ADDENDUM _3.pdf

PDF 5 MB Posted

Attached to
M/V Carteret Credit Dry Dock (CDD) - Dare County
Solicitation number
DA00708
Issued by
Cumberland County, Teachey Town, North Carolina

About this file

Addendum No. 3 Summary

This is Addendum No. 3 issued by the North Carolina Department of Transportation, Division of Highways—Division 1, for Contract No. DA00708, the M/V Carteret Credit Dry Dock project in Dare County. The addendum modifies bid documents for the comprehensive dry dock overhaul and structural refurbishment of the M/V Carteret Ferry, with a revised letting date of November 4, 2026. The addendum incorporates three primary revisions: updated Section 9 specifications for zinc anode replacements on pages FD-36 and FD-37, revised itemized proposal bid form pages 133 and 135 reflecting new quantities and sizes of zinc anodes, and updated HVAC modification plan sheets 17 through 23 (Sheets 1 through 7 in Revision B) incorporating technical modifications to the heating, ventilation, and air conditioning systems. The scope of work requires contractors to renew all vessel anodes including 60 twelve-pound rectangular welds on keel cooler guards, twelve six-pound teardrops on each rudder, two 23–24 pound anodes per rudder, four 5.3-pound teardrop welds in sea chests, and 100 additional 23–24 pound hull anodes, with compensation structured as separate unit pricing for each anode size based on actual installed quantities rather than estimated quantities.

The contract is state-funded with no federal aid component, and bidders will be compensated for zinc anode replacements under generic miscellaneous items with unit pricing established per individual anode installation. The HVAC modifications detailed in the addendum specify five independent heat pump zones with outdoor units ranging from 15,000 to 60,000 BTU/HR capacity, utilizing Mitsubishi Electric equipment and requiring compliance with U.S. Coast Guard regulatory standards for marine system installation. All piping materials must meet specified ASTM standards for refrigeration and condensate drain systems, with copper tubing for refrigerant lines and CPVC for drainage. The project maintains the original completion deadline of April 30, 2027, and all other terms and conditions of the original bidding documents remain unchanged.

View the file

Other files

File Type Posted
ADDEMDU_ _2.pdf PDF
ADDENDUM _1.pdf PDF
Bid Notice-M-V Carteret Credit Dry Dock (CDD) - Dare County.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATE OF NORTH CAROLINA

DEPARTMENT OF TRANSPORTATION

JOSH STEIN DANIEL H. JOHNSON

GOVERNOR SECRETARY

Mailing Address:

NC DEPARTMENT OF TRANSPORTATION

DIVISION OF HIGHWAYS – DIVISION 1

113 AIRPORT DIVE, SUITE 100

EDENTON, NC 27932

Telephone: (252) 482-1850

Fax: (252) 482-8722

Customer Service: 1-877-368-4968

Website: www.ncdot.gov

Location:

113 AIRPORT DRIVE, SUITE 100

EDENTON, NC 27932

ADDENDUM NO. 3

October 27, 2026

Contract No. DA00708

TIP No.: N/A

Federal Aid No.: State Funded

WBS Element: 16.401 County: Dare

Description: M/V Carteret Credit Dry Dock (CDD)

Letting Date: November 4, 2026 (Revised)

To Whom It May Concern:

This Addendum is issued to modify or clarify the bid documents previously furnished for the above-referenced project. The following changes shall be incorporated into the contract documents:

Proposal Revisions:

1. Pages FD-36 and FD-37 “Section 9 – Zinc Anode Replacements”: Section 9 of the Ferry

Division Special Provisions has been updated to revise the quantity and size of the Zinc Anodes required for the rudders. Please replace the original pages FD-36 and FD-37 with the attached revised pages.

2. Pages 133 - 135 – “Itemized Proposal (Bid Form)”: Updated the item list to revise the quantity and size of the Zinc Anodes shown in section 9 of the Ferry Division Special

Provisions. Please replace the original Pages 133 & 135 with the attached revised pages.

Plan Revisions:

1. Sheet 17 through 23 “HVAC Modifications, Sheets 1 through 7”: Updated HVAC plan sheets incorporating the revisions detailed on Sheet 1. Replace the original "HVAC

Modifications, Sheets 1 through 7, Revision A" in their entirety with the attached Revision B sheets.

http://www.ncdot.gov/

DA00708 Addendum #1

All other terms and conditions of the original bidding documents remain unchanged.

Sincerely, Mark S. Winslow Division Contract Engineer

Cc: R. K. Sawyer, PE M. B. Gill, PE

G. J. Liverman, PE

B. N. Braswell, PE

D. B. Otts, PE J. E. Dixon

J. J. Remme

DA00708 FD-36 STATE

REVISED 10/27/2026 (ADDENDUM 3)

9.0 ZINC ANODE REPLACEMENTS :

9.1 Description

This section describes the requirements to remove and replace with new identified zinc anodes on the hull and rudders.

9.2 References

9.2.1 DWG NC-250-0001-R0 - Lines & Offsets

9.3 Owner Furnished Equipment

None

9.4 Requirements

The Contractor shall renew all anodes on the vessel. Vessel is equipped with an estimated total of:

- Sixty (60) 12 lb. rectangular shape weld on zincs, ZSS-12 or equal on the keel cooler guards.

- Twelve (12) 6 lb teardrop shape anodes on each rudder

- Two (2) 23-24 lb. zinc anodes on each rudder (Total of 4)

- Four (4) 5.3 lb. teardrop shape weld on ZHC-23 or equal (inside the sea chest)

- One hundred (100) 23-24 lb. zincs All welding on the hull is to be accomplished prior to cleaning, prepping, and painting in the bilge areas. Repaint disturbed areas with anti-corrosive and anti-fouling paint in way of the zinc strap welds. Painting shall be as specified in the "Painting & Blasting Hull Below DLWL" section of these Special Provisions. All anodes shall be properly masked off when the surrounding areas are being painted. Compensation for the renewal of all anodes shall be paid under this work item.

NOTE: Keel cooler bolt on zinc anodes (specific to protecting the keel coolers themselves) shall be replaced in accordance with this work item and in accordance with the requirements of Section 21. "ENGINE WATER COOLING, INSPECTION, AND

MAINTENANCE."

9.5 Tests, Trials, and Documentation

None

DA00708 FD-37 STATE

REVISED 10/27/2026 (ADDENDUM 3)

9.6 Payment

The unit contract bid price per each and shall include labor and materials to remove and then install (1) zinc anode. Separate unit pricing shall be provided for each zinc size. Quantities indicated on the bid proposal are estimated and arbitrarily assigned for the purpose of developing a common proposal for all bidders and for that purpose only. The NCDOT will count installed zincs and pay only for the number of installed zincs, based on the quoted unit price.

Pay Items:

Generic Miscellaneous Items (Zinc Anode Replacements - Keel Cooler Guards / 12 LB.)

Generic Miscellaneous Items (Zinc Anode Replacements - Rudders / 6 LB. 23-24 LB. ) Generic Miscellaneous Items (Zinc Anode Replacements - Sea Chests & Bow Thruster /5.3 LB.)

Generic Miscellaneous Items (Zinc Anode Replacements - Vessel Hull / 23-24 LB.)

Line

Item Number Sec

Description Quantity Unit Cost Amount

County: DARE

FERRY ITEMS

0001 5

DAY

0000820000-N SP GENERIC MISCELLANEOUS ITEM

(BERTHING DAYS)

0002 5

DAY

0000820000-N SP GENERIC MISCELLANEOUS ITEM

(LAY DAYS)

0003 75

SF

0000950000-E SP GENERIC MISCELLANEOUS ITEM

(CROP AND RENEW STEEL -

BULKHEAD PLATE)

0004 25

SF

0000950000-E SP GENERIC MISCELLANEOUS ITEM

(CROP AND RENEW STEEL - DECK

PLATE)

0005 150

SF

0000950000-E SP GENERIC MISCELLANEOUS ITEM

(CROP AND RENEW STEEL - HULL

PLATE)

0006 2,000

SF

0000950000-E SP GENERIC MISCELLANEOUS ITEM

(SPOT PREP & PAINT VOIDS, TANK

RMS., STEERING COMPARTMENT AND

ENGINE RM. BILGES)

0007 60

EA

0001020000-N SP GENERIC MISCELLANEOUS ITEM

(ZINC ANODE REPLACEMENTS - KEEL

COOLER GUARDS / 12 LB.)

0008 4

EA

0001020000-N SP GENERIC MISCELLANEOUS ITEM

(ZINC ANODE REPLACEMENTS -

RUDDERS / 23-24 LB.)

0009 4

EA

0001020000-N SP GENERIC MISCELLANEOUS ITEM

(ZINC ANODE REPLACEMENTS - SEA

CHESTS & BOW THRUSTER / 5.3 LB.)

0010 100

EA

0001020000-N SP GENERIC MISCELLANEOUS ITEM

(ZINC ANODE REPLACEMENTS -

VESSEL HULL / 23-24 LB.)

0011 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(BLAST & PAINT - ALL DECKS)

0012 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(BLAST & PAINT - HULL ABOVE DLWL)

0013 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(BLAST & PAINT - HULL BELOW DLWL)

0014 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(BLAST & PAINT - SUPERSTRUCTURE)

0015 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(CLEAN AND CLEAR ALL DECK

DRAINS)

Page 1 of 3ITEMIZED PROPOSAL FOR CONTRACT NO. DA00708Oct 27, 2026 9:54 AM

REVISED 10/27/2026

Item Number Sec

Description Quantity Unit Cost Amount

County: DARE

0016 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(ENGINE WATER COOLING SYSTEM

INSPECTION AND MAINTENANCE)

0017 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(GLOBAL DAVIT - INSPECTION AND

MAINTENANCE REPAIR)

0018 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(HIGH - PRESSURE WATER WASH -

HULL ABOVE DLWL)

0019 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(HIGH - PRESSURE WATER WASH -

HULL BELOW DLWL)

0020 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(HIGH-PRESSURE WATER WASH -

SUPERSTRUCTURE)

0021 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(HVAC MODIFICATION)

0022 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(MAIN DECK HATCH MAINTENANCE

AND REPAIR)

0023 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(MAIN ENGINES MAJOR OVERHAUL)

0024 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(OPEN, CLEAN AND CERTIFY GAS

FREE: BILGES, HOLDS AND

ENCLOSED AREAS)

0025 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(PROPELLER AND TAILSHAFT

INSPECTIONS)

0026 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(REMOVE ALL MAIN DECK WTD,

MAINTENANCE, REPAIR AND

REINSTALL)

0027 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(RENEW WINDOW GASKETS)

0028 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(RUDDER REMOVALS AND

INSPECTIONS)

0029 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(SEA CHEST, STRAINER AND VALVE

INSPECTIONS)

Page 2 of 3ITEMIZED PROPOSAL FOR CONTRACT NO. DA00708Oct 27, 2026 9:54 AM

Item Number Sec

Description Quantity Unit Cost Amount

County: DARE

0030 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(SEWAGE SYSTEM - CLEAN, INSPECT,

AND PERFORM MAINTENACE)

0031 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(SHIPYARD SERVICES)

0032 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(STARTUP, DOCK TRAILS, AND SEA

TRIALS)

0033 Lump Sum0005000000-N SP L.S.GENERIC FERRY ITEM

(TAKE CONTROL AND DRY DOCK THE

M/V CARTERET)

Total Amount Of Bid For Entire Project :0954/Oct27/Q2451/D124520000/E33

Page 3 of 3ITEMIZED PROPOSAL FOR CONTRACT NO. DA00708Oct 27, 2026 9:54 AM

T +1 206.624.7850 GLOSTEN.COM

of RevisionDrawing NumberScale

Issue DateApprovedCheckedDrawn

Sheet

B

C

A

D

B

C

A

D

4 3 2 15678

4 3 2 15678

Size

B

NORTH CAROLINA DEPARTMENT OF TRANSPORTATION

MANNS HARBOR, NC

M/V CARTERET

HVAC MODIFICATIONS

COVER SHEET

AHN CJF MSM 2026/10/15

AS NOTED 25057.01-511-01 1 7 B

1. MITSUBISHI ELECTRIC, DOCUMENT NO. JG79N716H03, INSTALLATION MANUAL

MSZ-GX18/24/30/36NL, MSY-GX18/24/30/36NL, 2025.

2. MITSUBISHI ELECTRIC, DOCUMENT NO. M-P0956A, DATA BOOK MODEL MXZ-SM

36/48/60NL-U1, MXZ-SM36/42/48NLHZ-U1, FEBRUARY 2025.

3. MITSUBISHI ELECTRIC, DOCUMENT NO. OBD950, TECHNICAL AND SERVICE

MANUAL MSZ-GX06/09/12/15/18/24/30/36NL, MSY-GX09/12/15/18/24/30/36NL, 2025.

5. MITSUBISHI ELECTRIC, MSZ-GX15NL & MUZ-GX15NL, 2025.

6. MITSUBISHI ELECTRIC, MSZ-GX30NL & MUZ-GX30NL, 2025.

7. MITSUBISHI ELECTRIC, MXZ-SM60NL, 2025.

GENERAL NOTES

1. THIS DRAWING IS A DIAGRAMMATIC ILLUSTRATION OF HVAC SYSTEM

INSTALLATIONS, AND DOES NOT REPRESENT THE FULL EXTENT OF THE WORK.

EXACT ARRANGEMENTS AND PIPE/CABLE ROUTING SHALL BE DEVELOPED BY THE

CONTRACTOR IN ACCORDANCE WITH EQUIPMENT MANUFACTURER INSTALLATION

GUIDANCE.

2. SYSTEM DESIGN, MATERIAL, INSTALLATION, TESTING, AND QUALITY OF WORK

SHALL BE IN ACCORDANCE WITH THE REGULATORY REQUIREMENTS OF THE U.S.

COAST GUARD (USCG).

3. SYSTEM INSTALLATION SHALL PERMIT CLEAR PASSAGE ALONG WALKWAYS AND

LADDERWAYS; CLEAR ACCESS FOR OPERATION AND ROUTINE MAINTENANCE;

CLEAR ACCESS TO ALL DOORS, HATCHES, AND OPENINGS.

4. BULKHEAD MOUNTED INDOOR UNITS SHALL BE LOCATED AS HIGH AS PRACTICAL.

REFERENCES

EQUIPMENT LIST

ZONE EQUIP ID DESCRIPTION CAPACITY/RATING MFR MODEL SERVING

ZONE 1

511-E100 HEAT PUMP OUTDOOR UNIT #1 60,000 BTU/HR MITSUBISHI MXZ-SM60NL ZONE 1

511-E110 BRANCH BOX #1 3 PORT MITSUBISHI PAC-LMA30BC ZONE 1

511-E101 INDOOR UNIT, WALL MOUNT 30,000 BTU/HR MITSUBISHI MSZ-GX24NL LOWER LOUNGE, AFT

511-E102 INDOOR UNIT, WALL MOUNT 30,000 BTU/HR MITSUBISHI MSZ-GX24NL LOWER LOUNGE, AFT

511-E130 CIRCUIT BREAKER 50A SQUARE D QO250GFI ZONE 1

ZONE 2

511-E200 HEAT PUMP OUTDOOR UNIT #2 60,000 BTU/HR MITSUBISHI MXZ-SM60NL ZONE 2

511-E210 BRANCH BOX #2 3 PORT MITSUBISHI PAC-LMA30BC ZONE 2

511-E201 INDOOR UNIT, WALL MOUNT 30,000 BTU/HR MITSUBISHI MSZ-GX24NL LOWER LOUNGE, FORWARD

511-E202 INDOOR UNIT, WALL MOUNT 30,000 BTU/HR MITSUBISHI MSZ-GX24NL LOWER LOUNGE, FORWARD

511-E230 CIRCUIT BREAKER 50A SQUARE D QO250GFI ZONE 2

ZONE 3

511-E300 HEAT PUMP OUTDOOR UNIT #3 60,000 BTU/HR MITSUBISHI MXZ-SM60NL ZONE 3

511-E310 BRANCH BOX #3 3 PORT MITSUBISHI PAC-LMA30BC ZONE 3

511-E301 INDOOR UNIT, WALL MOUNT 30,000 BTU/HR MITSUBISHI MSZ-GX24NL UPPER LOUNGE

511-E302 INDOOR UNIT, WALL MOUNT 30,000 BTU/HR MITSUBISHI MSZ-GX24NL UPPER LOUNGE

511-E330 CIRCUIT BREAKER 50A SQUARE D QO250GFI ZONE 3

ZONE 4

511-E400 HEAT PUMP OUTDOOR UNIT #4 30,000 BTU/HR MITSUBISHI MUZ-GX30NL ZONE 4

511-E401 INDOOR UNIT, WALL MOUNT 30,000 BTU/HR MITSUBISHI MSZ-GX30NL WHEELHOUSE

511-E430 CIRCUIT BREAKER 25A SQUARE D QO225GFI ZONE 4

ZONE 5

511-E500 HEAT PUMP OUTDOOR UNIT #5 15,000 BTU/HR MITSUBISHI MUZ-GX15NL AUXILIARY MACHINERY ROOM

511-E501 INDOOR UNIT, WALL MOUNT 15,000 BTU/HR MITSUBISHI MLZ-GX15NL EOS

511-E520 CONDENSATE PUMP 1/9 HP LIBERTY PUMPS LCU-15S AUXILIARY MACHINERY ROOM

511-E521 SAFETY DISCONNECT SWITCH 30A LEVITON LDS30-AX CONDENSATE PUMP

511-E530 CIRCUIT BREAKER 20A SQUARE D QO220GFI ZONE 5

511-E531 CIRCUIT BREAKER 15A SQUARE D QO115 CONDENSATE PUMP BREAKER

SHEET LIST

SHT TITLE

1 COVER SHEET

2 MATERIAL SCHEDULE

3 PIPING SCHEMATIC

4 EOS PIPING SCHEMATIC & DETAILS

5 WHEELHOUSE AND UPPER LOUNGE ARRANGEMENTS

6 LOWER LOUNGE AND EOS ARRANGEMENTS

7 ELECTRICAL

REVISIONS

ZONE REV DESCRIPTION DATE APPD

INITIAL RELEASE 2026/02/27 MSM

SHT 7 1. UPDATED ELECTRICAL FEEDER CIRCUITS 2026/07/29 MSM

SHT 1, 7 2. UPDATED CONDENSATE PUMP CIRCUIT

BREAKER

SHT 1, 3 1. CHANGED MSZ-GX30NL INDOOR UNIT MODELS

TO MSZ-GX24NL IN PAX LOUNGES

10/15/2026 MSM

A

B

B

B

B

Digitally Signed 19-Oct-2026

Issue DateApprovedCheckedDrawn

Sheet

B

C

A

D

B

C

A

D

4 3 2 15678

4 3 2 15678

Size

B

NORTH CAROLINA DEPARTMENT OF TRANSPORTATION

MANNS HARBOR, NC

M/V CARTERET

HVAC MODIFICATIONS

MATERIAL SCHEDULE

AHN CJF MSM 2026/10/15

AS NOTED 25057.01-511-01 2 7 B

PIPING MATERIAL SCHEDULE

PIPING SYSTEM ITEM SIZE TYPE MATERIAL DESIGN SPECIFICATION NOTES

REFRIGERATION

MAX WORKING CONDITIONS

PRESSURE 601 PSIG, TEMP 150 °F

USCG CLASS I

PIPE ALL TUBE, SEAMLESS COPPER ASTM B280 HARD DRAWN ACR ASTM B280 TYPE L

FITTINGS ALL SOLDER JOINT WROUGHT COPPER ASTM B75 C12200 ASME B16.22 SOLDER JOINT D

CONDENSATE DRAINS

MAX WORKING CONDITIONS

PRESSURE 15PSIG, TEMP 100°F

USCG CLASS II

PIPE ALL PIPE, CPVC DRAINAGE CPVC TYPE IV, ASTM D1784 ASTM F2618 SCH 40 OR ASTM F441

SCH 40 OR 80

E

TAKEDOWN JOINTS 1-1/4" AND BELOW UNION CPVC TYPE IV, ASTM D1784 ASTM F441, ASTM F439

BOLTING ALL BOLTS CARBON STEEL ASTM A307 GR B OR SS ASTM A193 GR 8M ASME B18.2.1 C

NUTS/WASHERS CARBON STEEL ASTM A563 GR A OR SS A194 GR 8M ASME B18.2.2 C

FITTINGS 1-1/4" AND BELOW CPVC SCH 80 CPVC TYPE IV, ASTM D1784 ASTM F441, ASTM F439 E

VALVES BODY TRIM

ALL BALL BRASS OR BRONZE BRASS OR BRONZE OR SS MSS SP-110 CLASS 150, NPT OR

FLANGE

OVERBOARDS

MAX WORKING CONDITIONS

PRESSURE 15PSIG, TEMP 100°F

USCG CLASS II

PIPE ALL SEAMLESS OR ERW CARBON STEEL ASTM A106 GR B OR A53 GR B TYPE E ASME B36.10, SCH XS, SEAMLESS

OR ERW

TAKEDOWN JOINTS 2" AND BELOW UNION CARBON STEEL ASTM A105 MSS-SP-83, CLASS 3000, SW

BOLTING ALL BOLTS CARBON STEEL ASTM A307 GR B OR SS ASTM A193 GR 8M ASME B18.2.1 C

NUTS/WASHERS CARBON STEEL ASTM A563 GR A OR SS A194 GR 8M ASME B18.2.2 C

FITTINGS SOCKET WELD CARBON STEEL ASTM A105 OR A234 GR WPB ASME B16.11, CLASS 3000, SW

BODY TRIM

VALVES 2" AND BELOW GATE, GLOBE, CHECK, BALL CARBON STEEL ASTM A105 OR A216,

GR WCB

NCA OR BRONZE ASME B16.34 OR MSS SP-110, CLASS

150 MIN, SW

A

ABBREVIATIONS: SW - SOCKET WELD, SO - SLIP-ON, WN - WELDNECK, SCH - SCHEDULE, FLG - FLANGED, BW - BUTT WELD, GR - GRADE, SS - STAINLESS STEEL, NCA - NICKEL COPPER ALLOY, FLG - FLANGED

NOTES:

A. RESILIENT SEATED VALVES SHALL BE USCG CATEGORY A FOR MANIFOLDS, SYSTEM CROSS-CONNECTIONS, AND SHELL VALVES

B. MSS SP-80 VALVES LIMITED TO 75% OF VALVE DESIGN PRESSURE

C. BOLTING IN WEATHER OR WET LOCATIONS SHALL BE STAINLESS STEEL

D. COPPER PRESS-FIT MECHANICALLY ATTACHED FITTINGS APPROVED FOR THE INTENDED SERVICE AND MEETING USCG REQUIREMENTS ARE ALSO ACCEPTABLE E. PLASTIC PIPING AND FITTINGS SHALL MEET THE LOW FLAME SPREAD REQUIREMENTS AND SMOKE AND TOXICITY REQUIREMENTS OF THE IMO 2010 FTP CODE ANNEX 1. PARTS 2 AND 5.

DIAGRAM 3-7B

AFT LOWER LOUNGE

ZONE 1

OUTDOOR UNIT

30K BTU/HR

DIAGRAM 3-4C

WHEELHOUSE

ZONE 4

DIAGRAM 3-4B

FWD LOWER LOUNGE

ZONE 2

DIAGRAM 3-7C

UPPER LOUNGE

ZONE 3

OUTDOOR UNIT

60K BTU/HR

ROUTE CONDENSATE DRAIN TO

WEATHER, SEE INSTALLATION

GUIDANCE 3.2.

BRANCH BOX

F

T

≤ 180 FT: OUTDOOR UNIT TO

BRANCH BOX (ONE WAY)

Ø3/4"

Ø 3/

8" Ø5/8"

1/4"

Ø 5/

8"

Ø 1/

4"

Ø 5/

8"

Ø 1/

4"

1. EQUIPMENT INSTALLATION (ONE-WAY) PIPING LENGTHS PER MXZ-SM60NL OUTDOOR

UNIT SHALL BE IN ACCORDANCE WITH MITSUBISHI REQUIREMENTS FOR A BRANCH

BOX METHOD APPLICATION, INCLUDING:

1.1. TOTAL PIPING LENGTH SHALL BE ≤ 492 FT.

1.2. FARTHEST PIPING LENGTH SHALL BE ≤ 262 FT.

1.3. TOTAL PIPING LENGTH BETWEEN OUTDOOR UNIT AND BRANCH BOXES SHALL BE

≤ 180FT.

1.4. PIPING LENGTH BETWEEN THE FIRST BRANCH JOINT AND FARTHEST BRANCH

BOX SHALL BE ≤ 98 FT.

1.5. FARTHEST PIPING LENGTH AFTER BRANCH BOX SHALL BE ≤ 82 FT.

1.6. TOTAL PIPING LENGTH BETWEEN BRANCH BOXES AND INDOOR UNITS SHALL BE

≤ 312 FT.

2. EQUIPMENT INSTALLATION (ONE-WAY) PERMISSIBLE HEIGHT DIFFERENCE PER

OUTDOOR UNIT SHALL BE IN ACCORDANCE WITH MITSUBISHI REQUIREMENTS FOR A

BRANCH BOX METHOD APPLICATION, INCLUDING:

2.1. MAXIMUM HEIGHT DIFFERENCE BETWEEN OUTDOOR UNIT AND INDOOR UNIT

2.1.1. WHEN THE OUTDOOR UNIT IS SET HIGHER THAN THE INDOOR UNIT: 164 FT.

2.1.2. WHEN THE OUTDOOR UNIT IS SET LOWER THAN THE INDOOR UNIT: 131 FT.

2.2. MAXIMUM HEIGHT DIFFERENCE BETWEEN OUTDOOR UNIT AND BRANCH BOX

2.2.1. WHEN THE OUTDOOR UNIT IS SET HIGHER THAN THE BRANCH BOX: 164 FT.

2.2.2. WHEN THE OUTDOOR UNIT IS SET LOWER THAN THE BRANCH BOX: 131 FT.

2.3. MAXIMUM HEIGHT DIFFERENCE BETWEEN BRANCH BOX AND INDOOR UNIT: 49 FT.

2.4. MAXIMUM HEIGHT DIFFERENCE BETWEEN INDOOR UNITS: 39 FT.

2.5. NUMBER OF BENDS SHALL BE ≤ 15.

3. PIPING

3.1. REFRIGERANT PIPING SHALL BE COPPER TUBING PER MATERIALS

SCHEDULE ON SHEET 1.

3.2. CONDENSATE DRAIN PIPING SHALL SLOPE AT A MINIMUM OF 1/4 IN

PER FOOT.

3.3. SPARE BRANCH BOX CIRCUITS SHALL BE CAPPED IN ACCORDANCE WITH

MANUFACTURER INSTRUCTIONS.

E302

PAX CABIN

24K BTU/HR

E301

PAX CABIN

24K BTU/HR

E310

E202E201

E210

E400

T +1 206.624.7850 GLOSTEN.COM

of RevisionDrawing NumberScale

Issue DateApprovedCheckedDrawn

Sheet

B

C

A

D

B

C

A

D

4 3 2 15678

4 3 2 15678

Size

B

NORTH CAROLINA DEPARTMENT OF TRANSPORTATION

MANNS HARBOR, NC

M/V CARTERET

HVAC MODIFICATIONS

PIPING SCHEMATIC

AHN CJF MSM 2026/10/15

AS NOTED 25057.01-511-01 3 7 B

SYMBOL LIST

SYMBOL DESCRIPTION

GATE VALVE

BALL VALVE

CHECK VALVE

UNION ADAPTER

DRAIN CONNECTION

DECK/BULKHEAD PENETRATION (SEE PIPING NOTE 1)

OVERBOARD DISCHARGE

CHANGE IN MATERIAL

STL = CARBON STEEL

CPVC = MARINE GRADE CPVC PLASTIC

REFRIGERATION, LIQUID, COPPER

REFRIGERATION, GAS, COPPER

CONDENSATE DRAIN, CPVC

INSTALLATION GUIDANCE (SEE REF. 2)

Ø5/8"

ROUTE CONDENSATE DRAIN TO WEATHER

(TYP, 2 PLCS), SEE INSTALLATION

GUIDANCE 3.2.

PIPING NOTES

1. WHERE COPPER OR PLASTIC PIPING PENETRATES BULKHEADS OR DECKS, STEEL

PENETRATION SLEEVES WITH SLIPSIL SEALING PLUGS OR RISE/NOFIRNO SEALING

SHALL BE USED TO MAINTAIN THE WATERTIGHT, FUMETIGHT, AND FIRE RATING OF

THE BOUNDARY PER REGULATORY BODY REQUIREMENTS. INSTALL PIPING

TRANSITS IN ACCORDANCE WITH MANUFACTURER'S APPROVED INSTALLATION

DETAILS.

2. SYSTEM INSTALLATION SHALL COMPLY WITH THE FOLLOWING ASTM

SHIPBUILDING AND MARINE TECHNOLOGY STANDARDS:

2.1. RIGID PIPE HANGERS SHALL BE IN ACCORDANCE WITH ASTM F708.

EXCEPTION: PARAGRAPH 1.3 IS NOT APPLICABLE.

2.2. GAGE BOARD ASSEMBLIES SHALL BE IN ACCORDANCE WITH ASTM F707.

INSTALL TYPE 1 (3-1/2 SIZE), GRADE A.

2.3. INSTRUMENTATION PIPING ASSEMBLIES SHALL BE IN ACCORDANCE WITH

ASTM F721. EXCEPTION: INSTALL 1/2-INCH ROOT VALVE WITH ≤ 4 INCH STAND

OFF. FINAL BRANCH SIZING WILL BE DEPENDENT ON INSTRUMENTATION

SELECTED.

2.4. PIPE WELDING SHALL BE IN ACCORDANCE WITH ASTM F722. EXCEPTION:

NON-CONSUMABLE BACKING RINGS AND MITERED JOINTS NOT PERMITTED.

2.5. VALVE LABEL PLATES SHALL BE IN ACCORDANCE WITH ASTM F992. INSTALL

TYPE 1, GRADE E, CLASS 2, LETTER SIZE 2, PLATE SIZE TO SUIT.

2.6. SPRAY SHIELDS FOR MECHANICAL JOINTS SHALL BE IN ACCORDANCE WITH

ASTM F1138. EXCEPTION: REGULATORY BODY APPROVED ALTERNATIVES MAY

BE SUBSTITUTED.

3. PIPE RUNS BETWEEN WATERTIGHT BULKHEADS SHALL HAVE AT LEAST ONE

EXPANSION BEND.

4. GALVANIC ISOLATION KITS SHALL BE PROVIDED FOR FLANGED PIPING JOINTS OF

DISSIMILAR METALS.

WHEELHOUSE

30K BTU/HR

Ø5/8"

Ø1/4"

≤ 82 FT: BRANCH BOX TO

INDOOR UNIT (ONE WAY)

Ø5/8"

Ø3/4"

≤ 180 FT: OUTDOOR UNIT TO

BRANCH BOX (ONE WAY)

BRANCH BOX

Ø5/8"

1/4"

Ø 5/

8"

Ø 1/

4"

E102

PAX CABIN

24K BTU/HR

E101

PAX CABIN

24K BTU/HR

E110

Ø5/8"

ROUTE CONDENSATE DRAIN TO WEATHER

(TYP, 2 PLCS), SEE INSTALLATION

GUIDANCE 3.2.

≤ 82 FT: BRANCH BOX TO

INDOOR UNIT (ONE WAY)

Ø5/8"

BRANCH BOX

Ø5/8"

1/4"

Ø 5/

8"

Ø 1/

4"

PAX CABIN

24K BTU/HR

PAX CABIN

24K BTU/HR

Ø5/8"

ROUTE CONDENSATE DRAIN TO WEATHER

(TYP, 2 PLCS), SEE INSTALLATION

GUIDANCE 3.2.

≤ 82 FT: BRANCH BOX TO

INDOOR UNIT (ONE WAY)

Ø5/8"

Ø5/8"E401

OUTDOOR UNIT

60K BTU/HR

OUTDOOR UNIT

60K BTU/HR

E400

E100

E300

E200

≤ 100 FT (ONE WAY),

≤ 10 BENDS

F T

PENETRATION (TYP),

SEE PIPING NOTE 1

WHEELHOUSE DECK

WHEELHOUSE DECK WHEELHOUSE DECK

F

T Ø 3/

8"

F

T

Ø 3/

8"

Ø3/4"

≤ 180 FT: OUTDOOR UNIT TO

BRANCH BOX (ONE WAY)

WHEELHOUSE DECK

W H

E E

L H

O U

S E

B U

LK

H

E A

D

W H

E E

L H

O U

S E

B U

LK

H

E A

D

M1

M2

B

B

B

Issue DateApprovedCheckedDrawn

Sheet

B

C

A

D

B

C

A

D

4 3 2 15678

4 3 2 15678

Size

B

NORTH CAROLINA DEPARTMENT OF TRANSPORTATION

MANNS HARBOR, NC

M/V CARTERET

HVAC MODIFICATIONS

EOS PIPING SCHEMATIC & DETAILS

AHN CJF MSM 2026/10/15

AS NOTED 25057.01-511-01 4 7 B

Ø1/2"

Ø1/4"

E501

EOS

15K BTU/HR

GRAVITY DRAIN TO

OUTDOOR UNIT DRAIN PAN

Ø5/8"

OUTDOOR UNIT

15K BTU/HR

E500

DIAGRAM 4-5C

EOS

ZONE 5

≤ 65 FT (ONE WAY),

≤ 10 BENDS

≤ 40 FT

DRAIN PAN

SEE DETAIL 4-5A

FROM SEAWATER SYSTEM

SHELL

EXISTING OVERBOARD DISCHARGE

(STBD SIDE, FR. 84-85)

CONDENSATE PUMP

W/ INTEGRAL TANK, DISCHARGE

CHECK VALVE, AND FLOAT SWITCH

FROM DRAIN PAN

1 2 F

T

R E

F

E520

DETAIL 4-5A

CONDENSATE DRAIN

Ø1/2"

Ø3/8", BARBED OUTLET

BARBED

ADAPTER

Ø 1/

2"

PENETRATION (TYP),

SEE PIPING NOTE 1

E O

S B

U L

K H

E A

D

DRAIN FITTING

STL

CPVC

Ø3/4"

DN

WHEELHOUSE40

DN

VL

CREW BERTHING

DBL. BERTH

CL

GALLEY

SHWR

CAP-50

REF DBL. BERTH

DBL. BERTH

T A

B

LE

C A

P -5

C A

P -5

C A

P -5

70 65 60 55 50

UP DN

4045 35

CL

UPPER LOUNGE

PASSAGE

D.F.

EMERG. GEN. RM. STORAGE

4", PORT

511-E400

511-E100

511-E200

511-E300

511-E400

511-E301

511-E302

PLAN 5-3A

UPPER LOUNGE ARRANGEMENT

ZONE 3

1/8"=1'-0"

T +1 206.624.7850 GLOSTEN.COM

of RevisionDrawing NumberScale

Issue DateApprovedCheckedDrawn

Sheet

B

C

A

D

B

C

A

D

4 3 2 15678

4 3 2 15678

Size

B

NORTH CAROLINA DEPARTMENT OF TRANSPORTATION

MANNS HARBOR, NC

M/V CARTERET

HVAC MODIFICATIONS

WHEELHOUSE AND UPPER LOUNGE ARRANGEMENTS

AHN CJF MSM 2026/10/15

AS NOTED 25057.01-511-01 5 7 B

PLAN 5-3B

WHEELHOUSE DECK ARRANGEMENT

ZONE 4

1/8"=1'-0"

ELEVATION 5-6B

WHEELHOUSE

1/8"=1'-0"

5-6B3-6B

511-E100

ELEVATION 5-7B

AFT DECK

1/8"=1'-0"

5-7B3-7B

511-E401

511-E300

ENG. RM. ACCESS

95 90 85 7580 70

DN

65 55 50 4045 35ADA

RESTROOM WOMEN MEN

DN

UP

UP

LOWER LOUNGE

AHU LKR.

95 90 85

AUXILIARY MACHINERY COMPARTMENT

ENGINEER'S

CONTROL

BOOTH

ESCAPE

ABOVE

SETTEE

WORK BENCH

UP

3306B

3'-75 16"

'-0

3" (MIN)3

4" (MIN)

2" (MIN)

1" (MIN)

AIR INLET

AIR OUTLET

MSZ-30GX

MSZ-24GX

2'-77 16"

4"

4" (MIN)

2" (MIN)

2" (MIN)

4" (MIN)

AIR INLET

AIR OUTLET

MSZ-15GX

511-E101

511-E102

511-E201

511-E202

T +1 206.624.7850 GLOSTEN.COM

of RevisionDrawing NumberScale

Issue DateApprovedCheckedDrawn

Sheet

B

C

A

D

B

C

A

D

4 3 2 15678

4 3 2 15678

Size

B

NORTH CAROLINA DEPARTMENT OF TRANSPORTATION

MANNS HARBOR, NC

M/V CARTERET

HVAC MODIFICATIONS

LOWER LOUNGE AND EOS ARRANGEMENTS

AHN CJF MSM 2026/10/15

AS NOTED 25057.01-511-01 6 7 B

PLAN 6-4D

LOWER LOUNGE ARRANGEMENT

ZONE 1 & ZONE 2

1/8"=1'-0"

PLAN 6-7A

EOS ARRANGEMENT

ZONE 5

1/8"=1'-0"

511-E501

EXISTING HEAD EXHAUST FAN,

TYP (3 PLACES)

DETAIL 6-4C

BULKHEAD MOUNTED - LARGE

FRONT VIEW

1/2"=1'-0"

DETAIL 6-2C

BULKHEAD MOUNTED - SMALL

FRONT VIEW

1/2"=1'-0"

511-E500

Issue DateApprovedCheckedDrawn

Sheet

B

C

A

D

B

C

A

D

4 3 2 15678

4 3 2 15678

Size

B

NORTH CAROLINA DEPARTMENT OF TRANSPORTATION

MANNS HARBOR, NC

M/V CARTERET

HVAC MODIFICATIONS

ELECTRICAL

AHN CJF MSM 2026/10/15

AS NOTED 25057.01-511-01 7 7 B

OUTDOOR UNIT

(ZONE 2)

511-E200 511-E210

BRANCH BOX

OUTDOOR UNIT

(ZONE 1)

511-E100

LOWER LOUNGE

EOS

INDOOR UNIT

511-E202

INDOOR UNIT

511-E201

INDOOR UNIT

511-E102

INDOOR UNIT

511-E101

POWER PANEL P-6

UPPER LOUNGE

120/208VAC, 4W, 100A

SP6-611

3C-6AWG

SP6-611-1

3C-14AWG

SP7-717-1

4C-14AWG

SP6-612-1B

4C-14AWG

SP6-612-1A

4C-14AWG

SP6-611-1B

4C-14AWG

SP6-611-1A

4C-14AWG

SP6-612

3C-6AWG

SP6-612-1

3C-14AWG

DIAGRAM 7-5A

ELECTRICAL INSTALLATIONS

2P

2P

ELECTRICAL SYMBOLS LIST

SYMBOL DESCRIPTION

CIRCUIT BREAKER (UL 489SA)

(XX = TRIP RATING, Y = POLE NUMBER)

GFCI = GROUND FAULT CIRCUIT INTERRUPT

SAFETY DISCONNECT SWITCH (NORMALLY CLOSED)

CABLE ID NUMBER

CABLE TYPE

EQUIPMENT ID NUMBER

YP

XX

YP

XX

SP6-611-2

3C-16AWG (S)

SP6-612-2

3C-16AWG (S)

22.6FLA

22.6FLA

0.3FLA

0.3FLA

0.3FLA

0.3FLA

0.1FLA

CABLE TYPE KEY

BASE CABLE

SYMBOL DESCRIPTION

XC-YYAWG (S)

MULTI-CONDUCTOR POWER/CONTROL CABLE

X = NUMBER OF CONDUCTORS

C = INDICATES INDIVIDUAL CONDUCTORS

YY = CONDUCTOR SIZE

AWG = AMERICAN WIRE GAUGE

(S) = SHIELDED

SIGNAL CABLE (IEEE-45 OR IEC 60092-35313)

POWER CABLE (IEEE-45 OR IEC 60092-35313)

3C-6AWG (FR+S)

M

ODIF

IE

R(S

BASE C

ABLE

CABLE DESIGNATION:

P1-1

3C-6AWG

511-E100

GFCI

GFCI

OUTDOOR, WHEELHOUSE DECK

2P

2P

OUTDOOR UNIT

(ZONE 4)

511-E400

INDOORS

OUTDOOR UNIT

(ZONE 3)

511-E300

UPPER LOUNGE

WHEELHOUSE

511-E310

BRANCH BOX

INDOOR UNIT

511-E302

INDOOR UNIT

511-E301

POWER PANEL P-5

CREW SPACES

120/208VAC, 4W, 100A

SP6-607

3C-6AWG

SP5-507

3C-10AWG

SP6-607-1

3C-14AWG

SP5-507-1

4C-14AWG

SP6-607-1B

4C-14AWG

SP6-07-1A

4C-14AWG

SP6-607-2

3C-16AWG (S)

16.6FLA

22.6FLA

0.3FLA

0.3FLA

GFCI

GFCI

ELECTRICAL NOTES

1. CABLE AND PIPING INSTALLATIONS IN ACCOMMODATIONS AND COMMON SPACES

SHALL BE OBSCURED BEHIND BULKHEAD LININGS AND SUSPENDED CEILINGS.

2. NYLON OR BRASS CABLE STUFFING TUBES OR MULTI-CABLE TRANSITS SHALL BE

USED WHEN PENETRATING ELECTRICAL ENCLOSURES OR JUNCTION BOXES.

STEEL KICKPIPES WITH BRASS STUFFING GLANDS OR MULTI-CABLE TRANSITS

SHALL BE INSTALLED AT ALL DECK AND BULKHEAD PENETRATIONS. WATERTIGHT

AND STRUCTURAL FIRE BOUNDARY RATINGS SHALL BE MAINTAINED.

3. ALL EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH IEEE-45, IEEE-142,

AND IEEE-518 (INSOFAR AS IT MAY APPLY). EQUIPMENT GROUNDS SHALL BE

CARRIED BACK TO THE RESPECTIVE POWER PANEL.

4. ALL CABLES SHALL BE TESTED FOR INSULATION RESISTANCE (MEGGERED).

CABLES MUST MEET IEEE-45.6, CLAUSE 5.1. TEST RESULTS SHALL BE SUBMITTED

TO THE OWNER'S REPRESENTATIVE. NO CABLE SPLICING IS ALLOWED.

5. CABLES SHALL BE SIZED IN ACCORDANCE WITH IEEE-45 AND THE APPLICABLE

REGULATORY BODY. CABLE SIZES SHALL BE INCREASED TO COMPENSATE FOR

VOLTAGE DROP AND/OR CABLE BANKING, AS NECESSARY, TO MEET REGULATORY

REQUIREMENTS. CABLE SIZES SHOWN ARE FOR 50C AMBIENT TEMPERATURE AND

ALL CABLES 1AWG AND SMALLER ARE DOUBLE BANKED. MOTOR CIRCUIT CABLES

UPSTREAM OF AN OVERLOAD RELAY ARE SIZED BASED ON THE OVERLOAD

SETTING, ASSUMING 125% OF THE MOTOR'S FULL LOAD CURRENT.

6. ALL EQUIPMENT SHOWN SHALL BE NEW.

7. ELECTRICAL EQUIPMENT SHALL ADHERE TO THE FOLLOWING CONSTRUCTION

STANDARDS/REGULATIONS, WITH MARINE SUPPLEMENTS AS APPLICABLE:

7.1. CIRCUIT BREAKERS - UL489SA

7.2. ENCLOSURES - NEMA 250

7.3. CABLES - IEEE-45 OR IEC 60092-35313.

8. LOADS ON DISTRIBUTION POWER AND LIGHTING PANELS SHALL BE BALANCED TO

WITHIN 15 PERCENT WHEREVER POSSIBLE.

9. NEW EQUIPMENT UTILIZES INVERTERS AND GFCI CIRCUIT BREAKERS SHALL BE

SUITABLE FOR THE ASSOCIATED HIGHER HARMONICS.

10. STRIPPED WIRE CONDENSATE PUMP INSTALLATION SHALL BE IN ACCORDANCE

WITH LIBERTY PUMPS INSTALLATION REQUIREMENTS, UTILIZE AN APPROPRIATE

ENCLOSURE OR JUNCTION BOX, AND COMPLY WITH THE NEC AND APPLICABLE

CODES. PUMP WIRING IS AS FOLLOWS:

10.0.1. GREEN IS GROUND

10.0.2. BLACK IS LINE

10.0.3. WHITE IS NEUTRAL (115V)

511-E130

511-E230

511-E330

511-E430

INDOOR UNIT

511-E401

0.3FLA

OUTDOOR UNIT

(ZONE 5)

511-E500

POWER PANEL P-7

EOS

120/208VAC, 4W, 100A

SP7-717

3C-12AWG

511-E110

BRANCH BOX

INDOORS, AUXILIARY MACHINERY SPACE

2P

GFCI

511-E530

INDOOR UNIT

511-E501

PANEL LOAD SUMMARY

PANEL

TRIP

(A)

CIRCUIT

ID

REMOVE INSTALL LOAD CHANGE

PANEL

PH VOLTS TRIP (A) DESCRIPTION kVA EQUIPMENT CABLE BREAKER PH VOLTS TRIP (A) DESCRIPTION kVA EQUIPMENT CABLE BREAKER kVA

MAIN

SWITCHBOARD

21 3 208 80 HVAC PANEL -21.6 YES YES NO - - - - - - - -

-57.6

MAIN

SWITCHBOARD

23 3 208 80 CIRCULATION HEATER 1 -18.0 YES YES NO - - - - - - - -

25 3 208 80 CIRCULATION HEATER 2 -18.0 YES YES NO - - - - - - - -

P-2

(LOWER LOUNGE) 225

20 1 120 20 LOWER LOUNGE HVAC -1.3 YES YES NO - - - - - - - -

-2.6

P-2

(LOWER LOUNGE)21 1 120 20 LOWER LOUNGE HVAC -1.3 YES YES NO - - - - - - - -

P-5 (CREW SPACE) 100 5, 7 1 120 20 WHEELHOUSE HVAC -2.6 YES YES YES 1 208 25 ZONE 4 +3.5 YES YES YES +0.9

P-5

(CREW SPACE)

P-6

(UPPER LOUNGE) 100

3 1 120 20 UPPER LOUNGE HVAC -1.3 YES YES NO - - - - - - - -

+10.5 P-6

(UPPER LOUNGE)

5, 7 1 208 20 UPPER LOUNGE HVAC -2.3 YES YES YES 1 208 50 ZONE 3 +4.7 YES YES YES

11, 13 - - - - - - - - 1 208 50 ZONE 2 +4.7 YES YES YES

12, 14 - - - - - - - - 1 208 50 ZONE 1 +4.7 YES YES YES

P-7

(EOS) 100

17, 19 - - - - - - - - 1 208 20 ZONE 5 +1.1 YES YES YES

+1.3

P-7

(EOS)

16 - - - - - - - - 1 120 15 CONDENSATE PUMP +0.2 YES YES YES

SP7-716

3C-14AWG 1P

511-E531

CONDENSATE

PUMP

511-E520

JUNCTION BOX

SEE ELECTRICAL NOTE 10

511-E521

1.6 FLA

5.3FLA

SP7-716-1

3C-14AWG

9.0 ZINC ANODE REPLACEMENTS :
9.1 Description
9.2 References
9.2.1 DWG NC-250-0001-R0 - Lines & Offsets
9.3 Owner Furnished Equipment
9.4 Requirements
9.5 Tests, Trials, and Documentation
9.6 Payment