Addendum One .pdf
PDF 215 KB Posted
- Attached to
- RFB-261-25 KSP Post 8 HVAC Improvement Morehead
- Solicitation number
- RFB-785-2500000703-2
- Issued by
- Rowan County, Kentucky
About this file
The document is an Addendum (Addendum No. One) for Invitation to Bid No. RFB-261-25 issued by the Commonwealth of Kentucky's Department for Facilities and Support Services, Division of Engineering and Contract Administration. The project involves HVAC Improvements for Post 8 of the Kentucky State Police located in Morehead, Kentucky, dated June 4, 2025. The addendum directs bidders to refer to an additional addendum to be distributed by Lynn Imaging for all specifications and drawing changes.
A companion electrical addendum from Connolly Consulting Engineers, PLLC provides specific technical details, including a requirement to provide two NEMA L5-30R receptacles with associated 30AMP circuits in the IT room 023. The addendum is part of a comprehensive electrical and mechanical upgrade project, with the electrical design firm noting that bidders must acknowledge receipt of this and any other addenda in their proposal. The document includes detailed power and systems plans showing floor layouts, electrical panel schedules, and specific electrical infrastructure modifications for the Kentucky State Police facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2500000703_2_SO_FORM.PDF | ||
| Final_RFB_785_2500000703_1_SO_FORM.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-261-25
FOR: HVAC Improvements Post 8 Kentucky State Police Morehead, Kentucky
DATE: June 4, 2025
RFB-785-2500000703
ADDENDUM NO. One (1)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-261-25 For: HVAC Improvements Post 8 Kentucky State Police Morehead, Kentucky
Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration
2265 Harrodsburg Road, Suite 402 • Lexington, KY 40504 Office 859.402.0221 • www.cceky.com Pg. 1
ADDENDUM 1 – ELECTRICAL
To: All Plan Holders
From: Luke Powell, PE Connolly Consulting Engineers, PLLC
Project: KSP – POST 8 HVAC Improvements Morehead, Kentucky Acct: 520-CBBM-MD04-00
Release Date: June 2, 2025
This addendum is issued before award of contract to inform the bidders of revision/clarification to the bidding documents. All requirements contained in the bidding documents shall apply to this addendum, and the general character of the work called for in this addendum shall be the same as originally set forth in the applicable portions of the bidding documents for similar work, unless otherwise specified under this addendum. All incidental work necessitated by this addendum as required to complete the work shall be included in the bids, even though not particularly mentioned in this addendum. This addendum is hereby made a part of the bidding documents and shall be included in the contract and submitted with the proposal or bid. Bidder must acknowledge receipt of this and any other addenda issued related to the project in their proposal or bid.
Drawings Addenda
Item No. 1: Refer to Drawing EP101 – POWER AND SYSTEMS PLANS.
1. In IT room 023: Provide two (2) NEMA L5-30R Receptacles and associated 30AMP circuits.
End of Addendum 1 Mechanical and Electrical
F
F
F
F
F
F F
F
F
F
F
F
F
F
F
S
F
F F
F
F
S
F
F F
F
F
F
F
F
F
F F
F
F
F
F
F
F
EXIST
DIESEL
GENERATOR
IT-CU-2
HP-1.2
HP-1.1
HP-2.1
HP-2.4
HP-2.3
EXIST
IT-CU
HP-2.2
AHU-2.1
AHU-1.1
AHU-1.2
AHU-2.4
LP-E
LP-B
LP-C
MDP
ATS
LP-A
IT-WU-2
EXIST
EUH-2
E18
E16
LP-C -25,27
LP-C -17,19
LP-C -22,24
LP-C -13,15
LP-C -14,16
DETECTIVE OFFICE
SERGEANT OFFICE
CORRIDOR
MECH
EVIDENCE ROOM
EVIDENCE ROOM
TOILET
TOILET
LT. OFFICE
IT
RADIO
014B
INTELLIGENCE
014A
E17
WP
LP-C -6,8
LP-C -9,11
LP-C -10,12 LP-C -5,7
LP-C -2,4
LP-C -1,3
WP
LP-C -29
LP-C -30
DS
DS
DSDS
F6
UH-1
E27
EF-3
E28
REINSTALL ALL SALVAGED CEILING
MTD DEVICES ON NEW CEILING.
COORDINATE EXACT LOCATIONS
WITH OWNER PRIOR TO
INSTALLATION. TYPICAL.
LP-C -31,33
LP-C -32,34
FIELD COORDINATE EXACT
LOCATION WITH OWNER
PRIOR TO ROUGH-IN.
A N
N
FACP
AHU-2.2
AHU-2.3
EF-1
F5
CLERK
POST COMMANDER
CORRIDOR
DISPATCH
OFFICE
107STORAGE
KITCHENETTE
ASST POST COMMANDER
DAY ROOM
ADMINISTRATOR SERGEANT
OFFICE
VESTIBULE
WOMEN
MEN
STAIRS
CLS
110A
CLS
107A
E21
E22
E22
LP-C -18,20
LP-C -21,23
EF-2 EF-2
E19
DS
DS
F6
F6F7
F7
A. PROVIDE HEAVY DUTY, NON-FUSED (UON), EQUIPMENT DISCONNECT FOR ALL
POWERED HVAC, PLUMBING, AND ELECTRICAL EQUIPMENT. DISCONNECT SHALL
HAVE AMPACITY AND VOLTAGE CHARACTERISTICS TO MEET EQUIPMENT ELECTRICAL
REQUIREMENTS. PROVIDE NEMA 3R OUTDOORS, UON.
B. PROVIDE VINYL LABEL ON COVER PLATE OF EACH RECEPTACLE IN PROJECT AREA
INDICATING PANEL AND PANEL SPACE NUMBER FEEDING RECEPTACLE.
C. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE
COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE
ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER
TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS
IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT
NAMEPLATES OR ACCESS PANELS OR THROUGH ACCESS/MAINTENANCE
CLEARANCES OF EQUIPMENT BY OTHER TRADES.
D. PROVIDE NEW J-HOOK PATHWAYS FOR ALL EXISTING LOW-VOLTAGE CABLING
SYSTEMS ABOVE CEILING. PROVIDE J-HOOKS FROM EACH INDIVIDUAL ROOM AND IN
CORRIDORS BACK TO IT ROOM. PROVIDE QUANTITY OF J-HOOKS NECESSARY TO
SUPPORT ALL EXISTING CABLING AT A MAXIMUM OF 4-FOOT SPACING INTERVALS.
NEW WORK GENERAL NOTES
A. FIRE ALARM CONTRACTOR SHALL PERFORM BATTERY CALCULATIONS FOR THE
DEVICES IN THIS SYSTEM AND CONFIRM PROPER STROBE CANDELLA OUTPUTS.
B. ELECTRICAL CONTRACTOR SHALL COORDINATE SERVICE WITH LOCAL TELEPHONE
COMPANY FOR ANY REQUIRED ANALOG PHONE CONNECTIONS FOR THE FIRE ALARM
DIALER, AND MISCELLANEOUS OFFICE EQUIPMENT CONNECTIONS.
C. THE FIRE ALARM SYSTEM SHOWN ON THE PLANS IS FOR COORDINATION ONLY. THE
SYSTEM SHOWN ON THE DRAWINGS MAY NOT REPRESENT THE COMPLETE
REQUIRED FINAL FIRE ALARM SYSTEM LAYOUT REQUIREMENTS. THE FIRE ALARM
SYSTEM SHALL BE DESIGNED AND SUBMITTED FOR PERMIT BY A NICET CERTIFIED
FIRE ALARM SYSTEM CONTRACTOR. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE
ALL REQUIRED DEVICES (DETECTORS, NOTIFICATION DEVICES, ETC.), WHETHER
SHOWN ON THE DRAWINGS OR NOT, FOR A COMPLETE, CODE COMPLIANT SYSTEM
INSTALLATION.
FIRE ALARM GENERAL NOTES
TEMPORARY POWER GENERAL NOTES
A. THE FACILITY WILL REMAIN OPERATIONAL FOR THE DURATION OF THE
CONSTRUCTION PERIOD. REFER TO SPECIAL CONDITIONS FOR ADDITIONAL
CONSTRUCTION PHASING REQUIREMENTS.
B. IT ROOM EQUIPMENT SHALL REMAIN IN OPERATION FOR THE ENTIRE PROJECT.
CONTRACTOR SHALL CONSIDER THIS WHEN REPLACING THE BRANCH PANELS
IN BUILDING. CONTRACTOR SHALL TEMPORARILY BACK FEED ALL IT ROOM
CIRCUITS FROM A TEMPORARY GENERATOR IN A CODE APPROVED MANNER.
C. EACH PANEL REPLACEMENT IS LIMITED TO A MAXIMUM OF ONE 8-HOUR DAY
SHUTDOWN. COORDINATE EACH PANEL SHUTDOWN WITH OWNER & ENGINEER
MINIMUM 2 WEEKS IN ADVANCE.
D. EACH PANEL'S SHUTDOWN WINDOW, THE CONTRACTOR SHALL PROVIDE
TEMPORARY GENERATOR POWER TO POWER INDIVIDUAL OFFICE RECEPTACLES
FOR COMPUTER WORKSTATIONS. AS AN OPTION, CONTRACTOR MAY
TEMPORARILY REFEED EXISTING RECEPTACLE CIRCUITS FROM OTHER ACTIVE
PANELS RATHER THAN PROVIDING TEMPORARY GENERATOR IF THIS WOULD BE
ADVANTAGEOUS TO THE OWNER (SHORTER DOWNTIME FOR CHANGEOVER).
E. DISPATCH ROOM STAFF WILL BE TEMPORARILY RELOCATED TO THE DAY
ROOMS. THE DISPATCH ROOM AND DAY ROOMS SHALL NOT BE OFFLINE AT THE
SAME TIME. PROVIDE TEMPORARY RECEPTACLE POWER IN EACH DAYROOM AS
NEEDED FOR TEMPORARY COMPUTER WORKSTATIONS WHILE THE DISPATCH
ROOM IS OFFLINE.
F. VERIFY ALL EXISTING RECEPTACLE CIRCUIT POWER SOURCES PRIOR TO
SHUTTING DOWN ANY PANELS. CONTRACTOR SHALL PROPOSE A TEMPORARY
POWER PHASING PLAN TO OWNER & ENGINEER FOR APPROVAL PRIOR TO
BEGINNING ANY DEMOLITION WORK.
G. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE TEMPORARY
GENERATOR, REFUELING, ETC. FOR ITS ENTIRE DURATION.
H. REFER TO THE SPECIAL CONDITIONS FOR ADDITIONAL CONSTRUCTION PHASING
REQUIREMENTS.
2 2 4 6 8 10 12 14
3/16" = 1'-0"
FEETSCALE N
DESCRIPTION OF REVISION
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
DECA LOG #
DRAWING NO.
AS BUILT DATE
DATE
DESCRIPTION OF REVISION DATE
ACCOUNT NO.
REVISION HISTORY OF DRAWINGS
2265 Harrodsburg Road, Suite 402 ▪ Lexington, KY 40504
Office 859.402.0221 ▪ www.cceky.com
A&E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
DRAWING INFORMATION
/3
/2
:5
:5
A
M C
U s e rs \c h u c k \O n e
D ri v e
C o n n o lly C o n s u lt in g E n g in e e rs \D o c u m e n ts
\R e v it \C
K Y
K S
P -M
E P
-v
C h u c k c c e k y .r v t
EP101
POWER AND SYSTEMS PLANS
KSP - Post 8 HVAC Improvements
520-CBBM-MD04-00
CKYKSP
05/05/2025
CAF
LRP
RTA
05/05/2025
TBD
3/16" = 1'-0"
GROUND FLOOR POWER AND SYSTEMS PLAN
3/16" = 1'-0"
FIRST FLOOR POWER AND SYSTEMS PLAN
SHEET NOTES
E16 CIRCUIT FROM PANEL SHALL BE IN METAL CONDUIT IAW SPECIFICATION.
EXTEND CONDUCTORS IN LIQUID-TITE CONDUIT FROM DISCONNECT TO
EQUIPMENT. SUPPORT ALL CONDUITS ALONG REFRIGERANT PIPING
PATHWAYS. HOLD MIN. 8" A.F.G. PROVIDE DISCONNECTS MOUNTED ON
UNISTRUT FOR HEAT PUMPS. (TYPICAL)
E17 INDOOR UNIT POWER FED FROM OUTDOOR UNIT. SEE MECHANICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
E18 PROVIDE NEW POWER PANEL. COORDINATE WITH PROJECT MANAGER AND
OWNER TO MINIMIZE OPERATIONAL IMPACT WHILE TRANSFERRING
ELECTRICAL LOADS TO THE NEW PANEL.
E19 FEED EXHAUST FAN FROM ROOM LIGHT FIXTURE CIRCUIT AND CONNECT TO
LIGHT SWITCH AND DUAL TECHNOLOGY OCCUPANCY SENSOR.
E21 FEED EXHAUST FAN FROM EXISTING EXHAUST FAN CIRCUIT.
E22 PROVIDE 208V/2P HORSEPOWER RATED SNAP SWITCH DISCONNECT AT EACH
ABOVE CEILING HVAC EQUIPMENT. PROVIDE LABEL IAW DETAIL. TYPICAL.
E27 CONNECT UNIT HEATER TO AVAILABLE CIRCUIT ON PANEL E.. PROVIDE
DISCONNECT ON WALL ADJACENT TO EQUIPMENT.
E28 REWORK EXISTING EXHAUST FAN CIRCUIT TO NEW FAN. PROVIDE
DISCONNECT ON WALL ADJACENT TO EQUIPMENT.
F5 PROVIDE NEW ADDRESSABLE FIRE ALARM SYSTEM COMPLETE. REFER TO
FIRE ALARM CONTROL SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION.
F6 PROVIDE RETURN DUCT SMOKE DETECTOR. CONNECT TO CENTRAL FIRE
ALARM SYSTEM AND TO AHU TO SHUT DOWN AHU FAN ON DETECTION OF
SMOKE. (TYPICAL)
F7 PROVIDE REMOTE CONTROL TEST STATION FOR DUCT SMOKE DETECTOR.
PROVIDE IN LOCATION ACCEPTABLE TO AHJ.
Addendum 1 6/2/25
DESCRIPTION OF REVISION
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
DECA LOG #
DRAWING NO.
AS BUILT DATE
DATE
DESCRIPTION OF REVISION DATE
ACCOUNT NO.
REVISION HISTORY OF DRAWINGS
2265 Harrodsburg Road, Suite 402 ▪ Lexington, KY 40504
Office 859.402.0221 ▪ www.cceky.com
A&E FILE NO.
DRAWING DATE
DRAWN BY
CHECKED BY
PHASE
RTA DATE
DRAWING INFORMATION
/3
/2
:5
:5
A
M C
U s e rs \c h u c k \O n e
D ri v e
C o n n o lly C o n s u lt in g E n g in e e rs \D o c u m e n ts
\R e v it \C
K Y
K S
P -M
E P
-v
C h u c k c c e k y .r v t
E602
ELECTRICAL PANEL SCHEDULES
KSP - Post 8 HVAC Improvements
520-CBBM-MD04-00
CKYKSP
05/05/2025
CAF
LRP
RTA
05/05/2025
TBD
3. GFCI BREAKER.
2. OMIT NEUTRAL CONDUCTOR WHERE NOT REQUIRED BY MNFR. REFER TO MNFR'S EQPT WIRING DIAGRAMS FOR ADDITIONAL INFORMATION.
1. SPD SHALL BE IN THE INTERIOR OF THE PANEL WHERE: 1) PANEL IS INSTALLED IN OCCUPIED ROOM, OR VISIBLE TO THE PUBLIC, OR 2) THERE IS NOT ENOUGH SPACE BESIDE THE PANEL FOR THE SPD.
Notes:
Other 0 VA 0.00% 0 VA
Motor 0 VA 0.00% 0 VA Total Panel Current 0 A
Receptacle 0 VA 0.00% 0 VA 25% Additional Capacity 0 A
Water Heating 0 VA 0.00% 0 VA Total Est. Demand Current: 0 A
Lighting 0 VA 0.00% 0 VA Total Conn. Current: 0 A
HVAC 0 VA 0.00% 0 VA Total Est. Demand: 0 VA
Cooling 0 VA 0.00% 0 VA Total Conn. Load: 0 VA
Heating 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 kVA 0 kVA 0 kVA
41 0 0 42
Spare 30 A 2 --
0 0 40
37 0 0
-- 3 30 A SPD
EXISTING - TBD 20 A 2 --
0 0 36
33 EXISTING - TBD 20 A 1 -- 0 0
-- 2 50 A EXISTING - TBD
31 EXISTING - TBD 20 A 1 -- 0 0 32
29 EXISTING - TBD 20 A 1 -- 0 0
-- 2 20 A KITCHEN RANGE
27 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A UNIT HEATER RM #016 28
25 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - FLAG POLE LIGHT 26
23 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - PARKING LOT LTG 24
21 EXISTING - TBD 20 A 1 -- 0 0 22
19 EXISTING - TBD 20 A 1 -- 0 0
-- 2 40 A DISPATCH RM (TRANE)
17 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 18
15 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 16
13 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 14
11 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 12
9 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 10
7 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 8
5 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 6
3 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 4
1 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 2
Note CKT Circuit Description Trip Poles Wire Size A B C Wire Size Poles Trip Circuit Description CKT Note
Enclosure: NEMA 1 Indoor kAIC Rating: 22,000
Mounting: Surface Wires: 4 Mains Rating: 225 A Supply From: Phases: 3 Mains Type: MLO
Location: MECH 013 Volts: 120/208 Wye Feeder: EXISTING
Branch Panel: LP A
3. GFCI BREAKER.
2. OMIT NEUTRAL CONDUCTOR WHERE NOT REQUIRED BY MNFR. REFER TO MNFR'S EQPT WIRING DIAGRAMS FOR ADDITIONAL INFORMATION.
1. SPD SHALL BE IN THE INTERIOR OF THE PANEL WHERE: 1) PANEL IS INSTALLED IN OCCUPIED ROOM, OR VISIBLE TO THE PUBLIC, OR 2) THERE IS NOT ENOUGH SPACE BESIDE THE PANEL FOR THE SPD.
Notes:
Other 0 VA 0.00% 0 VA
Motor 0 VA 0.00% 0 VA Total Panel Current 0 A
Receptacle 0 VA 0.00% 0 VA 25% Additional Capacity 0 A
Water Heating 0 VA 0.00% 0 VA Total Est. Demand Current: 0 A
Lighting 0 VA 0.00% 0 VA Total Conn. Current: 0 A
HVAC 0 VA 0.00% 0 VA Total Est. Demand: 0 VA
Cooling 0 VA 0.00% 0 VA Total Conn. Load: 0 VA
Heating 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 0 A 0 A 0 A
Total Load: 0 kVA 0 kVA 0 kVA
41 0 0 42
39 0 0 40
SPARE 30 A 3 --
0 0
-- 3 30 A SPD
35 0 0 36
33 0 0 -- 2 30 A Spare
SPARE 20 A 3 --
0 0 -- 1 20 A RCPT 32
29 RCPT 20 A 1 -- 0 0 -- 1 20 A RCPT 30
27 RCPT 20 A 1 -- 0 0 28
25 0 0
-- 2 20 A SPARE
SPARE 20 A 2 --
0 0 24
21 Spare 20 A 1 -- 0 0
-- 2 20 A SPARE
19 Spare 20 A 1 -- 0 0 -- 1 20 A Spare 20
17 RCT RM# 015 - BREATHILIZER 20 A 1 -- 0 0 -- 1 20 A Space (No cover) 18
15 RCPT RM #014 20 A 1 -- 0 0 -- 1 20 A ??? 16
13 BATT CHARGER & BLOCK HEATER 20 A 1 -- 0 -- -- 1 -- Spare 14
11 NEW GENERATOR 20 A 1 -- 0 0 -- 1 20 A BACKLOT BLDG 12
9 RCPT - RM #014 20 A 1 -- 0 0 -- 1 20 A Spare 10
7 RCPT - RM #107 20 A 1 -- 0 0 -- 1 20 A LTG - IT ROOM 8
5 LTG - RM #015 20 A 1 -- 0 0 -- 1 20 A RCPT - DAY ROOM 6
3 RCPT - RM #105 20 A 1 -- 0 0 -- 1 20 A Spare 4
1 RCPTS - EXTERIOR 20 A 1 -- 0 0 -- 1 20 A RCPT - 1ST FL RR 2
Note CKT Circuit Description Trip Poles Wire Size A B C Wire Size Poles Trip Circuit Description CKT Note
Enclosure: NEMA 1 Indoor kAIC Rating: 22,000
Mounting: Surface Wires: 4 Mains Rating: 225 A Supply From: Phases: 3 Mains Type: MLO
Location: MECH-1 013-1 Volts: 120/208 Wye Feeder: EXISTING
Branch Panel: LP B
3. PROVIDE HACR BREAKER.
2. OMIT NEUTRAL CONDUCTOR WHERE NOT REQUIRED BY MNFR. REFER TO MNFR'S EQPT WIRING DIAGRAMS FOR ADDITIONAL INFORMATION.
1. SPD SHALL BE IN THE INTERIOR OF THE PANEL WHERE: 1) PANEL IS INSTALLED IN OCCUPIED ROOM, OR VISIBLE TO THE PUBLIC, OR 2) THERE IS NOT ENOUGH SPACE BESIDE THE PANEL FOR THE SPD.
Notes:
Other 0 VA 0.00% 0 VA
Motor 4784 VA 125.00% 5980 VA Total Panel Current 219 A
Receptacle 10344 VA 98.34% 10172 VA 25% Additional Capacity 44 A
Water Heating 0 VA 0.00% 0 VA Total Est. Demand Current: 175 A
Lighting 0 VA 0.00% 0 VA Total Conn. Current: 205 A
HVAC 58698 VA 80.00% 46958 VA Total Est. Demand: 63110 VA
Cooling 0 VA 0.00% 0 VA Total Conn. Load: 73826 VA
Heating 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 242 A 213 A 172 A
Total Load: 28 kVA 25 kVA 21 kVA
41 Spare 20 A 1 -- 0 0 42
39 Spare 20 A 1 -- 0 0 40
37 0 0
-- 3 30 A SPD
Spare 30 A 2 --
0 36
33 2.5 2.5 34
RCPT - IT 023 30 A 2 2-#10, 1-#10
2.5 2.5
2-#10, 1-#10 2 30 A RCPT - IT 023
29 RCPT - EXTERIOR 20 A 1 1-#12, 1-#12, 1-#12 0.18 0.18 1-#12, 1-#12, 1-#12 1 20 A RCPT - EXTERIOR 30
27 2.39 0 28 2,3
IT-CU-2 / IT-WU-2 30 A 2 2-#10, 1-#10
2.39 0
-- 2 40 A WATER HEATER (EXISTING)
23 2.5 2.5 24 2,3
AHU-2.3 25 A 2 2-#10, 1-#10
2.5 2.5
2-#10, 1-#10 2 25 A AHU-2.4
19 3.74 4.68 20 2,3
AHU-2.1 40 A 2 2-#8, 1-#10
3.74 4.68
2-#6, 1-#10 2 45 A AHU-2.2
2,3
15 3.74 2.39 16 2,3
AHU-1.1 40 A 2 2-#8, 1-#10
3.74 2.39
2-#10, 1-#10 2 25 A AHU-1.2
2,3
11 1.56 1.85 12 2,3
HP-2.3 25 A 2 2-#10, 1-#10
1.56 1.85
2-#10, 1-#10 2 30 A HP-2.4
2,3
7 1.85 1.56 8 2,3
HP-2.1 30 A 2 2-#10, 1-#10
1.85 1.56
2-#10, 1-#10 2 25 A HP-2.2
2,3
3 1.56 1.41 4 2,3
HP-1.1 25 A 2 2-#10, 1-#10
1.56 1.41
2-#12, 1-#12 2 20 A HP-1.2
2,3
Note CKT Circuit Description Trip Poles Wire Size A B C Wire Size Poles Trip Circuit Description CKT Note
Enclosure: NEMA 1 Indoor kAIC Rating: 22,000
Mounting: Surface Wires: 4 Mains Rating: 225 A Supply From: Phases: 3 Mains Type: MCB
Location: MECH 013 Volts: 120/208 Wye Feeder: EXISTING
Branch Panel: LP-C
3. GFCI BREAKER.
2. OMIT NEUTRAL CONDUCTOR WHERE NOT REQUIRED BY MNFR. REFER TO MNFR'S EQPT WIRING DIAGRAMS FOR ADDITIONAL INFORMATION.
1. SPD SHALL BE IN THE INTERIOR OF THE PANEL WHERE: 1) PANEL IS INSTALLED IN OCCUPIED ROOM, OR VISIBLE TO THE PUBLIC, OR 2) THERE IS NOT ENOUGH SPACE BESIDE THE PANEL FOR THE SPD.
Notes:
Other 0 VA 0.00% 0 VA
Motor 0 VA 0.00% 0 VA Total Panel Current 9 A
Receptacle 0 VA 0.00% 0 VA 25% Additional Capacity 2 A
Water Heating 0 VA 0.00% 0 VA Total Est. Demand Current: 7 A
Lighting 0 VA 0.00% 0 VA Total Conn. Current: 7 A
HVAC 125 VA 80.00% 100 VA Total Est. Demand: 2600 VA
Cooling 0 VA 0.00% 0 VA Total Conn. Load: 2625 VA
Heating 2500 VA 100.00% 2500 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 1 A 12 A 12 A
Total Load: 0 kVA 1 kVA 1 kVA
29 1.25 0 30
UH-1 20 A 2 2-#12, 1-#12
1.25 0 28
25 EF-3 20 A 1 1-#12, 1-#12, 1-#12 0.13 0
-- 3 20 A SPD
23 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 24
21 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 22
19 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 20
17 EXISTING - TBD 20 A 1 -- 0 0 -- 1 30 A EXISTING - TBD 18
15 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 16
13 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A EXISTING - TBD 14
11 EXISTING - TBD 20 A 1 -- 0 0 -- 1 20 A FACP 12
9 RADIO EQPT 20 A 1 -- 0 0 -- 1 20 A RCPT - RADIO 10
7 ISRAM (?1ST FL LTG?) 30 A 1 -- 0 0 -- 1 20 A RR OP 3 & 4 8
5 ISRAM (?1ST FL LTG?) 30 A 1 -- 0 0 -- 1 20 A RR OP1 & 2 6
3 EMERGENCY LTG - GF ? 40 A 1 -- 0 0 4
1 EMERGENCY LTG - GF ? 40 A 1 -- 0 0
-- 2 60 A PANEL M-1
Note CKT Circuit Description Trip Poles Wire Size A B C Wire Size Poles Trip Circuit Description CKT Note
Enclosure: NEMA 1 Indoor kAIC Rating: 18,000
Mounting: Surface Wires: 4 Mains Rating: 100 A Supply From: Phases: 3 Mains Type: MLO
Location: MECH-1 013-1 Volts: 120/208 Wye Feeder: EXISTING
Branch Panel: LP E
GENERAL NOTES
A. PROVIDE QTY & TYPE OF BREAKERS FOR EACH PANEL TO MATCH EXISTING
CIRCUIT REQUIREMENTS. FIELD VERIFY PRIOR TO ORDERING.
B. EXISTING CONNECTED LOADS ARE NOT KNOWN. CONTRACTOR SHALL ENSURE
THAT CIRCUITS AND PANELS MEET NEC REQUIREMENTS.
C. PROVIDE ELECTRICAL GROUNDING SYSTEM FOR EACH PANEL IAW NEC.
Addendum 1 6/2/25