRUCTURE PRIOR TO CONDUITS ENTERING A BUILDING
AND WHERE CONDUITS ENTER A BUILDING. INSTALL NYLON PULL STRING AND FOOTAGE
TAPE IN SPARE CONDUITS.
S. RACEWAY AND WIRING INDICATED ON THE DRAWINGS ARE RECOMMENDATIONS FOR
SPECIFIC ROUTES OR SPECIAL CONDITIONS. CONTRACTOR IS RESPONSIBLE FOR EXACT
ROUTING.
T. 120 VOLT BRANCH CIRCUITS OVER 100 FEET IN CONDUCTOR LENGTH SHALL BE
INCREASED ONE WIRE SIZE OVER CIRCUIT AMPACITY AND CIRCUITS OVER 170 FEET IN
CONDUCTOR LENGTH SHALL BE INCREASED TWO WIRE SIZES.
U. 277 VOLT BRANCH CIRCUITS OVER 230 FEET IN CONDUCTOR LENGTH SHALL BE
INCREASED ONE WIRE SIZE OVER CIRCUIT AMPACITY AND CIRCUITS OVER 380 FEET IN
CONDUCTOR LENGTH SHALL BE INCREASED TWO WIRE SIZES.
V. ELEVATIONS AND HEIGHTS ON ELECTRICAL DRAWINGS AND SPECIFICATIONS ARE
APPROXIMATE. FOR WALL MOUNTED DEVICES REFER TO ARCHITECTURAL ELEVATIONS.
FOR LOCATION OF CEILING MOUNTED DEVICES REFER TO ARCHITECTURAL REFLECTED
CEILING PLAN.
W. REFERENCES TO MECHANICAL INDICATES DIVISIONS 21, 22, 23, & 25 CONTRACTORS.
REFERENCES TO ELECTRICAL INDICATES DIVISIONS 26, 27 & 28 CONTRACTORS.
X. PAINT CONDUIT AND BOXES WHERE CONDUIT OR BOXES ARE VISIBLE IN FINISHED
SPACES. COORDINATE WITH OTHER TRADES.
Y. PROVIDE NEW, FIRST QUALITY MATERIAL FOR ALL PRODUCTS PROVIDED UNDER THIS
CONTRACT.
Z. DO NOT INSTALL OUTLETS BACK TO BACK. PROVIDE MINIMUM OF 24 INCH HORIZONTAL
SPACING IN FIRE RATED WALLS. MOUNT LOW VOLTAGE AND POWER OUTLETS IN
DIFFERENT STUD WALL CAVITIES. PROVIDE PUTTY PADS AT EACH BOX WHERE A
JUNCTION BOX OR OUTLET IS INSTALLED WITHIN THE SAME STUD WALL CAVITY AS
ANOTHER OUTLET OR JUNCTION BOX ON THE OTHER SIDE OF THE WALL. PROVIDE PUTTY
PADS WHERE REQUIRED TO MAINTAIN THE FIRE RATING OR THE SOUND TRANSMISSION
LEVEL OF THE WALL OR FINISH.
E
SE
R P
OF
S T
TA
E
NENIS O LA
E L
I C N S
IG
N
EE
D R
WILLIAM P.
N
22074
WILSON
OF KE
Y
CK
UT
NOTE:
IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, SPRINKLERS, AND DEVICE LOCATIONS REQUIRED FOR INSTALLATION OF THE WORK. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
06/21/23
470CAP5SS6800WPW
22-0864.00
06/21/23
EFN
FIRE ALARM GENERAL NOTES - SITE PLAN - SYMBOLS
FA000
RTA
KCTCS LIFE SAFETY UPGRADE - BID PACKAGE #1
SOMERSET COMMUNITY & TECHNICAL COLLEGE
ELECTRICAL SYMBOLS LEGEND NOTES:
1. THESE SYMBOLS COMPRISE A STANDARD LIST, NOT ALL SYMBOLS
MAY APPEAR ON THESE DRAWINGS.
2. MOUNTING HEIGHTS INDICATED ARE FOR STUD WALL
CONSTRUCTION. WHEN BLOCK OR BRICK CONSTRUCTION IS USED,
ADJUST MOUNTING HEIGHTS TO ALIGN DEVICE PLATES WITH
RUNNING JOINT.
3. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE ABOVE FINISHED
FLOOR UNLESS NOTED OTHERWISE. MOUNTING HEIGHTS
INDICATED ON ARCHITECTURAL WALL ELEVATIONS OR AS NOTED
SPECIFICALLY ON THE DRAWINGS
4. SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS LISTED.
5. PROVDE 4-11/16" SQUARE BOX WITH SINGLE DEVICE MUD RING AND
1"C MINIMUM STUBBED INTO ACCESSIBLE CEILING SPACE AS
REQUIRED FOR ROUGH-IN OF LOW VOLTAGE/ TECHNOLOGY
SYSTEM OUTLET LOCATIONS.
6. PROVIDE 4-11/16" SQUARE BOX WITH 1.25" MINIMUM STUBBED INTO
ACCESSIBLE CEILING SPACE FOR ALL AUDIO-VIDEO OUTLETS AND
DEVICES.
7. REFER TO CONSTRUCTION DRAWINGS AND SCHEDULES FOR
ADDITIONAL INFORMATION.
1 ADDENDUM 01 08.08.23
OFFICE
OFFICE
COPIER
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
102A
CLASSROOM
CLASSROOM
OFFICE
STORAGE
OFFICE
OFFICE
STORAGE
RR
RR
OFFICE
LOUNGE
107A
CLASSROOM
115A
STORAGE
115B
113A
RR
RR
STORAGE
LOBBY
SERVER ROOM
MAILROOM
115B
CONFERENCE
COPIER
OFFICE
117B
OFFICE
117A
117C
117D
OFFICE
116A
STORAGE
116B
LOBBY
POWER PLANT SYSTEMS
POWER PLANT
AIRFRAME SYSTEMS
AIRFRAME STRUCTURES
RELATED INSTRUCTION
CORR.
HANGAR
143A 143B
FABRICATION
ENGINE SHOP
ENGINE SHOP
147A
STORAGE
TOOLROOM
JAN.
RESTROOM
A/P RESOURCE
CORR.
OFFICE
185A
185B
RR
185D
RR
179E
FLUID POWER
WELDING
179F
VENDING
RESTROOM
RESTROOM
CORR.
MECHANICAL
STORAGE
166B
KITCHEN
166C
INDUSTRY CLASSROOM
WELDING 2
INDUSTRY TRAINING
RR
159B
RR
159B
159C
CLASSROOM
153J
INDUSTRY TRAINING
OFFICE
153D
RR
159D
RR
153A
AUTO TECH
BODY SHOP
CLASSROOM
187A
187C
PAINT BOOTH
188D
CLASSROOM
188A
RR
187B
RR
188B
188C
BOOTH
WELDING
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
LOCKERS
GRINDING
BOOTH
GRINDING
BOOTH
GRINDING
BOOTH
TOOL TOOL
Garage Door
Test Cell
MACHINE ROOM
LOCKERS LOCKERS LOCKERS
F
F
F
F
F
F
F
F H
F H
F H
F H F H
F
F
F
F H
F H
F H F H
F F
F F
F H
F H
F H
F
F
F
F
F F
F
FF FFAAPF
F F
F
F
F
F
F
F H F H F H
F H
F H
F H F H F H
F S
F S
F
F
F F
F H
F H
F F
F
F
F H
F
FF
F HF F
F
F H
F H
F F F
F
F
F H
F H
F F
F
F
F H F H
F S
F F F
S
F T
S
F S
F
F F
F H
F H
F
F
F
F
F
F H
F H
F
F F
F H
F H
F
F
F
F
F F
F
F FF F
F
F
F
F
F
F H
F H
F H
F H
F H
F H
F H
F H F H
F H
JJ
F
FF
F H
F T
S F
T S
F T
S
F T
S F
F S
F F
S
2 2
2 2
2 2
2 2
2 2 2
2 2
2 2
2 2
2 2
2 2
2 2 2
2 2
E
SE
R P
OF
S T
TA
E
NENIS O LA
E L
I C N S
IG
N
EE
D R
WILLIAM P.
N
22074
WILSON
OF KE
Y
CK
UT
NOTE:
IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, SPRINKLERS, AND DEVICE LOCATIONS REQUIRED FOR INSTALLATION OF THE WORK. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
06/21/23
470CAP5SS6800WPW
22-0864.00
06/21/23
EFN
BUILDING 1 FIRE ALARM DEMOLITION - LEVEL 1
S1-FA110
RTA
KCTCS LIFE SAFETY UPGRADE - BID PACKAGE #1
SOMERSET COMMUNITY & TECHNICAL COLLEGE
1/16" = 1'-0"S1-FA110
1 LEVEL 1 FIRE ALARM DEMOLITION PLAN - SOUTH BUILDING 1
GENERAL NOTES - DEMOLITION
A. COORDINATE PHASING OF SCOPE WITH GENERAL CONTRACTOR. COORDINATE DEMOLITION OF FIRE ALARM SYSTEM COMPONENTS
WITH OTHER TRADES.
B. COORDINATE ALL FIRE ALARM SHUT-DOWNS WITH OWNER PRIOR TO EXECUTION OF WORK. COORDINATE WITH GENERAL CONTRACTOR AND FACILITY STAFF TO PROVIDE A FIRE WATCH IN ACCORDANCE TO NFPA 101. NOTIFY AUTHORITY HAVING
JURISDICTION OF ALL PLANNED FIRE ALARM SHUT-DOWNS.
C. ALL EXISTING FIRE ALARM CONDUIT AND PENETRATIONS TO REMAIN IN PLACE FOR RE-USE. EXISTING FIBER TO EXISTING FIRE ALARM CONTROL PANELS TO REMAIN IN PLACE FOR RE-TERMINATION TO REPLACEMENT PANEL. REMOVE ALL FIRE ALARM CABLING FOR INITIATION AND ANNUNCIATION CIRCUITS BETWEEN EXISTING FIRE ALARM CONTROL PANEL AND DEVICES.
D. COORDINATE WITH GENERAL CONTRACTOR TO DISCONNECT, STORE, AND RE-INSTALL ALL ELECTRICAL DEVICES MOUNTED IN
CEILINGS TO BE REMOVED TO INSTALL NEW SPRINKLER PIPING.
E. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY
OR REPLACE AS REQUIRED.
F. FURNISH AND INSTALL CONDUIT AND/OR COMMUNICATIONS/DATA WIRING AS NECESSARY FOR CONTINUITY OF ANY WIRING ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY COMMUNICATIONS/DATA EQUIPMENT OR DEVICES TO REMAIN
AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED.
G. FURNISH AND INSTALL BLANK COVER PLATES OVER ALL EXISTING UNUSED OPENINGS.
KEYNOTES
1 DISCONNECT AND REMOVE EXISTING FACP AND ACCESSORY CABINETS. EXISTING 120V CIRCUIT AND BRANCH CONDUITS TO
REMAIN IN PLACE FOR RECONNECTION TO REPLACEMENT FACP.
2 DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE. REMOVE ALL CABLING BACK TO SOURCE. EXISTING DEVICE
BACKBOX AND CONDUIT TO REMAIN IN PLACE.
3 DISCONNECT AND REMOVE EXISTING ANNUNCIATOR PANEL. REMOVE ALL CABLING BACK TO SOURCE. CONDUIT AND BACKBOX
TO REMAIN IN PLACE.
4 DISCONNECT AND REMOVE EXISTING FLOW AND TAMPER SWITCHES. TAMPER SWITCHES INTEGRAL TO VALVES ARE TO REMAIN AND INTEGRATED TO NEW FIRE ALARM SYSTEM. REMOVE FLEX CONDUIT BACK TO NEAREST JUNCTION BOX. REMOVE ALL
CABLING BACK TO SOURCE.
6 DISCONNECT AND REMOVE EXISTING AIR HANDLER SMOKE DETECTOR. REMOVE ALL CABLING BACK TO SOURCE. REMOVE FLEX CONDUIT BACK TO NEAREST FIRE ALARM JUNCTION BOX. EXISTING CONDUIT TO REMAIN IN PLACE FOR REUSE.
7 EXISTING POWER AND FIRE ALARM CONDUIT TO BUILDING 4. SEE S4-FA110 FOR CONTINUATION.
1 ADDENDUM 01 08.08.23
OFFICE
OFFICE
COPIER
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
102A
CLASSROOM
CLASSROOM
OFFICE
STORAGE
OFFICE
OFFICE
STORAGE
RR
RR
OFFICE
LOUNGE
107A
CLASSROOM
115A
STORAGE
115B
113A
RR
RR
STORAGE
LOBBY
SERVER ROOM
MAILROOM
115B
CONFERENCE
COPIER
OFFICE
117B
OFFICE
117A
117C
117D
OFFICE
116A
STORAGE
116B
LOBBY
POWER PLANT SYSTEMS
POWER PLANT
AIRFRAME SYSTEMS
AIRFRAME STRUCTURES
RELATED INSTRUCTION
CORR.
HANGAR
143A 143B
FABRICATION
ENGINE SHOP
ENGINE SHOP
147A
STORAGE
TOOLROOM
JAN.
RESTROOM
A/P RESOURCE
CORR.
OFFICE
185A
185B
RR
185D
RR
179E
FLUID POWER
WELDING
179F
VENDING
RESTROOM
RESTROOM
CORR.
MECHANICAL
STORAGE
166B
KITCHEN
166C
INDUSTRY CLASSROOM
WELDING 2
INDUSTRY TRAINING
RR
159B
RR
159B
159C
CLASSROOM
153J
INDUSTRY TRAINING
OFFICE
153D
RR
159D
RR
153A
AUTO TECH
BODY SHOP
CLASSROOM
187A
187C
PAINT BOOTH
188D
CLASSROOM
188A
RR
187B
RR
188B
188C
BOOTH
WELDING
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
WELDING
BOOTH
LOCKERS
GRINDING
BOOTH
GRINDING
BOOTH
GRINDING
BOOTH
TOOL TOOL
Garage Door
Test Cell
MACHINE ROOM
LOCKERS LOCKERS LOCKERS
F T
S
F
F
F
F
F
F
F
F H
F H
F H
F H F H
F
F
F
F H
F H
F H F H
F F
F F
F H
F H
F H
F
F
F
F
F F
F
FF FFAAPF
F F
F
F
F
F
F
F H F H F H
F H
F H
F H F H F H
F S
F S
F
F
F F
F H
F H
F F
F
F
F H
F
FF
F HF F
F
F H
F H
F F F
F
F
F H
F H
F F
F
F
F H F H
F S
F
F S
F
F F
F H
F H
F
F
F
F
F
F H
F H
F
F F
F H
F H
F
F
F
F
F F
F
F FF F
F
F
F
F
F
F H
F H
F H
F H
F H
F H
F H
F H F H F H
JJ
F F
F F
F FF
F H
F
F
F
F
F H
F
F T
S
F T
S
F F
S
F T
S F
T S
F F
S F
F S
E1
E3
E2
E2
E2
E2
E2
E2
E2
E3 E2
E7
E8
E6
E11
E12
E13
E
SE
R P
OF
S T
TA
E
NENIS O LA
E L
I C N S
IG
N
EE
D R
WILLIAM P.
N
22074
WILSON
OF KE
Y
CK
UT
NOTE:
IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, SPRINKLERS, AND DEVICE LOCATIONS REQUIRED FOR INSTALLATION OF THE WORK. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
06/21/23
470CAP5SS6800WPW
22-0864.00
06/21/23
EFN
BUILDING 1 FIRE ALARM - LEVEL 1
S1-FA210
RTA
KCTCS LIFE SAFETY UPGRADE - BID PACKAGE #1
SOMERSET COMMUNITY & TECHNICAL COLLEGE
1/16" = 1'-0"S1-FA210
1 LEVEL 1 FIRE ALARM PLAN - SOUTH BUILDING 1
KEYNOTES
E1 PROVIDE NEW FACP CONTROL PANEL IN EXISTING LOCATION. WIRE FACP TO EXISTING 120V CIRCUIT SERVING FIRE ALARM PANEL MADE AVAILABLE DURING DEMOLITION. REPLACE EXISTING 20A BREAKER SERVING FACP WITH NEW DEVICE WITH RED DEVICE WITH CLEAR PERMANENT INDICATION OF FIRE ALARM CIRCUIT IN ACCORDANCE WITH NEC ARTICLE 760.121(B) AND NFPA 72 ARTICLE 10.6.5.2. PROVIDE CAT6 CABLE FROM SYSTEM DIALER TO BUILDING TELECOMMUNICATIONS NETWORK AT
LOCATION INDICATED ON PLAN.
E2 PROVIDE NEW FIRE ALARM ANNUNCIATOR AS SHOWN. PROVIDE NEW CONDUIT FROM NEAREST EXISTING FIRE ALARM JUNCTION BOX. EXTEND NEAREST ANNUNCIATOR CIRCUIT TO NEW LOCATION. PROVIDE CLASS B WIRING TO NEW DEVICE.
E3 PROVIDE NEW FIRE ALARM INITIATION DEVICE AS SHOWN. PROVIDE NEW CONDUIT FROM NEAREST EXISTING FIRE ALARM JUNCTION BOX. EXTEND NEAREST ANNUNCIATOR CIRCUIT TO NEW LOCATION. PROVIDE CLASS B WIRING TO NEW DEVICE.
E6 PROVIDE NEW EMERGENCY VOICE EVACUATION EQUIPMENT PANEL AND CONNECT TO FACP.
E7 UTLIZE EXISTING PATHWAY TO ROUTE NEW FIRE ALARM CABLING TO INSTRUCTION SPACES 187 AND 188.
E8 EXISTING POWER AND FIRE ALARM CONDUITS TO BUILDING 4. REFER TO SHEET S4-FA210 FOR CONTINUATION.
E11 PROVIDE REMOTE MICROPHONE UNIT IN LOCKABLE SURFACE MOUNTED CABINET. CONNECT TO EMERGENCY VOICE
EVACUATION EQUIPMENT PANEL LOCATED IN MECH
E12 LOCATION OF EXISTING BUILDING TELECOMMUNICATIONS ROOM. PROVIDE CAT6 CABLING FROM NEW FACP TO EXISTING AVAILABLE PORT ON EXISTING PATCH PANEL. COORDINATE INSTALLATION AND PROGRAMMING WITH OWNER.
E13 CONNECT EXISTING FLOW SWITCHES TO NEW FIRE ALARM SYSTEM. PROVIDE ADDRESSABLE FIRE ALARM MODULES AS REQUIRED TO INTERFACE WITH NEW FIRE ALARM SYSTEM. MOUNT MODULE TO SURFACE MOUNTED BOX NEAR DEVICE.
PROVIDE CABLING BACK TO FACP.
GENERAL NOTES - FIRE ALARM
A. ALL NEW FIRE ALARM DEVICES SHOWN ARE TO BE INSTALLED IN EXISTING DEVICE BACKBOX OF DEVICES REMOVED IN DEMOLITION, UNLESS NOTED OTHERWISE. REUSE EXISTING CONDUIT AND JUNCTION BOXES FOR NEW CLASS B FIRE ALARM CABLING. INSTALL ALL NEW DEVICES PER NFPA 72 REQUIREMENTS. EXTEND CONDUIT AND CABLING AS REQUIRED FOR CODE COMPLIANT INSTALLATION. PROVIDE ALL CONDUIT, SURFACE RACEWAY, CABLING, AND ACCESSORIES AS
REQUIRED.
B. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS SHOWN ON THE DRAWINGS, EXCEPT ITEMS LISTED ON SHEET E0.01 GENERAL ELECTRICAL NOTES.
C. INSTALL CONDUIT WITH NO MORE THAN (2) 90° BENDS BETWEEN PULL BOXES, AND NO MORE THAN 100'-0" BETWEEN PULL
BOXES. PULL BOXES SHALL BE INSTALLED FOR STRAIGHT THRU PULLS ONLY.
D. ALL FIRE ALARM AND ACCESS CONTROL CABLES SHALL BE INSTALLED IN CONDUIT.
1 ADDENDUM 01 08.08.23
ACT
STORAGE
8’−2"
EXP
TOOL RM
EXP
ELECTRIC RM
EXP
TRANSMISSION RM
ACT
DIESEL CLASSROOM
9’−0"
ACT
OFFICE
9’−0"
ACT
COMPUTER LAB
9’−0"
EXP
DIESEL GARAGE
GYP
501C
RR
7’−11"
GYP
501D
RR
7’−9"
8’−9"
GYP
7’−9"
GYP
LOCKERS
F H F H
F H
F
F
F
F
F F
F F
F
F
F F H
F S
F S
F
F
F H F H
2 2
2 2
2 2
1/8" = 1'-0"S5-FA110
1 LEVEL 1 FIRE ALARM DEMOLITION PLAN - SOUTH BUILDING 5
E
SE
R P
OF
S T
TA
E
NENIS O LA
E L
I C N S
IG
N
EE
D R
WILLIAM P.
N
22074
WILSON
OF KE
Y
CK
UT
NOTE:
IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, SPRINKLERS, AND DEVICE LOCATIONS REQUIRED FOR INSTALLATION OF THE WORK. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
06/21/23
470CAP5SS6800WPW
22-0864.00
06/21/23
EFN
BUILDING 5 FIRE ALARM DEMOLITION - LEVEL 1
S5-FA110
RTA
KCTCS LIFE SAFETY UPGRADE - BID PACKAGE #1
SOMERSET COMMUNITY & TECHNICAL COLLEGE
GENERAL NOTES - DEMOLITION
A. COORDINATE PHASING OF SCOPE WITH GENERAL CONTRACTOR. COORDINATE DEMOLITION OF FIRE ALARM SYSTEM COMPONENTS
WITH OTHER TRADES.
B. COORDINATE ALL FIRE ALARM SHUT-DOWNS WITH OWNER PRIOR TO EXECUTION OF WORK. COORDINATE WITH GENERAL CONTRACTOR AND FACILITY STAFF TO PROVIDE A FIRE WATCH IN ACCORDANCE TO NFPA 101. NOTIFY AUTHORITY HAVING
JURISDICTION OF ALL PLANNED FIRE ALARM SHUT-DOWNS.
C. ALL EXISTING FIRE ALARM CONDUIT AND PENETRATIONS TO REMAIN IN PLACE FOR RE-USE. EXISTING FIBER TO EXISTING FIRE ALARM CONTROL PANELS TO REMAIN IN PLACE FOR RE-TERMINATION TO REPLACEMENT PANEL. REMOVE ALL FIRE ALARM CABLING FOR INITIATION AND ANNUNCIATION CIRCUITS BETWEEN EXISTING FIRE ALARM CONTROL PANEL AND DEVICES.
D. COORDINATE WITH GENERAL CONTRACTOR TO DISCONNECT, STORE, AND RE-INSTALL ALL ELECTRICAL DEVICES MOUNTED IN
CEILINGS TO BE REMOVED TO INSTALL NEW SPRINKLER PIPING.
E. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY
OR REPLACE AS REQUIRED.
F. FURNISH AND INSTALL CONDUIT AND/OR COMMUNICATIONS/DATA WIRING AS NECESSARY FOR CONTINUITY OF ANY WIRING ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY COMMUNICATIONS/DATA EQUIPMENT OR DEVICES TO REMAIN
AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED.
G. FURNISH AND INSTALL BLANK COVER PLATES OVER ALL EXISTING UNUSED OPENINGS.
KEYNOTES
1 DISCONNECT AND REMOVE EXISTING FACP AND ACCESSORY CABINETS. EXISTING 120V CIRCUIT AND BRANCH CONDUITS TO
REMAIN IN PLACE FOR RECONNECTION TO REPLACEMENT FACP.
2 DISCONNECT AND REMOVE EXISTING FIRE ALARM DEVICE. REMOVE ALL CABLING BACK TO SOURCE. EXISTING DEVICE
BACKBOX AND CONDUIT TO REMAIN IN PLACE.
ACT
STORAGE
8’−2"
EXP
TOOL RM
EXP
ELECTRIC RM
EXP
TRANSMISSION RM
ACT
DIESEL CLASSROOM
9’−0"
ACT
OFFICE
9’−0"
ACT
COMPUTER LAB
9’−0"
EXP
DIESEL GARAGE
GYP
501C
RR
7’−11"
GYP
501D
RR
7’−9"
8’−9"
GYP
7’−9"
GYP
LOCKERS
F H F H
F H
F
F
F
F
F F
F F
F
F
F F H
F S
F S
F
F
F F
S
F T
S
F T
S
F T
S
F
F H F H
E1
E5
E4
E10
1/8" = 1'-0"S5-FA210
1 LEVEL 1 FIRE ALARM PLAN - SOUTH BUILDING 5
E
SE
R P
OF
S T
TA
E
NENIS O LA
E L
I C N S
IG
N
EE
D R
WILLIAM P.
N
22074
WILSON
OF KE
Y
CK
UT
NOTE:
IT IS NOT INTENDED THAT THE PLANS SHOW ALL OFFSETS IN PIPES, CONDUITS, SPRINKLERS, AND DEVICE LOCATIONS REQUIRED FOR INSTALLATION OF THE WORK. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SUB-CONTRACTORS TO COORDINATE INSTALLATION OF THE WORK AND TO PROVIDE THE NECESSARY OFFSETS, TRANSFORMATIONS, AND FITTINGS REQUIRED. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CORRECTION CONFLICTS BETWEEN THE WORK OF VARIOUS TRADES. DETAILS AND SECTIONS ARE SHOWN FOR THE CONTRACTORS CONVENIENCE AND SHALL NOT BE CONSIDERED COMPLETE IN EVERY DETAIL.
REVISION HISTORY OF THIS DRAWING
DRAWING NO.
AS-BUILT DATE
DECA LOG #
DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE
DRAWING INFORMATION
A & E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
FRANKFORT, KENTUCKY
ACCOUNT NO.
06/21/23
470CAP5SS6800WPW
22-0864.00
06/21/23
EFN
BUILDING 5 FIRE ALARM - LEVEL 1
S5-FA210
RTA
KCTCS LIFE SAFETY UPGRADE - BID PACKAGE #1
SOMERSET COMMUNITY & TECHNICAL COLLEGE
GENERAL NOTES - FIRE ALARM
A. ALL NEW FIRE ALARM DEVICES SHOWN ARE TO BE INSTALLED IN EXISTING DEVICE BACKBOX OF DEVICES REMOVED IN DEMOLITION, UNLESS NOTED OTHERWISE. REUSE EXISTING CONDUIT AND JUNCTION BOXES FOR NEW CLASS B FIRE ALARM CABLING. INSTALL ALL NEW DEVICES PER NFPA 72 REQUIREMENTS. EXTEND CONDUIT AND CABLING AS REQUIRED FOR CODE COMPLIANT INSTALLATION. PROVIDE ALL CONDUIT, SURFACE RACEWAY, CABLING, AND ACCESSORIES AS
REQUIRED.
B. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS SHOWN ON THE DRAWINGS, EXCEPT ITEMS LISTED ON SHEET E0.01 GENERAL ELECTRICAL NOTES.
C. INSTALL CONDUIT WITH NO MORE THAN (2) 90° BENDS BETWEEN PULL BOXES, AND NO MORE THAN 100'-0" BETWEEN PULL
BOXES. PULL BOXES SHALL BE INSTALLED FOR STRAIGHT THRU PULLS ONLY.
D. ALL FIRE ALARM AND ACCESS CONTROL CABLES SHALL BE INSTALLED IN CONDUIT.
KEYNOTES
E1 PROVIDE NEW FACP CONTROL PANEL IN EXISTING LOCATION. WIRE FACP TO EXISTING 120V CIRCUIT SERVING FIRE ALARM PANEL MADE AVAILABLE DURING DEMOLITION. REPLACE EXISTING 20A BREAKER SERVING FACP WITH NEW DEVICE WITH RED DEVICE WITH CLEAR PERMANENT INDICATION OF FIRE ALARM CIRCUIT IN ACCORDANCE WITH NEC ARTICLE 760.121(B) AND NFPA 72 ARTICLE 10.6.5.2. PROVIDE CAT6 CABLE FROM SYSTEM DIALER TO BUILDING TELECOMMUNICATIONS NETWORK AT
LOCATION INDICATED ON PLAN.
E4 PROVIDE CONNECTIONS TO FLOW AND TAMPER SWITCHES FOR NEW SPRINKLER SERVICE ENTRANCE. REFER TO FIRE
PROTECTION DRAWINGS FOR EXACT LOCATION.
E5 PROVIDE NEW FIRE SPRINKLER HORN AND TIE IN TO REPLACEMENT FIRE ALARM SYSTEM. COMPLY WITH ALL REQUIREMENTS
OF NFPA 13 AND NFPA 72.
E10 PROVIDE BONDING JUMPER TO NEW SPRINKLER PIPING SYSTEM. CONNECT TO EXISTING BUILDING GROUNDING SYSTEM AT NEAREST AVAILABLE POINT IN COMPLIANCE WITH NEC. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
| Addendum One |
| RFB-21-24 KCTCS - Upgrade Life Safety - Somerset CC Addendum 01 |
| KCTCS - Upgrade Life Safety - Somerset CC - Addendum 01 Drawings |
| Sheets |
| FA000 - FIRE ALARM GENERAL NOTES - SITE PLAN - SYMBOLS |
| S1-FA110 - BUILDING 1 FIRE ALARM DEMOLITION - LEVEL 1 |
| S1-FA210 - BUILDING 1 FIRE ALARM - LEVEL 1 |
| S5-FA110 - BUILDING 5 FIRE ALARM DEMOLITION - LEVEL 1 |
| S5-FA210 - BUILDING 5 FIRE ALARM - LEVEL 1 |
File details come from the government source that posted it. Updated .