Addendum #2 Revised Electrical drawings- Part 2.pdf

PDF 23 MB Posted

Attached to
RFP NORTH CAMPUS BID PKG #2
Solicitation number
RFP JCI 260000001841 5
Issued by
Michigan

About this file

This document is Addendum #2 Revised Electrical Drawings - Part 2, related to the North Campus Bid Package #2 for the Jc Is D Torrant Center Additions & Renovations project in Michigan. The addendum provides comprehensive revised electrical drawings for multiple areas (D through M) of the facility, detailing new power distribution, equipment installations, panel modifications, and control systems. The drawings specify installation requirements for HVAC units (RTUs, PTACs, ECH units), lighting fixtures with occupancy sensors and dimming controls, electrical panels, distribution systems, and associated branch circuits. Key electrical installations include new and modified distribution panels (MDP, DP1, DP2, and various sub-panels), door operators, exhaust fans with timeclock controls, data device boxes, and emergency power systems. The drawings establish a 1/8" = 1'-0" scale for floor plans and include detailed specifications for conduit sizing, wire gauging, and circuit requirements across all project areas.

The electrical work encompasses significant panel modifications including replacement of existing breakers with new capacities, relocation of existing circuits, and installation of new circuits for renovated equipment. Load summaries are provided for affected panels, showing removed and added loads with net load changes. The drawings specify control details for exterior lighting using McGraw Edison fixtures with photocell and timeclock controls, occupancy sensors with approved alternates from manufacturers including Acuity, Hubbell, Lutron, and Legrand, and multi-circuit receptacle configurations. An Arc-Flash Study is required as part of the contractor's scope of work, with results to be included in the project closeout package. The existing electrical riser diagram shows the current distribution system configuration with transformer connections and primary switchgear, while the revised riser diagram reflects new panel installations and modifications to accommodate the renovation work.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONV

CONV

RTU-6

208V-1Ø, 17.0A

J

DOOR OPERATOR

(TYP.)

J-15

J-17

CU-5B

208V-1Ø, 15.1MCA

UV-5

120V-1Ø, 6.3MCA

WP

A-8

A-32,34

J

J-15

WP

EXIST. PNL

"M"

EXIST. PNL

"L"

EXIST. PNL

"X"

EXIST. PNL

"K"

EXIST. PNL

"J"

NEW PNL

"MDP"

WP

GFI

A-36

WP

EWC

J-16

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "D"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E30

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A D

PTAC

PTAC

PTAC

PTAC

CONV

PTAC

PTAC

CONV

EF

CONV

CONV

CONV

CONV

ECH-1

208V-1Ø, 3.0KW

RTU-6

208V-1Ø, 17.0A

F-24,26

J

J

CR

CR

DOOR OPERATOR

(TYP.)

J-26,28

J-15

J-15

J-17

J

J-15

J

WP

J-19

WP

EXIST. PNL

"L"

EXIST. PNL

"X"

EXIST. PNL

"K"

EXIST. PNL

"J"

NEW PNL

"MDP"

EXIST. PNL

"G"

EXIST. PNL

"H"

NEW PNL

"DP2"

EXIST. PNL

"F"

WP

GFI

J-12

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "E"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E31

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A E

CONVCONVCONVCONV

CU-3A

208V-1Ø, 13.6A

CU-2A

208V-1Ø, 16.5ACU-1A

208V-1Ø, 16.5A

F-1 120V-1Ø, 11.0A

F-2 120V-1Ø, 11.0A

F-3 120V-1Ø, 8.2A

B2-8,10

B2-2

B1-7,9 B1-8,10

B1-4B1-2

WPWPWP

EXIST. PNL

"B"

EXIST.

PNL

"DP1A"

EXIST. PNL

"B1"

EXIST. PNL

"B2"

EXIST. PNL

"DP1"

3 3

WP

GFI

B1-11

J

W-35

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "F"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E32

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A F

CONV

CONV

CU-5A

208V-1Ø, 17.6A

CU-4A

208V-1Ø, 17.6A

F-5 120V-1Ø, 11.0A

F-4 120V-1Ø, 11.0A

C1-8,10

C1-2

C2-8,10

C2-2

CU-11B

208V-1Ø, 15.1MCA

WP

WP

W-38,40

EXIST. PNL

"C1"

EXIST. PNL

"C2"

EXIST. PNL

"C"

WP

GFI

C2-4

CONV

CONV

CONV

CONV

F-7 120V-1Ø, 11.0A

F-6 120V-1Ø, 11.0A

CU-7A

208V-1Ø, 17.6A

CU-6A

208V-1Ø, 17.6A

D1-2

D2-2 D2-8,10

D1-8,10

WP

WP

EXIST. PNL

"D"

EXIST. PNL

"D1"

EXIST. PNL

"D2"

WP

GFI

WP

GFI

D2-4

D1-4

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "G"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E33

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A G

CUH

CONV CONV CONV CONV CONV CONV

CONVCONV

CONV

RTU-7

208V-3Ø, 43.0A

ECH-4

208V-1Ø, 1.5KW

ECH-3

208V-1Ø, 3.0KW

ECH-1

208V-1Ø, 3.0KW

ECH-2

208V-1Ø, 1.5KW

DP2-20,22,24

F-24,26

F-28,30

E-30,32

E-38,40

WP

EXIST. PNL

"F"

EXIST. PNL

"E"

WP

GFIE-5

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N

PARTIAL FLOOR PLAN - NEW POWER - AREA "H" (ALTERNATE)

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E34

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A H

CU-11B

208V-1Ø, 15.1MCA

CU-10B

208V-1Ø, 15.1MCA

CU-8B

208V-1Ø, 15.1MCA

CU-9B

208V-1Ø, 15.1MCA

UV-8

120V-1Ø, 6.3MCA

UV-9

120V-1Ø, 6.3MCA

UV-10

120V-1Ø, 6.3MCA

UV-11

120V-1Ø, 6.3MCA

120V-1Ø, 6.3MCA

WP

WP

W-22

W-20

W-16

W-18

WP

W-32,34

WP

W-38,40

W-31,33

W-37,39

EXIST. PNL

"W"

EXIST. PNL

"V"

WP

GFI

W-41

WP

GFI

W-42

J

W-35

EWC

W-36

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "I"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E35

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A

I"

CU-11B

208V-1Ø, 15.1MCA

CU-10B

208V-1Ø, 15.1MCA

CU-12B

208V-1Ø, 15.1MCA

UV-10

120V-1Ø, 6.3MCA

UV-11

120V-1Ø, 6.3MCA

UV-13

120V-1Ø, 6.3MCA

UV-12

120V-1Ø, 6.3MCA

WP

W-16

W-18

WP

W-32,34

WP

W-38,40

V-26,28

V-10

V-20

EXIST. PNL

"V"

EXIST. PNL

"RP-AA"

WP

GFI

V-30

WP

GFI

W-42

EWC

W-36

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "J"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E36

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A J

A2-31,33,35

CU-9B

208V-1Ø, 15.1MCA

CU-14B

208V-1Ø, 17.5MCA

CU-13B

208V-1Ø, 15.1MCA

UV-9

120V-1Ø, 6.3MCA

UV-14

120V-1Ø, 6.3MCA

UV-13

120V-1Ø, 6.3MCA

WP

WP

WP

W-22

W-37,39

V-31,33

V-25,27

V-8

V-10

EPO

EXIST. PNL

"V"

EXIST. PNL

"S"

EXIST. PNL

"T"

EXIST.

POOL "PNL

#1"

WP

WP

GFI

V-29

WP

GFI

W-41

J

S-15

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "K"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E37

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A K

RTU-10

208V-3Ø, 31.0A

RTU-8

208V-3Ø, 31.0A

RTU-9

208V-3Ø, 31.0A

RTU-11

208V-3Ø, 31.0A

RTU-12

208V-3Ø, 31.0A

RTU-13

208V-3Ø, 26.0A

A2-31,33,35

A2-32,34,36

A2-37,39,41

A2-38,40,42

A2-43,45,47

A2-44,46,48

CONTROL PANEL (TYP.)

CU-14B

208V-1Ø, 17.5MCA

CU-13B

208V-1Ø, 15.1MCA

CU-12B

208V-1Ø, 15.1MCA

UV-13

120V-1Ø, 6.3MCA

WP

WP

WP

V-31,33

V-25,27

V-26,28

V-10

EXIST. PNL

"A1"

EXIST. PNL

"A2"

WP

WP

WP

WP

WP

WP

WP

GFI

A2-54

WP

GFI

WP

GFI

V-30

V-29

EWC

A2-55

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "L"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E38

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A L

120V-1Ø, 1/15HP

120V-1Ø, 1/15HP

CONTROL PANEL (TYP.)

T-12 T-32 T-34 T-36

CU-14B

208V-1Ø, 17.5MCAUV-14

120V-1Ø, 6.3MCA

CH-2

120V-1Ø, 17.5MCA

R-37

WP

V-8

B-2 120V-1Ø, 12.0A

B-1 120V-1Ø, 12.0A

P-1

208V-3Ø, 1.5HP

P-2

208V-3Ø, 1.5HP

J J

J J

T-14,16,18

T-19,21,23

T-33

T-35

P-3 120V-1Ø, 3.0A

P-4 120V-1Ø, 3.0A

EPO

EXIST. PNL

"S"

EXIST. PNL

"T"

EXIST.

POOL "PNL

#1"

EX

EX

J

S-15

J

S-15

J

S-15J

S-15

J

S-15

ELECTRICAL KEY NOTES

RELOCATED EQUIPMENT. CONTRACTOR SHALL EXTEND ASSOCIATED

BRANCH CIRCUIT CONDUIT AND WIRE TO NEW LOCATION.

CONTRACTOR SHALL PROVIDE AND INSTALL POWER FOR OWNER PROVIDED

SIGNAGE. VERIFY LOCATION WITH OWNER, PRIOR TO ROUGH-IN.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT.

CONTRACTOR SHALL REUSE EXISTING CONDUIT AND WIRE FOR NEW

EQUIPMENT. CONTRACTOR SHALL REMOVE PHASE WIRE FROM PANEL

CONNECTION, FOR USE ON 2-POLE UNIT.

CONTRACTOR SHALL PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR

NEW EQUIPMENT.

EXHAUST FAN SHALL BE CONTROLLED BY NEW TIMECLOCK. CONFIRM TIME

SCHEDULING WITH OWNER.

REMOVE EXISTING PNEUMATIC INTERLOCK WITHIN STARTER, AND CONNECT

TO NEW CONTROL PANEL FOR CONTROLS.

CONTRACTOR SHALL PROVIDE CIRCUIT TO TRANSFORMER, FOR CONTROL

VALVE POWER.

1. CONTRACTOR SHALL PROVIDE AND INSTALL 4-11/16" DEEP SQUARE BOX WITH 1" CND

AND SINGLE GANG PLASTER RING, STUBBED TO NEAREST CIRCULATION CEILING OR

CABLE TRAY FOR ALL DATA DEVICES.

GENERAL ELECTRICAL NOTES

SCALE: 1/8" = 1'-0"

0 1 5 10 20

N PARTIAL FLOOR PLAN - NEW POWER - AREA "M"

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E39

P A R

T

IA

L F

L O

O R

N KEY PLAN

NOT TO SCALE

P L A N

N

E W

P O

W E R

A

R E A M

PANEL

EXISTING

"L" 120/208V 3Ø, 4W

400A, MLO

CUSTOMER OWNED

TR-1

400A/3P

GROUND BUS

EXISTING "MDP"

1600A, 120/208V, 3Ø-4W

800A/3P

1600A/3P

800A/3P

#6BUILDING

STEEL

COLD WATER

PIPING

GROUND

ROD #6

CONCRETE

ENCASED

EXEX

1000A BUS RATING 1200A BUS RATING

225A/3P

PANEL

EXISTING

"M" 120/208V 3Ø, 4W

225A, MLO

200A/3P

PANEL

EXISTING

"J" 120/208V 3Ø, 4W

225A, MLO

200A/3P

SPARE

FORMER PANEL "L"

SHORT NOTED ON BREAKER

200A/3P

PANEL

EXISTING

"K" 120/208V 3Ø, 4W

225A, MLO

SPACE

150A/3P

PANEL

EXISTING

"A" 120/208V 3Ø, 4W

225A, MLO

100A/3P

SPARE

FORMER UV CORP 23

SPACE

SHORT NOTED ON BREAKER

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

EXISTING CABINET

100A/3P

GROUND BUS

EXISTING "DP-3"

600A, 120/208V, 3Ø-4W

100A/3P

600A/3P

1000A BUS RATING

CUSTOMER OWNED

TR-2

EXISTING PRIMARY

SWITCHGEAREXISTING PRIMARY

METERING CABINET

FROM UTILITY COMPANY

PANEL

EXISTING

"R" 120/208V 3Ø, 4W

225A, MCB

PANEL

EXISTING

"Q" 120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"S" 120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"T" 120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"POOL"

120/208V 3Ø, 4W

100A, MLO

PANEL

EXISTING

"V" 120/208V 3Ø, 4W

225A, MCB

PANEL

EXISTING

"A1" 120/208V 3Ø, 4W

300A, MCB

PANEL

EXISTING

"A2" 120/208V 3Ø, 4W

300A, MLO

PANEL

EXISTING

"RP-AA"

120/208V 3Ø, 4W

225A, MCB

PANEL

EXISTING

"W" 120/208V 3Ø, 4W

225A, MCB

PANEL

EXISTING

"HOME LAB"

120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"C" 120/208V 3Ø, 4W

225A, MLO

100A/3P

3PH 3W

NEMA 3R

FUSED

CAFETERIA

RTU

PANEL

EXISTING

"B" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"D" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"Z" 120/208V 1Ø, 3W

100A, MCB

M

PANEL

EXISTING

"C1" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"C2" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"D1" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"D2" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"E" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"F" 120/208V 3Ø, 4W

225A, MLO

300A/3P

GROUND BUS

EXISTING "DP1"

800A, 120/208V, 3Ø-4W

800A BUS RATING

SPACE

SPACE

100A/2P

100A/3P

100A/3P

225A/3P

100A/3P

225A/3P

225A/3P

SPACE

225A/3P

225A/3P

PANEL

EXISTING

"G" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"H" 120/208V 3Ø, 4W

225A, MLO

150A/3P

GROUND BUS

EXISTING "DP2"

800A, 120/208V, 3Ø-4W

800A BUS RATING

150A/3P

200A/3P

200A/3P

225A/3P

225A/3P

100A/3P

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPARE

FORMER UVSPARESPARE

PANEL

EXISTING

"X" 120/208V 1Ø, 3W

100A, MCB

PANEL

EXISTING

"B1" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"B2" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"N" 120/208V 3Ø, 4W

125A, MCB

PANEL

EXISTING

"P" 120/208V 3Ø, 4W

225A, MLO

100A/3P

100A/3P

125A/3P

100A/3P

225A/3P

225A/3P

SPARE

DEFECTIVE BREAKER

100A/3P

3PH 3W

NEMA 3R

FUSED

RTU

SPARE

#6BUILDING

STEEL

COLD WATER

PIPING

GROUND

ROD #6

CONCRETE

ENCASED

EXEX

EXISTING EQUIPMENT TO REMAIN.

DISCONNECT & REMOVE EXISTING EQUIPMENT. REMOVE ASSOCIATED

CONDUIT & WIRE.

DISCONNECT & REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT &

WIRE TO REMAIN FOR NEW EQUIPMENT.

DISCONNECT & REMOVE EXISTING EQUIPMENT. MODIFY ASSOCIATED

FEEDER CONDUIT & WIRE FOR NEW FEED SOURCE.

DEMOLITION NOTES

1 1

1 1

4 4

4 2 4 4

4 4 4 4

4 4 4 4

1 1 1 1 1 1 1 1 1 1

1 1 1 1 1 1

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E X

IS

T

IN

G E L E C

T R

IC

A L R

IS

E R

D

IA

G R

A

E40

PANEL

EXISTING

"L" 120/208V 3Ø, 4W

400A, MLO

CUSTOMER OWNED

TR-1

400A/3P

GROUND BUS

NEW "MDP"

1600A, 120/208V, 3Ø-4W

800A/3P

1600A/3P

800A/3P

#6BUILDING

STEEL

COLD WATER

PIPING

GROUND

ROD #6

CONCRETE

ENCASED

225A/3P

PANEL

EXISTING

"M" 120/208V 3Ø, 4W

225A, MLO

200A/3P

PANEL

EXISTING

"J" 120/208V 3Ø, 4W

225A, MLO

200A/3P

200A/3P

PANEL

EXISTING

"K" 120/208V 3Ø, 4W

225A, MLO

150A/3P

PANEL

EXISTING

"A" 120/208V 3Ø, 4W

225A, MLO

100A/3P

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

EXISTING CABINET

100A/3P

GROUND BUS

EXISTING "DP-3"

600A, 120/208V, 3Ø-4W

100A/3P

600A/3P

1000A BUS RATING

CUSTOMER OWNED

TR-2

EXISTING PRIMARY

SWITCHGEAREXISTING PRIMARY

METERING CABINET

FROM UTILITY COMPANY

PANEL

NEW

"R" 120/208V 3Ø, 4W

225A, MCB

PANEL

NEW

"Q" 120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"S" 120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"T" 120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"POOL"

120/208V 3Ø, 4W

100A, MLO

PANEL

EXISTING

"E" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"F" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"G" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"H" 120/208V 3Ø, 4W

225A, MLO

150A/3P

GROUND BUS

NEW "DP2"

800A, 120/208V, 3Ø-4W

800A BUS RATING

150A/3P

200A/3P

200A/3P

225A/3P

225A/3P

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

PANEL

EXISTING

"X" 120/208V 1Ø, 3W

100A, MCB

PANEL

EXISTING

"N" 120/208V 3Ø, 4W

125A, MCB

PANEL

NEW

"P" 120/208V 3Ø, 4W

225A, MLO

100A/3P

100A/3P

125A/3P

100A/3P

225A/3P

225A/3P

#6BUILDING

STEEL

COLD WATER

PIPING

GROUND

ROD #6

CONCRETE

ENCASED

#3/0#3/0

ELECTRICAL KEY NOTES

MAIN BREAKER SHALL HAVE INTEGRAL ERMS.

CONTRACTOR SHALL PROVIDE AND INSTALL OWNER PROVIDED DIGITAL

METER.

CONNECT EXISTING EQUIPMENT TO NEW DISTRIBUTION PANEL.

#4/0#4/0

SPARE

DEFECTIVE BREAKER SPARE

1. CONTRACTOR'S SCOPE OF WORK SHALL INCLUDE PROVIDING ARC-FLASH STUDY, AS

REQUIRED BY NEC. AVAILABLE FAULT CURRENT RATINGS SHALL BE LISTED ON ALL

PANELS LOCATED THROUGHOUT THE BUILDING. STUDY SHALL BE TURNED OVER TO

OWNER, WITHIN PROJECT CLOSEOUT PACKAGE.

GENERAL ELECTRICAL NOTES

1600A BUS RATING

GFI

100A/3P

TVSS

80A/3P

TVSS

80A/3P

TVSS

3 3 3 3 3 3

(3) #3

(1) #8 GND

1-1/4" CND

(3) #3

(1) #8 GND

1-1/4" CND

(3) #3

(1) #8 GND

1-1/4" CND

(4) #4/0

(1) #4 GND

2-1/2" CND

(4) #4/0

(1) #4 GND

2-1/2" CND

(4) #1

(1) #8 GND

1-1/2" CND

(5) SETS OF

(4) #400KCMIL

(1) #4/0 GND

3-1/2" CND

PANEL

EXISTING

"V" 120/208V 3Ø, 4W

225A, MCB

PANEL

EXISTING

"A1" 120/208V 3Ø, 4W

300A, MCB

PANEL

EXISTING

"A2" 120/208V 3Ø, 4W

300A, MLO

PANEL

EXISTING

"RP-AA"

120/208V 3Ø, 4W

225A, MCB

PANEL

EXISTING

"W" 120/208V 3Ø, 4W

225A, MCB

PANEL

EXISTING

"HOME LAB"

120/208V 3Ø, 4W

100A, MCB

PANEL

EXISTING

"C" 120/208V 3Ø, 4W

225A, MLO

100A/3P

3PH 3W

NEMA 3R

FUSED

CAFETERIA

RTU

PANEL

EXISTING

"B" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"D" 120/208V 3Ø, 4W

225A, MLO

PANEL

EXISTING

"Z" 120/208V 1Ø, 3W

100A, MCB

PANEL

EXISTING

"C1" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"C2" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"D1" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"D2" 120/208V 3Ø, 4W

60A, MCB

300A/3P

GROUND BUS

EXISTING "DP1"

800A, 120/208V, 3Ø-4W

800A BUS RATING

SPACE

SPACE

100A/2P

100A/3P

100A/3P

225A/3P

100A/3P

225A/3P

225A/3P

225A/3P

225A/3P

PANEL

EXISTING

"B1" 120/208V 3Ø, 4W

60A, MCB

PANEL

EXISTING

"B2" 120/208V 3Ø, 4W

60A, MCB

80A/3P

TVSS

(3) #3

(1) #8 GND

1-1/4" CND

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

R E V

IS

E D

E L E C

T R

IC

A L R

IS

E R

D

IA

G R

A

E41

PHOTO CONTROL,

INTERMATIC

NOTE:

-MOUNT PHOTO EYE FACING NORTH ON NORTH SIDE OF BUILDING.

WITH CLOCK MOTOR, 7-DAY

TIME SWITCH CONTROL

INTERMATIC #T7402BC

CONTROL AND 40 AMP 4 POLE CONTACTS,

N

AREA LIGHTS

2 EXTERIOR LIGHTING CONTROL DETAIL

SCALE: N.T.S.

BUILDING LIGHTSLINE

NEUTRAL

PLAN

ELECTRICAL

COMPOSITE GASKETED BOX,

QUAZITE OR EQUAL

HEAVY DUTY, SKID-RESISTANT COVER,

BOLT-DOWN TYPE, TAMPER RESISTANT

HARDWARE

3" MIN. SAND OR

GRANULAR BACKFILL

1 ELECTRICAL HANDHOLE DETAIL

SCALE:NTS

LIFTING EYE

FINISHED GRADE

UNDISTURBED EARTH

CONDUIT

SECTION

24"

13"

OPEN BOTTOM

BOX EXTENSION

DIVIDER

24" DIAMETER

SONOTUBE

6 LIGHT POLE DETAIL

SCALE: N.T.S.

24"60"

36"

CURB & ROADWAY

SEAL TIGHT HOLE

LIGHT POLE:

ULS POLES #RPSQ-20-5-11-AB-MODBASE/MODAB-DD1-XHH

(20' POLE WITH 2 HH 1-3/8" HOLE) WITH ANCHOR BOLTS

· STEEL POLE: 20' POLE x 5" SQ x 11 GAUGE

· MODBASE/MODAB: 10.5"-11.5" BOLT CIRCLE WITH 3/4"

O.D. ANCHOR BOLTS

· XHH: 15' ABOVE BASE AT 90°

HAND HOLE ON SIDE

OPPOSITE OF ROADWAY

216"

48"

12"

18"

24" DIAMETER GRAY

"CEMETUBE" HDPE WITH BELLED

END

1.75'

(TYP. U.N.O.)

1" CONDUIT OUT OF BOX

INTO POLE BASE

2" CONDUIT IN

12"x12" QUAZITE BOX

(COMMUNICATION)

2" CONDUIT

2" CONDUIT

LIGHT POLE

1.75'

(TYP. U.N.O.)

CURB & GUTTER

PLAN VIEW

24" DIAMETER BASE

1" CONDUIT

FOR COMMUNICATIONS

1" CONDUIT

FOR ELECTRIC

1" SEAL TIGHT WITH 90°

FITTING AT TOP

FOR COMMUNICATIONS

HAND HOLE: QUAZITE #PC1212BA12, 12"x12", 12" DEEP OPEN BOTTOM. PROVIDE

#PC1212CA0012 "COMMUNICATIONS" COVER. INSTALL ENCLOSURE ON 6" GRAVEL BASE.

INSTALL 1" PVC CONDUIT FROM HAND HOLE THROUGH CONCRETE POLE BASE AND

INTO POLE. COMMUNICATION CONDUIT SHALL EXTEND UNINTERRUPTED FROM PVC

CONDUIT TO 90° FITTING AT 17' ABOVE POLE BASE BY MEANS OF SEAL TIGHT FLEXIBLE

CONDUIT. ELECTRICIAN SHALL DRILL HOLE IN 11 GAUGE STEEL FOR FITTING. PAINT

METAL TO PREVENT RUSTING.

HAND HOLE: QUAZITE #PC1212BA12, 12"x12", 12" DEEP OPEN

BOTTOM. PROVIDE #PC1212CA0017 "ELECTRIC" COVER.

INSTALL ENCLOSURE ON 6" GRAVEL BASE. INSTALL POWER IN

1" PVC CONDUIT FROM HAND HOLE THROUGH CONCRETE POLE

BASE AND INTO POLE.

FIXTURE(S) PER SCHEDULE

BASE COVER

GROUND LUG

#6 TW GREEN GRD. WIRE

GROUND ROD/CADWELD

8'-0" x 5/8" GROUND ROD.

PROVIDE IN-LINE WATERPROOF FUSES AS

RECOMMENDED BY LUMINAR MANUFACTURER.

INSTALL NEAR HANDHOLE.

ANCHOR BOLTS FURNISHED

BY MANUFACTURER

RIGID STEEL CONDUIT

STUB-OUT MIN. DEPTH PER

N.E.C. OR SPECS.

PROVIDE DOUBLE NUTS FOR LEVELING OF UNIT (ONE ABOVE,

ONE BELOW BASE FLANGE) GROUT BETWEEN BASE AND

FLANGE. SLOPE TOP TO PREVENT WATER ACCUMULATION.

2'-0"

5' -0

3'

-0

'-0

4 AREA LIGHT - POLE BASE DETAIL

SCALE: N.T.S.

PROVIDE IN-LINE WATER

BY MANUFACTURER

CONNECT GRD. TO POLE

BASE WITH BURNDY #GB4C

HANDHOLE

SIZE AS RECOMMENDED

PROOF FUSES IN CIRCUIT

POLE MANUFACTURER

REBAR (TYP.)

BASE BY E.C.

GRD. ROD CLAMP

8'-0" x 5/8" DIA.

#6 TW GREEN GRD. WIRE

RIGID CONDUIT

GROUND ROD

COPPER CLAD

BASE COVER

LEVELING OF UNIT (ONE ABV. & ONE

TO PREVENT WATER ACCUMULATION.

ANCHOR BOLTS FURNISHED BY

ANCHOR BOLTS TO PROJECT ABOVE TOP

OF BASE. PROVIDE DOUBLE NUTS FOR

BELOW BASE FLANGE). GROUT BETWEEN

CONCRETE BASE & FLANGE. SLOPE TOP

CONDUIT & WIRE AS SPECIFIED

2'-0" 3'

-0

'-0

INSTALL NEAR HANDHOLE

5 PEDESTRIAN LIGHT - POLE BASE DETAIL

SCALE: N.T.S.

CONCRETE SLAB

3" MIN. BELOW SLAB

OR AS REQUIRED FOR

SWEEPS

SCHEDULE 40 PVC CONDUIT

REFER TO SPECS FOR CONDUIT REQUIREMENTS

PVC TO RIGID ADAPTOR

TO TRANSITION FROM UNDERFLOOR

PROVIDE RGC WITH SWEEP

PVC CONDUIT.

COMPACTED

UNDERFLOOR CONDUITS IN

SLAB ON GRADE INSTALLATION

SCALE: N.T.S.

FIXTURE

MOUNTING

HEIGHT

LIGHT ENGINEDESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.

LIGHTING FIXTURE SCHEDULE

T5W

2T4W

T4W

T4FT

T2-HSS

T2

SL2

DIMMING INFO

1. ALTERNATE LIGHTING NOT ALLOWED FOR THE FIXTURES LISTED.

FIXTURE SCHEDULE NOTES

GALN-SA2C-740-U-T2-BZMCGRAW EDISON AS SHOWN ON

DRAWINGS

EXTERIOR SITE LIGHT WITH 2 LIGHT SQUARES, TYPE 2 OPTICS, INTEGRAL

PHOTOCELL, AND BRONZE FINISH. 0-10V

14219 LUMENS

108W, 4000K

LED

GPC-SA1C-740-U-SL2-BZMCGRAW EDISON AS SHOWN ON

DRAWINGS

EXTERIOR SITE LIGHT WITH 1 LIGHT SQUARE, TYPE 2 SPILL-CONTROL OPTICS,

INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V

7399 LUMENS

59W, 4000K

LED

GALN-SA2C-740-U-T2-BZ-HSSMCGRAW EDISON AS SHOWN ON

DRAWINGS

EXTERIOR SITE LIGHT WITH 2 LIGHT SQUARES, TYPE 2 OPTICS, HOUSE SIDE

SHIELD, INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V

14219 LUMENS

108W, 4000K

LED

GALN-SA6C-740-U-T4FT-BZMCGRAW EDISON AS SHOWN ON

DRAWINGS

EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 4 FORWARD OPTICS,

INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V

42558 LUMENS

321W, 4000K

LED

GALN-SA6C-740-U-5WQ-BZMCGRAW EDISON AS SHOWN ON

DRAWINGS

EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 5 WIDE OPTICS, INTEGRAL

PHOTOCELL, AND BRONZE FINISH. 0-10V

44560 LUMENS

321W, 4000K

LED

GALN-SA4C-740-U-T4W-BZMCGRAW EDISON AS SHOWN ON

DRAWINGS

EXTERIOR SITE LIGHT WITH 4 LIGHT SQUARES, TYPE 4 WIDE OPTICS, INTEGRAL

PHOTOCELL, AND BRONZE FINISH. 0-10V

28333 LUMENS

213W, 4000K

LED

(2): GALN-SA6C-740-U-T4FT-BZMCGRAW EDISON AS SHOWN ON

DRAWINGS

DOUBLE HEAD EXTERIOR SITE LIGHT WITH 6 LIGHT SQUARES, TYPE 4 FORWARD

OPTICS, INTEGRAL PHOTOCELL, AND BRONZE FINISH. 0-10V

85116 LUMENS

642W, 4000K

LED

-PROVIDE ADEQUATE COMPONENTS FOR CIRCUITING SHOWN ON SITE PLAN

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E42

E L E C

T R

IC

A L

S

IT

E D

E T A

IL

S

QUANTITY AS SHOWN ON PLANS.

LIGHTING LOAD

(TYPICAL)

POWER PACK

(TYP.)

CAT 5e CABLE (TYP.)

OCCUPANCY/PHOTOCELL

SENSORS (TYPICAL)

TOP CONTROL

BOTTOM CONTROL

S

ON/OFF

DOS

TOP CONTROL

BOTTOM CONTROL

120V IN0

10V

POWER CIRCUIT

QUANTITY AS SHOWN ON PLANS.

LIGHTING LOAD

(TYPICAL)

POWER PACK

(TYP.)

CAT 5e CABLE (TYP.)

OCCUPANCY/PHOTOCELL

SENSORS (TYPICAL)

TOP CONTROLED

BOTTOM NOT

CONTROLED

D

POWER PACK

(TYP.) TOP CONTROLED

BOTTOM NOT

CONTROLED

CAT 5e

CABLE

(TYP.)

POWER PACK

(TYP.) TOP CONTROLED

BOTTOM NOT

CONTROLED

POWER PACK

(TYP.) TOP CONTROLED

BOTTOM NOT

CONTROLED

SINGLE VOLTAGE, MULTI-CIRCUIT RECEPTACLE AND

LIGHTING CONTROL

SCALE: N.T.S.

POWER CIRCUIT

POWER CIRCUIT

POWER CIRCUIT

277V POWER CIRCUIT

QUANTITY AS SHOWN ON PLANS.

LIGHTING LOAD

(TYPICAL)

POWER PACK

(TYP.)

CAT 5e CABLE (TYP.)

OCCUPANCY/PHOTOCELL

SENSORS (TYPICAL)

D

POWER PACK

(TYP.) TOP CONTROLED

BOTTOM NOT

CONTROLED

CAT 5e

CABLE

(TYP.)

POWER PACK

(TYP.) TOP CONTROLED

BOTTOM NOT

CONTROLED

POWER PACK

(TYP.) TOP CONTROLED

BOTTOM NOT

CONTROLED

DUAL VOLTAGE, MULTI-CIRCUIT RECEPTACLE AND

LIGHTING CONTROL

SCALE: N.T.S.

120V POWER CIRCUIT

120V POWER CIRCUIT

120V POWER CIRCUIT

CEILING OCC SENSOR RECEPTACLE AND LIGHTING

CONTROL

SCALE: N.T.S.

WALL OCC SENSOR RECEPTACLE AND LIGHTING

CONTROL

SCALE: N.T.S.

POWER CIRCUIT

QUANTITY AS SHOWN ON PLANS.

LIGHTING LOAD

(TYPICAL)

POWER PACK

(TYP.)

CAT 5e CABLE (TYP.)

S K

TYPICAL DIMMING LAYOUTS

ON/OFF

S D

OCCUPANCY/PHOTOCELL

SENSORS (TYPICAL)

1.

2.

3.

4.

SEQUENCE OF OPERATION:

ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN

ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.

MANUAL ON, LOCAL DIMMING AND ON/OFF OVERRIDE,

AUTOMATIC OFF.

PROVIDE SINGLE (1) COVERPLATE. SIZE BASED ON

SWITCHES REQUIRED.

SEE PLANS FOR SPECIFIC QUANTITY AND LOCATION OF

SWITCH TYPES.

S K

TURN TO RIGHT

FOR ON/UP

LEFT FOR

OFF/DOWN

POWER CIRCUIT

QUANTITY AS SHOWN ON PLANS.

LIGHTING LOAD

(TYPICAL)

POWER PACK

(TYP.)

CAT 5e CABLE (TYP.)

S D

S D

TYPICAL DIMMING LAYOUTS

ON/OFF

S D

POWER PACK

(TYP.)

LIGHTING LOAD

(TYPICAL)

OCCUPANCY/PHOTOCELL

SENSORS (TYPICAL)

1.

2.

3.

4.

SEQUENCE OF OPERATION:

ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN

ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.

MANUAL ON, LOCAL DIMMING AND ON/OFF OVERRIDE,

AUTOMATIC OFF.

PROVIDE SINGLE (1) COVERPLATE. SIZE BASED ON

SWITCHES REQUIRED.

SEE PLANS FOR SPECIFIC QUANTITY AND LOCATION OF

SWITCH TYPES.

ON/OFF

S

ON/OFF

DOS

1.

BASIS OF DESIGN:

PROVIDE ACUITY #WSX-PDT-D-SA

1.

2.

SEQUENCE OF OPERATION:

ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN

ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.

MANUAL ON, LOCAL DIMMING AND ON/OFF OVERRIDE,

AUTOMATIC OFF.

APPROVED ALTERNATES:

S

1.

BASIS OF DESIGN:

PROVIDE ACUITY #WSX-PDT

OS

1.

2.

3.

SEQUENCE OF OPERATION:

ALL CONTROLS TO BE COMPLIANT WITH MICHIGAN

ENERGY CODE, BASED UPON ASHRAE 90.1, 2013.

MANUAL ON, ON/OFF OVERRIDE, AUTOMATIC OFF.

TOILETS AND STORAGE CLOSETS SHALL BE

AUTOMATIC ON/OFF.

APPROVED ALTERNATES:

1.

2.

3.

4.

APPROVED ALTERNATES:

HUBBELL

LUTRON

LEGRAND

LEVITON

S

ON/OFF

S

ON

OFF

STANDARD

SWITCH

D

DIMMER

SWITCH

ON/OFF ON/OFF

S D S D

DUAL DIMMER

SWITCH

ALL ON ON/OFF

S D S D

TRIPLE DIMMER

SWITCH

S D

ON/OFF ON/OFF

ALL OFF

1.

2.

3.

BASIS OF DESIGN:

ACUITY NLIGHT.

PROVIDE WIRED OR WIRELESS VERSIONS

BASED ON SPACE CONTROL SYSTEM.

PROVIDE WITH SINGLE COVERPLATE BASED

UPON SWITCH CONFIGURATION AND

EXISTING JUNCTION BOX SIZE.

D

CAT 5e

CABLE

(TYP.)

LIGHTING LOAD

(TYPICAL)

5 WALL OCC SENSOR DETAIL

SCALE: N.T.S.

6 DIMMABLE WALL OCC SENSOR DETAIL

SCALE: N.T.S.

1.

2.

3.

4.

HUBBELL

LUTRON

LEGRAND

LEVITON

1.

2.

3.

4.

HUBBELL

LUTRON

LEGRAND

LEVITON

1.

BASIS OF DESIGN:

PROVIDE ACUITY #WSX-PDT

APPROVED ALTERNATES:

1.

2.

3.

4.

HUBBELL

LUTRON

LEGRAND

LEVITON

1.

BASIS OF DESIGN:

PROVIDE ACUITY #WSX-PDT

APPROVED ALTERNATES:

1.

2.

3.

4.

HUBBELL

LUTRON

LEGRAND

LEVITON

7 SINGLE ZONE CEILING MOUNTED OCC SENSOR DETAIL

SCALE: N.T.S.

9 TYPICAL LIGHTING CONTROL LAYOUTS

SCALE: N.T.S.

8 DUAL ZONE CEILING MOUNTED OCC SENSOR DETAIL

SCALE: N.T.S.

POWER CIRCUIT

ROOM CONTROLLER POWER

PACKS (TYP. OF ALL)

ROOM CONTROLLER POWER

PACKS (TYP. OF ALL)

ROOM CONTROLLER POWER

PACKS (TYP. OF ALL)

ROOM CONTROLLER STYLE

CONTROLS (TYP. OF ALL)

ROOM CONTROLLER POWER

PACKS (TYP. OF ALL)

ROOM CONTROLLER POWER

PACKS (TYP. OF ALL)

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E44

L

IG

H T

IN

G C

O N

T R

O L

D E T A

IL

S

ELECTRICAL KEY NOTES

CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH NEW 50A 3P

BREAKER TO SERVE NEW ROOFTOP UNIT.

CONTRACTOR SHALL REPLACE EXISTING 50A 3P BREAKER WITH NEW 40A 3P

BREAKER TO SERVE NEW ROOFTOP UNIT.

LOAD SUMMARY

REMOVED LOAD: 14411W

ADDED LOAD: 6778W

NET LOAD: (7633)W

LOAD SUMMARY

REMOVED LOAD: 62623W

ADDED LOAD: 63342W

NET LOAD: 719W

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E45

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

A

CONTRACTOR SHALL REPLACE EXISTING 20A 1P BREAKER WITH NEW 15A 1P

BREAKER TO SERVE NEW FURNACE.

CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 25A

2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING

UNIT.

2 2

LOAD SUMMARY

REMOVED LOAD: 21133W

ADDED LOAD: 7604W

NET LOAD: (135293)W

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E46

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

BREAKER TO SERVE NEW FURNACE.

CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P

BREAKER TO SERVE NEW CONDENSING UNIT.

LOAD SUMMARY

REMOVED LOAD: 10566W

ADDED LOAD: 3052W

NET LOAD: (7514)W

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E47

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

BREAKER TO SERVE NEW FURNACE.

LOAD SUMMARY

REMOVED LOAD: 6912W

ADDED LOAD: 3986W

NET LOAD: (2926)W

LOAD SUMMARY

REMOVED LOAD: 6912W

ADDED LOAD: 3986W

NET LOAD: (2926)W

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E48

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

BREAKER TO SERVE NEW FURNACE.

LOAD SUMMARY

REMOVED LOAD: 6912W

ADDED LOAD: 3986W

NET LOAD: (2926)W

LOAD SUMMARY

REMOVED LOAD: 6912W

ADDED LOAD: 3986W

NET LOAD: (2926)W

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E49

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

CONTRACTOR SHALL RELOCATE EXISTING BRANCH CIRCUIT TO NEW PANEL.

FORMER BREAKER LISTED ON EXISTING PANEL SCHEDULE. EXTEND

ASSOCIATED CONDUIT AND WIRE AS NEEDED.

CONTRACTOR SHALL INSTALL NEW 50A 3P BREAKER TO SERVE NEW

ROOFTOP UNIT.

CONTRACTOR SHALL INSTALL NEW 80A 3P BREAKER TO SERVE NEW TVSS.

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E50

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

CONTRACTOR SHALL RELOCATE EXISTING BRANCH CIRCUIT TO NEW PANEL.

FORMER BREAKER LISTED ON EXISTING PANEL SCHEDULE. EXTEND

ASSOCIATED CONDUIT AND WIRE AS NEEDED.

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E51

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P

BREAKER TO SERVE NEW ELECTRIC CABINET UNIT HEATER.

CONTRACTOR SHALL INSTALL WITH NEW 20A 2P BREAKER TO SERVE NEW

ELECTRIC CABINET UNIT HEATER.

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E52

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

CONTRACTOR TO VERIFY EXISTING BREAKER SIZE. SERVE NEW ROOFTOP

UNIT WITH 25A 2P BREAKER.

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E53

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

CONTRACTOR SHALL REPLACE EXISTING 30A 2P BREAKER WITH NEW 20A 2P

BREAKER TO SERVE NEW MINI-SPLIT HEAT PUMP.

CONTRACTOR SHALL REPLACE EXISTING 20A 1P BREAKER WITH NEW 15A 1P

BREAKER TO SERVE NEW UNIT VENTILATOR.

CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 25A

2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING

UNIT..

4 CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 30A

2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING

UNIT.

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E55

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

CONTRACTOR SHALL RELOCATE EXISTING BRANCH CIRCUIT FROM EXISTING

PANEL Q TO NEW PANEL R. FORMER BREAKER LISTED ON EXISTING PANEL

SCHEDULE. EXTEND ASSOCIATED CONDUIT AND WIRE AS NEEDED.

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E56

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

BREAKER TO SERVE NEW UNIT VENTILATOR.

CONTRACTOR SHALL REPLACE EXISTING 30A 3P BREAKER WITH (1) NEW 25A

2P BREAKER AND (1) NEW 20A 1P BREAKER TO SERVE NEW CONDENSING

UNIT.

LOAD SUMMARY

REMOVED LOAD: 23057W

ADDED LOAD: 9357W

NET LOAD: (13700)W

LOAD SUMMARY

REMOVED LOAD: 21616W

ADDED LOAD: 12874W

NET LOAD: (8742)W

CONTRACTOR SHALL REPLACE EXISTING 20A 3P BREAKER WITH NEW 15A 3P

BREAKER TO SERVE NEW PUMP.

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E57

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC

J C

IS

D

T O

R R

A N

T C

E N

T E R

A D

D

IT

IO

N

S

R E N

O V A T

IO

N S

M A

T R

I X

E58

P A N

E L S

C H

E D

U L E S

E L E C

T R

IC