Addendum One .pdf
PDF 3 MB Posted
- Attached to
- RFB-258-25 CHFS WSH Campus Wide Roof Replacement
- Solicitation number
- RFB-785-2500000695-2
- Issued by
- Clinton County, Kentucky
About this file
This document is an Addendum (No. 1) for a Campus-Wide Roof Replacement project at Western State Hospital in Hopkinsville, Kentucky, issued by the Commonwealth of Kentucky's Department for Facilities and Support Services, Division of Engineering and Contract Administration. The addendum, dated June 10, 2025, is part of Request for Bid No. RFB-258-25 and introduces a key modification to the project's special conditions: all workers must now provide negative tuberculosis skin test results to work on-site. The addendum also indicates a change to the project drawings, specifically noting the omission of Sheet SP and its replacement with an attached Addendum #1 Sheet SP.
The pre-bid meeting sign-in sheet reveals seven attendees from various organizations, including representatives from PDM Architects, DECA (Division of Engineering and Contract Administration), CHFS (Cabinet for Health and Family Services), Kalkreuth Roofing & Sheet Metal, Barrier Roofs, and Galt Construction. The site plan and general notes provide extensive details about site utilization, construction requirements, safety protocols, and specific instructions for roof replacement, including debris removal, protection of existing structures, and maintenance of site security. The project involves roof replacements for multiple buildings (Buildings 20, 31, 33, 48, and 78) at the Western State Hospital campus, with comprehensive guidelines for contractor conduct, site preparation, and restoration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2500000695_1_SO_FORM.PDF | ||
| Final_RFB_785_2500000695_2_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-258-25
FOR: Campus Wide Roof Replacement Western State Hospital Cabinet for Health and Family Services Hopkinsville, Kentucky
DATE: June 11, 2025
RFB-785-2500000695
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-258-25 For: Campus Wide Roof Replacement Western State Hospital Cabinet for Health and Family Services
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
PATRICK D. MURPHY CO., INC. ARCHITECTS
4606 Illinois Avenue • Louisville, Kentucky 40213-1923 • (502) 454-5632
Member - American Institute of Architects
ADDENDUM NO. 1 June 10, 2025
RE: Request for Bid No. RFB-258-25
Campus-Wide Roof Replacement
Western State Hospital
From: Patrick D. Murphy Co., Inc. Architects
4606 Illinois Avenue
Louisville, KY 40213
To: Prospective Bidders
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THE INVITATION TO BID.
Note: Acknowledgement of this Addendum shall be made on the “Bid Document”
CHANGES TO PROJECT MANUAL
1. Special Conditions, Article 12 Special Project Site Security or Access Requirements, add paragraph 12.6 Negative Tuberculosis skin test results are required to work on-site.
CHANGES TO SPECIFICATIONS
1. N/A
CHANGES TO DRAWINGS
1. Omit Sheet SP and replace with attached Addendum #1 Sheet SP.
GENERAL ITEMS
1. N/A
END OF ADDENDUM NO. 1
PRE-BID MEETING FOR: DATE:
SIGN IN SHEET
PATRICK D. MURPHY, INC. ARCHITECTS
Phone # E-Mail AddressCompany Name Contact Person
WSH: Campus Wide Roof Replacements 06/04/2025
Jean-Paul Grivas PDM Architects 502-494-5965 jpgrivas@pdmarchitects.com
Dwayne Brown DECA 270-210-0253 Dwayne.Brown@ky.gov
John Shramm CHFS 502-229-3497 john.shramm@ky.gov
Susan Ward DECA 502-226-0335 susan.ward@ky.gov
Justin Spillman Kalkreuth Roofing & Sheet Metal 859-231-7663 jspillman@krsm.net
Eddie McGarrah Barrier Roofs 606-383-2844 eddie@barrierroofs.com
Evangeline Ezirim Building Consultant/ Galt Construction 847-744-9323 info@morrah.work
GENERAL SITE PLAN NOTES:
1. SITE UTILIZATION PLAN: SHOW TEMPORARY FACILITIES, TEMPORARY UTILITY LINES & CONNECTIONS, STAGING AREAS, CONSTRUCTION SITE
ENTRANCES, VEHICLE CIRCULATION, & PARKING AREAS FOR CONSTRUCTION PERSONNEL..
2. PLASTIC FENCING: PLASTIC CONSTRUCTION FENCING CONSTRUCTED OF HIGH-DENSITY EXTRUDED AND STRETCHED POLYETHYLENE FABRIC WITH 2-INCH MAXIMUM OPENING IN PATTERN & WEIGHING A MINIMUM OF 0.4 LB/FT.; REMAINING FLEXIBLE FROM MINUS 60 TO PLUS 200 DEG F;
INERT TO MOST CHEMICALS AND ACIDS; MINIMUM TENSILE YIELD STRENGTH OF 2000 PSI & ULTIMATE TENSILE STRENGTH OF 2680 PSI;
SECURED WITH PLASTIC BANDS OR GALVANIZED-STEEL OR STAINLESS-STEEL WIRE TIES & SUPPORTED BY TUBULAR OR T-SHAPE GALVANIZED-STEEL POSTS SPACED NOT MORE THAN 96 INCHES APART. FENCING IS TO BE 48" HIGH, HIGH VISIBILITY ORANGE (NON-FADING).
3. STORAGE & FABRICATION SHEDS: PROVIDE SHEDS SIZED, FURNISHED, & EQUIPPED TO ACCOMMODATE MATERIALS & EQUIPMENT FOR
CONSTRUCTION OPERATIONS. STORE COMBUSTIBLE MATERIALS APART FROM BUILDING.
4. TREE & PLANT PROTECTION: INSTALL TEMPORARY FENCING LOCATED AS INDICATED OR OUTSIDE THE DRIP LINE OF TREES TO PROTECT VEGETATION FROM DAMAGE FROM CONSTRUCTION OPERATIONS. PROTECT TREE ROOT SYSTEMS FROM DAMAGE, FLOODING, AND EROSION
5. PROPOSED CONTRACTOR STORAGE AREA, STAGING AREA, CONTRACT LIMITS & PARKING AREA LOCATION SHALL BE DISCUSSED @ THE
PRE-BID CONFERENCE.
GENERAL NOTES:
1. 1. VERIFICATION OF EXISTING CONDITIONS
1.1 - Dimensions indicated on drawings, which have a direct relationship with the existing construction, must be verified in the field prior to the construction, fabrication or installation of any related work. Such dimensions and elevations include, but are not limited to, building dimensions, parapet heights and thickness, etc. If field verifications of dimensions at existing construction differ from that indicated on the drawing, the contractor should document the actual conditions and submit to the architect. If necessary a field directives (Change Order) will be issued to clarify requirements of the work.
2. 2. VERIFICATION OF EXISTING ROOF CONSTRUCTION
2.1 - Existing roof construction including type of deck, wood nailer, underlayment, & shingles is indicated of the drawings for the convenience of the contractor. This information is not warranted as to accuracy or completeness. The contractor is responsible for verification prior to bid of existing roof construction relative to its impact on demolition and disposal operations.
No allowance will be made for failure of the contractor to obtain such existing conditions information prior to bidding except as indicated below.
3. Clean & prepare existing roof substrate and as required for new roof installation.
4. Downspout hubs: once cleaned, contractor shall test all to verify water flow. Submit in writing notice that all downspout hubs have been inspected and tested and are functioning properly. Notify owner in writing of all that are clogged and/or if the water flow is very slow.
5. Maintain watertight roof condition at all times, before and during roof construction.
* NO Phased construction allowed. Remove only the amount of roofing that can be made water tight in the same day or before the onset of inclement weather.
6. In the event of any discrepancies and/or errors found in the drawings or if problems are encountered during construction that would cause hardships on the contractor, the contractor shall be required to notify the architect before proceeding with the work.
7. All areas requiring patching, it shall be done in a manner to match adjacent surfaces and finishes.
8. Contractor shall be responsible for closing, patching and repairing of all holes, openings, damage to all surfaces, e.g., masonry walls, wood decks, resulting during construction by Contractor and/or Subcontractor.
9. Contractor shall be responsible for maintaining security of the work place, setup areas, storage areas, parking areas, equipment, tools, etc.
10. Care shall be taken to protect all utilities and equipment to remain.
11. Contractor shall give all necessary notices and obtain all permits.
12. Provide continuous wind cleats (22 gauge min.) @ all eave fascia (24 gauge min.) and rake flashing (24 gague min.) with exposed face of greater than 4-inches. Install all sheet metal items according to SMACNA latest recommendations.
13. Any damage to existing asphalt, paved surfaces, concrete, etc., resulting from new construction shall be replaced by like materials at Contractors' expense.
14. Contractor shall repair after construction is complete, at the contractor expense, all damage to the grounds in the area of work and/or setup and restore to original condition. Ground shall be leveled, install new grass seed (type matching surrounding grass), straw over seeded areas and watered on a daily basis till the new grass is three (3") inches tall.
15. Dump trucks &/ or dumpsters used for debris removal shall be the responsibility of Contractor. Verify locations of each with Owner.
Dump trucks &/ or dumpsters shall be covered to prevent debris from blowing out.
16. All roofing construction shall comply with manufacturers latest standards for warranty specified and NRCA guidelines (latest edition).
17. Run magnet over the ground after work on a daily basis and again at completion of project.
18. Remove all existing fasteners/anchors from roof substrate prior to installing new roof system.
19. During the construction of this project, the Contractor shall not allow their workers to harass building employees, staff, security, residents, visitors, etc., with catcalling, whistles, yelling, etc. No boom boxes or radios allowed. Workers to wear shirts at all times. No vulgar language spoken or printed on shirts. No staring/looking/peeping in building windows.
20. No tobacco, alcohol, drugs, firearms, etc., shall be allowed on this project.
21. Contractor is responsible for their own tools, materials, equipment, vehicles, etc., from loss, theft, damage, etc. Lock all tools up, lock all vehicles, and secure dump trucks, etc., at end of each day.
22. Contractor shall be responsible for cleaning building(s), walks, grounds, etc. of all black marks, gravel, paper, sealant debris, etc., after project is complete.
23. If contractor and/or subcontractor employees are required to enter the building with work related activity, they must put on clean shoes.
The contractor is responsible to clean all tracks, dirt, marks on floor, walls, ceilings, ladders, etc.
24. Parking for Contractor employees is limited. Verify with Owner exact location. This will be covered in more detail at the Pre-Construction Conference.
25. Contractor shall provide canvas tarps full height against the wall, where hand derricks, chutes, and/or hoists is setup for the protection of the building wall from damage, black marks, sealant, adhesive spilling, etc. No plastic tarps shall be used.
26. Where setup areas along building have windows, the tarps shall be hung between windows so as not to block the use of the windows by building tenants.
27. Remove debris from roof via the use of trash chutes and/ or cranes with trash trays. No debris, materials, equipment, etc., is allowed to be thrown from the roof.
28. Contractors' job foreman shall remain on the job each day, all day during construction.
29. Temporary Fire Protection: Install and maintain temporary fire-protection facilities of types needed to protect against reasonably predictable and controllable fire losses. Comply with NFPA 241; manage fire-prevention program.
30. Develop and supervise an overall fire-prevention and -protection program for personnel at Project site. Review needs with local fire department and establish procedures to be followed. Instruct personnel in methods and procedures. Post warnings and information.
31. Downspouts to be secured to walls with hangers or straps at a minimum of two locations with one every 10 feet & at every direction change.
32. Splash pans are to be located at all down spout outlets. Metal splash pans only at roof surfaces. Concrete splash pans only at grade.
33. All antenna disconnect requirements to be coordinated with the owner 72 hours prior to the the work. Refer to roof plans & notes for specific guidance.
LEGEND
1. REPLACEMENT AREA
2. SET-UP AREAS
COMBINED LEGEND - FOR ALL DRAWINGS
N.I.C. = NOT IN CONTRACT
RP = ROOF PENETRATION
PV = PLUMBING VENT
MOD. = MODIFIED
SYS. = SYSTEM
MEMB. = MEMBRANE
MCF = METAL COUNTER FLASHING
INSUL = INSULATION
DS = DOWN SPOUT
MTL = METAL
AFR = ABOVE FINISHED ROOF
RH = ROOF HATCH
N.T.S. = NOT TO SCALE
VS = VENT STACK
EF = EXHAUST FAN
PP = PITCH POCKET
TYP = TYPICAL
SIM. = SIMILAR
ACM = ASBESTOS CONTAINING MATERIAL
REQ'D = REQUIRED
LWCF = LIGHTWEIGHT CONCRETE FILL
JT = JOINT
V.I.F. = VERIFY IN ROOF
N
RTA DATE
DECA LOG #
A&E FILE NO.
CHECKED BY
DRAWN BY
DRAWING DATE
DRAWING INFORMATION
DRAWING NO.
AS BUILT DATE
PHASE
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKY
PATRICK D. MURPHY CO., INC.
ARCHITECTS
P.O. BOX 20835
LOUISVILLE, KENTUCKY 40250
ACCOUNT NO.
WESTERN STATE HOSPITAL24-731-21
02-26-2025
03-11-2025
RBSII
JPG
R.T.A.
729-CBYH-WS84-00
SP
SITE PLANS & GENERAL NOTES
CHFS - WSH - CAMPUS-WIDE ROOF REPLACEMENT
2400 RUSSELLVILLE RD., HOPKINSVILLE, KY 42240
NOT TO SCALE
OVERALL SITE PLAN1
BLDG. # 33BLDG. # 31
BLDG. # 20
BLDG. # 48
BLDG. # 78
NOT TO SCALE
BLDG. 20 - SITE PLAN2
NOT TO SCALE
BLDG. 31 & 33 - SITE PLAN3 NOT TO SCALE
BLDG. 48 - SITE PLAN4
NOT TO SCALE
BLDG. 78 - SITE PLAN5
BLDG. # 33
BLDG. # 31
CHECK-IN
LOCATION
DUMPSTER
LOCATION
(BLDG 48)
MATERIAL
STORAGE
(BLDG. 48)
DUMPSTER,
MAT. &
EQUIP.
STORAGE
STAGING
AREA
MATERIAL
& EQUIP.
STORAGE
STAGING
STAGING
STAGING
STAGING
STAGING
NOTE:
STORM DRAINS &
UNDERGROUND PIPING
IN THIS COURTYARD
STAGING & STORAGE AREAS NOTED 06/10/25
AutoCAD SHX Text
| Addendum One |
| Addendum No. 1, WSH Roofs (06-10-25) |
| WSH Sign In Sheet - PRE-BID (1) |
| WSH - Sheet 'SP' (Add #2) |
| Sheets and Views |
| 01 - SP |
File details come from the government source that posted it. Updated .