This Addendum 2 document provides equipment schedules and technical drawings for HVAC construction and maintenance services at two North Carolina National Guard facilities in McLeansville: the Regional Readiness Center and the Field Maintenance Shop located at 4250 Camp Burton Road. The addendum specifies detailed equipment schedules for Variable Refrigerant Flow (VRF) systems, rooftop units (RTUs), dedicated outdoor air systems (DOAS), ductless split units, air distribution devices, fans, louvers, and accessory equipment. Equipment includes 8 VRF heat recovery units with capacities ranging from 65.3 to 250.3 MBH cooling, multiple branch controller boxes, over 100 indoor units (cassette and concealed ducted configurations), 7 rooftop units with capacities ranging from 54.9 to 403.7 MBH cooling, and numerous fans, louvers, and air curtains manufactured primarily by Daikin, Greenheck, and other specified suppliers. The document establishes technical requirements for equipment testing per AHRI 1230, refrigerant charge calculations, condensate systems, BACnet interfaces, and control systems integration. Bid Opening Date is May 12, 2026, at 2:00 PM, with a mandatory site visit required on April 30, 2026, at 10:00 AM Eastern Time and written questions due by May 4, 2026, at 2:00 PM.
The procurement specification requires vendors to provide quarterly preventive maintenance services for cooling, electrical, mechanical, filtration, drainage, and heating systems according to seasonal checklists; submit pricing for quarterly and annual maintenance at both locations; provide hourly rates for non-emergency business hours repairs and emergency after-hours services; quote refrigerant charges; and offer parts cost discounts for a three-year period. The contract term is one year from the effective date with options to renew for up to two additional one-year periods with thirty days' written notice before each expiration. Vendors must be registered with the North Carolina Secretary of State and possess NC vendor registration through the Electronic Vendor Portal, complete required certifications including financial condition and lobbying activity certifications, designate a contract manager, provide one-year workmanship warranties, and complete repairs within thirty days of purchase order issuance unless alternative arrangements are made. The procurement specialist is Debbie Hill at Debbie.hill@ncdps.gov or 984-255-7172. No budget range, incumbent vendor information, or award value is specified in the solicitation documents.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Purchasing and Logistics
IMPORTANT BID ADDENDUM
May 7, 2026
BID NUMBER: 19-IFB-2168066896-HDE COMMODITY: 721512 Heating and Cooling and air conditioning HVAC Construction and Maintenance Services
ADDENDUM Number: 2 USING AGENCY-NCDPS PURCHASER: Debbie Hill BID OPENING DATE: May 12, 2026 @2:00 PM
INSTRUCTIONS:
1. Equipment Schedule and Drawings Attached
T 919 781 8582
F 919 781 3979
4600 Lake Boone Trail Suite 205 Raleigh, NC 27607 info@smithsinnett.com
PDC #18065
DRAWN BY:
CHECKED BY:
LEED REGISTERED
PURSUING CERTIFIED
Th is d ra w in g an d th e de si gn s ho w n is th e pr op er ty o f S m ith S in ne tt Ar ch ite ct ur e, P.
A.
t he re pr od uc tio n or u se o f t hi s pr op er ty w ith ou t t he w rit te n co ns en t o f t he
Ar ch ite ct is p ro hi bi te d.
A ny in fri ng em en t of th e ow ne rs hi p rig ht s w ill be s ub je ct to le ga l a ct io n.
A ll co pi es o f t hi s dr aw in g m us t b e re tu rn ed to th e
Ar ch ite ct a t t co m pl et io n of th e co nt ra ct
Sm ith
S in ne tt
Ar ch ite ct ur e, P .A
. 2
TH
IS
D R
AW
IN
G
IS
F O
R M
A
TT
ED
T
O
BE
P
R
IN
TE
D
O N
A
0" X
2"
S H
E
ET
DESCRIPTIONDATEID
S C
O
-1
-0
A
#1000138258
C U s e rs
\d lo w ry
\D o c u m e n ts \1
N
C N
G
M c L e a n s v ill e
F M
S
C e n tr a l_
M o d e l_ d lo w ry
P D
C B
IM
.r v t
8/
/2
8:
:3
A
M
F O
R C
O N
S T
R U
C T
IO
N
M7-01
SCHEDULES
2020057 01 SEPT 2023
PDC
SWC
N O
R T
H C
A R
O L
IN
A
N A
T
IO
N A
L G
U A
R D
M cL
E A
N S
V
IL
L E
F
IE
L D
M A
IN
T
E N
A N
C E
S H
O P
C A
M P
B U
R T
O N
R D
M c L
E A
N S
V
IL
L E
N
C
VRF HEAT RECOVERY UNIT SCHEDULE
TAG
TOTAL
COOLING
(MBH)
HEATING
CAPACITY
(MBH)
COMPRESSOR/
RLA
FANS/
FLA
ELECTRICAL DATA
MANUFACTURER MODEL NUMBER WEIGHT REMARKSMODULE 1 MODULE 2
IEER EER SCHE
REF
CHARGE
(LBS)
VOLTAGE/PH
MCA MOCP MCA MOCP
VRF-1 114.0 129.0 2/15.5,15.7 2/2.3 36.5 45 - - 25.5 13.2 26.0 25.8 208/3 DAIKIN REYQ120AATJA 713
VRF-2 92.0 103.0 2/13.5,13.6 2/2.3 36.1 40 - - 27.8 14.6 26.4 25.8 208/3 DAIKIN REYQ96AATJA 710
VRF BRANCH CONTROLLER BOX SCHEDULE
MARK
MODEL
NO. OF
PORTS
MAX. CAP.
PER PORT
(MBH) MCA/MFS VOLT/PH
WEIGHT
(lbs)
REMARKS
MCU-1-01 BSF6Q54TVJ 6 54 1/15 208/1 73
MCU-1-02 BSF4Q54TVJ 4 54 1/15 208/1 50
MCU-1-03 BSF4Q54TVJ 4 54 1/15 208/1 50
MCU-2-01 BSF4Q54TVJ 4 54 1/15 208/1 50
MCU-2-02 BSF4Q54TVJ 4 54 1/15 208/1 50
MCU-2-03 BSF4Q54TVJ 4 54 1/15 208/1 50
MCU-2-04 BSF4Q54TVJ 4 54 1/15 208/1 50
VRF INDOOR UNIT SCHEDULE
TAG MANUFACTURER MODEL STYLE CFM
ESP
IN. WG
TOTAL
COOLING
(MBH)
SENSIBLE
(MBH)
ACTUAL
HEATING
(MBH)
MCA MOP V PH
REMARKS
IU-1-01A DAIKIN FXZQ12TAVJU 2x2 CASSETTE 353 - 10.19 7.08 13.6 1 15 208 1
IU-1-01B DAIKIN FXSQ12TAVJU 2x2 CASSETTE 353 - 10.19 7.08 13.6 1 15 208 1
IU-1-02A DAIKIN FXZQ09TAVJU 2x2 CASSETTE 317 - 7.98 5.92 10.57 1 15 208 1
IU-1-02B DAIKIN FXZQ09TAVJU 2x2 CASSETTE 317 - 7.98 5.92 10.57 1 15 208 1
IU-1-03A DAIKIN FXZQ09TAVJU 2x2 CASSETTE 317 - 7.98 5.92 10.57 1 15 208 1
IU-1-03B DAIKIN FXZQ09TAVJU 2x2 CASSETTE 317 - 7.98 5.92 10.57 1 15 208 1
IU-1-04 DAIKIN FXAQ07PVJU WALL 260 - 6.27 5.61 8.5 1 15 208 1
IU-1-05A DAIKIN FXZQ05TAVJU 2x2 CASSETTE 300 - 4.94 4.41 6.48 1 15 208 1
IU-1-05B DAIKIN FXZQ05TAVJU 2x2 CASSETTE 300 - 4.94 4.41 6.48 1 15 208 1
IU-1-06 DAIKIN FXSQ36TAVJU DUCTED 1130 - 30.92 23.19 39.92 4 15 208 1 1
IU-1-07 DAIKIN FXFQ24TVJU 2x2 CASSETTE 777 - 20.15 17.34 26.99 1 15 208 1
IU-1-08 DAIKIN FXSQ07TAVJU DUCTED 281 - 6.51 5.14 8.53 2 15 208 1 1
IU-1-09 DAIKIN FXZQ05TAVJU 2x2 CASSETTE 300 - 4.94 4.41 6.48 1 15 208 1
IU-2-01 DAIKIN FXZQ07TAVJU 2x2 CASSETTE 300 - 6.25 5.55 8.2 1 15 208 1
IU-2-02 DAIKIN FXZQ05TAVJU 2x2 CASSETTE 300 - 4.94 4.41 6.48 1 15 208 1
IU-2-03 DAIKIN FXZQ18TAVJU 2x2 CASSETTE 515 - 15.13 11.50 20.12 1 15 208 1
IU-2-04 DAIKIN FXZQ07TAVJU 2x2 CASSETTE 300 - 6.46 5.23 8.53 1 15 208 1
IU-2-05 DAIKIN FXZQ18TAVJU 2x2 CASSETTE 515 - 15.13 11.50 20.12 1 15 208 1
IU-2-06 DAIKIN FXSQ18TAVJU DUCTED 600 - 15.36 12.25 20.13 2 15 208 1 1
IU-2-07 DAIKIN FXSQ12TAVJU DUCTED 335 - 10.21 8.61 13.65 2 15 208 1 1
IU-2-08 DAIKIN FXSQ24TAVJU DUCTED 745 - 20.52 15.49 26.96 2 15 208 1 1
IU-2-09 DAIKIN FXZQ05TAVJU 2x2 CASSETTE 300 - 4.94 4.41 6.48 1 15 208 1
IU-2-10 DAIKIN FXZQ05TAVJU 2x2 CASSETTE 300 - 4.94 4.41 6.48 1 15 208 1
IU-2-11 DAIKIN FXZQ05TAVJU 2x2 CASSETTE 300 - 4.94 4.41 6.48 1 15 208 1
IU-2-12 DAIKIN FXZQ18TAVJU 2x2 CASSETTE 515 - 15.13 11.50 20.12 1 15 208 1
DUCTLESS SPLIT UNIT (INDOOR) SCHEDULE
MARK MODEL
SUPPLY
CFM
ESP
TOTAL
COOLING
(MBH)
SENSIBLE
COOLING
(MBH)
ELECTRICAL
WEIGHT
(LBS)
REMARKS
V PH FLA MFS
IDSU-1 AC024MNADCH/AA 550 0.1 24.0 17.5 208 1 0.7 15 35
DUCTLESS SPLIT UNIT (OUTDOOR) SCHEDULE
MARK MODEL
TOTAL
COOLING
(MBH)
HEATING
(MBH)
SEER
COMP.
QTY/RLA
ELECTRICAL
HSPF
WEIGHT
(LBS)
REMARKS
V PH MCA MFS
DSHP-1 AC024MXSCCC/AA 24.0 - 18.3 1/10.5 208 1 16 20 - 115
ROOF VENT SCHEDULE
MARK MANUFACTURER MODEL CFM LENGTH WIDTH
MAX
APD
THROAT
VEL (FPM)
SYSTEM REMARKS
RV-1 GREENHECK FGI 13,500 54 54 0.10 617 MAKEUP AIR
RV-2 GREENHECK FGI 13,500 54 54 0.10 617 MAKEUP AIR
RV-3 GREENHECK GRSR-16 800 16 16 0.05 552 EXHAUST
RV-4 GREENHECK GRSR-16 800 16 16 0.05 552 EXHAUST
GENERAL NOTES:
A. MODEL NUMBERS ARE BASED ON SAMSUNG EQUIPMENT. EQUIVALENTS BY MITSUBISHI, DAIKIN, LG, OR AS LISTED
IN THE SPECIFICATIONS
B. UNITS SHALL BE TESTED PER AHRI 1230
C. PROVIDE OPTIONAL WIND BAFFLE FOR ALL UNITS FOR LOW AMBIENT COOLING DOWN TO 0 DEG. F D. ALL ROOF CURBS/RAILS AND ATTACHMENTS THERETO SHALL BE THIRD PARTY LISTED FOR THE PROJECT WIND
ZONE. ANCHORING DETAILS FOR THE UNIT TO THE RAILS, AND RAILS TO THE STRUCTURE, SHALL BE INCLUDED
WITH THE SUBMITTAL
E. POWER AND LOW VOLTAGE WIRING AND CONDUIT INTERCONNECTING INDOOR AND OUTDOOR UNITS SHALL BE
BY DIVISION 23
GENERAL NOTES:
A. MODEL NUMBERS ARE BASED ON SAMSUNG EQUIPMENT. EQUIVALENTS BY MITSUBISHI, DAIKIN, LG, OR AS LISTED IN
THE SPECIFICATIONS
B. PROVIDE CONDENSATE PUMP, POWERED DIRECTLY FROM INDOOR UNIT TERMINALS, WITH EACH UNIT. 1 GPH AT 33
FT OF HEAD
C. PROVIDE WIRED CONTROLLER FOR ALL UNITS UNLESS OTHERWISE SPECIFIED
D. UNITS SHALL BE TESTED PER AHRI 1230
E. PROVIDE BACnet INTERFACE F. BAS CONTRACTOR SHALL PROVIDE A SEPARATE TEMPERATURE SENSOR FOR MONITORING SPACE OF EACH
INDOOR UNIT AND ESTABLISH A HIGH LEVEL ALARM FOR EACH (85 DEG F, ADJ).
GENERAL NOTES:
A. SELECTIONS BASED ON DAIKIN EQUIPMENT. EQUALS BY SAMSUNG, MITSUBISHI, OR AS LISTED IN THE SPECIFICATION.
B. PROVIDE ALL REQUIRED ACCESSORIES FOR A COMPLETE WORKING SYSTEM.
C. UNITS TO BE RATED AND CERTIFIED IN ACCORDANCE WITH AHRI 1230.
D. CAPACITY RATINGS ARE AT INDOOR 64°F-WB/75°F-DB AND OUTDOOR 95°F; AND 68°F INDOOR AND 17°F OUTDOOR.
CAPACITIES INCLUDE EFFECTS OF LINE LENGTHS AND CONNECTED DIVERSITY. PROVIDE OUTDOOR TWINNING KITS AS
REQUIRED.
E. PROVIDE TWO (2) DMS 2.5 CENTRALIZED CONTROLLERS. PROVIDE BACNET INTERFACE FOR EACH. BAS CONTRACTOR SHALL INTEGRATE BACNET POINTS INTO OWNER'S FRONT END GRAPHICS FOR SCHEDULING AND STATUS.
F. PROVIDE WEB BASED MONITORING SOFTWARE.
G. PROVIDE HAIL GUARD KITS FOR OUTDOOR UNITS.
H. REFRIGERANT CHARGE LISTED IN THE FACTORY CHARGE PLUS THAT ESTIMATED FOR THE DISTRIBUTION PIPING
CONNECTED. PROVIDE REFRIGERANT CHARGE FOR WHOLE SYSTEM WITH SUBMITTALS/SHOP DRAWINGS TO SHOW
COMPLIANCE WITH MAXIMUM SYSTEM CHARGES LISTED BELOW.
GENERAL NOTES:
A. SELECTION IS BASED ON DAIKIN EQUIPMENT. EQUIVALENTS BY SAMSUNG, MITSUBISHI OR AS LISTED IN THE
SPECIFICATION.
B. PROVIDE BALL VALVES, JOINT ADAPTORS, AND ALL REQUIRED ACCESSORIES FOR A COMPLETE WORKING
SYSTEM.
C. PROVIDE REDUCER ACCESSORIES FOR INDOOR UNITS AS REQUIRED BY MANUFACTURER.
D. EACH CIRCUIT FROM BOX TO INDOOR UNIT SHALL HAVE ISOLATION VALVES.
E. BASIS OF DESIGN UNITS DO NOT REQUIRE CONDENSATE PANS UNDER BRANCH DISTRIBUTION BOXES. IF
ANOTHER MANUFACTURER IS SUBSTITUTED WHERE THIS IS NOT THE CASE, THE CONTRACTOR SHALL
PROVIDE THE DRAIN PANS AT NO ADDITIONAL COST TO THE PROJECT.
GENERAL NOTES:
A. EQUIVALENTS BY TWIN CITY, PENN BARRY, OR AS LISTED IN THE SPECIFICATIONS.
B. LENGTH AND WIDTH LISTED ARE THROAT DIMENSIONS.
C. PROVIDE ALUMINUM BIRD SCREEN AND 20" ROOF CURB.
D. PROVIDE BAKED ENAMEL FINISH. PROVIDE COLOR CHART WITH SUBMITTAL FOR SELECTION BY ARCHITECT.
E. PROVIDE 20" INSULATED ROOF CURB. 1.5" INSULATION. MATCH SLOPE OF ROOF ON ARCHITECTURAL DRAWINGS.
LOUVER SCHEDULE
MARK MANUFACTURER MODEL PURPOSE DESCRIPTION CFM
MAX
APD
WIDTH HEIGHT
MIN.
FREE
AREA (SF)
MAX
VELOCITY
(FPM)
REMARKS
LV-1 RUSKIN EME520DD MAKEUP AIR INTAKE 300 0.05 76 16 3.39 200
LV-2 RUSKIN EME520DD MAKEUP AIR INTAKE 450 0.05 76 16 3.39 200
GENERAL NOTES:
A. PROVIDE FRAMED 1/2" x 1/2" ALUMINUM BIRD SCREEN FOR ALL LOUVERS
B. ALL LOUVERS SHALL BE RATED FOR THE PROJECT WIND ZONE
C. LOUVERS SHALL HAVE 3-COAT 70% KYNAR 500/HYLAR 5000 FINISH WITH A DRY FILM THICKNESS OF 2.0 mil
MINIMUM. PROVIDE STANDARD AND CUSTOM COLOR CHARTS WITH SUBMITTAL. COLOR SHALL BE SELECTED
BY ARCHITECT
D. ALL LOUVERS SHALL BE AMCA 500-L CERTIFIED FOR AIR PERFORMANCE, WATER PENETRATION,, AND WIND
DRIVEN RAIN AND BEAR APPROPRIATE SEAL
E. EQUIVALENTS BY GREENHECK, ARROW, AIROLITE, NAILOR, RELIABLE, POTTORFF, OR AS LISTED IN THE
SPECIFICATIONS
GENERAL NOTES (VRF INDOOR UNITS):
A. PROVIDE CONDENSATE PUMP INTEGRAL TO EACH INDOOR UNIT AND POWERED OFF SAME TERMINALS.
B. UNITS TO BE TESTED PER AHRI 1230.
C. PROVIDE DECORATIVE PANELS FOR ALL CEILING CASSETTE UNITS.
D. MECHANICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED DUCT TRANSITIONS FROM DUCTED UNIT FAN
OUTLETS.
E. PROVIDE AUXILIARY DRAIN PAN WITH FLOAT SWITCH UNDER ALL DUCTED UNITS.
F. CAPACITY RATINGS ARE AT INDOOR 64°F-WB/75°F-DB AND OUTDOOR 95°F; AND 68°F INDOOR AND 17°F
OUTDOOR. CAPACITIES INCLUDE EFFECTS OF LINE LENGTHS AND CONNECTED DIVERSITY. RATINGS
ASSUME SIMULTANEOUS HEATING AND COOLING OPERATION.
G. COORDINATE LOCATION OF UNITS WITH ELECTRICAL TRADE TO AVOID CONFLICTS WITH LIGHTS AND OTHER
DEVICES.
H. SELECTIONS BASED ON DAIKIN EQUIPMENT. EQUIVALENTS BY SAMSUNG, MITSUBISHI, OR AS LISTED IN THE
SPECIFICATION.
I. THE MECHANICAL CONTRACTOR SHALL SUBMIT A CERTIFICATION OF TRAINING AND QUALIFICATIONS FOR
INSTALLATION OF THE VRF SYSTEM BY THE VRF EQUIPMENT MANUFACTURER.
J. PROVIDE WIRED CONTROLLER WITH LCD SCREEN AND SET POINT ADJUSTMENT.
K. COORDINATE REQUIREMENT FOR SHIELDED CABLE WITH THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
OUTSIDE AIR CALCULATIONS
REMARKS:
1. PROVIDE 1" FILTER RACK.
0 09/01/23 REV 0 - ADDENDA & VE0 09/01/23 REV 0 - ADDENDA & VE
08/31/2023
DRAWN BY:
CHECKED BY:
T 919 781 8582
F 919 781 3979
4600 Lake Boone Trail Suite 205 Raleigh, NC 27607 info@smithsinnett.com
Th is d ra w in g an d th e de si gn s ho w n is th e pr op er ty o f S m ith S in ne tt Ar ch ite ct t he re pr od uc tio n or u se o f t hi s pr op er ty w ith ou t t he w rit te n co ns en t o ite ct is p ro hi bi te d.
A ny in fri ng em en t of th e ow ne rs hi p rig ht s w ill be s ub je l a ct io n.
A ll co pi es o f t hi s dr aw in g m us t b e re tu rn ed to th e
Ar ch ite ct a pl et io n of th e co nt ra ct
Sm ith
S in ne tt
Ar ch ite ct ur e, P .A
. 2
TH
IS
D R
AW
IN
G
IS
F O
R M
A
TT
ED
R
IN
TE
D
O N
A
0" X
2"
S H
E
ET
PDC #18065.01
DESCRIPTIONDATEID
S C
O
-1
-0
A
C U s e rs
\d lo w ry
\D o c u m e n ts \1
N
C N
G
M c L e a n s v ill e
R R
C
C e n tr a l_
M o d e l_ d lo w ry
P D
C B
IM
.r v t
6/
/2
2:
:1
P
M
M7-01
SCHEDULES
2020056 21 JUNE 2023
JAV
SWC
F O
R C
O N
S T
R U
C T
IO
N
N O
R T
H C
A R
O L
IN
A
N A
T
IO
N A
L G
U A
R D
M cL
E A
N S
V
IL
L E
R E
G
IO
N A
L R
E A
D
IN
E S
S C
E N
T E
R
C A
M P
B U
R T
O N
R D
M c L
E A
N S
V
IL
L E
N
C
AIR DISTRIBUTION SCHEDULE
MARK MANUFACTURER MODEL PURPOSE
MIN
CFM
MAX
CFM
FACE
SIZE
INLET
SIZE
REMARKS
10x4 PRICE 620 SUPPLY 12x6 10x4 1,7
10x4E PRICE 630 EXHAUST/RETURN 12x6 10x4 1,7
12x6 PRICE 620 SUPPLY 14x8 12x6 1,7
14x6 PRICE 620 SUPPLY 16x8 14x6 1,7
14x8 PRICE 620 SUPPLY 16x10 14x8 1,7
16x10R PRICE 630 EXHAUST/RETURN 18x12 16x10 1,7
48x80 PRICE 98 EXHAUST/RETURN 8500 50x82 48x80 1,5,7
A PRICE ASPD SUPPLY 24x24 6 1,2,3
B PRICE ASPD SUPPLY 24x24 8 1,2,3
C PRICE ASPD SUPPLY 24x24 10 1,2,3
DL PRICE HCD SUPPLY 6x15 6x15 1,9
DP PRICE APDDR SUPPLY 24x24 12 1,2,3
L2 PRICE SDS 100 SUPPLY 2' 2 SLOT 6 6
L4 PRICE SDS 100 SUPPLY 4' 2 SLOT 8 6
LB1 PRICE LBMH SUPPLY 48x5 48x5 8
LB2 PRICE LBMH SUPPLY 24x6 24x6 8
R PRICE APDDR EXHAUST/RETURN 24x24 6 1,2,3,4
S PRICE APDDR EXHAUST/RETURN 24x24 8 1,2,3,4
T PRICE APDDR EXHAUST/RETURN 24x24 10 1,2,3,4
TR PRICE 98 EXHAUST/RETURN 38x26 36x24 1,5,7
V PRICE APDDR EXHAUST/RETURN 24x24 14 1,2,3,4
Z PRICE APDDR RETURN 24x24 22x22 1,2,4
DUCTLESS SPLIT UNIT (INDOOR) SCHEDULE
MARK MODEL
SUPPLY
CFM
ESP
TOTAL
COOLING
(MBH)
HEATING
(MBH)
ELECTRICAL
WEIGHT
(LBS)
REMARKS
V PH MCA MFS
IWU-01A AM024TNVDCH/AA 530 - 23.2 23.8 208 1 1 15 30
IWU-01B AM024TNVDCH/AA 530 - 23.2 23.8 208 1 1 15 30
IWU-01C AM024TNVDCH/AA 530 - 23.2 23.8 208 1 1 15 30
IWU-02A AM024TNVDCH/AA 530 - 23.2 23.8 208 1 1 15 30
IWU-02B AM024TNVDCH/AA 530 - 23.2 23.8 208 1 1 15 30
IWU-03A AM024TNVDCH/AA 530 - 23.2 23.8 208 1 1 15 30
IWU-03B AM024TNVDCH/AA 530 - 23.2 23.8 208 1 1 15 30
IWU-4 AC018BNNDCH/AA 336 - 17.4 20.0 208 1 1 15 26 1
DUCTLESS SPLIT UNIT (OUTDOOR) SCHEDULE
MARK MODEL
TOTAL
COOLING
(MBH)
HEATING
(MBH)
SEER
COMP
QTY/FLA
ELECTRICAL
HSPF
WEIGHT
(LBS)
REMARKS
V PH MCA MFS
ODS-1 AM060MXMDCH/AA 60.0 66.0 20.6 1/24.5 208 1 32 50 11.5 280 1
ODS-2 AM048TXMDCH/AA 48.0 54.0 21.0 1/22.1 208 1 29 50 10.7 220 2
ODS-3 AM048TXMDCH/AA 48.0 54.0 21.0 1/22.1 208 1 29 50 10.7 220 2
ODS-4 AC018BXADCH/AA 17.4 20.0 19.3 1/12.7 208 1 18.3 25 10.1 118
ELECTRIC UNIT HEATER SCHEDULE
MARK MODEL
CAPACITY
(MBH)
KW
EAT
(°F)
LAT
(°F)
FAN DATA ELECTRICAL MOUNTING
HEIGHT
REMARKS
TYPE CFM THROW HP V PH
EUH-01 G3424T 13.6 4.0 55 106 PROP 245 10' - 277 1 8' 1,2,3,
EUH-02 G3424T 13.6 4.0 55 106 PROP 245 10' - 277 1 8' 1,2,3,
EUH-03 G3422T 6.8 4.0 55 81 PROP 245 10' - 277 1 2' 1,2,3,
RHP-01 CP703 1.3 0.38 - - - - - - 277 1 CEILING 7,8
RHP-02 CP703 1.3 0.38 - - - - - - 277 1 CEILING 7,8
RHP-03 CP703 1.3 0.38 - - - - - - 277 1 CEILING 9,10
FAN SCHEDULE
MARK MANUFACTURER MODEL CFM ESP HP/WATTS RPM
MAX
RPM
SONES
ELECTRICAL
WEIGHT REMARKS
V PH
EF-01 GREENHECK G-120-VG 1045 0.7 0.50 1290 1350 9.9 115 1 65 1,2,3,4
EF-02 GREENHECK CUE-095-VG 375 0.5 0.17 1390 1450 6.9 115 1 60 1,2,3,4
EF-03 GREENHECK CUE-095-VG 375 0.5 0.17 1390 1450 6.9 115 1 60 1,2,3,4
EF-04 GREENHECK CUE-095-VG 375 0.5 0.17 1390 1450 6.9 115 1 60 1,2,3,4
EF-05 GREENHECK CUE-095-VG 375 0.5 0.17 1390 1450 6.9 115 1 60 1,2,3,4
EF-06 GREENHECK CUE-080-VG 200 0.4 0.10 1388 1450 6.4 115 1 60 2,3,4
EF-08 GREENHECK G-097-VG 120 0.4 0.10 1081 1300 4.3 115 1 60 1,2,3,4
EF-09 GREENHECK QEI-12 800 0.5 0.33 1097 1200 8.0 115 1 125 9
EF-10 GREENHECK G-098-VG 480 0.7 0.25 1494 1550 8.5 115 1 60 1,2,3,4
EF-11 GREENHECK SP-80-VG 70 0.4 6w 935 1000 1.5 115 1 20 3,4,5,6,7
EF-12 GREENHECK CUE-090-VG 465 0.4 0.10 1332 1450 6.4 115 1 60 2,3,4,7
EF-13 GREENHECK AER-24-02-0315-VG 0.3 1.0 1163 1250 13.2 115 1 100 3,11
KEF-1 CAPTIVE AIRE DU85HFA 1,666 1.0 1.0 1335 1450 12.6 115 1 100 2,10
KEF-2 CAPTIVE AIRE DU85HFA 1,666 1.0 1.0 1335 1450 12.6 115 1 100 2,3,10
KEF-3 CAPTIVE AIRE DU33HFA 500 0.4 0.33 1079 1200 8.3 115 1 70 2,3,10
GENERAL NOTES:
A. PROVIDE ALL DUCT TRANSITIONS FOR FANS.
B. THE UNIT HOUSING SHALL BE CONSTRUCTED OF ALUMINUM.
C. ALL FANS TO BE U.L. LISTED.
D. PROVIDE WITH UNIT MOUNTED DISCONNECT.
E. EXTERNALLY OR INTERNALLY MOUNTED DISCONNECT SWITCH FURNISHED BY DIVISION 23 AND INSTALLED BY
DIVISION 26.
F. EXTERNALLY MOUNTED STARTER FURNISHED BY DIVISION 23 INSTALLED BY DIVISION 26.
G. PROVIDE 24V MOTORIZED DAMPER(S) UNLESS OTHERWISE DIRECTED.
H. PROVIDE OVERLOAD PROTECTION FOR ALL FANS, COORDINATE WITH DIVISION 26.
I. PROVIDE SPEED CONTROLLERS FOR ALL FANS.
REMARKS:
1. CONTROLS CONTRACTOR SHALL WIRE TO FAN. CONTROL FAN WITH DDC SYSTEM VIA SCHEDULE.
2. PROVIDE WITH 18" HIGH PRE-FABRICATED INSULATED CURB. CURB SHALL BE COMPATIBLE WITH THE ROOFING
SYSTEM.
3. PROVIDE DISCONNECT SWITCH, NEMA-1 INDOORS, NEMA 3R OUTDOORS, TOGGLE, MOUNTED AND WIRED.
4. PROVIDE GRAVITY OPERATED DAMPER.
5. PROVIDE VIBRATION ISOLATION KIT.
6. PROVIDE PLASTIC CEILING GRILLE.
7. FAN SHALL BE CONTROLLED BY MANUAL SWITCH.
8. PROVIDE WALL HOUSING AND FACTORY DISCONNECT.
9. FAN TO RUN CONTINUOUSLY. PROVIDE SPARK A CONSTRUCTION WITH BEARINGS OUTSIDE AIRSTREAM. ALL
PARTS OF FAN SHALL BE GROUNDED.
10. FAN FURNISHED BY HOOD MANUFACTURER AND CONTROLLED BY HOOD CONTROLLER.
11. PROVIDE WALL HOUSING, EDJ-430 LOUVER ON DISCHARGE, AND GRAVITY DAMPER. COLOR FOR LOUVER TO BE
SELECTED BY ARCHITECT FROM FULL COLOR LINE. FAN SHALL BE CONTROLLED BY LINE VOLTAGE
THERMOSTAT.
GENERAL NOTES:
A. MODEL NUMBERS ARE BASED ON SAMSUNG EQUIPMENT. EQUIVALENTS BY MITSUBISHI, DAIKIN, LG, OR AS LISTED
IN THE SPECIFICATIONS
B. UNITS SHALL BE TESTED PER AHRI 1230
C. PROVIDE OPTIONAL WIND BAFFLE FOR ALL UNITS FOR LOW AMBIENT COOLING DOWN TO 0 DEG. F D. ALL ROOF CURBS/RAILS AND ATTACHMENTS THERETO SHALL BE THIRD PARTY LISTED FOR THE PROJECT WIND
ZONE. ANCHORING DETAILS FOR THE UNIT TO THE RAILS, AND RAILS TO THE STRUCTURE, SHALL BE INCLUDED
WITH THE SUBMITTAL
E. POWER AND LOW VOLTAGE WIRING AND CONDUIT INTERCONNECTING INDOOR AND OUTDOOR UNITS SHALL BE
BY DIVISION 23
GENERAL NOTES:
A. MODEL NUMBERS ARE BASED ON SAMSUNG EQUIPMENT. EQUIVALENTS BY MITSUBISHI, DAIKIN, LG, OR AS LISTED IN
THE SPECIFICATIONS
B. PROVIDE CONDENSATE PUMP, POWERED DIRECTLY FROM INDOOR UNIT TERMINALS, WITH EACH UNIT. 1 GPH AT 33
FT OF HEAD
C. PROVIDE WIRED CONTROLLER FOR ALL UNITS UNLESS OTHERWISE SPECIFIED
D. UNITS SHALL BE TESTED PER AHRI 1230
E. PROVIDE BACnet INTERFACE F. BAS CONTRACTOR SHALL PROVIDE A SEPARATE TEMPERATURE SENSOR FOR MONITORING SPACE OF EACH
INDOOR UNIT AND ESTABLISH A HIGH LEVEL ALARM FOR EACH (85 DEG F, ADJ).
REMARKS:
1. CEILING CASSETTE TYPE UNIT
GENERAL NOTES:
A. BASIS OF DESIGN IS PRICE. EQUIVALENTS BY TITUS, KRUEGER, TUTTLE AND BAILEY, NAILOR, OR AS LISTED IN
SPECIFICATIONS
B. PROVIDE VOLUME DAMPERS AT TAKE-OFF FOR EACH GRILLE
C. ALL AIR DISTRIBUTION DEVICES SHALL BE ALUMINUM
D. THE PRICE MODELS SCHEDULED HERE ARE BASIS OF DESIGN, INCLUDING GENERATED NOISE. PROPOSED
SUBSTITUTIONS WILL BE JUDGED BY THOSE CRITERIA ALSO
E. WHERE LOCATED IN HARD CEILINGS, PROVIDE ALUMINUM MOUNT FRAME/PLASTER FRAME FOR HARD CEILING
THAT ALLOWS DIFFUSER/GRILLE WITH FLEX CONNECTION TO BE LIFTED OUT OF FRAME TO ACCESS CEILING SPACE. TYPICAL OF ALL HARD CEILING LOCATIONS. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN
F. FOR SIDE WALL GRILLES, PROVIDE REMOTE CABLE OPERATED, GEAR DRIVEN BALANCING DAMPER OPERABLE
FROM FACE OF DIFFUSER
REMARKS:
1. PROVIDE WITH OFF-WHITE ENAMEL FINISH
2. PROVIDE WITH TRIM TO MATCH CEILING TYPE. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
CEILINGS
3. PROVIDE DIFFUSER/GRILLE WITH ROUND NECK OR PROVIDE SQUARE TO ROUND TRANSITION
4. ALL CEILING MOUNTED RETURN GRILLES SHALL BE FULL FACED. NO LAY-IN PANELS ALLOWED
5. PROVIDE 1/2 INCH BLADE SPACING
6. PROVIDE INSULATED SDB LINEAR SLOT PLENUM WITH FLEXIBLE CONNECTION AND FRAME STYLE MATCHING
ARCHITECTURAL CEILING. PLENUM SHALL BE FACTORY INSULATED. PROVIDE CONCEALED PLASTER FRAME MOUNTING. PROVIDE CABLE OPERATED BALANCING DAMPER OPERABLE FROM FACE OF DIFFUSER.
7. PROVIDE OPPOSED BLADE DAMPER.
8. PROVIDE CONCEALED PLASTER FRAME MOUNTING. PROVIDE 15B REMOVABLE CORE.
9. PROVIDE SPLIT BLADE OPTION, POLE OPERATOR BRACKET, AND OPPOSED BLADE DAMPER
REMARKS:
1. PROVIDE SEMI-RECESSED SLEEVE.
2. PROVIDE FACTORY CIRCUIT BREAKER.
3. PROVIDE BUILT-IN TAMPERPROOF THERMOSTAT.
4. PROVIDE WALL-MOUNTED 24V THERMOSTAT.
5. PROVIDE HANGING BRACKET.
6. PROVIDE FACTORY MOUNTED DISCONNECT
SWITCH.
7. PANEL TO BE SURFACE MOUNTED TO CEILING.
8. BAS CONTRACTOR SHALL PROVIDE THERMOSTAT
FOR RADIANT HEAT PANEL AND CONNECT TO BAS
FOR CONTROL. HEATERS SHALL BE LOCKED OUT
WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 50
DEG F (ADJ).
9. LAY-IN MOUNTING
10. BAS CONTRACTOR TO PROVIDE THERMOSTAT FOR
CONTROL
GENERAL NOTES:
A. UNIT HEATERS BASED ON MARKEL 5100
AND 3420 SERIES.
B. EQUIVALENTS: REZNOR, BERKO,
RAYWALL, INDEECO.
C. WHERE A REMOTE WALL MOUNTED
THERMOSTAT IS INDICATED, PROVIDE
24V THERMOSTAT AND CONTROL
TRANSFORMER.
VRF HEAT RECOVERY UNIT SCHEDULE
TAG
TOTAL
COOLING
(MBH)
HEATING
CAPACITY
(MBH)
COMPRESSOR/ RLA
FANS/
FLA
ELECTRICAL DATA
MANUFACTURER MODEL NUMBER WEIGHT REMARKSMODULE 1 MODULE 2
IEER EER SCHE
REF
CHARGE
(LBS)
VOLTAGE/PH
MCA FUSE MCA FUSE
VRF-1 250.3 227.0 4 / 7.0, 7.1, 5.5, 8.9 4/1.0 21.7 25 16.6 20 23.9 11.30 22.20 51.6 480/3 DAIKIN REYQ264AAYDA 728 + 800
VRF-2 236.1 227.4 4 / 7.0, 7.1, 5.5, 8.9 4/1.0 21.7 25 16.6 20 23.9 11.30 22.20 51.6 480/3 DAIKIN REYQ264AAYDA 728 + 800
VRF-3 194.7 162.7 2 / 12.7, 12.7 2/1.5 29.9 35 - - 23.0 11.25 23.7 25.8 480/3 DAIKIN REYQ216AAYDA 972
VRF-4 180.1 160.9 2 / 12.7, 12.7 2/1.5 29.9 35 - - 23.0 11.25 23.7 25.8 480/3 DAIKIN REYQ216AAYDA 972
VRF-5 160.5 127.6 2 / 6.9, 11.0 2/1.0 24.9 30 - - 24.0 11.30 23.95 25.8 480/3 DAIKIN REYQ168AAYDA 802
VRF-6 139.1 124.9 2 / 5.5, 8.9 2/1.0 21.7 25 - - 24.5 12.25 23.85 25.8 480/3 DAIKIN REYQ144AAYDA 800
VRF-7 65.3 77.1 1 / 6.5 1/1.5 12.4 15 - - 25.5 14.25 24.05 23.4 480/3 DAIKIN REYQ72AAYDA 525
VRF-8 95.1 96.3 2 / 7.0, 7.1 2/1.0 16.6 20 - - 25.5 12.8 24.15 25.8 480/3 DAIKIN REYQ120AAYDA 728
VRF BRANCH CONTROLLER BOX SCHEDULE
MARK
MODEL
NO. OF
PORTS
MAX. CAP.
PER PORT
(MBH) MCA/MFS VOLT/PH
WEIGHT
(lbs)
REMARKS
MCU-1-1 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-2 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-3 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-4 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-5 BSF4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-6 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-7 BSF4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-8 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-1-9 BSQ36TVJ 1 36.0 0.1/15 208/1 27
MCU-2-1 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-2-2 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-2-3 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-2-4 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-2-5 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-2-6 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-1 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-2 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-3 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-4 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-5 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-6 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-7 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-8 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-3-9 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-1 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-2 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-3 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-4 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-5 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-6 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-7 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-4-8 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-5-1 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-5-2 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-5-3 BSQ60TVJ 1 60.0 0.1/15 208/1 27
MCU-5-4 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-5-5 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-6-01 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-6-02 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-6-03 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-7-01 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-7-02 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-8-1 BS4Q54TVJ 4 54.0 0.4/15 208/1 49
MCU-8-2 BSQ36TVJ 1 36.0 0.1/15 208/1 27
GENERAL NOTES:
A. SELECTIONS BASED ON DAIKIN EQUIPMENT. EQUALS BY SAMSUNG, MITSUBISHI OR AS LISTED IN THE SPECIFICATION.
B. PROVIDE ALL REQUIRED ACCESSORIES FOR A COMPLETE WORKING SYSTEM.
C. UNITS TO BE RATED AND CERTIFIED IN ACCORDANCE WITH AHRI 1230.
D. CAPACITY RATINGS ARE AT INDOOR 64°F-WB/75°F-DB AND OUTDOOR 95°F; AND 68°F INDOOR AND 17°F OUTDOOR.
CAPACITIES INCLUDE EFFECTS OF LINE LENGTHS AND CONNECTED DIVERSITY. PROVIDE OUTDOOR TWINNING KITS AS
REQUIRED.
E. PROVIDE TWO (2) CENTRALIZED CONTROLLERS. PROVIDE BACNET INTERFACE FOR EACH. BAS CONTRACTOR SHALL INTEGRATE BACNET POINTS INTO OWNER'S FRONT END GRAPHICS FOR SCHEDULING AND STATUS.
F. PROVIDE WEB BASED MONITORING SOFTWARE.
G. PROVIDE HAIL GUARD KITS FOR OUTDOOR UNITS.
H. REFRIGERANT CHARGE LISTED IS THE FACTORY CHARGE OF THE UNIT ONLY. PROVIDE REFRIGERANT CHARGE FOR
WHOLE SYSTEM WITH SUBMITTALS/SHOP DRAWINGS TO SHOW COMPLIANCE WITH MAXIMUM SYSTEM CHARGES LISTED
ON NEXT PAGE.
GENERAL NOTES:
A. SELECTION IS BASED ON DAIKIN EQUIPMENT. EQUIVALENTS BY SAMSUNG, MITSUBISHI, OR AS LISTED IN THE
SPECIFICATION.
B. PROVIDE BALL VALVES, JOINT ADAPTORS, AND ALL REQUIRED ACCESSORIES FOR A COMPLETE WORKING
SYSTEM.
C. PROVIDE REDUCER ACCESSORIES FOR INDOOR UNITS AS REQUIRED BY MANUFACTURER.
D. EACH CIRCUIT FROM BOX TO INDOOR UNIT SHALL HAVE ISOLATION VALVES.
E. BASIS OF DESIGN DOESN'T NOT REQUIRE CONDENSATE PANS UNDER UNITS. IF ANOTHER MANUFACTURER IS
SUBMITTED THAT REQUIRES CONDENSATE PANS, THE MECHANICAL CONTRACTOR SHALL PROVIDE AT NO
ADDITIONAL COST TO THE PROJECT.
HIGH VOLUME LOW SPEED (HVLS) FAN SCHEDULE
MACROAIR AIRVOLUTION-D 550. 14 FT DIAMETER. PROVIDE UNIVERSAL MOUNTING HARDWARE KIT. DROP TUBE LENGTH TO BE FIELD MEASURED AND COORDINATED WITH LIGHTS PRIOR TO ORDERING. PROVIDE FUSED DISCONNECT SWITCH AND NOISE DAMPENER. 1.05 HP FAN MOTOR. 480V/3PH. PROVIDE FACTORY VARIABLE FREQUENCY DRIVE. PROVIDE FIRE ALARM RELAY TO SHUT OFF FAN UPON SPRINKLER OR FIRE ALARM ACTIVATION. PROVIDE AIRFOIL RETAINERS, RETAINER CLIPS, AND SAFETY CABLES. UL LISTED. PROVIDE POWDER COATED FINISH. COLOR SELECTION BY OWNER. PROVIDE FACTORY CERTIFIED INSTALLATION. PROVIDE DIGITAL REMOTE CONTROLLER (ONE PER FAN) WITH TOUCHPAD AND 200 FT REMOTE CABLE 5E CABLE.
COORDINATE WITH DIVISION 26 ON LIGHTING LAYOUT AND DIVISION 21 ON SPRINKLER HEAD LAYOUT. EQUIVALENTS BY
GREENHECK, HUNTER, OR AS LISTED IN THE SPECIFICATIONS.
HVLS-1, 2
AIR CURTAIN SCHEDULE
AIR CURTAIN. POWERED-AIR RMP-2-72 OR EQUIVALENT BY MARS OR SCHWANK. UNHEATED. 71" NOZZLE WIDTH. 2,142 AVERAGE FPM. 2,356 CFM AT NOZZLE. TWO (2) 1/5 HP MOTORS. WEIGHT 94 LBS. PROVIDE DOOR SWITCH FOR CONTROL. 115V/1PH. 4.0 FLA
PER MOTOR.
AC-1
DEHUMIDIFIER SCHEDULE
BASIS OF DESIGN IS EBAC. SEREIES CS90-E. EQUIVALENTS BY QUEST CLIMATE, SEAIRA, OR AS LISTED IN SPECIFICATIONS. 230
CFM, 70 PINTS/DAY EXTRACTION. 115V/1PH.
A. OPERATING RANGE 35°F-95°F
B. ALL STEEL CONSTRUCTION WITH EPOXY POWDER-COATED FINISH
C. INTEGRAL CONDENSATE PUMP WITH PROVISIONS FOR PERMINANT DRAINAGE
D. PROVIDE MANUFACTURER INSTALLED HUMIDITY SENSOR WITH ADJUSTABLE HUMIDITY SETPOINT AND DATALOGGING
CAPABILITY.
E. PLUG TYPE CONNECTION
F. MANUFACTURER PROVIDED HOT-GAS-REHEAT DEFROST CYCLE
G. SUSPEND FROM STRUCTURE AS HIGH AS POSSIBLE INSIDE VAULTS.
DHM-1, 2, 3, 4
AIR CURTAIN. POWERED-AIR RMP-1-48 OR EQUIVALENT BY MARS OR SCHWANK. UNHEATED. 47" NOZZLE WIDTH. 2,045 AVERAGE FPM. 3,050 CFM AT NOZZLE. ONE (1) 1/5 HP MOTORS. WEIGHT 67 LBS. PROVIDE DOOR SWITCH FOR CONTROL. 115V/1PH. 4.0 FLA.
AC-2
GENERAL NOTES:
A. ALL UNITS ARE DOWNFLOW ORIENTATION
B. UNITS WITH ONE COMPRESSOR SHALL BE VARIABLE SPEED 15-100% CAPACITY. UNITS WITH TWO COMPRESSORS
SHALL HAVE ONE 0-15% VARIABLE SPEED COMPRESSOR AND ONE TWO-STAGE COMPRESSOR.
C. TOTAL ENTHALPY WHEELS SHALL HAVE AN EATR OF 5% OR LESS
D. PROVIDE ALL DUCT TRANSITIONS FROM UNIT
E. PROVIDE METAL MESH OUTDOOR AIR MERV 8 PREFILTER AND 2" MERV 13 FILTERS
F. PROVIDE 0-100% ECONOMIZER WITH LOW LEAKAGE DAMPERS. PROVIDE DRY BULB SENSOR FOR ECONOMIZER
OPERATION
G. PROVIDE FACTORY CIRCUIT BREAKER IN NEMA 3R ENCLOSURE, SINGLE POINT POWER CONNECTION, AND 24 VOLT
CONTROLS TRANSFORMER. 65 kA SCCR H. PROVIDE WALL MOUNTED TEMPERATURE SENSOR WITH SETPOINT OVERRIDE ADJUSTMENT. PROVIDE WALL
MOUNTED HUMIDITY SENSOR.
I. PROVIDE WITH STAINLESS STEEL DRAIN PAN MEETING ASHRAE 62.1
J. PROVIDE ACOUSTICAL ROOF CURB - BRD HUSHCORE WHISPER E OR APPROVED EQUAL FOR DOAS-1 AND 2 AND
RTU-1. MECHANICAL CONTRACTOR SHALL FIELD CUT OPENINGS IN BOTTOM OF CURB TO ALIGN WITH STRUCTURAL.
MECHANICAL CONTRACTOR SHALL COORDINATE CURB AND SILENCER SELECTIONS WITH UNIT MANUFACTURER'S
ACTUAL SOUND DATA.
K. PROVIDE FIELD WIRED 115 VOLT GFI RECEPTACLE
L. PROVIDE DOUBLE-WALL CONSTRUCTION WITH R-13 FOAM INSULATION
M. PROVIDE MODULATING GAS HEAT
N. PROVIDE PHASE LOSS AND PROTECTION, HAIL GUARDS, AND ACCESS DOORS
O. MECHANICAL CONTRACTOR SHALL PROVIDE FINAL GAS REGULATOR FOR ALL UNITS OPERATING WITH NATURAL GAS
P. PROVIDE SERVICE LIGHTS IN CONTROL SECTION
Q. EQUIVALENTS BY GREENHECK OR TRANE
R. NOTE DELETED
S. PROVIDE STANDARD 24" TALL CURB FOR DOAS- 3, 4, 5, 6 AND K.
REMARKS:
1. PROVIDE MODULATING HOT GAS REHEAT
2. PROVIDE WALL MOUNTED CO2 SENSOR FOR DCV.
3. PROVIDE BYPASS DAMPERS AROUND WHEEL FOR ECONOMIZER OPERATION.
4. UNIT IS 100 PERCENT OUTSIDE AIR OPERATION
5. UNIT IS SINGLE-ZONE VAV (SZVAV) OPERATION
ROOFTOP UNIT SCHEDULE
MARK MANUFACTURER MODEL
OA
MAX
CFM
OA
MIN
CFM
SUPPLY FAN EXHAUST FAN ENTHALPY WHEEL SUMMER PERFORMANCE ENTHALPY WHEEL WINTER PERFORMANCE COOLING COIL GAS HEAT REHEAT COIL RERIGERATION CIRCUIT ELECTRICAL
WEIGHT
(LBS)
REMARKS
QTY CFM
ESP
IN. WG
HP BHP QTY CFM
ESP
IN. WG
HP BHP
SUM
OA DB
(°F)
SUM
OA WB
(°F)
SUM
RET DB
(°F)
SUM
RET WB
(°F)
SUM
LDB
(°F)
SUM
LWB
(°F)
WIN
OA DB
(°F)
WIN
OA WB
(°F)
WIN
RET DB
(°F)
WIN
RET WB
(°F)
WIN
LDB
(°F)
WIN
LWB
(°F)
EDB
(°F)
EWB
(°F)
TOTAL
COOLING
(MBH)
SENSIBLE
COOLING
(MBH)
LDB
(°F)
LWB
(°F)
INPUT
(MBH)
OUTPUT
(MBH)
AFUE
TURND
OWN
EDB
(°F)
LDB
(°F)
CAPACITY
(MBH)
EDB
(°F)
LDB
(°F)
COMP
QTY
COMP RLA
(EA.)
COND
FAN
QTY/HP EER
V PH MCA MFS
DOAS-1 AAON RN-020 3,980 - 1 3,980 1.4 5.0 3.22 1 3,300 0.8 3.0 1.45 83.0 79.0 75.0 64.0 77.8 71.0 15.0 12.0 68.0 54.0 47.8 39.9 77.8 70.9 232.5 104.4 51.5 51.3 270.0 218.7 80 9:1 48.0 97.4 81.0 51.5 70.0 2 16.7/16.7 2 12.0 480 3 54 70 4000 1,3,4
DOAS-2 AAON RN-020 3,680 - 1 3,680 1.4 5.0 2.85 1 2,500 0.8 3.0 0.91 83.0 79.0 75.0 64.0 78.5 72.1 15.0 12.0 68.0 54.0 43.6 36.7 78.5 72.1 232.7 100.3 51.3 51.1 270.0 218.7 80 9:1 43.6 96.9 76.0 51.5 70.0 2 16.7/16.7 2 12.0 480 3 54 70 4000 1,3,4
DOAS-3 AAON RN-011 2,150 - 1 2,150 1.4 2.0 1.80 1 1,950 0.8 2.0 1.06 83.0 79.0 75.0 64.0 77.5 70.3 15.0 12.0 68.0 54.0 51.0 41.5 77.5 70.3 118.0 53.8 50.6 50.4 195.0 156.0 80 10:1 50.0 118.0 43.0 51.0 72.0 2 8.1/7.8 2/1.6 12.2 480 3 28 35 2800 1,3,4
DOAS-4 AAON RN-009 1,750 - 1 1,750 1.5 2.0 1.43 1 2,000 0.8 2.0 1.10 83.0 79.0 75.0 64.0 76.9 69.3 15.0 12.0 68.0 54.0 54.8 44.7 76.9 69.3 90.7 43.1 51.0 50.8 195.0 156.0 80 10:1 54.8 137.4 35.0 51.0 72.0 2 7.8/6.2 2/1.6 12.6 480 3 26 30 2800 1,3,4
DOAS-5 AAON RN-030 4,225 - 1 4,225 1.3 5.0 3.32 1 1,600 0.8 2.0 0.52 83.0 79.0 75.0 64.0 80.1 74.7 15.0 12.0 68.0 54.0 32.5 28.1 80.1 74.7 300.3 117.8 51.1 80.9 270.0 218.7 80 9:1 32.5 80.7 84.0 51.0 70.0 2 18.6/18.6 3/1.8 11.4 480 3 59 70 4000 1,3,4
DOAS-6 AAON RN-011 900 - 1 900 1.4 2.0 1.06 1 1,000 0.8 1.0 0.55 83.0 79.0 75.0 64.0 78.2 71.7 15.0 12.0 68.0 54.0 44.8 37.7 78.2 71.7 54.9 23.1 50.3 50.1 60.0 48.6 80 10:1 44.8 94.8 19.0 50.3 70.0 1 8.1 1/1.6 11.6 480 3 17 25 1700 1,3,4
DOAS-K CAPTIVE AIR CASRTU3-I300 3,100 - 1 3,100 1.0 3.0 2.50 - - - - - - - - - - - - - - - - - 83.0 77.5 264.0 99.1 54.0 53.7 296.0 236.6 80 14:1 17.0 83.0 65.5 54.0 70.0 480 3 40 45 2900 1,3,4
RTU-1 AAON RN-031 3,200 1,600 1 8,500 1.2 10.0 8.2 1 7,000 0.8 5.0 1.89 - - - - - - - - - - - - 78.0 69.7 403.7 198.4 53.1 53.0 600.0 480.0 80 4:1 48.1 100.8 156.0 53.0 70.0 3 26.9/9.7/14.7 4/3.6 10.7 480 3 94 110 6500 1,2,5
ROOF VENT SCHEDULE
MARK MANUFACTURER MODEL CFM LENGTH WIDTH
MAX
APD
THROAT
VEL (FPM)
SYSTEM REMARKS
RV-1 GREENHECK GRSR-16 700 16 16 0.04 600 EXHAUST
GENERAL NOTES:
1. PROVIDE ROOF CURB MATCHING ROOF SLOPE
2. PROVIDE BIRD SCREEN
3. EQUIVALENTS BY PENN OR TWIN CITY
REMARKS:
1. 3:1 SYSTEM. 1 OUTDOOR UNIT SERVES 3 INDOOR UNITS. PROVIDE Y-JOINTS, ETC.
2. 2:1 SYSTEM. 1 OUTDOOR UNIT SERVES 3 INDOOR UNITS. PROVIDE Y-JOINTS, ETC.
WELDING EXTRACTOR SCHEDULE
BASIS OF DESIGN IS PLYMOVENT MONOGO PLUS 3M. EQUIVALENTS BY MILLER, NEDERMAN, OR AS LISTED IN SPECIFICATIONS.
STATIONARY WELDING FUME FILTER WITH BUILT-IN FAN. DISPOSABLE FILTER PACAKGE. 115V/1PH/60. 243 LBS. PROVIDE 3 METER LONG ARM WITH COLLECTION HOOD. ONE PREFILTER AND ONE HEPA FILTER. 500 CFM AND 67 dB(A). PROVIDE WALL BRACKET, MOUNTING HARDWARE, HOOD WITH COLLAR AND SAFETY MESH, AND REMOTE CONTROL BOX (TO BE MOUNTED AT 48" AFF).
EXTR-1
0 06/21/23 REV 0 - ADDENDA & VE0 06/21/23 REV 0 - ADDENDA & VE
06/20/2023
RFI 62
https://app.procore.com/2517858/project/rfi/show/18118358
DRAWN BY:
CHECKED BY:
T 919 781 8582
F 919 781 3979
4600 Lake Boone Trail Suite 205 Raleigh, NC 27607 info@smithsinnett.com
Th is d ra w in g an d th e de si gn s ho w n is th e pr op er ty o f S m ith S in ne tt Ar ch ite ct t he re pr od uc tio n or u se o f t hi s pr op er ty w ith ou t t he w rit te n co ns en t o ite ct is p ro hi bi te d.
A ny in fri ng em en t of th e ow ne rs hi p rig ht s w ill be s ub je l a ct io n.
A ll co pi es o f t hi s dr aw in g m us t b e re tu rn ed to th e
Ar ch ite ct a pl et io n of th e co nt ra ct
Sm ith
S in ne tt
Ar ch ite ct ur e, P .A
. 2
TH
IS
D R
AW
IN
G
IS
F O
R M
A
TT
ED
R
IN
TE
D
O N
A
0" X
2"
S H
E
ET
PDC #18065.01
DESCRIPTIONDATEID
S C
O
-1
-0
A
C U s e rs
\d lo w ry
\D o c u m e n ts \1
N
C N
G
M c L e a n s v ill e
R R
C
C e n tr a l_
M o d e l_ d lo w ry
P D
C B
IM
.r v t
6/
/2
2:
:1
P
M
M7-02
SCHEDULES
2020056 21 JUNE 2023
JAV
SWC
F O
R C
O N
S T
R U
C T
IO
N
N O
R T
H C
A R
O L
IN
A
N A
T
IO
N A
L G
U A
R D
M cL
E A
N S
V
IL
L E
R E
G
IO
N A
L R
E A
D
IN
E S
S C
E N
T E
R
C A
M P
B U
R T
O N
R D
M c L
E A
N S
V
IL
L E
N
C
VRF INDOOR UNIT SCHEDULE
TAG MANUFACTURER MODEL STYLE CFM
ESP
IN. WG
COOLING
LAT (°F)
HEATING
LAT (°F)
TOTAL
COOLING
(MBH)
SENSIBLE
(MBH)
ACTUAL
HEATING
(MBH)
MCA MOP V PH
REMARKS
ICU-1-01 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-02 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-03 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-04 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-05 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-06 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-07 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-08 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-1-09 DAIKIN FXZQ15TAVJU CASSETTE 405 - 54.0 107.9 13.08 9.33 17.74 0.4 15 208 1
ICU-1-10 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-11 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-1-12 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-13 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-15 DAIKIN FXZQ18TAVJU CASSETTE 511 - 54.9 105.1 15.47 11.30 20.81 0.4 15 208 1
ICU-1-16 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-17 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-1-19 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-20 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-21 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-22 DAIKIN FXZQ12TAVJU CASSETTE 300 - 56.9 104.1 10.46 7.04 13.99 0.4 15 208 1
ICU-1-23 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-1-24 DAIKIN FXZQ18TAVJU CASSETTE 511 - 54.9 105.1 15.47 11.30 20.81 0.4 15 208 1
ICU-1-25 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-1-26 DAIKIN FXZQ12TAVJU CASSETTE 300 - 56.9 104.1 10.46 7.04 13.99 0.4 15 208 1
ICU-1-27A DAIKIN FXZQ15TAVJU CASSETTE 405 - 54.0 107.9 13.08 9.33 17.74 0.4 15 208 1
ICU-1-27B DAIKIN FXZQ15TAVJU CASSETTE 405 - 54.0 107.9 13.08 9.33 17.74 0.4 15 208 1
ICU-2-01A DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-2-01B DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-2-03 DAIKIN FXZQ12TAVJU CASSETTE 300 - 56.9 104.1 10.46 7.04 13.99 0.4 15 208 1
ICU-2-05 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-2-06 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-2-07 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-01 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-02 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-03 DAIKIN FXZQ12TAVJU CASSETTE 300 - 56.9 104.1 10.46 7.04 13.99 0.4 15 208 1
ICU-3-04 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-05 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-3-06 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-07 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-08 DAIKIN FXZQ09TAVJU CASSETTE 282 - 58.3 99.3 8.19 5.82 10.92 0.3 15 208 1
ICU-3-09 DAIKIN FXZQ15TAVJU CASSETTE 511 - 54.0 107.9 13.08 9.33 17.74 0.4 15 208 1
ICU-3-10 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-3-11 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-12 DAIKIN FXZQ15TAVJU CASSETTE 405 - 54.0 107.9 13.08 9.33 17.74 0.4 15 208 1
ICU-3-13 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-3-14 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-15 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-16 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-17 DAIKIN FXZQ15TAVJU CASSETTE 405 - 54.0 107.9 13.08 9.33 17.74 0.4 15 208 1
ICU-3-19 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-3-20 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-21 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-22 DAIKIN FXZQ12TAVJU CASSETTE 300 - 56.9 104.1 10.46 7.04 13.99 0.4 15 208 1
ICU-3-23 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-3-25 DAIKIN FXZQ09TAVJU CASSETTE 282 - 58.3 99.3 8.19 5.82 10.92 0.3 15 208 1
ICU-3-26 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-27 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-3-28 DAIKIN FXZQ12TAVJU CASSETTE 300 - 56.9 104.1 10.46 7.04 13.99 0.4 15 208 1
ICU-4-01 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-02 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-03 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-04 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-05 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-06 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-07 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-08 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-09 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-10 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-4-13 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-4-17 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-18 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-19 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-20 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-21 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-22 DAIKIN FXZQ15TAVJU CASSETTE 511 - 54.0 107.9 13.08 9.33 17.74 0.4 15 208 1
ICU-4-23 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-4-24 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-5-01A DAIKIN FXUQ24PVJU SUSP. CASSETTE 690 - 57.6 100.0 20.65 15.21 27.98 0.6 15 208 1
ICU-5-01B DAIKIN FXUQ24PVJU SUSP. CASSETTE 690 - 57.6 100.0 20.65 15.21 27.98 0.6 15 208 1
ICU-5-02A DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-5-02B DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-5-03 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-5-04 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-5-05 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-5-06 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-6-06 DAIKIN FXZQ12TAVJU CASSETTE 300 - 56.9 104.1 10.46 7.04 13.99 0.4 15 208 1
ICU-7-02 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-7-03 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-7-06 DAIKIN FXZQ05TAVJU CASSETTE 229 - 62.1 88.7 5.00 4.26 6.82 0.3 15 208 1
ICU-8-03 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
ICU-8-04 DAIKIN FXZQ07TAVJU CASSETTE 229 - 59.8 94.3 6.59 5.13 8.87 0.3 15 208 1
IDU-1-14 DAIKIN FXSQ48TAVJU CONCEALED DUCTED 1130 0.4 53.9 107.0 42.33 30.23 55.96 2.8 15 208 1
IDU-1-18 DAIKIN FXSQ54TAVJU CONCEALED DUCTED 1300 0.4 52.5 109.3 47.72 34.10 62.44 3.3 15 208 1
IDU-2-02 DAIKIN FXSQ36TAVJU CONCEALED DUCTED 850 0.4 55.5 101.4 30.94 24.24 41.49 2.5 15 208 1
IDU-2-04 DAIKIN FXSQ54TAVJU CONCEALED DUCTED 1350 0.4 52.5 109.3 47.72 34.10 62.44 3.3 15 208 1
IDU-2-08 DAIKIN FXSQ54TAVJU CONCEALED DUCTED 1350 0.4 52.5 109.3 47.72 34.10 62.44 3.3 15 208 1
IDU-2-09 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 700 0.4 52.6 107.4 26.48 20.00 35.14 1.8 15 208 1
IDU-2-10 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 700 0.4 52.6 107.4 26.48 20.00 35.14 1.8 15 208 1
IDU-2-11 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 710 0.4 52.6 107.4 26.48 20.00 35.14 1.8 15 208 1
IDU-2-12 DAIKIN FXSQ12TAVJU CONCEALED DUCTED 315 0.3 52.2 106.0 10.47 8.41 13.99 0.8 15 208 1
IDU-3-18 DAIKIN FXSQ24TAVJU CONCEALED DUCTED 650 0.4 56.3 102.3 21.05 15.21 27.98 1.8 15 208 1
IDU-3-24 DAIKIN FXSQ36TAVJU CONCEALED DUCTED 950 0.4 56.7 101.3 31.69 22.74 41.28 2.5 15 208 1
IDU-4-11 DAIKIN FXSQ24TAVJU CONCEALED DUCTED 500 0.4 56.3 102.3 21.05 15.21 27.98 1.8 15 208 1
IDU-4-12 DAIKIN FXSQ24TAVJU CONCEALED DUCTED 500 0.4 56.3 102.3 21.05 15.21 27.98 1.8 15 208 1
IDU-4-14 DAIKIN FXSQ24TAVJU CONCEALED DUCTED 500 0.4 56.3 102.3 21.05 15.21 27.98 1.8 15 208 1
IDU-4-15 DAIKIN FXSQ12TAVJU CONCEALED DUCTED 310 0.4 52.2 106.0 10.47 8.41 13.99 0.8 15 208 1
IDU-4-16 DAIKIN FXSQ36TAVJU CONCEALED DUCTED 900 0.4 56.7 101.3 31.69 22.74 41.28 2.5 15 208 1
IDU-5-07A DAIKIN FXSQ36TAVJU CONCEALED DUCTED 820 0.4 56.7 101.3 31.69 22.74 41.28 2.5 15 208 1
IDU-5-07B DAIKIN FXSQ36TAVJU CONCEALED DUCTED 820 0.4 56.7 101.3 31.69 22.74 41.28 2.5 15 208 1
IDU-5-08 DAIKIN FXAQ24PVJU WALL 635 - 53.5 107.4 20.63 14.98 27.50 0.6 15 208 1
IDU-5-09 DAIKIN FXAQ24PVJU WALL 635 - 53.5 107.4 20.63 14.98 27.50 0.6 15 208 1
IDU-5-10 DAIKIN FXAQ07PVJU WALL 260 - 56.0 98.5 6.43 5.44 8.70 0.4 15 208 1
IDU-6-01 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 715 0.4 52.6 107.4 26.48 20.00 35.14 1.8 15 208 1
IDU-6-02 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 700 0.4 52.6 107.4 26.48 20.00 35.14 1.8 15 208 1
IDU-6-03 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 700 0.4 52.6 107.4 26.48 20.00 35.14 1.8 15 208 1
IDU-6-04 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 700 0.4 52.6 107.4 26.48 20.00 35.14 1.8 15 208 1
IDU-6-05 DAIKIN FXSQ12TAVJU CONCEALED DUCTED 300 0.3 52.2 106.0 10.47 8.41 13.99 0.8 15 208 1
IDU-6-07 DAIKIN FXSQ12TAVJU CONCEALED DUCTED 300 0.3 52.2 106.0 10.47 8.41 13.99 0.8 15 208 1
IDU-6-08 DAIKIN FXSQ12TAVJU CONCEALED DUCTED 300 0.3 52.2 106.0 10.47 8.41 13.99 0.8 15 208 1
IDU-6-09 DAIKIN FXSQ12TAVJU CONCEALED DUCTED 320 0.3 52.2 106.0 10.47 8.41 13.99 0.8 15 208 1
IDU-7-01 DAIKIN FXSQ36TAVJU CONCEALED DUCTED 1075 0.4 56.7 101.3 31.69 22.74 41.28 2.5 15 208 1
IDU-7-04 DAIKIN FXSQ18TAVJU CONCEALED DUCTED 500 0.3 56.9 99.6 15.73 11.95 20.81 1.6 15 208 1
IDU-7-05 DAIKIN FXAQ07PVJU WALL 160 - 56.0 98.5 6.43 5.44 8.70 0.4 15 208 1
IDU-7-07 DAIKIN FXAQ07PVJU WALL 160 - 56.0 98.5 6.43 5.44 8.70 0.4 15 208 1
IDU-8-01 DAIKIN FXSQ36TAVJU CONCEALED DUCTED 825 0.4 56.7 101.3 31.69 22.74 41.28 2.5 15 208 1
IDU-8-02 DAIKIN FXSQ36TAVJU CONCEALED DUCTED 825 0.4 56.7 101.3 31.69 22.74 41.28 2.5 15 208 1
IDU-8-05 DAIKIN FXSQ30TAVJU CONCEALED DUCTED 665 0.4 52.6 107.4 26.48 20.10 35.15 1.8 15 208 1
GENERAL NOTES (VRF INDOOR UNITS):
A. PROVIDE CONDENSATE PUMP INTEGRAL TO EACH INDOOR UNIT AND POWERED OFF SAME TERMINALS.
B. UNITS TO BE TESTED PER AHRI 1230.
C. PROVIDE DECORATIVE PANELS FOR ALL CEILING CASSETTE UNITS.
D. PROVIDE ALL REQUIRED DUCT TRANSITIONS FROM DUCTED UNIT FAN OUTLETS.
E. PROVIDE GALVANIZED STEEL AUXILIARY DRAIN PAN WITH FLOAT SWITCH UNDER ALL DUCTED UNITS.
F. CAPACITY RATINGS ARE AT INDOOR 64°F-WB/75°F-DB AND OUTDOOR 95°F; AND 68°F INDOOR AND 17°F OUTDOOR.
CAPACITIES INCLUDE EFFECTS OF LINE LENGTHS AND CONNECTED DIVERSITY. RATINGS ASSUME SIMULTANEOUS
HEATING AND COOLING OPERATION.
G. COORDINATE LOCATION OF UNITS WITH ELECTRICAL TRADE TO AVOID CONFLICTS WITH LIGHTS AND OTHER DEVICES.
H. SELECTIONS BASED ON DAIKIN EQUIPMENT. EQUIVALENTS BY SAMSUNG, MITSUBISHI, OR AS LISTED IN THE
SPECIFICATION.
I. THE MECHANICAL CONTRACTOR SHALL SUBMIT A CERTIFICATION OF TRAINING AND QUALIFICATIONS FOR INSTALLATION
OF THE VRF SYSTEM BY THE VRF EQUIPMENT MANUFACTURER.
J. PROVIDE WIRED CONTROLLER WITH LCD SCREEN AND SET POINT ADJUSTMENT.
K. CONTRACTOR SHALL PROVIDE TEMPORARY FILTER MEDIA AND FINAL FILTER MEDIA FOR ALL UNITS. FINAL FILTER MEDIA
SHALL BE INSTALLED JUST PRIOR TO TAB.
L. NOTE DELETED
REFRIGERANT VOLUME CALCULATIONS
PER TABLE 1103.1, THE MAXIMUM PERMISSIBLE REFRIGERANT CHARGE FOR R-410A IS 26 LBS / 1000 CU FT.
VRF-1
SMALLEST ROOM IS 99 SF x 10 FT = 990 CU FT + CEILING PLENUM VOLUME (8,493 SF x 4 FT) = 34,962 CU FT
TOTAL PERMISSIBLE CHARGE = 34,962 CU FT / 26 CU FT/1000 CU FT = 909 LBS
VRF-2
SMALLEST ROOM IS 158 SF x 10 FT = 1,580 CU FT + CEILING PLENUM VOLUME (3,854 SF x 4 FT) = 16,996 CU FT
TOTAL PERMISSIBLE CHARGE = 16,996 CU FT / 26 CU FT/1000 CU FT = 442 LBS
VRF-3
SMALLEST ROOM IS 80 SF x 10 FT = 800 CU FT + CEILING PLENUM VOLUME (8,562 SF x 4 FT) = 35,048 CU FT
TOTAL PERMISSIBLE CHARGE = 35,048 CU FT / 26 CU FT/1000 CU FT = 911 LBS
VRF-4
SMALLEST ROOM IS 140 SF x 10 FT = 1400 CU FT + CEILING PLENUM VOLUME 4,153 SF x 4 FT = 18,012 CU FT
TOTAL PERMISSIBLE CHARGE = 18,012 CU FT / 26 CU FT/1000 CU FT = 468 LBS
VRF-5
SMALLEST ROOM IS 349 SF x 14.8 FT = 5,165 CU FT
TOTAL PERMISSIBLE CHARGE = 5,165 CU FT / 26 CU FT/1000 CU FT = 134 LBS
VRF-6
SMALLEST ROOM IS 172 SF x 10 FT = 1,720 CU FT + CEILING PLENUM 577 SF x 9.5 FT = 7,201 CU FT
TOTAL PERMISSIBLE CHARGE = 7,201 CU FT / 26 CU FT/1000 CU FT = 187 LBS
VRF-7
SMALLEST ROOM IS 95 SF x 10 FT = 950 CU FT + CEILING PLENUM 479 SF x 4.66 FT = 3,182 CU FT
TOTAL PERMISSIBLE CHARGE = 3,182 CU FT / 26 CU FT/1000 CU FT = 82.7 LBS
KITCHEN AIR BALANCE
GREASE HOOD -3,333 CFM
DISHWASH HOOD -500 CFM
DOAS-K +3,100 CFM
DISH DROP EXHAUST -75 CFM
TOTAL -808 CFM
TRANSFER AIR FROM DRILL HALL 808 CFM
OTHER REQUIRED EXHAUST
TOILET ROOMS 70 CFM / FLUSHABLE FIXTURE
LOCKER ROOMS 0.5 CFM/SQ FT (1030 AND 1061)
SHOWER ROOMS 20 CFM / SHOWER HEAD
MAINTENANCE SHOP 0.5 CFM/SQ FT (1065)
HAZARDOUS EXHAUST 1.0 CFM SQ FT (001 FLAMMABLE STORAGE)
OUTSIDE AIR FOR RTU-1
0 06/21/23 REV 0 - ADDENDA & VE0 06/21/23 REV 0 - ADDENDA & VE
06/20/2023
| Addendum 2 -Equipment and Drawings |
| Drawings and Equipment Schedules |
| McLeansville RRC Mechanical |
| McLeansville RRC Mechanical |