Addendum #3 10-12-2022.pdf
PDF 6 MB Posted
- Attached to
- Palestine Hatchery New Facilities
- Solicitation number
- CRFQ 0310 DNR2300000002 4
- Issued by
- Wetzel County, West Virginia
About this file
This is Addendum #3 to a Centralized Request for Quote (CRFQ) issued by the West Virginia Department of Administration Purchasing Division on behalf of the Division of Natural Resources for the construction of a new hatchery building at Palestine State Fish Hatchery located in Elizabeth, West Virginia in Wirt County. The solicitation (CRFQ DNR23*02) seeks construction of new facilities and associated infrastructure for the hatchery. The solicitation was issued on October 12, 2022, with bids closing on October 18, 2022, at 1:30 p.m. Addendum #3 publishes responses to vendor-submitted questions regarding equipment specifications and materials. Bids should be submitted to the Department of Administration Purchasing Division, 2019 Washington Street East, Charleston, West Virginia 25305. The primary point of contact is Joseph E. Hager III at (304) 558-2306 or joseph.e.hageriii@wv.gov.
The addendum addresses vendor questions regarding pump specifications and piping materials for the aquaponics system. The contractor is responsible for supplying and installing all pumps, including four Pentair Sparus variable-speed pumps (model specifications MP-1, MP-2, MP-3, and MP-4) and two Pentair P2 self-priming transfer pumps (MAP-1 and MAP-2). Aquaponics piping is specified as Schedule 40 polyvinyl chloride (PVC). The addendum includes comprehensive technical documentation for both pump models, including installation guides, performance curves, electrical specifications, maintenance procedures, and troubleshooting information. All provisions of the solicitation and prior addenda remain in full force and effect, and vendors must acknowledge receipt of all addenda by submitting a completed Addendum Acknowledgment Form with their bid to avoid disqualification.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date Printed: Oct 12, 2022 Page: 1 FORM ID: WV-PRC-CRFQ-002 2020/05
Department of Administration Purchasing Division 2019 Washington Street East Post Office Box 50130 Charleston, WV 25305-0130
State of West Virginia Centralized Request for Quote
Construction
Proc Folder: 1082852 Reason for Modification:
Doc Description: Palestine Hatchery New Facilities Addendum #3 issued to publish agency responses to additional vendor submitted questions.
Proc Type: Central Purchase Order
Date Issued Solicitation Closes Solicitation No Version
2022-10-12 2022-10-18 13:30 CRFQ 0310 DNR2300000002 4
BID RECEIVING LOCATION
BID CLERK
DEPARTMENT OF ADMINISTRATION
PURCHASING DIVISION
2019 WASHINGTON ST E
CHARLESTON WV 25305
US
VENDOR
Vendor Customer Code:
Vendor Name :
Address :
Street :
City :
State : Country : Zip :
Principal Contact :
Vendor Contact Phone: Extension:
FOR INFORMATION CONTACT THE BUYER
Joseph E Hager III
(304) 558-2306 joseph.e.hageriii@wv.gov
Vendor Signature X FEIN# DATE
All offers subject to all terms and conditions contained in this solicitation
Date Printed: Oct 12, 2022 Page: 2 FORM ID: WV-PRC-CRFQ-002 2020/05
ADDITIONAL INFORMATION
The West Virginia Purchasing Division is soliciting bids on behalf of The West Virginia Division of Natural Resources to establish a contract for the construction of a hatchery building at Palestine State Fish Hatchery located in Elizabeth, WV in Wirt County per the attached specifications, project drawings, and project manual
INVOICE TO SHIP TO
DIVISION OF NATURAL
RESOURCES
STATE OF WEST VIRGINIA
PARKS & RECREATION-PEM
SECTION
JOBSITE - SEE
SPECIFICATIONS
324 4TH AVE
SOUTH CHARLESTON WV No City WV
US US
Line Comm Ln Desc Qty Unit Issue Unit Price Total Price 1 Construction of New Facilities
Comm Code Manufacturer Specification Model #
72000000
Extended Description:
Construction of New Facilities
SCHEDULE OF EVENTS
Line Event Event Date
SOLICITATION NUMBER: CRFQ DNR23*02
Addendum Number: No. 3
The purpose of this addendum is to modify the solicitation identified above to reflect the change (s) identified and described below.
Applicable Addendum Category:
[ ] Modify bid opening date and time
[ ] Modify specifications of product or service being sought
[ X ] Attachment of vendor questions and responses
[ ] Attachment of pre-bid sign-in sheet
[ ] Correction of error
[ ] Other – Clarification
Description of Modification to Solicitation:
Addendum issued to publish and distribute the attached documentation to the vendor community.
1 This addendum provides responses to vendor submitted questions
Additional Documentation: Documentation related to this Addendum (if any) has been included herewith as Attachment A and is specifically incorporated herein by reference.
Terms and Conditions:
1. All provisions of the Solicitation and other addenda not modified herein shall remain in full force and effect.
2. Vendor should acknowledge receipt of all addenda issued for this Solicitation by completing an Addendum Acknowledgment, a copy of which is included herewith. Failure to acknowledge addenda may result in bid disqualification. The addendum acknowledgement should be submitted with the bid to expedite document processing.
DNR_07042017
RFI: Questions from vendors for CRFQ DNR 23*02 Palestine Fish Hatchery
Question 1: Are there any detail to the specs for the MAP-1, MAP-2, MP-1, MP-2, FP-1, FP-2 on page AP1.01? I cannot find any details for what these items are. Are they owner provided?
Answer: MP-1, MP-2, MP-3, and MP-4 will be similar. Manufacturer is Pentair. Model is Sparus. MAP-1 and MAP -2 are similar. Manufacture is Pentair. Model is P2 self primer pump. See the attached information on the pumps. Contractor shall supply and install the pumps.
Question 2: Also, what is the piping material for the aquaponics as well?
Answer: Aquaponics piping is Schedule 40 pvc.
NEW PRODUCT ANNOUNCEMENT
9.8.16
NE
W
PR
OD
UC
T A
NN
OU
NC
EM
EN
T
9.8 .16
P2 PLUS 2" SELF-PRIMING POLY TRANSFER PUMPS
P2 PLUS 2" SELF-PRIMING POLY TRANSFER PUMPS
VERSATILE PUMPS IDEAL FOR SALTWATER APPLICATIONS
The polypropylene pump body makes this product line ideal for saltwater applications or when transferring a variety of other fluids. Tank filling, chemical transfer and other stationary liquid transfer applications are just a few of its many uses.
FEATURES & BENEFITS
• �Polypropylene housing and TEFC motor are suitable for harsh environments
• �Easily handles high-capacity liquid transfer jobs with flow rates up to 188 gpm/ 712 lpm
• �Self-priming capabilities with maximum suction lift up to 25 feet/7.6 meters
• �Nylon impellers constructed for improved strength can handle solid particles in suspension up to 3/8” diameter
• �EPDM mechanical seal and inlet valve for longevity and reliability in most applications
• ��Available with either 5 hp or 7.5 hp 50/60 hz TEFC Baldor electric motor
• Three phase 230/460 volt motors in both 5 hp & 7.5 hp
• Single phase 230 volt motor available in 5 hp
Nylon impellers can handle solid particles in suspension up to 3/8” diameter.
Self-priming capabilities with maximum suction lift up to 25 feet/7.6 meters.
Strainer or Foot Valve
Suction screen area must be at least four times suction pipe area.
Customer-supplied priming tee, plug and nipple.
Priming plug.
Suction hose.
Pump inlet.
Discharge pipe.
25’ Max.
If you have any questions, please do not hesitate to contact your Pentair Aquatic Eco-Systems Representative or email PAES.General@Pentair.com.
All Pentair trademarks and logos are owned by Pentair or one of its global affiliates. Pentair Aquatic Eco-Systems® is a registered trademark of Pentair Aquatic Eco-System, Inc. and/or its affiliated companies in the United States and/ or other countries. Unless expressly noted, names and brands of third parties that may be used in this document are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Aquatic Eco-Systems, Inc. Those names and brands may be the trademarks or registered trademarks of those third parties. Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice. Pentair is an equal opportunity employer.
NEW! P2 PLUS 2" SELF-PRIMING POLY TRANSFER PUMPS
2395 Apopka Blvd., Apopka, FL 32703 407.886.3939 PentairAES.com ©2016 Pentair Aquatic Eco-Systems, Inc. All rights reserved
MODEL HP PHASE
MAX FLOW RATE
GPM/LPM
MAX PRESSURE
PSI/BAR PORTS
SHIP WEIGHT
LBS/KG MOUNTING BOLTS VOLTAGE AMPS
60Hz Models 340904 5 1 150/568 47/3.2 2" NPT Inlet & Outlet 110/50 5/16” or M8 230 19.4 340905 5 3 150/568 47/3.2 2" NPT Inlet & Outlet 90/41 5/16” or M8 230/460 12/6 340906 7.5 3 188/712 54/3.7 2" NPT Inlet & Outlet 90/41 5/16” or M8 230/460 17.4/8.7
50Hz Models 340904 5 1 120/454 32/2.2 2" NPT Inlet & Outlet 110/50 5/16” or M8 220 14 340905 5 3 120/454 32/2.2 2" NPT Inlet & Outlet 90/41 5/16” or M8 190/380 11.4/5.7 340906 7.5 3 160/606 37/2.6 2" NPT Inlet & Outlet 90/41 5/16” or M8 190/380 14.4/7.2
PAES100-103.A
SPECIFICATIONS
340906 IMPERIAL
60 Hz PSI 0 5 10 15 20 25 30 35 40 45 50 54
GPM 188 185 181 173 163 151 136 120 102 76 44 0
50 Hz PSI 0 5 10 15 20 25 30 35 37 — — —
GPM 160 155 143 129 112 90 65 20 0 — — —
340906 METRIC
60 Hz BAR 0 0.3 0.7 1 1.4 1.7 2.1 2.4 2.8 3.1 3.4 3.7
LPM 712 700 685 655 617 572 515 454 386 288 167 0
50 Hz BAR 0 0.3 0.7 1 1.4 1.7 2.1 2.4 2.6 — — —
LPM 606 587 541 488 424 341 246 76 0 — — —
PERFORMANCE
340904 & 340905 IMPERIAL
60 Hz PSI 0 5 10 15 20 25 30 35 40 45 47 —
GPM 150 142 133 123 111 97 84 66 43 9 0 —
50 Hz PSI 0 5 10 15 20 25 30 32 — — — —
GPM 120 110 100 85 67 42 10 0 — — — —
340904 & 340905 METRIC
60 Hz BAR 0 0.3 0.7 1 1.4 1.7 2.1 2.4 2.8 3.1 3.2 —
LPM 568 538 503 466 420 367 318 250 163 34 0 —
50 Hz BAR 0 0.3 0.7 1 1.4 1.7 2.1 2.2 — — — —
LPM 454 416 379 322 254 159 38 0 — — — —
7.5 hp 5 hp
0 5 10 15 20 25 30 35 40 45
0 20 40 60 80 100 120 140 160 180 200 gpm m3/h
CAPACITY
0 0
TO
TA
L
DY
N
AM
IC
H
EA
D m ft 60 Hz Performance
0 0
TO
TA
L
DY
N
AM
IC
H
EA
D m ft
0 5 10 15 20 25 30 35 40
0 20 40 60 80 100 120 140 160 180 gpm m3/h
CAPACITY
7.5 hp 5 hp
50 Hz Performance
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
SPARUS™ PUMP
INSTALLATION AND
USER’S GUIDE
WITH CONSTANT FLOW TECHNOLOGY™
AQUATIC ECO-SYSTEMS®
SPARUS™ Pump with Constant Flow Technology™ Installation and User’s Guide i
P/N 356643 Rev. A 4/7/17
If you have questions about ordering Pentair Aquatic Eco-Systems, Inc. replacement parts, and pool products, please contact:
CUSTOMER SERVICE / TECHNICAL SUPPORT
TABLE OF CONTENTS
Setting Programs 1-8
Pump Operating Modes Set Programs 1-4 in Manual Mode Set Programs 1-4 in Egg-Timer Mode Set Programs 1-8 in Schedule Mode
Features Time Out Quick Clean/Only High Speed Override Feature
Priming Priming Features Setting Priming Features
Thermal Mode
Maintenance Pump Strainer Basket Cleaning the Pump Strainer Basket Winterizing
Servicing Motor and Drive Care Shaft Seal Replacement Pump Disassembly Pump Reassembly Drive Assembly Removal and Installation
Troubleshooting Alerts and Warnings Troubleshooting Chart
Replacement Parts
Technical Data Pump Dimensions Electrical Specifications Pump Performance Curves Agency Materials List Operator Control Panel Quick Reference Guide
Important Pump Warning and Safety Instructions
Pump Overview Drive Assembly and Control Panel External Control Motor Features Drive Features
Installation Location Piping Electrical Requirements Fittings and Valves Electrical Installation
Wiring, Grounding and Bonding General Requirements
Operating the Pump Priming the Pump Using the Operator Control Panel Stopping and Starting the Pump Adjusting and Saving a Pump Speed/Flow Operating the Pump at Preset Speeds Pump Operating Modes Program Types Control Panel: Pump Menu Guide
Pump Settings Set Date and Time Set AM/PM or 24-Hour Clock Set Min/Max Speeds Set Min/Max Flow Rates Set Flow Limit for Speed Program Set Maximum System Pressure Set Pressure Limit for Speed Program Pump Address Set Screen Contrast Set Control Panel Language Set Temperature Unit Password Protection Setting Password Set Ramping Rate ii
Customer Service 8 AM to 7 PM — Eastern and Pacific Times
US International
| Phone: | (877) 347-4788 Phone: (407) 886-3939 | |
| FAX: | (407) 886-6787 | FAX: (407) 886-4884 |
Web site Visit www.pentairaes.com
IMPORTANT NOTICE
This guide provides installation and operation instructions for this product. Consult Pentair with any questions regarding this equipment.
Attention Installer: This guide contains important information about the installation, operation and safe use of this product. This information should be given to the owner and/or operator of this equipment after installation or left on or near the pump. This pump is for use for aquaculture installations ONLY. Do not use with any type of swimming pool, hot tub, or spa.
Attention User: This manual contains important information that will help you in operating and maintaining this product. Please retain it for future reference. This pump is for use for aquaculture installations ONLY. Do not use with any type of swimming pool, hot tub, or spa. Warnings and safety instructions for Pentair Aquatic Eco-Systems pumps and other related products are available at:
http://www.pentairaes.com or call U.S. (877) 347-4788 • International
(407) 886-3939 for additional free copies of these instructions.
IMPORTANT PUMP WARNING AND SAFETY INSTRUCTIONS
When installing and using this electrical equipment, basic safety precautions should always be followed, include the following:
RISK OF ELECTRICAL SHOCK. Connect only to a branch circuit protected by a ground-fault circuit-interrupter (GFCI). Contact a qualified electrician if you cannot verify that the circuit is protected by a GFCI.
This unit must be connected only to a supply circuit that is protected by a ground-fault circuit-interrupter
(GFCI). Such a GFCI should be provided by the installer and should be tested on a routine basis. To test the GFCI, push the test button.
The GFCI should interrupt power. Push the reset button. Power should be restored. If the GFCI fails to operate in this manner, the GFCI is defective. If the GFCI interrupts power to the pump without the test button being pushed, a ground current is flowing, indicating the possibility of an electric shock. Do not use this pump. Disconnect the pump and have the problem corrected by a qualified service representative before using.
General Warnings
• Never open the inside of the drive motor enclosure. There is a capacitor bank that holds a 230 VAC charge even when there is no power to the unit.
| • | The pump is not submersible. |
| • | The pump is capable of high flow rates; use caution when installing |
and programming to limit pumps performance potential with old or questionable equipment.
• Code requirements for the electrical connection differ from country to country, state to state, as well as local municipalities. Install equipment in accordance with the current National Electrical Code and all applicable local codes and ordinances.
• Before servicing the pump; switch OFF power to the pump by disconnecting the main circuit to the pump.
• This appliance is not intended for use by persons (including children) of reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
FAILURE TO FOLLOW ALL INSTRUCTIONS AND
WARNINGS CAN RESULT IN SERIOUS BODILY
INJURY OR DEATH. THIS PUMP SHOULD BE INSTALLED AND SER-
VICED ONLY BY A QUALIFIED SERVICE PROFESSIONAL. INSTALL-
ERS, OPERATORS AND OWNERS MUST READ THESE WARNINGS
AND ALL INSTRUCTIONS IN THE OWNER’S MANUAL BEFORE US-
ING THIS PUMP. THESE WARNINGS AND THE OWNER’S MANUAL
MUST BE LEFT WITH THE PRODUCT OWNER.
SUCTION ENTRAPMENT HAZARD: STAY OFF
THE MAIN DRAIN AND AWAY FROM ALL SUCTION
OUTLETS!
F
THIS PUMP PRODUCES HIGH LEVELS OF SUCTION AND CREATES
A STRONG VACUUM AT THE MAIN DRAIN AT THE BOTTOM OF THE
BODY OF WATER. THIS SUCTION IS SO STRONG THAT IT CAN TRAP
ADULTS OR CHILDREN UNDER WATER IF THEY COME IN CLOSE
PROXIMITY TO A DRAIN OR A LOOSE OR BROKEN DRAIN COVER
OR GRATE.
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This is the safety alert symbol. When you see this symbol on your system or in this manual, look for one of the following signal words and be alert to the potential for personal injury.
Warns about hazards that can cause death, serious personal injury, or major property damage if ignored.
Warns about hazards that may cause death, serious personal injury, or major property damage if ignored.
Warns about hazards that may or can cause minor personal injury or property damage if ignored.
NOTE Indicates special instructions not related to hazards.
Carefully read and follow all safety instructions in this manual and on equipment. Keep safety labels in good condition; replace if missing or damaged.
R I S K O F E L E C T R I C A L S H O C K O R
ELECTROCUTION: PUMPS REQUIRE HIGH
VOLTAGE WHICH CAN SHOCK, BURN, OR
CAUSE DEATH. BEFORE WORKING ON PUMP!
Always disconnect power to the pump at the circuit breaker from the pump before servicing the pump.
Failure to do so could result in death or serious injury to service person, system users or others due to electric shock.
ii iii
Warning Page P/N 352560 Rev. B 12/15
For Installation of Electrical Controls at Equipment Pad (ON/OFF Switches, Timers and Automation Load Center)
Install all electrical controls at equipment pad, such as on/off switches, timers, and control systems, etc. to allow the operation (startup, shut-down, or servicing) of any pump or filter so the user does not place any portion of his/her body over or near the pump strainer lid, filter lid or valve closures. This installation should allow the user enough space to stand clear of the filter and pump during system start-up, shut down or servicing of the system filter.
SAVE THESE INSTRUCTIONS
IMPORTANT PUMP WARNING AND SAFETY INSTRUCTIONS
HAZARDOUS PRESSURE: STAND CLEAR OF
PUMP AND FILTER DURING START UP
Circulation systems operate under high pressure.
When any part of the circulating system (i.e.
locking ring, pump, filter, valves, etc.) is serviced, air can enter the system and become pressurized.
Pressurized air can cause the pump housing cover, filter lid and valves to violently separate which can result in severe personal injury or death. Filter tank lid and strainer cover must be properly secured to prevent violent separation. Stand clear of all circulation system equipment when turning on or starting up pump.
Before servicing equipment, make note of the filter pressure. Be sure that all controls are set to ensure the system cannot inadvertently start during service. Turn off all power to the pump. IMPORTANT: Place filter manual air relief valve in the open position and wait for all pressure in the system to be relieved.
Before starting the system, fully open the manual air relief valve and place all system valves in the “open” position to allow water to flow freely from the tank and back to the tank. Stand clear of all equipment and start the pump.
IMPORTANT: Do not close filter manual air relief valve until all pressure has been discharged from the valve and a steady stream of water appears. Observe filter pressure gauge and be sure it is not higher than the pre-service condition.
General Installation Information
• All work must be performed by a qualified service professional, and must conform to all national, state, and local codes.
| • | Install to provide drainage of compartment for electrical components. |
| • | These instructions contain information for a variety of pump models |
and therefore some instructions may not apply to a specific model. All models are intended for use in aquaculture applications. The pump will function correctly only if it is properly sized to the specific application and properly installed.
Pumps improperly sized or installed or used in applications other than for which the pump was intended can result in severe personal injury or death. These risks may include but not be limited to electric shock, fire, flooding, suction entrapment or severe injury or property damage caused by a structural failure of the pump or other system component.
The pump can produce high levels of suction within the suction side of the plumbing system. These high levels of suction can pose a risk if a person comes within the close proximity of the suction openings. A person can be seriously injured by this high level of vacuum or may become trapped and drown. It is absolutely critical that the suction plumbing be installed in accordance with the latest national and local codes for aquaculture systems.
A clearly labeled emergency shut-off switch for the pump must be in an easily accessible, obvious place.
Make sure users know where it is and how to use it in case of emergency.
NOTE: ALL SUCTION PLUMBING MUST BE INSTALLED IN
ACCORDANCE WITH THE LATEST NATIONAL AND LOCAL CODES,
STANDARDS AND GUIDELINES.
This pump has been evaluated for use with water only.
Before operation, be sure to completely rinse the pump volute with water.
Cord Connected Models Only
RISK OF ELECTRICAL SHOCK. This pump is supplied with a grounding conductor and grounding type attachment plug. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, grounding-type receptacle.
SPARUS™ Pump with Constant Flow Technology Installation and User’s Guide
PUMP OVERVIEW
The Sparus™ Pump with Constant Flow Technology™ can be programmed to run at a speed or a constant flow rate over set time intervals for maximum operating efficiency and energy conservation for a variety of applications.
• The pump can operate from 450 RPM to 3450 RPM with four preset speeds of 750, 1500, 2350 and 3110 RPM, or the pump can be set to control its own speed and maintain a constant flow rate.
• The pump can adapt to any application below 140 GPM. Simply program the pump to suit the application, and the pump will automatically determine perfect operating conditions for that specific flow rate.
• Up to 8 customizable programs that can be set for or speed in either Manual, Egg Timer or Schedule modes.
• Pump control panel alarm LED and error messages warn the user of improper operation.
• Programmable priming mode with automatic detection of prime for easy start-up and automatic detection of loss of prime.
• UL/CUL
Drive Assembly and Control Panel The Sparus pump drive is designed to produce maximum motor operational efficiency. The drive controls the motor’s rotational speed by controlling the frequency of the supplied current. It also protects the motor and pump from operating outside of their intended operating parameters.
The control panel can be mounted on the pump in four different directions in order to provide the user the best access.
Motor Features
• High Efficiency Permanent Magnet Synchronous
Motor (PMSM)
• Superior speed control
• Operates at lower temperatures due to high efficiency
• Designed to withstand outdoor environment
• Ten-Pole, Three-Phase, Totally Enclosed Fan Cooled (TEFC) Motor
• 56 Square Flange
• Low noise
Drive Features
• Active Power Factor Correction
• UL 60730 Compliant
• Rotatable Keypad
• Easy Overhead Wiring
• High Drive Operational Efficiency
• Sensorless Flow and Pressure Control Technology
• Loss of Prime Detection
Variable Speed and Flow Drive Assembly
Operator Control Panel Cover Buttons and LED (Beneath)
Strain Relief Port for Incoming AC Power
Motor Stand
INSTALLATION
Location Be sure the pump location meets the following requirements:
1. Install the pump as close to the body of water as possible. To reduce friction loss and improve efficiency, use short, direct suction piping returns.
2. Install a minimum of 5 feet (1.52 meters) from the inside wall of the body of water. Canadian installations require a minimum of 9.8 feet (3 meters) from water level.
3. Install the pump a minimum of 3 feet (.9 meters) from the heater outlet.
4. Do not install the pump more than 10 feet (3.1 meters) above the water level.
5. Install the pump in a well ventilated location protected from excessive moisture (i.e., rain gutter downspouts, sprinklers, etc.)
6. Install the pump with a rear clearance of at least 3-inches (76.2 mm) so that the motor can be removed easily for maintenance and repair. See Figure 1.
Piping
1. For improved plumbing, it is recommended to use a larger pipe size. When installing the inlet and outlet fittings (male adaptors), use thread sealant.
2. Piping on the suction side of the pump should be the same or larger than the return line diameter.
3. Plumbing on the suction side of the pump should be as short as possible.
4. For most installations Pentair recommends installing a valve on both the pump suction and return lines so that the pump can be isolated during routine maintenance. We also recommend a valve, elbow or tee installed in the suction line should be no closer to the front of the pump than five (5) times the suction line pipe diameter. See Figure 2.
Example: A 2-inch pipe requires a 10-inch (254
mm) straight run in front of the suction inlet of the pump). This will help the pump prime faster and last longer.
Note: DO NOT install 90° elbows directly into the pump inlet and outlet.
Electrical Requirements
• Install all equipment in accordance with the National
Electrical Code and all applicable local codes and ordinances.
• A means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
Fittings and Valves
1. Do not install 90° elbows directly into pump inlet.
2. Flooded suction systems should have valves installed on suction and discharge pipes for maintenance, however, the suction valve should be no closer than five times the suction pipe diameter as described in this section.
3. Use a check valve in the discharge line when using this pump for any application where there is significant height to the plumbing after the pump.
4. Be sure to install check valves when plumbing in parallel with another pump. This helps prevent reverse rotation of the impeller and motor.
Only a qualified plumbing professional should install the Sparus™ Pump with Constant Flow Technology™.
Refer to “Important Pump Warning And Safety Instructions” on pages ii - iii for additional installation and safety information.
Figure 1: Pump Rear and Overhead Clearance
3 IN.
(7.6 CM)
MINIMUM
6 IN.
(15.2 CM)
MINIMUM
Figure 2: Recommended Piping
MIN 5 X SUCTION PIPE DIAMETER
ELBOW
Electrical Installation
Note: ALWAYS reinstall the drive lid onto the field wiring compartment when leaving the pump unsupervised during servicing. This will prevent foreign matter (i.e. rainwater, dust, etc.) from accumulating in the drive.
Wiring
1. Be sure all electrical breakers and switches are turned off before wiring motor.
2. Be sure that the supply voltage meets the requirements listed on the motor nameplate. If these requirements are not met, permanent damage may occur.
3. For wiring sizes and general guidelines for proper electrical installation, please follow the specifications defined in the National Electric Code and any local codes as required.
4. Use strain relief and be sure all electrical connections are clean and tight.
5. Cut the wires to the appropriate length so they do not overlap or touch when connected.
6. Reinstall the keypad after wiring the pump by plugging the cover back into the drive wiring connection and re-seating the keypad in the desired orientation with the four (4) corner screws.
Note: Ensure that the keypad cable is not pinched between the drive and keypad during re-seating.
Grounding
1. Permanently ground the drive using the green ground screw, as shown below. Use the correct wire size and type specified by National Electrical Code. Be sure the ground wire is connected to an electrical service ground.
2. The pump should be permanently connected to either a circuit breaker, 2-pole timer or 2-pole relay.
Note: If AC power is supplied by a GFCI circuit breaker, the pump should be wired on its own independent circuit.
Bonding
1. Bond the motor to the structure in accordance with the
National Electrical Code. Use a solid copper bonding conductor not smaller than 8 AWG. For Canadian installations, a 6 AWG or larger solid copper bonding conductor is required. Run a wire from the external bonding screw or lug to the bonding structure.
2. Connect the wire from the accessible bonding lug on the motor to all metal parts of the structure and to all electrical equipment, metal conduit, and metal piping within 5 feet (1.52 meters) of the inside walls of the structure. Run a wire from the external bonding screw or lug to the bonding structure.
RISK OF ELECTRICAL SHOCK OR ELECTROCUTION. This pump must be installed by a licensed or certified electrician or a qualified service professional in accordance with the National Electrical Code and all applicable local codes and ordinances.
Improper installation will create an electrical hazard which could result in death or serious injury to users, installers, or others due to electrical shock, and may also cause damage to property.
Always disconnect power to the pump at the circuit breaker before servicing the pump. Failure to do so could result in death or serious injury to service people, users or others due to electric shock.
Read all servicing instructions before working on the pump.
Note: When the pump is started and stopped by removing power with a relay or timer, a two-pole device should be used to apply and remove power to both POWER
LINE TERMINALS.
STORED CHARGE - Wait at least sixty (60) seconds before servicing.
Field Wiring Compartment
Drive Wiring Connection
1/2” NPD
Conduit Port
Ground Wire Connection (Green Screw)
Bonding Lug
General Requirements
Note: 230 volts is the ideal input voltage for the Sparus pump, although it can operate on stable voltage from 207V to 253V. It is important to ensure that periodic line voltage fluctuations do not expose the pump to voltages outside its allowable range. The pump’s drive electronics may have reduced length of service life if the pump is consistently operated at or near the extreme ends of its allowable voltage range (+/-).
Note: All wiring should be performed by a qualified electrician. It is the responsibility of the installer/ electrician to perform the installation in compliance with the National Electric Code and all State, local codes and ordinances. It is the responsibility of the installer to perform the installation in such a manner that the pump is provided with 230 volt (+/-10%), single phase, AC power, 50Hz or 60Hz.
In some field installations (particularly commercial properties) direct access to single-phase power may not be available. In an application where only three-phase power is available, it is possible for qualified installers to follow standard electrical wiring procedures that will allow the pumps to be installed and operated.
Three-phase power may be sourced from a three-phase electrical panel and connected to a two-pole circuit breaker; thereby creating single phase power as required by the pump. Only single-phase electrical power may be terminated into the field wiring compartment junction box located on the side of the pump.
When installing a pump always safely use a multi-meter to measure the actual voltage across the two live conductors to verify that it is 230 volt (+/-10%), single-phase, AC power, 50Hz or 60Hz.
The Sparus™ Pump with Constant Flow Technology™ is designed to operate on 230 volt (+/-10%), single-phase, AC power, 50Hz or 60Hz.
OPERATING THE PUMP
Priming Features
The default priming setting is ENABLED.
The pump also allows you to set the following from the operator control panel:
| • | Priming speed |
| • | Priming range (1-10) |
| • | Priming delay |
Set up instructions on page 18.
Priming the Pump Prime the pump before starting the pump for the first time. Remove the lid and fill the basket with water. The pump basket must be filled with water before initial start up or after servicing.
Follow the steps below to prime the pump for start up:
1. Press Start/Stop to stop the pump. Disconnect the pump main power supply and communication cable.
2. Close all valves in suction and discharge pipes.
Relieve all pressure from the system.
3. Remove the pump lid and locking ring.
4. Fill the pump strainer pot with water.
5. Reassemble the pump lid and locking ring onto the strainer basket. The pump is now ready to prime.
6. Open all valves in suction and discharge pipes.
7. Open the filter air relief valve and stand clear of the filter.
8. Connect power to the pump. Be sure green power light is on.
9. Press Start/Stop to start the pump. The pump will enter into priming mode (if enabled) and speed up to the maximum speed set in the pump menu settings.
10. When water comes out of the filter air relief valve, close the valve. The system should now be free of air and recirculating water to and from the body of water.
11. Do not allow your pump to run longer than 30 minutes time without developing full flow. If the pump does not prime, check your priming settings on the control panel or see the “Troubleshooting” section on pages 24-26.
DO NOT run the pump dry. If the pump is run dry, the mechanical seal will be damaged and the pump will start leaking. If this occurs, the damaged seal must be replaced. ALWAYS maintain proper water level in your circulating system. If the water level falls below the intake, the pump will draw air, losing the prime and causing the pump to run dry, resulting in a damaged seal. Continued operation in this manner could cause a loss of pressure, resulting in damage to the pump case, impeller and seal and may cause property and personal injury.
This pump is shipped with Priming mode ENABLED. Unless the Priming settings are changed in the menu, be aware that the pump will speed up to the maximum speed when the pump is powered on for the first time, and the Start/Stop button is pressed. To change the maximum speed of the pump, refer to page 10.
Before turning the pump ON, be sure the following conditions are met:
1. Open filter air relief valve.
2. Open valves.
3. Return line is completely open and clear of any blockages.
4. Water in the pump basket.
5. Stand clear of the filter or other pressurized vessels.
NOTE: When setting up the Sparus™ Pump with Constant Flow Technology™, the user must set the pump’s internal clock and establish an operation schedule by following the steps in this manual. Please refer to user’s guide sections: ‘Set Time’ (page 10) and ‘Set Programs 1-8 in Schedule Mode’ (page 15) to schedule a time to run the pump.
Top View
Lid Locking Ring
Volute
Control Panel #1-8
12:15p
750 RPM
T 0.00 150 WATTS
Running Speed 1
SaveBack
Select Menu
1 2 3 4
Quick Clean
Time Out
12:15p
750 RPM
T 0.00 150 WATTS
Running Speed 1
SaveBack
Select Menu
1 2 3 4
Quick Clean
Time Out
Line 1
Line 2
Line 3 Line 4
Save?
Control Panel #9-15
Using the Operator Control Panel Use the operator control panel to start and stop the Sparus™ Pump with Constant Flow Technology™, set, and change pro-grams, and access pump features and settings.
Button 1: Press to select Program 1 (750 RPM). LED on indicates Program 1 is active.
Button 2: Press to select Program 2 (1500 RPM). LED on indicates Program 2 is active.
Button 3: Press to select Program 3 (2350 RPM). LED on indicates Program 3 is active.
Button 4: Press to select Program 4 (3110 RPM). LED on indicates Program 4 is active.
Back: Goes one step back in menu; exits without saving current setting.
Save: Saves current menu item setting. When a parameter has been adjusted the "Save?" icon will be displayed.
Menu: Accesses the menu items when and if the pump is stopped.
Select: Press to select the currently displayed option on the screen.
Arrow buttons:
• Up arrow: Move one level up in the menu or increase a digit when editing a setting.
• Down arrow: Move one level down in the menu or decrease a digit when editing a setting.
• Left arrow: Move cursor left one digit when editing a setting.
• Right arrow: Move cursor right one digit when editing a setting.
Quick Clean: Pump increases to a higher RPM. LED light is on when active.
Time Out: Allow the pump to remain in a stopped state for a set period of time before resuming normal operation. LED is on when active.
Start/Stop button: To start or stop the pump. When LED is on, the pump is running or in a mode to start automatically.
Reset button: Reset alarm or alert.
LEDs:
On: Green light when pump is powered on.
Warning: On if warning condition is present. See “Alerts and Warnings” on page 24.
Alarm: Red LED on if alarm condition occurs. See “Alerts and Warnings” on page 24.
Control Panel LCD Screen:
• Line 1: Key icon indicates password protection mode is active. If password protect is not enabled, no key icon is displayed. Also shows current time of day. Active cursors display when arrow key input is available.
• Line 2: Displays current pump speed/flow (RPM/GPM).
• Line 3: Countdown time and watts
• Line 4: Current pump status and current feature. "Save?"
will display on this line when a parameter adjustment can be saved.
Controls and LEDs on Keypad
Note: Always close the keypad cover after using the keypad.
Note: Using screwdrivers or pens to program the pump will damage the keypad overlay. Use your fingers only when programming the pump.
Key Lockout Icon
Current Speed/Flow
Countdown Time
"Save?" Icon
Current Time
Current Power Usage
Active Cursors
Current Running Feature
Stopping and Starting the Pump Starting the Pump
1. Be sure the pump is powered on and the green power LED is on.
2. Select one of the program buttons, then press the Start/Stop button (LED on) to start the pump. The pump will go into priming mode if priming feature is enabled.
Stopping the Pump
1. Press Start/Stop to stop the pump.
When servicing equipment (filters, heaters, chlorinators etc.), disconnect the communication cable, and switch OFF circuit breaker to remove power from the pump.
Note: The pump can automatically restart if the com-munication cable is connected.
Operating the Pump at Preset Speeds The pump is programmed with four default speeds of 750, 1500, 2350 and 3110 RPM. Program buttons 1-4 are for each of the preset speeds as shown below.
1. Be sure the pump is powered on and the green power LED is on.
2. Press the Program button (1- 4) corresponding to the desired preset speed and release quickly. The LED above the button will turn on.
3. Press Start/Stop. The pump will quickly change to the selected preset speed.
Adjusting and Saving a Pump Speed/Flow
1. While the pump is running, press the Up or Down arrow to adjust to desired speed or flow setting.
2. Press and hold down a Program button (1-4) for three (3) seconds to save speed/flow to the button or press Save to save the speed/flow.
LED lit
1 2 3 4
Pump Operating Modes
The Sparus™ Pump with Constant Flow Technology™ can be programmed in three different modes:
Programs 1-4 can be programmed in all three modes.
Programs 5-8 can only be programmed in Schedule mode since there are no buttons on the control panel for Programs 5-8. The default setting for Programs 5-8 is “Disabled”.
Manual Assigns a speed or flow to one of the four Program buttons on the control panel. This mode can only be used for programs 1-4. Programs 1 and 2 are Manual by default.
To operate in Manual mode, press one of the four program buttons and then press the Start/Stop button.
The pump will run the assigned speed or flow assigned to that program button.
Egg Timer Programs 1-4 can be programmed to run at a certain speed or flow and for a duration of time once a program button is pressed.
Programs 3 and 4 are Egg Timers by default. If you desire a different method of operation, programs 3 and 4 can be changed to Manual mode in the control menu.
To operate in Egg Timer mode, press a program button and then press Start/Stop. The pump will run that setting for the set amount of time and then turn off.
Schedule Programs 1-8 start and stop at a specific time during a 24 hour period. Speeds or flows programmed in Schedule mode will override any manually selected speed or flow once the next Schedule command commences.
Program Types This pump can run saved programs at either constant speeds or constant flow rates. This gives the user the ability to precisely assign the output from the pump so that no energy is wasted and the job is completed accurately.
Set Flow Manual
Schedule
Egg Timer
Set SpeedSet Type Set Flow
Set Type
Set Start Time Set Stop Time
Set Flow Set Speed Set Flow
Set Duration
Set Type Set Flow
Set Speed Set Flow
Program 1-4
Schedule Disabled Default: Disabled
Set Type
Set Start Time Set Stop Time
Set Flow Set Speed Set Flow
Program 5-8
Program Menu Tree Options
Operator Control Panel: Pump Menu Guide
Press MENU button to access menus
DateSETTINGS
MENU
Time
Hour Format
Months (1-12) Days (1-31) Years (2010-2100 Plus) Hours (24hr Mode: 0-23) (12hr Mode: 1-12 AM & PM) Minutes (0-60) AM/PM - Default: AM/PM
Set Min Speed (450-1700 RPM) - Default: 450 RPM Set Max Speed (1900-3450 RPM) - Default: 3450 RPM
24 Hour
Set Min Flow (20-70 GPM) - Default: 20 GPM Set Max Flow (80-140 GPM) - Default: 140 GPM Flow Limit Speed (Disabled / Enabled) - Default: Disabled Max Pressure (1-50 PSI) - Default: 30 PSI Pressure Limit Speed (Disabled / Enabled) - Default: Disabled
Date and Time
Min/Max
(pages 10-13)
Pump Address (1-16) - Default: 1 Contrast Level (1-5) - Default: 3 Language
Manual
Schedule
Egg Timer
Set Speed or Flow (450-3450 RPM or 20-140 GPM) - Default Program 1-2: Manual
Schedule Disabled
PROGRAM 1-8
English - Default: English Português Deutsch Italiano Nederlands
Français Español
Temperature Unit Fahrenheit - Default: F° Celsius C°
Firmware Version
Password Disabled - Default: Disabled Enabled Password Timeout (1 min. to 6 hrs.) - Default: 1 hour
Set Password (0000 - 9999) - Default: 1234
Fast - Default: Fast Medium Slow Fast - Default: Fast Medium Slow
Type (Speed / Flow)
Type (Speed / Flow)
Start Time Stop Time
Default: Disabled
Duration
Type (Speed / Flow)
Start Time Stop Time
Type (Speed / Flow)
Device
Program 1-4
Program 5-8
(pages 14-15)
Alarm Log (1-10)
Flow Unit GPM - Default: GPM
LPM
Pressure Unit PSI - Default: PSI
BAR
Ramping Ramp Up
Ramp Down
MENU TREE
CONTINUES TO
NEXT PAGE
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Set Speed or Flow (450-3450 RPM or 20-140 GPM) - Default Program 3-4: Egg Timer
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Operator Control Panel: Pump Menu Guide (cont.)
Disabled / Enabled - Default: Enabled
40° F - 50° F (4.4° C through 10° C) Default: 40° F (4.4° C)
Speed - Default: Speed
THERMAL MODE Disabled/Enabled
Set Type
Pump Temperature
(page 19)
Quick Clean Duration (1 min. to 10 hrs.) Default: 10 minutes
Time Out Duration (1 min. to 10 hrs.) Default: 3 hoursFEATURES
Quick Clean
Time Out
(page 16)
(1 min. to 30 min.) Default: 11 minutes
(1 - 10) Default: 5
(1 sec. to 10 min.) Default: 20 seconds
PRIMING
Max Priming Duration
Priming Range
Priming Delay
(pages 16-18) Priming Speed Set Speed (2400-3450 RPM) Default: 3450 RPM
Type (Speed / Flow)
Loss of Prime Enabled / Disabled - Default: Enabled
Flow
Disabled / Enabled - Default: EnabledDisabled/Enabled
Set Speed/Flow Set Speed (450-3450 RPM) Default 1000 RPM Set Flow (20-140 GPM) Default: 40 GPM
MENU TREE
CONTINUED FROM
PREVIOUS PAGE
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Pump Menu: Settings
Set Date and Time The time controls all scheduled times, functions, and programmed cycles and stores the correct time for up to 96 hours after power is turned off. Reset if the power is off longer than 96 hours.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Date and Time”. Press Select.
5. Press Select again and use Up or Down arrows to set the date.
6. Press Save to save user input and return to "Date and Time."
7. Use the Up or Down arrows to scroll to “Time”. Press Select.
8. Use the Up or Down arrows to scroll to edit the time.
Note: To set AM/PM or a 24 hour clock see the next section "Set AM/PM or 24 Hour Clock."
9. Press Save to save. To cancel any changes, press Back to exit without saving.
10. Press Back to exit.
Set AM/PM or 24-Hour Clock To change the time from a 12 hour clock (AM/PM) to a 24 hour clock:
1. Press Menu.
2. Press Select to select “Settings”.
3. Use the Up or Down arrows to scroll to “Date and Time". Press Select.
4. Use the Up or Down arrows to scroll to "AM/PM".
Press Select.
5. Use the Up or Down arrows to scroll to choose between 24 hr. and AM/PM.
6. Press Save to save. To cancel any edits, press Back to exit without saving.
7. Press Back to exit.
Set Minimum Speed (RPM) The minimum pump speed can be set from 450 RPM to 1700 RPM. The default setting is 450 RPM.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
5. Use the Up or Down arrows to scroll to “Set Min Spd”.
6. Press Select to change the setting. The cursor will appear in the first number column (ones).
MENU
SETTINGS
Note: Maximum Speed will limit Priming Speed, except in one case. If the Maximum Speed is set below the lowest available Priming Speed (2400 RPM) then the pump will exceed the Maximum Speed while the priming feature is running. This prevents the pump from having trouble priming if the Maximum Speed is set this low. If this is a problem, priming can be disabled in the Priming Menu (see “Priming” section on page 16).
Set Minimum Flow Rate (GPM) The minimum programmed flow rate can be set from 20 GPM to 70 GPM.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max” and press Select.
5. Use the Up or Down arrows to scroll to “Set Minimum Flow”.
6. Press Select to change the setting. The cursor will appear in the first number column (ones).
7. Press the Up or Down arrows to edit the minimum flow rate setting from 20 to 70 GPM.
8. Press Save to save. To cancel, press Back to exit edit mode without saving.
9. Press Back to exit.
7. Press the Up or Down arrows to edit the minimum speed setting from 450 to 1700 RPM.
8. Press Save to save. To cancel, press Back to exit edit mode without saving.
9. Press Back to exit.
Set Maximum Speed (RPM) The maximum speed can be set from 1900 RPM to 3450 RPM (default is 3450). Use this setting to set the maximum running speed of the Sparus™ Pump with Constant Flow Technology™.
Note: Maximum and minimum speed settings, and the associated alarms, remain active when in Flow mode.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
5. Use the Up or Down arrows to scroll to “Set Max Spd”.
6. Press Select to change. The cursor will appear in the first number column (ones).
7. Press Up or Down arrows to edit the maximum speed setting from 1900 to 3450 RPM.
8. Press Save to save. Press Back to exit. To cancel, press the Back to exit without saving.
Set Maximum Flow Rate (GPM) The maximum programmed flow rate can be set from 80 GPM to 140 GPM.
Note: Maximum and minimum speed settings, and the associated alarms, remain active when in Flow mode.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
5. Use the Up or Down arrows to scroll to “Set Maximum Flow”.
6. Press Select to change the setting. The cursor will appear in the first number column (ones).
7. Press the Up or Down arrows to edit the maximum flow rate setting from 80 to 140 GPM.
8. Press Save to save. To cancel, press Back to exit edit mode without saving.
9. Press Back to exit.
Set Flow Limit for Speed Program The flow limit in constant speed program type is disabled by default. This setting allows the user to ensure that the drive does not exceed the flow rate output that is set when they are operating in a constant speed mode. The system may change during a run at a constant speed that would increase the flow rate, it this feature is enabled then the pump will automatically limit itself to keep below the previously set Maximum Flow Rate.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max” and press Select.
5. Use the Up or Down arrows to scroll to “Flow Limit (Speed)”.
6. Press Select to move the cursor over the "Disabled".
7. Press and the Up or Down arrows to change it to "Enabled".
8. Press Save to save. To cancel, press Back to exit edit mode without saving.
9. Press Back to exit.
Set Maximum System Pressure The maximum pressure can be set using the drive, so that the pump does not exceed a set system pressure level when it is asked to do a high power job, or if the system changes during normal operation. This gives the user a better way than Maximum Speed to limit the output of their pump. If the system is less restrictive, then the pump is still capable of the higher flow rates than it would have been if the user had used a speed limit, but the pressure is still limited where the user needed it to be limited.
The pressure is the total system head, so it is a product of the suction pressure and the discharge pressure. The calculated value is equivalent to Total Dynamic Head (TDH). This value may not correspond with the filter's pressure reading, because it is the TDH across the pump and not the local pressure of the filter.
When the pump is running a Flow Program, it will always attempt to reach the set flow no matter what the system setup is. If the system pressure changes during the run (such as from filter dirt loading, or manually changing a valve position), the drive adjusts motor RPM to maintain a consistent flow rate.
In some cases the newly requested motor speed will increase the discharge pressure in order to maintain the requested flow rate. While maintaining the flow rate, the drive will remain within the pressure and speed limits set within the Min/Max menu. If the pump meets one of the limits, it will continue to run at the limit and the warning light will illuminate. The limit warning will be displayed on the bottom of the drives' keypad screen indicating that the requested flow rate is not being achieved and which limit that the drive is running into.
When the pump is running a Speed Program, the drive is not monitoring the flow or pressure limits by default.
These features need to be Enabled in the Min/Max menu.
To Set Maximum System Pressure:
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
5. Use the Up or Down arrows to scroll to “Set Maximum Pressure”.
6. Press Select to change the setting. The cursor will appear in the first number column (ones).
7. Press the Up or Down arrows to edit the maximum flow rate setting from 1 to 50 GPM.
8. Press Save to save. To cancel, press Back to exit edit mode without saving.
9. Press Back to exit.
Pump Menu: Settings
MENU
SETTINGS
Set Temperature Unit The default setting is Fahrenheit (°F). The pump can be set to either Celsius (°C) or Fahrenheit (°F).
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Device” menu item. Press Select.
5. Use Up or Down arrows to scroll to "Temperature Units". Press Select.
6. Use Up or Down arrows to choose Celsius (°C) or Fahrenheit (°F).
7. Press Save to save. To cancel any changes, press Back to exit without saving.
8. Press Back to exit.
Set Control Panel Language To access the language menu:
1. Check that the green power LED is on.
2. Press Menu and press Select to select “Settings”.
3. Use the Up or Down arrows and scroll to “Device”.
Press Select.
4. Use the Up or Down arrows to scroll to “Select Language". Press Select.
5. Use the Up or Down arrows to choose the desired language.
6. Press Save to select the control panel language. To cancel any changes, press Back to exit without saving.
7. Press Back to exit.
Pump Menu: Settings
Pump Address The default pump address is #1.
Note: Sparus™ Pump with Constant Flow Technology™ cannot be connected in series with other pumps.
1. Be sure the green power LED is on and the pump is stopped.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to…