addendum no 10.pdf

PDF 17 MB Posted

Attached to
RFB-265-24 Ashland Readiness Center Envelope Renovation
Solicitation number
RFB 785 2500000110 6
Issued by
Boyd County, Kentucky

About this file

This is Addendum No. 10 to Request for Bid (RFB) No. RFB-265-24 issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for the Ashland Readiness Center Envelope Renovation located at 2519 Lexington Avenue in Ashland, Kentucky, under the Department of Military Affairs. The project involves the renovation of the building envelope with a significant scope change: the original work for restoration of historical steel windows has been eliminated and replaced with complete replacement of existing windows with new aluminum ATFP (Antiterrorism and Force Protection) compliant systems. The revised project specifications include Sections 08400 (Glazed Aluminum Door Entrances, Storefronts, and Curtainwalls), 085110 (Aluminum Windows), and 08800 (Glass and Glazing). Bids are due on September 19, 2024 at 1:30 PM ET, with official bid opening at 3:00 PM ET. The low bidder must submit performance and payment bonds and a certificate of insurance within 48 hours of receiving the intent to award letter. Revised architectural sheets A511, A512, and A631 are included with the addendum and reflect the scope changes.

The project requires aluminum window systems with blast-resistant capabilities meeting ASTM F1642 Low Hazard Rating standards and ATFP compliance per UFC 4-010-01. Acceptable manufacturers include Kawneer, YKK, and Tubelite for storefront systems, and Kawneer, Peerless, and Winco for aluminum windows, with substitutions permitted under DECA procedures. Glazing specifications include Type G-04 blast-resistant glass featuring 1-inch insulated units with laminated inner panes, clear Solarban 70XL solar control low-E outer lites, and dual-seal systems. Energy performance requirements include U-Factor of 0.68 Btu/sq ft·h·°F for Climate Zone 4a and SHGC of 0.36 maximum. Installation must comply with manufacturer guidelines and industry standards, with mock-ups required for architect approval. The manufacturer's one-year warranty covers defects in materials and workmanship, with extended warranties of 20 years available for window units and sealed glass units.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-265-24

FOR: Ashland Readiness Center Envelope Renovation 2519 Lexington Ave Department of Military Affairs Ashland, Kentucky

DATE: August 30, 2024

RFB-785-2400000705

ADDENDUM NO. Ten (10)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: This project is being re-advertised via this addendum. All previously issued documents (plans, specs and addenda) are still applicable to this project including any changes provided in this addendum.

Item 2: The bids are due on September 19, 2024 at 1:30 PM, ET. The official bid opening will be at

3:00 PM, ET. The call-in information in the spec book still apply.

Item 3 Performance and payment bonds and certificate of insurance will be required from the low bidder within 48 hours of the issuance of the intent to award letter.

Item 4: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.

Item 5: Attached are the revised Architectural Sheets A511, A512, and A631 for a change in project scope. Scope of work related to the restoration of historical steel windows has been eliminated. Revised scope changed to complete replacement of existing windows with new aluminum ATFP compliant systems. Attached are the revised Specification Sections 08400, 085110, and 08800 for information related to Glazed Aluminum Entrance Systems, Aluminum Windows, and Glazing.

END OF ADDENDUM

Invitation to Bid No. RFB-265-24 For: Ashland Readiness Center Envelope Renovation 2519 Lexington Ave Department of Military Affairs Ashland, Kentucky

Kristi Sharp, Statewide Procurement Manager Division of Engineering and Contract Administration

DMA – ASHLAND RC ENVELOPE RENOVATION WRK.DEC2301

095-CAXB-AS23-00 AUGUST 2024

084000-1 GLAZED ALUMINUM DOOR ENTRANCES, STOREFRONTS, AND CURTAINWALLS

SECTION 084000

GLAZED ALUMINUM SECURITY DOOR ENTRANCES, STOREFRONTS, AND CURTAIN WALLS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Glazed aluminum security curtain wall systems.

B. Glazed aluminum security storefront systems.

C. Glazed aluminum security doors and frame systems.

1.02 RELATED SECTIONS

A. Section 08 44 23 - Structural Sealant Glazed Curtain Wall.

1.03 REFERENCES

A. AAMA 611 - Voluntary Specification for Anodized Architectural Aluminum.

B. AAMA 701 - Voluntary specification for pile weatherstripping and replaceable fenestration weather seals.

C. AAMA 2603 - Voluntary Specification, Performance Requirements and Test Procedures For Pigmented Organic

Coatings on Aluminum Extrusions and Panels.

D. ASHRAE 90.1 - Energy Standard for Buildings Except Low-Rise Residential Buildings.

E. ASTM A1008/A1008M - Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength

Low-Alloy, High-Strength Low-Alloy with Improved Formability, Required Hardness, Solution Hardened, and Bake

Hardenable.

F. ASTM B209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate.

G. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and

Tubes.

H. ASTM C1172 - Standard Specification for Laminated Architectural Flat Glass.

I. ASTM E330/E330M - Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and

Curtain Walls by Uniform Static Air Pressure Difference.

J. ASTM E331 - Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference.

K. ASTM F1642 - Standard Test Method for Glazing and Glazing Systems Subject to Airblast Loadings.

L. ASTM F2248 - Standard Test Method for Specifying an Equivalent 3-Second Duration Design Loading for Blast

Resistant Glazing Fabricated with Laminated Glass.

M. NFRC 100 - Procedure for Determining Fenestration Product U-Factors.

N. NFRC 200 - Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence.

O. NFRC 400 - Procedure for Determining Fenestration Product Air Leakage.

1.04 SUBMITTALS

A. Submit under provisions of Section 01 30 00 - Administrative Requirements.

B. Product Data:

1. Manufacturer's data sheets on each product to be used.

2. Preparation instructions and recommendations.

3. Storage and handling requirements and recommendations.

4. Typical installation methods.

C. Verification Samples: Two representative units of each type, size, pattern, and color.

084000-2 GLAZED ALUMINUM DOOR ENTRANCES, STOREFRONTS, AND CURTAINWALLS

D. Shop Drawings: Include details of materials, construction, and finish. Include relationship with adjacent construction.

E. Certificate of Compliance: Certification that installed products meet specified design and performance requirements.

1.05 QUALITY ASSURANCE

A. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with a minimum five years documented experience.

B. Installer Qualifications: Company specializing in performing Work of this section with minimum two years documented experience with projects of similar scope and complexity.

C. Source Limitations: Provide each type of product from a single manufacturing source to ensure uniformity.

E. Mock-Up: Construct a mock-up with actual materials in sufficient time for Architect's review and to not delay construction progress. Locate mock-up as acceptable to Architect and provide temporary foundations and support.

1. Intent of mock-up is to demonstrate quality of workmanship and visual appearance.

2. If mock-up is not acceptable, rebuild mock-up until satisfactory results are achieved.

3. Retain mock-up during construction as a standard for comparison with completed work.

4. Do not alter or remove mock-up until work is completed or removal is authorized.

1.06 PRE-INSTALLATION CONFERENCE

A. Convene a conference approximately two weeks before scheduled commencement of the Work. Attendees shall include Architect, Contractor and trades involved. Agenda shall include schedule, responsibilities, critical path items and approvals.

1.07 DELIVERY, STORAGE, AND HANDLING

A. Store and handle in strict compliance with manufacturer's written instructions and recommendations.

B. Protect from damage due to weather, excessive temperature, and construction operations.

1.08 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

1.09 WARRANTY

A. Manufacturer's one year warranty against defects in materials and workmanship.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Acceptable Manufacturers:

1. Kawneer

2. YKK

3. Tubelite

B. Substitutions: Permitted.

C. Requests for substitutions will be considered in accordance with DECA Procedures Manual.

2.02 GLAZED ALUMINUM SECURITY STOREFRONT SYSTEMS

A. Performance Requirements:

1. Blast Resistance:

084000-3 GLAZED ALUMINUM DOOR ENTRANCES, STOREFRONTS, AND CURTAINWALLS

a. Hazard Rating according to ASTM F1642: Low

2. Water Penetration: No uncontrolled water leakage, Tested to ASTM E331.

a. A minimum static air pressure differential of 10.0 psf.

3. Energy Performance: Certify and label energy performance for fixed glazing and framing areas per NFRC or other nationally recognized accredited standards organization acceptable to authorities having jurisdiction.

a. Thermal Transmittance (U-Factor): Climate Zone per ASHRAE 90.1-19 and IECC.

i Climate Zone: 4a U-Factor per NFRC 100:

(a) 0.68 Btu/sq ft. x h x degree F.

b. Air Infiltration: Maximum air leakage through fixed framing and glass areas of 0.4 cfm per sq. ft. of fixed wall area per NFRC 400.

c. Solar Heat Gain Coefficient: Climate Zones per ASHRAE 90.1-19 and 2021 IECC.

i Climate Zone: 4. SHGC of not more than 0.36 per NFRC 200.

B. Glazed Aluminum Security Curtain Wall System:

1. Product: Model USAW-400. Flush-glazed, thermally broken, extruded aluminum framed.

a. Type: Ballistic and blast-resistant storefront.

2. Framing: 2-1/2” to 3-1/2” x 4-1/2. Designed to receive blast-resistant glazing retained mechanically with gaskets on four sides.

a. Glazing Thickness: minimum ¼ inch laminated.

3. Blast-Resistant Glazing in thicknesses as necessary to comply with requirements indicated.

a. Form: Laminated glass per ASTM F2248.

C. Accessories:

1. Anchors: Series 316 stainless steel.

2. Exposed Flashing: Aluminum sheet per Div. 07 Section "FLASHING AND SHEET METAL"; finish to match framing members.

3. Concealed Flashing: Dead-soft, 0.018 inch (0.457 mm) thick stainless steel, ASTM A240 of type recommended by manufacturer.

4. Framing Sealants: Manufacturer's standard.

5. Joint Sealants: For installation at perimeter of framing, as specified in Section 07 91 23 - Backer Rods0.

D. Materials:

1. Aluminum: Alloy and temper recommended by manufacturer for type of use and finish indicated.

a. Extrusions: ASTM B221.

b. Sheet: ASTM B209.

2. Steel Reinforcement: Manufacturer's standard; galvanized or zinc-rich primed finish.

a. Structural Shapes, Plates, and Bars: ASTM A36/A36M.

b. Cold-Rolled Sheet and Strip: ASTM A1008/A1008M.

E. Finishes:

1. Aluminum Finish: Anodized in accordance with AAMA 611, Architectural Class I anodized.

a. Color: Clear.

b. Color: Dark bronze.

2. Aluminum Finish: Organic 2-Coat PVDF Fluoropolymer. Prepare, pretreat, and apply to exposed metal surfaces complying with coating and resin manufacturers' written instructions.

a. Performance: Superior in accordance with AAMA 2605. Not less than 70 percent PVDF resin by weight in color coat.

b. Performance: High in accordance with AAMA 2604. Not less than 50 percent PVDF resin by weight in color coat.

c. Color: Stock color selected from manufacturer's full color range.

3. Aluminum Finish: Pigmented Organic. Thermosetting polyester baked enamel coating system.

a. Performance: AAMA 2603.

b. Color: Stock color selected from manufacturer's full color range.

c. Color: Custom color as directed.

PART 3 EXECUTION

3.01 EXAMINATION AND PREPARATION

084000-4 GLAZED ALUMINUM DOOR ENTRANCES, STOREFRONTS, AND CURTAINWALLS

A. Inspect and prepare openings and substrates using the methods recommended by the manufacturer for achieving best result for the substrates under project conditions.

1. Inspect assembly components prior to installation.

2. Verify rough opening conditions are within recommended tolerances.

3. Form sheet metal sill pan in accordance with manufacturer’s recommendations.

4. Prepare assembly components for installation in accordance with manufacturer’s recommendations.

B. Do not proceed with installation until openings and substrates have been prepared using the methods recommended by the manufacturer and deviations from manufacturer’s recommended tolerances are corrected.

Commencement of installation constitutes acceptance of conditions.

C. If preparation is the responsibility of another installer, notify Architect in writing of deviations from manufacturer’s recommended installation tolerances and conditions.

3.02 INSTALLATION

A. Install assemblies in accordance with manufacturer’s installation guidelines and recommendations including the following.

B. Aluminum Security Curtainwall and Storefront:

1. Install framing and glazing in accordance with manufacturer's instructions and approved Shop Drawings.

2. Installation Tolerances: Comply with the following non-accumulating maximum tolerances:

3. Maximum Variation in Diagonal Framing Measurements: 1/8 inch 3 mm).

4. Offset Between Adjacent Framing Members: 1/16 inch (1.5 mm).

5. Maximum Variation from Plumb: 1/8 inch (3 mm) per 12 ft (3.658 m).

6. Sealant space between system and adjacent construction:

a. As indicated but not greater than 1/2 inch (13 mm) or less than 1/4 inch (6 mm).

C. Aluminum Security Doors and Frames:

1. Install doors, framing, and glazing in accordance with manufacturer's instructions and approved Shop

Drawings and appropriate related sections in Division 08,

2. Installation Tolerances: Comply with the following non-accumulating maximum tolerances:

a. Maximum Variation in Diagonal Framing Measurements: 1/8 inch (3 mm).

b. Offset Between Adjacent Framing Members: 1/16 inch (1.5 mm).

c. Maximum Variation from Plumb: 1/8 inch (3 mm) per 12 ft (3.658 m).

d. Alignment: Plus or minus 1/16 inch (1.5 mm) from door face to face of framing.

e. Door Twist: Plus or minus 1/16 inch (1.5 mm), measured at opposite face corners of jambs on parallel lines, and perpendicular to plane of wall.

f. Sealant space between system and adjacent construction:

i As indicated but not greater than 1/2 inch (13 mm) or less than 1/4 inch (6 mm).

3. Design Clearances:

a. Between Door and Frame: Maximum 1/8 inch (3 mm).

b. Between Edges of Pairs of Doors: 1/8 inch (3 mm) plus or minus 1/16 inch (1.5 mm).

4. Between Bottom of Door and Top of Threshold: Maximum 3/8 inch (10 mm).

3.01 FIELD QUALITY CONTROL

A. Manufacturers’ Field Services: Field inspections.

3.02 CLEANING AND PROTECTION

A. Clean the exterior surface and glass with mild soap and water.

B. Protect installed windows from damage.

C. Remove and dispose of protective film from glass; touch-up, repair or replace damaged components and assemblies before Substantial Completion.

084000-5 GLAZED ALUMINUM DOOR ENTRANCES, STOREFRONTS, AND CURTAINWALLS

3.03 SCHEDULES

A. Reference Construction Documents Window Schedules.

END OF SECTION 08511

08511-1 ALUMINUM WINDOWS

SECTION 08511

ALUMINUM WINDOWS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Blast-Resistant Aluminum Windows

1. Glazed Aluminum Blast-Resistant Windows.

1.02 REFERENCES

A. American Architectural Manufacturer Association (AAMA):

1. AAMA 611 - Voluntary Specification for Anodized Architectural Aluminum.

2. AAMA 701 - Voluntary specification for pile weatherstripping and replaceable fenestration weather seals.

3. AAMA 2603 - Voluntary Specification, Performance Requirements and Test Procedures For Pigmented Organic

Coatings on Aluminum Extrusions and Panels.

B. ASTM International (ASTM):

1. ASTM E 283 - Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain

Walls, and Doors Under Specified Pressure Differences Across the Specimen.

2. ASTM E 330 - Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and

Curtain Walls by Uniform Static Air Pressure Difference.

3. ASTM E331 - Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain

Walls by Uniform Static Air Pressure Difference.

4. ASTM F1642 - Standard Test Method for Glazing and Glazing Systems Subject to Airblast Loadings.

5. ASTM F2248 - Standard Test Method for Specifying an Equivalent 3-Second Duration Design Loading for Blast

Resistant Glazing Fabricated with Laminated Glass.

6. ASTM B209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate.

7. ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and

Tubes.

8. ASTM C1172 - Standard Specification for Laminated Architectural Flat Glass.

C. National Fenestration Rating Council (NFRC):

1. NFRC 100 - Procedure for Determining Fenestration Thermal Properties.

2. NFRC 200 - Solar Heat Gain Coefficient and Visible Transmittance.

3. NFRC 400 - Procedure for Determining Fenestration Product Air Leakage.

E. Antiterrorism and Force Protection Standards (ATFP). Refer to UFC 4-010-01 with Change 1 dated 19 August, 2020 for Department of Defense Minimum Antiterrorism Standards for Buildings.

1.03 SUBMITTALS

A. Submit under provisions of Section 01300.

B. Product Data: Manufacturer's data sheets on each product to be used, including:

1. Preparation instructions and recommendations.

2. Storage and handling requirements and recommendations.

3. Installation methods.

C. Shop Drawings: Submit shop drawings indicating details of construction, flashings, relationship with adjacent construction, and elevations of each opening type depicting configuration of mullion and muntin pattern.

D. Selection Samples: For each factory-finished product specified, two complete sets of color chips representing manufacturer's full range of available finishes.

08511-2 ALUMINUM WINDOWS

E. Verification Samples: For each factory-finished product specified, two samples, minimum size 6 inches (150 mm) square, representing actual finishes.

F. Quality Assurance Submittals:

1. Design Data, Test Reports: Provide manufacturer test reports indicating product compliance with indicated requirements.

G. Closeout Submittals: Refer to Section 01700 Closeout Submittals.

1.04 QUALITY ASSURANCE

A. Installer Qualifications: Minimum 2 years installing similar assemblies.

B. Mock-Up: Provide a mock-up for evaluation of installation techniques and workmanship.

1. Mock-ups shall incorporate surrounding construction, including wall assembly fasteners, flashing, and other related accessories installed in accordance with manufacturer’s approved installation methods.

2. Do not proceed with remaining work until workmanship is approved by Architect.

3. Rework mock-up as required to produce acceptable work.

4. At Substantial Completion, approved mockups may become part of completed work.

5. Demolish mockups and remove from site.

C. Pre-installation Meeting: Conduct pre-installation meeting on-site two weeks prior to commencement of installation.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Deliver, store and handle materials and products in strict compliance with manufacturer's instructions and recommendations and industry standards.

B. Deliver and store assembly materials and components in manufacturer’s original, unopened, undamaged containers with identification labels intact. Protect from damage.

1.06 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

1.07 WARRANTY

A. Manufacturer’s Standard Warranty: Assemblies will be free from defects in materials and workmanship from the date of Substantial Completion for the time periods indicated below:

1. Window Units: 20 years.

2. Clad Finishes: 20 years against peeling, checking, cracking caulk or color change.

3. Glazing:

a. Insulated Glass: 20 years against seal breakage.

b. Laminated Glass: 5 years.

c. Specialty Glazing: 5 years against delamination.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Acceptable Manufacturer:

1. Kawneer

2. Peerless

3. Winco

B. Substitutions: Permitted.

08511-3 ALUMINUM WINDOWS

C. Requests for substitutions will be considered in accordance with provisions of Section 01600.

2.02 GLAZED ALUMINUM WINDOWS

A. Performance Requirements:

1. Blast Resistance:

a. Hazard Rating according to ASTM F1642: Low

2. Water Penetration: No uncontrolled water leakage, Tested to ASTM E331.

a. A minimum static air pressure differential of 10.0 psf.

3. Energy Performance: Certify and label energy performance for fixed glazing and framing areas per NFRC or other nationally recognized accredited standards organization acceptable to authorities having jurisdiction.

a. Thermal Transmittance (U-Factor): Climate Zone per ASHRAE 90.1-19 and IECC.

i Climate Zone: 4a U-Factor per NFRC 100:

(a) 0.68 Btu/sq ft. x h x degree F.

b. Air Infiltration: Maximum air leakage through fixed framing and glass areas of 0.4 cfm per sq. ft. of fixed wall area per NFRC 400.

c. Solar Heat Gain Coefficient: Climate Zones per ASHRAE 90.1-19 and 2021 IECC.

i Climate Zone: 4. SHGC of not more than 0.36 per NFRC 200.

B. Glazed Aluminum Windows:

1. Product: Flush-glazed, thermally broken, extruded aluminum framed.

a. Type: Blast-Resistant storefront.

2. Framing: 2-1/2” to 3-1/2” x 4-1/2. Designed to receive ballistics-resistant glazing retained mechanically with gaskets on four sides.

a. Glazing Thickness: minimum ¼ inch laminated.

3. Ballistics-Resistant Glazing: Thicknesses indicated are minimums. Ballistics-resistant glazing in thicknesses as necessary to comply with requirements indicated.

a. Form: Laminated glass per ASTM C1172

C. Accessories:

1. Glazing Accessories: Specified in Section 08 83 13 - Mirrored Glass Glazing0.

2. Anchors: Series 316 stainless steel.

3. Concrete and Masonry Inserts: Hot-dip galvanized cast-iron, malleable-iron, or steel inserts, complying with

ASTM A123/A123M or ASTM A153/A153M.

4. Exposed Flashing: Aluminum sheet per Div. 07 Section "FLASHING AND SHEET METAL"; finish to match framing members.

5. Concealed Flashing: Dead-soft, 0.018 inch (0.457 mm) thick stainless steel, ASTM A240 of type recommended by manufacturer.

6. Framing Sealants: Manufacturer's standard.

7. Joint Sealants: For installation at perimeter of framing, as specified in Section 07 91 23 - Backer Rods0.

D. Materials:

1. Aluminum: Alloy and temper recommended by manufacturer for type of use and finish indicated.

a. Extrusions: ASTM B221.

b. Sheet: ASTM B209.

2. Steel Reinforcement: Manufacturer's standard; galvanized or zinc-rich primed finish.

a. Structural Shapes, Plates, and Bars: ASTM A36/A36M.

b. Cold-Rolled Sheet and Strip: ASTM A1008/A1008M.

E. Finishes:

1. Aluminum Finish: Anodized in accordance with AAMA 611, Architectural Class I anodized.

a. Color: Clear.

b. Color: Dark bronze.

2. Aluminum Finish: Organic 2-Coat PVDF Fluoropolymer. Prepare, pretreat, and apply to exposed metal surfaces complying with coating and resin manufacturers' written instructions.

a. Performance: Superior in accordance with AAMA 2605. Not less than 70 percent PVDF resin by weight in color coat.

08511-4 ALUMINUM WINDOWS

b. Performance: High in accordance with AAMA 2604. Not less than 50 percent PVDF resin by weight in color coat.

c. Color: Stock color selected from manufacturer's full color range.

3. Aluminum Finish: Pigmented Organic. Thermosetting polyester baked enamel coating system.

a. Performance: AAMA 2603.

b. Color: Stock color selected from manufacturer's full color range.

c. Color: Custom color as directed.

3.01 EXAMINATION AND PREPARATION

A. Inspect and prepare openings and substrates using the methods recommended by the manufacturer for achieving best result for the substrates under project conditions.

1. Inspect assembly components prior to installation.

2. Verify rough opening conditions are within recommended tolerances.

3. Form sheet metal sill pan in accordance with manufacturer’s recommendations.

4. Prepare assembly components for installation in accordance with manufacturer’s recommendations.

B. Do not proceed with installation until openings and substrates have been prepared using the methods recommended by the manufacturer and deviations from manufacturer’s recommended tolerances are corrected.

Commencement of installation constitutes acceptance of conditions.

C. If preparation is the responsibility of another installer, notify Architect in writing of deviations from manufacturer’s recommended installation tolerances and conditions.

3.02 INSTALLATION

A. Install assemblies in accordance with manufacturer’s installation guidelines and recommendations including the following.

B. Installation of Windows Without Nailing Fins: Insert windows into rough opening.

1. Inspect window for square, level and plumb.

2. Fasten window through jamb, shim and into rough opening jamb.

3. Test and adjust for smooth operation of window, if an operable type.

4. Install backer rod and structural sealant at exterior jambs and head.

5. Apply backer rod and structural sealant on exterior below sill. Leave gaps for drainage.

6. Seal interior joints between rough opening and jambs with backer rod and sealant.

3.03 FIELD QUALITY CONTROL

A. Manufacturers’ Field Services: Field inspections.

3.04 CLEANING AND PROTECTION

A. Clean the exterior surface and glass with mild soap and water.

B. Protect installed windows from damage.

C. Remove and dispose of protective film from glass; touch-up, repair or replace damaged components and assemblies before Substantial Completion.

3.05 SCHEDULES

A. Reference Construction Documents Window Schedules.

END OF SECTION 08511

08800-1 GLASS AND GLAZING

SECTION 08800

GLASS AND GLAZING

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Glass and glazing for other Sections referencing this Section for products and installation.

B. Glass and glazing for flush wood doors and hollow metal work.

1.02 RELATED SECTIONS

A. Section 07900 - Joint Sealers: Sealant and back-up material.

B. Section 08111 - Standard Steel Doors.

C. Section 08112 - Standard Steel Frames.

D. Section 08400 - Aluminum Storefront and Entrances.

E. Section 08462 - Automatic Sliding Doors

1.03 REFERENCES

A. ANSI/ASTM E330 - Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air

Pressure Difference.

B. ANSI Z97.1 - Safety Performance Specifications and Methods of Test for Safety Glazing Used in Buildings.

C. ASTM C1036 - Flat Glass.

D. ASTM C1048 - Heat-Treated Flat Glass - Kind HS, Kind FT Coated and Uncoated Glass.

E. ASTM C1172 - Standard Specification for Laminated Architectural Float Glass.

F. ASTM E546 - Test Method For Frost Point of Sealed Insulating Glass Units.

G. ASTM E576 - Test Method For Dew/Frost Point of Sealed Insulating Glass Units in Vertical Position.

H. ASTM E773 - Test Method for Seal Durability of Sealed Insulating Glass Units.

I. ASTM E774 - Sealed Insulating Glass Units.

J. FGMA - Glazing Manual.

K. FGMA - Sealant Manual.

L. FS TT-C-00598 - Calking Compound, Oil and Resin Base Type.

M. FS TT-S-001657 - Sealing Compound, Single Component, Butyl Rubber Based, Solvent Release Type.

N. FS TT-S-00227 - Sealing Compound, Rubber Base, Two Component.

O. FS TT-S-00230 - Sealing Compounds, Synthetic-Rubber Base, Single Component, Chemically Curing.

P. FS TT-S-01543 - Sealing Compound, Silicone Rubber Base.

Q. FS TT-G-410 - Glazing Compound, Sash (Metal) for Back Bedding and Face Glazing (Not for Channel or Stop Glazing).

R. Laminators Safety Glass Association - Standards Manual.

S. SIGMA - Sealed Insulated Glass Manufacturers Association.

T. ASTM F1642 - Standard Test Method for Glazing and Glazing Systems Subject to Airblast Loadings.

U. ASTM F2248 - Standard Test Method for Specifying an Equivalent 3-Second Duration Design Loading for Blast

Resistant Glazing Fabricated with Laminated Glass.

T. UFC 4-010-01 – Unified Facilities Code.

1.04 PERFORMANCE REQUIREMENTS

A. Glass and glazing materials of this Section shall provide continuity of building enclosure vapor and air barrier:

1. In conjunction with materials described in Section 07270 and Section 07900.

2. To utilize the inner pane of multiple pane sealed units for the continuity of the air and vapor seal.

3. Maintain continuous air and vapor barrier throughout glazed assembly from glass pane to heel bead of glazing sealant.

B. Size glass to withstand dead loads and positive and negative live loads acting normal to plane of glass as calculated in accordance with current Kentucky Building Codes and as indicated on the Structural Drawings.

C. Limit glass deflection to 1/200 or flexure limit of glass with full recovery of glazing materials, whichever is less.

1.05 SUBMITTALS

A. Submit under provisions of Section 01300.

08800-2 GLASS AND GLAZING

B. Product Data on Glass Types Specified:

1. Provide structural, physical and environmental characteristics, size limitations, special handling or installation requirements.

C. Product Data on Glazing Accessories: Provide chemical, functional, and environmental characteristics, limitations, special application requirements. Identify available colors.

D. Samples: Submit two samples, 12x12 inch in size, illustrating each glass unit, coloration and design.

E. Samples: Submit one 12 inch long bead of glazing sealant, color as selected.

F. Manufacturer's Installation Instructions: Indicate special precautions required.

G. Manufacturer's Certificate: Certify that glass meets or exceeds specified requirements.

1.06 QUALITY ASSURANCE

A. Perform Work in accordance with FGMA Glazing Manual, FGMA Sealant Manual, SIGMA and Laminators Safety Glass

Association - Standards Manual for glazing installation methods.

B. Maintain one copy of each document on site.

1.07 PRE-INSTALLATION CONFERENCE

A. Convene one week prior to commencing Work of this Section, under provisions of Section 01039.

1.08 ENVIRONMENTAL REQUIREMENTS

A. Do not install glazing when ambient temperature is less than 50 degrees F.

B. Maintain minimum ambient temperature before, during and 24 hours after installation of glazing compounds.

1.09 FIELD MEASUREMENTS

A. Verify that field measurements are as indicated on Shop Drawings.

1.10 COORDINATION

A. Coordinate Work under provisions of Section 01039.

B. Coordinate the Work with glazing frames, wall openings, and perimeter air and vapor seal to adjacent Work.

1.11 WARRANTY

A. Provide ten year manufacturer's warranty for all materials specified herein under provisions of Section 01700.

B. Warranty: Include coverage for sealed glass units from seal failure, interpane dusting or misting, and replacement of same.

C. Warranty: Include coverage for delamination of laminated glass and replacement of same.

PART 2 PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. Clear Glass, Tinted Glass for Single Pane and Insulating Unit Applications:

1. PPG Industries, Inc. (Pittsburgh, PA).

2. Interpane Glass Co. (Clinton, NC).

3. Pilkington North America, Inc. (Toledo, OH).

4. Viracon (Owatonna, MN).

B. Substitutions: Under provisions of Section 01600.

C. Acceptable Manufacturers/Fabricators (General Note): Obtain materials from only one manufacturer and one fabricator for each aforementioned category (A/B).

2.02 GLASS/GLAZING

A. (Type G-01) Vision – Clear Insulating Solar Low-E Glass Unit:

1. Overall Unit Thickness: 1”.

2. Thickness: 1/4” (6.0mm).

3. Airspace: 1/2”.

4. Sealing System: Dual seal.

08800-3 GLASS AND GLAZING

5. Warranty Ten (10) year.

6. Outdoor Lite: Clear, Solarban 70XL Solar Control Low-E (sputtered, second surface) as manufactured by PPG Industries, Inc. (Pittsburgh, PA).

7. Indoor Lite: Clear, “transparent” float glass (heat strengthened) as manufactured by PPG

Industries, Inc. (Pittsburgh, PA).

8. Performance Values: Visible Light Transmission: 64%/48%.

U-Value Winter: .28/.29

U-Value Summer: .26/.27

SHGC: .27/.24

Shading Coefficient: .32/.28

Outdoor Visible Light Reflectance: 12%/33%

9. Provide units meeting the aforementioned Performance Values which comply with all requirements of Section

2406 - Safety Glazing of the Kentucky Building Code (KBC - 2007 Edition) at all locations indicated in the

Drawings or required by the KBC.

B. (Type G-02) Vision - Clear Single-Pane Glass - Tempered:

1. Description: 1/4” Clear Float Glass (tempered), as manufactured by PPG Industries, Inc.

C. (Type G-03) Vision - Clear Fire-Rated Glass:

1. Description: 1/4” Firelite (20 minute rating) or Firelite NT (greater than 20 minute rating)

Fire Rated Glazing, as manufactured by Technical Glass Products (Kirkland, WA) capable of providing a certified fire rating compatible with the stipulated fire rating of the door and/or window assembly in which it is located.

C. (Type G-04) Vision - Clear Blast Resistant Glass:

1. Overall Unit Thickness: 1”.

2. Lite Thickness: 1/4” (6.0mm).

3. Airspace: 1/2”.

4. Sealing System: Dual seal.

5. Warranty Ten (10) year.

6. Outdoor Lite: Clear, Solarban 70XL Solar Control Low-E (sputtered, second surface) as manufactured by PPG Industries, Inc. (Pittsburgh, PA).

7. Indoor Lite: 1/4" (6.0mm) laminated glass consisting of two nominal 1/8” (3.0 mm) glass panes bonded together with a minimum of a 0.030 in. (0.75 mm) interlayer of a material that has typically been used in blast resistant window applications.

8. Performance Values: Visible Light Transmission: 64%/48%.

U-Value Winter: .28/.29

U-Value Summer: .26/.27

SHGC: .27/.24

Shading Coefficient: .32/.28

Outdoor Visible Light Reflectance: 12%/33%

9. Additional Notes: For insulated glass units (IGU), use the laminated glass for the innermost pane as a minimum. For laminated glass, the laminated pane shall be adhered to its supporting frame using structural silicone sealant or adhesive glazing tape.

The structural silicone sealant bite shall be equal to the larger of 3/8-in. (10-

mm) or the thickness of the laminated glass to which it adheres. The minimum thickness of the structural silicone bead shall be 3/16-in. (5-mm). The glazing tape bite shall be equal to two times the thickness of the laminated glass to which it adheres. The structural silicone bead or glazing tape shall be applied to both sides of single pane laminated glass but need only be applied to the inboard (protected) side of an IGU.

2.03 GLAZING ACCESSORIES

08800-4 GLASS AND GLAZING

A. Setting Blocks: Neoprene 80 - 90 Shore A durometer hardness, length of 0.1 inch for each square foot of glazing or minimum 4 inch x width of glazing rabbet space minus 1/16 inch x height to suit glazing method and pane weight and area.

B. Spacer Shims: Neoprene, 50 - 60 Shore A durometer hardness, minimum 3 inch long x one half the height of the glazing stop x thickness to suit application.

C. Glazing Tape: Preformed butyl compound with integral resilient tube spacing device; 10 - 15 Shore A durometer hardness; coiled on release paper; gray color.

D. Glazing Gaskets: Resilient polyvinyl chloride extruded shape to suit glazing channel retaining slot; color as selected.

E. Glazing Clips: Manufacturer's standard type.

F. Aluminum Glazing Channels: Where indicated in Construction Drawings, provide clear anodized aluminum glazing channels with concealed fasteners at casework/soffits to secure glass panels. Coordinate exact configuration with Architect.

2.04 SOURCE QUALITY CONTROL AND TESTS

A. Provide testing of glass under provisions of Section 01400.

B. Provide shop inspection and testing for glass.

C. Test samples in accordance with ANSI Z97.1.

D. Provide identification on each pane of safety (tempered) glazing consisting of a clearly visible label specifying the labeler, the manufacturer or installer, and the safety glazing standard with which it complies. The label shall be acid etched, sand blasted, ceramic fired, or an embossed mark, or shall be of a type that once applied cannot be removed without being destroyed.

3.01 EXAMINATION

A. Examine areas to receive glass. Notify Architect of conditions that would adversely affect installation. Do not proceed with installation until unsatisfactory conditions are corrected.

3.02 PREPARATION

A. Verify glazing openings are correct size and within tolerance.

B. Verify glazing channels, recesses, and weeps are clean and free of obstructions.

3.03 GLAZING

A. Install glass in accordance with manufacturer's instructions, except where local codes or GANA Glazing Manual indicate more stringent requirements.

3.04 FIELD QUALITY CONTROL

A. Coated glass, when viewed from minimum of 10 feet, exhibiting slightly different hue or color not apparent in hand samples, will not be cause of rejection of glass units, as determined by Architect.

B. Verify glass is free of chips, cracks, and other inclusions that could inhibit structural or aesthetic integrity.

3.05 CLEANING

A. Clean glass promptly after installation in accordance with manufacturer's instructions.

B. Remove labels from glass surface.

C. Do not use harsh cleaning materials or methods that would damage glass.

3.06 PROTECTION

A. Protect installed glass from damage during construction.

B. Protect installed glass from contact with contaminating substances resulting from construction operations.

08800-5 GLASS AND GLAZING

C. Remove and replace glass that is broken, chipped, cracked, abraded, or damaged in other ways during construction period, including natural causes, accidents, and vandalism.

3.07 SCHEDULE

A. Reference Opening Schedule and Frame Elevations for glass types.

END OF SECTION

01 06

05 05

0505 0404

INSPECT EXISTING GRADE AND

MODIFY FOR POSITIVE

DRAINAGE. REFER TO CIVIL.

03 03

REMOVE EXISTING HISTORICAL WINDOW COMPLETE AND SALVAGE TO USER AGENCY.

PREPARE SURFACES OF EXISTING OPENING FOR INSTALLATION OF NEW WINDOW.

PROVIDE NEW ATFP RATED WINDOW WITHIN EXISTING OPENING AND ANCHORED TO

EXISTING WALL ASEMBLY. NEW WINDOW SYSTEM SHALL MIMIC MUNTIN PATTERN OF

HISTORIC FENESTRATION. VERIFY MUNTIN PATTERN IN-FIELD. SEE DETAILS AND

SPECIFICATIONS FOR REQUIREMENTS.

ELEVATION KEYED NOTES

MODIFY EXISTING METAL DOOR TO MEET ATFP STANDARD. DOORS ARE TO SWING

OUTWARD, AND GLAZING TO BE REPLACED WITH ATFP COMPLIANT MATERIAL. REFER

TO SPECIFICATIONS FOR GLAZING REQUIREMENTS.

INSPECT, PATCH, AND REPAIR EXISTING OVERHEAD DOOR. OVERHEAD DOORS DO

NOT HAVE AFTP REQUIREMENTS.

INSPECT, PATCH, AND REPAIR DAMAGED COMPONENTS OF EXISTING MASONRY

FACADE AND COPING.

INSPECT, PATCH, AND REPAIR DAMAGED EXISTING COMPONENTS OF STORM WATER

DRAINAGE SYSTEM.

INSPECT, PATCH, AND REPAIR HISTORIC DOORS FOR RE-INSTALLATION AT EXTERIOR

OPENING. REPLACE STOREFRONT SYSTEM AT INTERIOR OPENING WITH AN ATFP RATED

ASSEMBLY. REFER TO SPECIFICATIONS FOR REQUIREMENTS.

DMA - ASHLAND RC ENVELOPE RENOVATION

2519 LEXINGTON AVE. ASHLAND, KY 41101

05-03-2024

KERSTING

JRC

C

095CAXBAS2300

REVISION HISTORY OF THIS DRAWING

DECA LOG #

ENGR. FILE NO.

DRAWING NO.

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

A511

EXTERIOR ELEVATIONS

DISCLAIMER:

EXISTING DRAWINGS INCLUDED ON THIS SHEET ARE NOT

TO A SCALE. DIMENSIONS AND SIZING SHALL BE VERIFIED

IN-FIELD PRIOR TO PERORMANCE OF THE WORK.

01 01

01 01 01 01 01

010101

03 0302

05 05

INSPECT EXISTING GRADE AND

MODIFY FOR POSITIVE

DRAINAGE. REFER TO CIVIL.

INSPECT, PATCH, AND REPAIR SINGLE-PLY

ROOFING, FLASHING, AND SEALANTS TO

ENSURE WEATHERTIGHT CONDITION. TYP.

REFER TO CIVIL FOR DETAIL TO ROUTE

WINDOW WELL STORM DRAINAGE

THROUGH EXISTING WALL TO NEW SUMP.

INSPECT, PATCH, AND

REPAIR EXISTING TRENCH

DRAIN. REFER TO CIVIL.

01 0202

05 05 04040404

04 04

REMOVE EXISTING HISTORICAL WINDOW COMPLETE AND SALVAGE TO USER AGENCY.

PREPARE SURFACES OF EXISTING OPENING FOR INSTALLATION OF NEW WINDOW.

PROVIDE NEW ATFP RATED WINDOW WITHIN EXISTING OPENING AND ANCHORED TO

EXISTING WALL ASEMBLY. NEW WINDOW SYSTEM SHALL MIMIC MUNTIN PATTERN OF

HISTORIC FENESTRATION. VERIFY MUNTIN PATTERN IN-FIELD. SEE DETAILS AND

SPECIFICATIONS FOR REQUIREMENTS.

ELEVATION KEYED NOTES

MODIFY EXISTING METAL DOOR TO MEET ATFP STANDARD. DOORS ARE TO SWING

OUTWARD, AND GLAZING TO BE REPLACED WITH ATFP COMPLIANT MATERIAL. REFER

TO SPECIFICATIONS FOR GLAZING REQUIREMENTS.

INSPECT, PATCH, AND REPAIR EXISTING OVERHEAD DOOR. OVERHEAD DOORS DO

NOT HAVE AFTP REQUIREMENTS.

INSPECT, PATCH, AND REPAIR DAMAGED COMPONENTS OF EXISTING MASONRY

FACADE AND COPING.

INSPECT, PATCH, AND REPAIR DAMAGED EXISTING COMPONENTS OF STORM WATER

DRAINAGE SYSTEM.

INSPECT, PATCH, AND REPAIR HISTORIC DOORS FOR RE-INSTALLATION AT EXTERIOR

OPENING. REPLACE STOREFRONT SYSTEM AT INTERIOR OPENING WITH AN ATFP RATED

ASSEMBLY. REFER TO SPECIFICATIONS FOR REQUIREMENTS.

DMA - ASHLAND RC ENVELOPE RENOVATION

2519 LEXINGTON AVE. ASHLAND, KY 41101

05-03-2024

KERSTING

JRC

C

095CAXBAS2300

REVISION HISTORY OF THIS DRAWING

DECA LOG #

ENGR. FILE NO.

DRAWING NO.

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E FILE NO.

DRAWING INFORMATION

A512

EXTERIOR ELEVATIONS

DISCLAIMER:

EXISTING DRAWINGS INCLUDED ON THIS SHEET ARE NOT

TO A SCALE. DIMENSIONS AND SIZING SHALL BE VERIFIED

IN-FIELD PRIOR TO PERORMANCE OF THE WORK.

REFERENCE GENERAL PROJECT NOTES SHEETS FOR COMPLETE

LISTING OF GENERAL NOTES AND CONVENTIONS.

1. REFER TO SECTION KEYED NOTES FOR SPECIFIC INSTRUCTIONS. REFER TO SECTION

LEGEND FOR STANDARD INDICATIONS.

2. REFER TO THE SPECIFICATION SECTIONS AS DENOTED BY THE KEYED NOTES.

3. REFER TO ENGINEER DRAWINGS WHEN KEYED NOTES DENOTE THE DISCIPLINE'S

ABBREVIATION AND SEQUENCE (IE; MECH.A1).

4. ALL OPENINGS TO BE FLASHED IN SUCH A MANNER AS TO PREVENT MOISTURE FROM

ENTERING THE WALL OR TO REDIRECT IT TO THE EXTERIOR. ALL FLASHING TO BE

INSTALLED IN A SINGLE-FASHION WITH END DAMS IN SUCH A MANNER TO PREVENT

THE ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE

BUILDING STRUCTURAL FRAMING COMPONENTS, AN THAT THE FLASHING IS TO EXTEND

TO THE SURFACE OF THE EXTERIOR WALL FINISH OR TO THE WATER-RESISTIVE

BARRIER FOR SUBSEQUENT DRAINAGE TO LIGHT.

5. REFERENCE INSULATION SCHEDULE FOR TYPICAL INSULATION TYPES AND

CONFIGURATION.

1.) REFER TO THE SPECIFICATION SECTIONS AS DENOTED BY THE KEYED NOTES.

2.) REFER TO ENGINEER DRAWINGS WHEN KEYED NOTES DENOTE THE DISCIPLINES

ABBREVIATION AND SEQUENCE (IE: MECH.A1).

3.) REFER TO ELEVATION KEYED NOTES FOR SPECIFIC INSTRUCTIONS. REFER TO

ELEVATION LEGEND FOR STANDARD INDICATIONS.

4.) REFERENCE OPENINGS ELEVATIONS AND SECTION DRAWINGS AS DENOTED BY THE

STANDARD INDICATORS AND KEYED NOTES.

5.) REFER TO HISTORIC WINDOW STUDY DOCUMENT CONDUCTED BY OWNER'S

HISTORIC PRESERVATION CONSULTANT FOR EXACT SCOPE OF WORK AND NOTES

REGARDING HISTORIC WINDOW AND DOOR REPAIR AND REPLACEMENT.

6.) REFERENCE PARTITION DETAILS SHEETS FOR RATED AND NON-RATED PARTITION

ASSEMBLY INFORMATION.

GENERAL SECTION NOTES

SUPPLEMENTAL REFERENCE DIRECTORY

EXTERIORINTERIOR

TYPICAL HEAD DETAIL

PREPARE SURFACES OF EXISTING

OPENING TO RECEIVE NEW BLAST

RESISTANT WINDOW SYSTEM.

PROTECT EXISTING FINISHES FROM

DEMOLITION WORK, PATCH AND

REPAIR TO LIKE NEW CONDITION

AFTER WINDOW INSTALLATION.

DELEGATED DESIGN OF STEEL

BACK SUPPORT EXPOXY BOLTED

INTO EXISTING CONCRETE LINTEL

NEW ATFP ALUMINUM WINDOW

SYSTEM WITH HSITORIC MUNTIN

PATTERN. REFER TO SPECIFICATIONS.

GLAZING: G-04.

1"

PRE-FINISHED BENT ALUMINUM

FLASHING WITH DRIP EDGE SET IN BED

OF CONTINUOUS SILICON SELANT.

REMOVE EXISTING METAL

STOOL AS REQUIRED FOR

INSTALLATION OF NEW

WINDOW SYSTEM.

TYPICAL JAMB DETAIL

EXTERIORINTERIOR

PREPARE SURFACES OF EXISTING

OPENING TO RECEIVE NEW BLAST

RESISTANT WINDOW SYSTEM.

PROTECT EXISTING FINISHES FROM

DEMOLITION WORK, PATCH AND

REPAIR TO LIKE NEW CONDITION

AFTER WINDOW INSTALLATION.

DELEGATED DESIGN OF STEEL

BACK SUPPORT EXPOXY BOLTED

INTO EXISTING GROUTED CMU

NEW ATFP ALUMINUM WINDOW

SYSTEM WITH HSITORIC MUNTIN

PATTERN. REFER TO SPECIFICATIONS.

GLAZING: G-04.

1"

SILICONE SELANT AND BACKER ROD

CONTINUOUS AT JAMB CONDITIONS.

STRUCTURAL SEALANT . REFER TO

MANUFACTURER'S RECOMMENDATION.

EXTERIORINTERIOR

TYPICAL SILL DETAIL

PREPARE SURFACES OF EXISTING

OPENING TO RECEIVE NEW BLAST

RESISTANT WINDOW SYSTEM.

PROTECT EXISTING FINISHES FROM

DEMOLITION WORK, PATCH AND

REPAIR TO LIKE NEW CONDITION

AFTER WINDOW INSTALLATION.

DELEGATED DESIGN OF STEEL

BACK SUPPORT EXPOXY BOLTED

INTO EXISTING GROUTED CMU

NEW ATFP ALUMINUM WINDOW

SYSTEM WITH HSITORIC MUNTIN

PATTERN. REFER TO SPECIFICATIONS.

GLAZING: G-04.

1"

STRUCTURAL SEALANT . REFER TO

MANUFACTURER'S RECOMMENDATION.

GLAZING SCHEDULE

LABEL

G-01

G-02

G-03

PANES THERMAL COATINGS NOTES

DUAL YES - INSULATED LOW-E

ALL GLASS TO BE TEMPERED, U.N.O.

SINGLE

G-04 MULTI-PANE

SINGLE

NO ---

REFER TO SPECIFICATION

SECTION 08000

BLAST RESISTANTYES - INSULATED LOW-E

NO LOW-E NOT USED

NOT USED

REFERENCE GENERAL PROJECT NOTES SHEETS FOR COMPLETE

LISTING OF GENERAL NOTES AND CONVENTIONS. REFERENCE

ELEVATIONS DRAWINGS FOR COMPLETE LISTING OF GENERAL

ELEVATIONS NOTES AND CONVENTIONS.

1. REFER TO THE SPECIFICATION SECTIONS AS DENOTED BY THE KEYED NOTES.

2. REFER TO ENGINEER DRAWINGS WHEN KEYED NOTES DENOTE THE DISCIPLINES

ABBREVIATION AND SEQUENCE (IE: MECH.A1).

3. REFER TO ELEVATION KEYED NOTES FOR SPECIFIC INSTRUCTIONS. REFER TO

ELEVATION LEGEND FOR STANDARD INDICATIONS.

4. REFERENCE OPENINGS ELEVATIONS AND SECTION DRAWINGS AS DENOTED BY THE

STANDARD INDICATORS AND KEYED NOTES.

5. DOOR NUMBERS TYPICALLY CORRESPOND SEQUENTIALLY TO THE SPACE THEY

SERVE.

6. REFER TO SPECIFIC HEAD, JAMB, AND SILL DETAILS FOR TYPICAL CONDITIONS.

7. COORDINATE AND PROVIDE DOOR HARDWARE AS SCHEDULE IN THE

SPECIFICATIONS OR, IF NOT SPECIFIED, PROVIDE HARDWARE REQUIRED OR

DOORS TO OPERATE AND APPEAR AS INTENDED OF EQUAL QUALITY TO THAT

SPECIFIED IN MOST SIMILAR FUNCTION.

8. PROVIDE STAINLESS STEEL KICK PLATES ON PUSH SIDE OF DOORS WITH PUSH

BAR IN FINISH SELECTED BY ARCHITECT.

9. PROVIDE CONTINUOUS WEATHERSTRIPPING, HEAD RAIN DEFLECTOR, THRESHOLD,

AND DOOR BOTTOM SEALS AT EXTERIOR DOORS.

10. PROVIDE ACOUSTIC GASKETING AND DOOR BOTTOM SEAL AT AREAS REQUIRING

ACOUSTIC CONSIDERATIONS.

11. VERIFY IN FIELD DOOR SWINGS AND CONFIGURATIONS PRIOR TO INSTALLING

DOORS TO ENSURE INTENDED DOOR OPERATION.

12. COORDINATE REQUIRED TOLERANCES FOR SHIMS, ROUGH-OPENINGS, MOVEMENT,

ETC. WITH MANUFACTURER.

13. PROVIDE APPROPRIATE ANCHORAGE SYSTEM FOR ALL CONDITIONS TO SECURE

FRAMES IN ROUGH OPENINGS. PROVIDE

14. CONTINUOUSLY SEAL ALL SIDES OF HOLLOW METAL FRAMES ABUTTING

DISSIMILAR MATERIALS.

15. FRAME SECTION DEPTHS VARY IN WIDTH WITH THEIR RESPECTIVE WALL TYPE.

COORDINATE IN FIELD.

16. FILL HOLLOW METAL FRAMES ABUTTING MASONRY SOLID WITH GROUT. FILL

HOLLOW METAL FRAMES AT EXTERIOR LOCATIONS WITH THERMAL INSULATION,

U.O.N.

17. PROVIDE GALVANIZED HOLLOW METAL DOOR SYSTEMS AT EXTERIOR

CONDITIONS.

18. CONTINUOUSLY SEAL ALL SIDES OF ALUMINUM FRAMES AND SUBFRAMES

ABUTTING DISSIMILAR MATERIALS.

19. PROVIDE FOR THERMAL EXPANSION AT ALUMINUM FRAME SYSTEMS PER

MANUFACTURER'S RECOMMENDATIONS AT EACH INSTANCE.

20. AS REQUIRED FOR DESIGN LOADING, MANUFACTURER SHALL PROVIDE MULLION

REINFORCING, VERTICAL EXTENSIONS, AND STRUCTURAL ATTACHMENTS.

21. PROVIDE MANUAL ROLLER SHADES IN FINISH AS SELECTED BY ARCHITECT AT

ALL EXTERIOR WINDOWS, U.O.N.

GENERAL OPENINGS NOTES

1.) REFER TO WINDOW AND OPENINGS ELEVATIONS AND SCHEDULES FOR COMPLETE

DELINEATION OF WORK.

SUPPLEMENTAL REFERENCE DIRECTORY

REFERENCE GENERAL PROJECT NOTES SHEETS FOR COMPLETE

LISTING OF GENERAL NOTES AND CONVENTIONS. REFERENCE

HORIZONTAL ASSEMBLIES DETAILS AND LIFE SAFETY PLANS FOR

COMPLETE DELINEATION OF WORK.

1. RECESSED ITEMS: WHERE ITEMS ARE SHOWN TO BE RECESSED IN OR MOUNTED ON

FIRE-RATED OR ACOUSTIC PARTITIONS, THE FINISH SURFACE SHALL BE

CONTINUOUS BEHIND AND AROUND SUCH ITEM TO MAINTAIN THE CONTINUITY OF

THE SCHEDULED REQUIREMENT.

2. RECESSED WALL MOUNTED ELECTRICAL BOXES SHOULD BE OFFSET 24" MIN. AND

IN DIFFERING STUD CAVITIES. RECESSED BOXES ARE PROHIBITED FROM BEING

INSTALLED BACK TO BACK AND/OR SHARING A STUD CAVITY. PERIMETER OF ALL

RECESSED BOXES SHALL BE SEALED AIR-TIGHT WITH NON HARDENING

ACOUSTICAL SEALANT. PIPE/DUCT PENETRATIONS SHALL BE SLEEVED AND

PACKED WITH 10 LB. DENSITY CLOSED-CELL FOAM INSULATION AND SEALED TO

WALL WITH NON-HARDENING ACOUSTICAL SEALANT.

3. PROVIDE CONTINUOUS 3/8" BED OF NON-HARDENING SEALANT AT BASE OF ALL

GYP. BOARD (BOTH SIDES) TO FORM A COMPLETE CONTACT WITH BOTTOM

TRACK. REPEAT FOR MULTIPLE LAYERS OF GYPSUM BOARD. DO NOT ALLOW

GYPSUM BOARD TO SET DIRECTLY ON FLOOR.

4. PARTITIONS SCHEDULED WITH STC QUALITIES REQUIRE SPECIAL ATTENTION FOR

CONSISTENT AND CONTINUOUS CONSTRUCTION DETAILING. STARTER TRACKS,

CEILING TRACKS, AND FLOOR RUNNERS SHALL BE SUFFICIENTLY MECHANICALLY

FASTENED AND SET IN A CONTINUOUS SOUND ISOLATION SEALANT OR MATT

MATERIAL TO RESIST THE TRANSFER OF SOUND AT JOINTS AND TERMINATIONS.

ACOUSTICAL BATT INSULATION SHALL BE USED IN THESE PARTITIONS. SEAL

AIRTIGHT W/ NON-HARDENING ACOUSTICAL SEALANT AT TOP, BOTTOM, AND

SIDES.

5. PROVIDE SOUND BOX OR CONTINUITY OF FULL DEPTH OF ACOUSTICAL BATT

INSULATION BEHIND ALL RECESSED BOXES.

6. WALL BASE TRIM: MAINTAIN 1/4" GAP BETWEEN SCHEDULED WALL BACK AND

FINISH FLOORING. FILL AND FORM GAP WITH MATCHING NON-HARDING SEALANT

FULL DEPTH.

7. RIGID CONDUIT, DUCTS, PIPING, AND VENTS LOCATED IN SOUND ASSEMBLIES

SHALL BE ISOLATED FROM THE BUILDING CONSTRUCTION AT POINTS OF CONTACT

BY MEANS OF RESILIENT SLEEVES, MOUNTS, OR MINIMUM 1/4" APPROVED

RESILIENT MATERIAL.

8. METAL VENTILATION AND CONDITIONING AIR DUCTS LOCATED IN SOUND

ASSEMBLIES SHALL BE LINED AND UTILIZED FLEXIBLE CONNECTIONS WHERE

ALLOWABLE.

9. PROVIDE ACOUSTIC GASKETING AND DOOR BOTTOM SEAL AT AREAS REQUIRING

ACOUSTIC CONSIDERATIONS.

SOUND CONTROL NOTES

REFERENCE GENERAL PROJECT NOTES SHEET FOR COMPLETE

LISTING OF GENERAL NOTES. REFERENCE STANDARD FINISHES

DETAILS WHERE APPLICABLE.

1. PROVIDE AND INSTALL TEMPERED/SAFETY GLAZING OR FIRE-PROTECTION-RATED

GLAZING IN ALL HAZARDOUS AREAS AND/OR LOCATIONS REQUIRED BY CURRENT

LOCAL CODE. THESE AREAS INCLUDE BUT ARE NOT LIMITED TO:

A. FIXED OR OPERABLE PANELS IN SWINGING, SLIDING AND BIFOLD DOORS AND FIXED

OR OPERABLE PANELS ADJACENT TO DOORS.

B. FIXED OR OPERABLE WINDOW PANELS WITH PANES LARGER THAN 9 SQUARE FEET

AND ARE LESS THAN 18 INCHES ABOVE THE FLOOR, HAVE A TOP EDGE GREATER

THAN 36 INCHES ABOVE THE FLOOR AND HAVE ONE OR MORE WALKING SURFACES

WITHIN 36 INCHES, MEASURED HORIZONTALLY AND IN A STRAIGHT LINE, OF THE

GLAZING.

C. GLAZING WITHIN A 24" ARC OF A DOOR THAN IS LESS THAN 60 INCHES ABOVE THE

FLOOR. SAFETY GLAZING REQUIRED ON A WALL LESS THAN 180 DEGREES FROM THE

PLANE OF THE DOOR IN A CLOSED POSITION AND WITHIN 24" OF HINGE SIDE OF AN

IN-SWING DOOR.

D. GLAZING IN GUARDS AND RAILING, ADJACENT TO WET SURFACES, ADJACENT TO

STAIRS AND RAMPS, AND ADJACENT TO BOTTOM STAIR LANDINGS.

E. EACH LIGHT OF SAFETY GLAZING MATERIAL INSTALLED IN HAZARDOUS LOCATION

SHALL BE IDENTIFIED BY A PERMANENT LABEL THAT SPECIFIES THE LABELER, AND

STATES THAT SAFETY GLAZING MATERIAL HAS BEEN UTILIZED IN SUCH

INSTALLATIONS.

SAFETY GLAZING NOTES

ALTERNATE SILL DETAIL

EXTERIORINTERIOR

PREPARE SURFACES OF EXISTING

OPENING TO RECEIVE NEW BLAST

RESISTANT WINDOW SYSTEM.

PROTECT EXISTING FINISHES FROM

DEMOLITION WORK, PATCH AND

REPAIR TO LIKE NEW CONDITION

AFTER WINDOW INSTALLATION.

DELEGATED DESIGN OF STEEL

BACK SUPPORT EXPOXY BOLTED

INTO NEW GROUTED CMU

NEW ATFP ALUMINUM WINDOW

SYSTEM WITH HSITORIC MUNTIN

PATTERN. REFER TO SPECIFICATIONS.

GLAZING: G-04.

1"

STRUCTURAL SEALANT . REFER TO

MANUFACTURER'S RECOMMENDATION.

(FOR USE WHERE INTERIOR SILLS SLOPE)

DMA - ASHLAND RC ENVELOPE RENOVATION

2519 LEXINGTON AVE. ASHLAND, KY 41101

05-03-2024

KERSTING

JRC

C

095CAXBAS2300

REVISION HISTORY OF THIS DRAWING

DECA LOG #

ENGR. FILE NO.

DRAWING NO.

DRAWN BY

AS BULT DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

DESCRIPTION OF REVISIONS DATE DESCRIPTION OF REVISIONS DATE

CHECKED BY

PHASE

RTA DATE

DRAWING DATE

A & E…