About this file

Addendum 2 Summary

This is Addendum No. 2 to Invitation to Bid (RFB) No. RFB-109-27, issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for the re-advertisement of RFB-158-25 for Pennyrile Forest Beach Complex Repair and Upgrade in Dawson Springs, Kentucky. The addendum, dated November 24, 2026, modifies the original specifications and drawings dated September 8, 2026, and contains three primary modifications: revision to gravel mulch specifications on Drawing C101 requiring #8 limestone per specification 31 20 00, section 2.1.F; replacement of the duplex sewage ejector pump system on Drawing P301 to provide 40 GPM at 78 feet of head while retaining the existing basin; and addition of lighting fixtures to the Lighting Fixture Schedule on Drawing E101. The addendum must be acknowledged by bidders by inserting its number on the official bid document.

The addendum includes comprehensive plumbing schedules and specifications for the restroom building, detailing mechanical equipment including a domestic hot water circulating pump (CP-1), thermal expansion tank (TXT-1), electric water heater (EWH-1), thermostatic mixing valve (TMV-1), and sewage ejector system (SEP-1). Plumbing fixtures specifications include multiple water closets, urinals, lavatories with sensor-activated faucets, floor drains, mop basins, beach shower columns, and trench drain systems, along with fixture schedules indicating fixture unit ratings and connection requirements. The electrical components include an expanded lighting fixture schedule with LED fixtures in various configurations, occupancy sensor controls, emergency lighting with battery backup capability, and detailed electrical legends and control diagrams for lighting systems. All specifications reference manufacturer model numbers and performance requirements, with notes indicating contractors are responsible for verifying complete material requirements and coordinating installations across trades.

View the file

Other files

File Type Posted
Addendum 1.pdf PDF
Final_RFB_785_2700000190_3_SO_FORM.PDF PDF
Final_RFB_785_2700000190_1_SO_FORM.PDF PDF
Final_RFB_785_2700000190_2_SO_FORM.PDF PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-109-27

FOR: Re-Advertisement of RFB-158-25 Pennyrile Forest Beach Complex Repair/Upgrade Department of Parks Dawson Springs, Kentucky

DATE: November 24, 2026

RFB-785-2700000190

ADDENDUM NO. Two (2)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-109-27 For: Re-Advertisement of RFB-158-25 Pennyrile Forest Beach Complex Repair/Upgrade Department of Parks Dawson Springs, Kentucky

Janis Wilhoite, Statewide Procurement Analyst II Division of Engineering and Contract Administration

Parks – Pennyrile Forest Beach Complex Repair/Upgrade Engineering File No. 670-CBRB-PF28-00 C/S Project No. 2422

RFB 109-27 Re-Ad of RFB 158-25

2026.11.24

Addendum No. 02 _

The original specifications and drawings dated RTA 09/08/2026 for the above referenced project are amended as noted in this Addendum.

Receipt of this Addendum shall be acknowledged by inserting its number in the space provided on the Official Bid Document for RFB 109-27.

DRAWINGS

1) C101: Add the following to Detail B/C101: Gravel mulch shall be #8 limestone, per 31 20 00, 2.1.F.

2) P301: All pump station - pumps, controls, and accessories shall be replaced as specified. The existing basin shall remain. The duplex sewage ejector pump system has been revised to provide 40 GPM at 78 feet of head.

3) E101: Additional lights added to Lighting Fixture Schedule.

END of ADDENDUM

LOCATIONSYMBOL REMARKS/COMMENTSDESCRIPTION

MISCELLANEOUS EQUIPMENT SCHEDULE

CP-1

BASED ON BELL &

GOSSETT MODEL

NBF-12F

MECHANICAL

ROOM

DOMESTIC HOT WATER CIRCULATING PUMP - LEAD FREE, PERMANENTLY LUBRICATED,

CLOSED COUPLED, IN-LINE, 1 GPM @ 11 FT HEAD, 2,800 RPM, 55 WATTS, 120V/1PH, 3/4"

FLANGED CONNECTIONS. PROVIDE WITH COMBINATION AQUASTAT/TIME CLOCK CONTROL.

TXT-1

BASED ON A WESSELS

MODEL TXA-35

MECHANICAL

ROOM

THERMAL EXPANSION TANK - REPLACEABLE BLADDER TYPE, PRECHARGED, 150 PSI

MAXIMUM DESIGN PRESSURE, 3/4" NPT STAINLESS STEEL SYSTEM CONNECTION,

STANDARDTIRE VALVE CHARGING CONNECTION, 10 GALLON TANK VOLUME, SET TANK

PRESSURE TO 60 PSI. MOUNT AS HIGH AS POSSIBLE IN MECHANICAL ROOM.

BASED ON AO SMITH

DEL-20S-5.5

MECHANICAL

ROOM

ELECTRIC WATER HEATER - 20 GAL HEATER STORAGE, 23 GPH 100°F RISE, 73LBS, SURFACE

MOUTED THERMOSTAT, CSA CERTIFIED AND ASME RATED T&P RELIEF VALVE, SET

INTERNAL TEMPERATURE TO 140°F, 5.5KW, 240V/ 1PH, 1 ELEMENTS. BOTTOM AND TOP

OUTLET, BRASS DRAIN VALVE, SINGLE PANEL CONTROL BOX, FOAM INSULATED.

TMV-1

BASED ON SYMMONS

MODEL 7-200

MECHANICAL

ROOM

THERMOSTATIC MIXING VALVE - 12 GPM @ 10 PSI PRESSURE DROP, MEETS ASSE 1017, SET

AT 110°F DISCHARGE, 3/4" INLETS, 3/4" OUTLET, VOLUME CONTROL SHUT-OFF VALVE,

BIMETAL DIAL THERMOMETER, BRASS FITTINGS AND UNIONS AND WALL MOUNTING

BRACKET. PROVIDE WITH CHECK STOPS, AND REMOVABLE CARTRIDGE WITH STRAINER.

EWH-1

SEP-1

BASED ON MYERS

MODEL WG50-21

OUTSIDE

DUPLEX SEWAGE EJECTORS: CAST IRON PUMPS QUICK REMOVAL SYSTEM SUBMERSIBLE

GRINDER PUMP, 5 HP, 40 GPM, 78' HEAD, 3,450 RPM, 230 VOLT, 35 AMP, SINGLE PHASE,

PIGGY BACK VARIABLE LEVEL FLOAT SWITCH, CONTROL PANEL WITH MAIN CIRCUIT

BREAKER DISCONNECT.

SCP-1

BASED ON EXISTING

CONTROL PANEL

OUTSIDE

NEMA 4x CONTROL PANEL WITH INTEGRAL CIRCUIT BREAKER TYPE SAFETY DISCONNECT

SWITCH FOR SINGLE-POINT POWER CONNECTION AND ALTERNATOR. LOCATE ON BASIN.

YCO

WC-2WC-1

WC-1

WC-1

UR-1

UR-2

WC-1

WC-1

WC-2

VTR

1 1/2"

4"

LAV-1

LAV-1

LAV-1

LAV-1

LAV-1

LAV-1

LAV-1

LAV-1

FD-1

MB-1

YCO

SH-1

3"

4"

6"

3"

1 1/2"

2"

TD-1

TD-1

1 1/2"

1 1/2"

1 1/2"

4"

3"

2"

2"

2"

3"

2"

2"

4"

3"

ST-X

SEB-X

YCO-X

4"

4"

6"

STM

YCO

3" 3"

3"

3"

TD-1

TD-1

1 1/2"

1 1/2"

1 1/2"

1 1/2"

CO

CO

CO

2"

1 1/2"

4"

VTR

4"

4"

SEP-1

2"

3"

4"

CO

1 1/2"

4"

4"

1 1/2"

4"

4"

4"

2"

3"

3"

R E

NIGNEAN LOIS

ES

F O R P

E

KENTUCKY

FOETAT

S

DESNE

L I C

STEINHART

23766

W.

YANR

A&E FILE NO.

DRAWING DATE

DRAWN BY

CHECKED BY

DECA LOG #

DRAWING INFORMATION

DRAWING NO.

AS BUILT DATE

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKY

ACCOUNT NO.

670-CBRB-PF28-00

PHASE

RTA DATE

RTA

09/08/2026

09/08/2026

/2 3/

4:

:5

P

M

P301BVN

09/08/2026

2505-196

RWS

PLUMBING SCHEDULES & SANITARY RISER DIAGRAM

5-

P

E N

N Y

R

IL

E F

O R

E S

T B

E A

C H

F A

C

IL

IT

Y

A N

D S

IT

E

IM

P

R O

V M

E N

T S

PENNYRILE FOREST BEACH FACILITY AND SITE IMPROVMENTS

SANITARY RISER DIAGRAM

WATER HAMMER ARRESTOR SCHEDULE

MARK I.P.S. F.U. RATING J.R. SMITH JOSAM ZURN

D 1" 61 - 113 5030 75004 400

FIXTURE FINAL CONNECTION SCHEDULE

FIXTURE

COLD WATER HOT WATER WASTE VENT

IPC 2006

REMARKSDFU CWFU HWFU

4'' FLOOR DRAIN - - 4'' - 6 - -

LAVATORY 1/2'' 1/2'' 2'' 1 1/2'' 1 1.5 1.5

MOP BASIN 3/4'' 3/4'' 3'' 1 1/2'' 3 2.25 2.25

URINAL 3/4'' - 2'' 1 1/2'' 2 5 -

WALL HYDRANT 3/4'' - - - - 2.5 -

WATER CLOSET - FLUSH VALVE 1 1/2'' - 4'' 2'' 4 10 -

PLUMBING FIXTURE LIST

TP-1

DESCRIPTION: TRAP PRIMER, 1/2" PIPE SIZE.

MANUFACTURER & CATALOG NO.: ZURN Z1022-XL

UR-1

DESCRIPTION: URINAL - WHITE VITREOUS CHINA WALL HUNG URINAL WITH EXTENDED

SHIELDS, FLUSHING RIM, SIPHEN JET, INTEGRAL TRAY AND TOP SPUD. 1.0 GPF.

MANUFACTURER & CATALOG NO.: AMERICAN STANDARD TRIMBROOK 6561017

DESCRIPTION: FLUSH VALVE - 1.0 GALLONS PER FLUSH. PROVIDE WITH BOX TRANSFORMER

AND HARD-WIRED SENSOR OPERATED FLUSH VALVE WITH WALL MOUNTED SENSOR WITH

OVER-RIDE BUTTON, CHROME COVER PLATES, SOLENOID OPERATOR WITH VACUUM

BREAKER, SCREWDRIVER STOP AND QUIET EQUIPMENT.

PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED LOW VOLTAGE

TRANSFORMERS, LINE AND LOAD SIDE OVERCURRENT PROTECTION, LOAD SIDE LOW

VOLTAGE CABLING, AND ALL LOW VOLTAGE RACEWAY SYSTEMS. PLUMBING CONTRACTOR

SHALL COORDINATE ALL LOW VOLTAGE TRANSFORMER REQUIREMENTS AND LOCATIONS

WITH ELECTRICAL CONTRACTOR.

MANUFACTURER & CATALOG NO.: SLOAN 186-1.0 ESS ROYAL

DESCRIPTION: FURNISH WITH FLOOR MOUNTED CARRIER FITTING SUPPORT. MOUNT 24"

FLOOR TO RIM.

MANUFACTURER & CATALOG NO.: ZURN ZZ1222

UR-2

DESCRIPTION: WATER CLOSET - SAME AS UR-1 EXCEPT MOUNT AT 17" FLOOR TO RIM.

WC-1

DESCRIPTION: WATER CLOSET - WHITE VITREOUS CHINA WALL HUNG SIPHON JET

ELONGATED BOWL WITH TOP SPUD, 1.6 GPF. MOUNT 15" FINISHED FLOOR TO RIM AND

FURNISH WITH EXTRA HEAVY DUTY (500 LB.) CLOSET SUPPORT CARRIER BOLTED SECURELY

TO FLOOR.

MANUFACTURER & CATALOG NO.: AMERICAN STANDARD AFWALL

DESCRIPTION: SEAT - WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID ANTI-

MICROBIAL PLASTIC SELF-SUSTAINING SEAT WITH CHECK HINGE AND STAINLESS STEEL OR

PLATED STEEL POSTS AND NUTS.

MANUFACTURER & CATALOG NO.: AMERICAN STANDARD 5904.100SS; BEMIS 3155C, CHURCH

3155C, BENEKE 533PC, OLSONITE 95CCAM

DESCRIPTION: FLUSH VALVE - 1.6 GALLONS PER FLUSH. PROVIDE WITH BOX TRANSFORMER

AND HARD-WIRED WALL MOUNTED SENSOR WITH OVERRIDE BUTTON, SOLENDOID

OPERATED, CHROME PLATED, 1" I.P.S. WITH VACUUM BREAKER SCREWDRIVER STOP. UNIT

SHALL INCLUDE A MINIMUM 3-YEAR WARRANTY.

SENSOR LOCATION SHALL BE 12" MAXIMUM ABOVE BOWL RIM AND OPERATE WITH NO

GREATER THAN 5 LB FORCE, IN COMPLIANCE WITH ADA SECTION 4.16.5 AND 4.27.4.

CONTRACTOR TO VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.

COORDINATE FLUSH SENSOR LOCATION WITH GRAB BAR LOCATION AND ELECTRICAL

CONTRACTOR.

PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED LOW VOLTAGE

TRANSFORMERS, LINE AND LOAD SIDE OVERCURRENT PROTECTION, LOAD SIDE LOW

VOLTAGE CABLING, AND ALL LOW VOLTAGE RACEWAY SYSTEMS. PLUMBING CONTRACTOR

SHALL COORDINATE ALL LOW VOLTAGE TRANSFORMER REQUIREMENTS AND LOCATIONS

WITH ELECTRICAL CONTRACTOR.

MANUFACTURER & CATALOG NO.: SLOAN ROYAL 111-1.6 ES-S "ROYAL"

WC-2

DESCRIPTION: WATER CLOSET - SAME AS WC-1 EXCEPT MOUNT AT 17" FLOOR TO RIM.

WH-1

DESCRIPTION: HOSE BIBB - FREEZELESS BOX AND DOOR WALL HYDRANT, AUTOMATIC

DRAINING, VACUUM BREAKER, 3/4" MALE HOSE THREAD, BRASS VALVE BODY AND SEAT,

STAINLESS STEEL STEM, STANDARD FINISH, WALL CLAMP. FURNISH TWO KEY OPERATORS.

ASSE 1019 APPROVED AND LISTED. MOUNT AT 18" ABOVE GRADE UNLESS NOTED

OTHERWISE ON DRAWINGS.

MANUFACTURER & CATALOG NO.: WOODFORD B65

YCO

DESCRIPTION: YARD CLEANOUT- PROVIDE WITH ACCESS COVER. ROUND-FLANGED

HOUSING WITH HEAVY-DUTY CAST-IRON COVER. PROVIDE WITH 2'-0" SQ. CONCRETE

COLLAR.

MANUFACTURER & CATALOG NO.: JR. SMITH 4251.

THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.

CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR

FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT. CATALOG NUMBERS SHALL

NOT BE CONSIDERED COMPLETE BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO

INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE

DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE

ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG

NUMBER. THE FIRST MANUFACTURER IS THE BASIS OF DESIGN.

LOW VOLTAGE CABLING AND ASSOCIATED CONDUIT SHALL BE PROVIDED BY PLUMBING

CONTRACTOR. REFER TO MECHANICA DRAWINGS FOR LOCATIONS OR CONTROL POWER

TRANSFORMERS

BFP-1 (1-1/2")

DESCRIPTION: REDUCED PRESSURE BACKFLOW PREVENTER - SPRING LOADED CHECKS

WITH A DIFFERENTIAL PRESSURE RELIEF VALVE BETWEEN THE CHECK VALVES. BRONZE UP

TO 2" SIZE, FDA APPROVED EPOXY COATED CAST IRON OVER 2" SIZE, WITH BRONZE, OR

STAINLESS-STEEL INTERNAL PARTS AND STAINLESS-STEEL SPRINGS. UNITS SHALL INCLUDE

FOUR TEST COCKS WITH SHUT-OFF VALVES AND SHALL BE BACKFLOW TESTED AT THE

FACTORY. RATED FOR 175 PSI AT 33 DEGREES F. TO 140 DEGREES F. MAXIMUM PRESSURE

DROP 15 PSI AT 10 FPS REGARDLESS OF SIZE. FLOW PRESSURE DROP CURVES SHALL BE

SUBMITTED. ALL PARTS TO BE SERVICEABLE WITHOUT REMOVING UNIT FROM LINE WITH

SHUTOFF VALVES ON BOTH SIDES OF UNIT (BALL VALVES ON SIZES 2-1/2" OR SMALLER,

GATE VALVES ON SIZES 3" OR LARGER) AND AIR GAP DRAIN FITTING. PROVIDE AND INSTALL

BRONZE OR EPOXY COATED STRAINER IF REQUIRED FOR SERVICING STRAINER. APPROVED

BY: USC FCCC & HR, AWWA C511-92, ASSE 1013, IAPMO AND SBCCI LISTED. UNIT SHALL BE

SAME SIZE AS PIPE IF NO SIZE IS SHOWN ON THE DRAWING.

MANUFACTURER & CATALOG NO.: WATTS 009 & 909, CONBRACO 40-200, FEBCO 860, WILKINS

975XL & 375

FD-1

DESCRIPTION: 4" FLOOR DRAIN - 6"ø STRAINER, CAST IRON BODY, ADJUSTABLE TOP, POLISHED NICKEL-BRONZE TYPE I STRAINER.

REFER TO PLANS FOR CONNECTION SIZE AND TRAPS TO BE FURNISHED WITH TRAP PRIMER

CONNECTION.

MANUFACTURER & CATALOG NO.: ZURN 415I

LAV-1

DESCRIPTION: LAVATORY - 23-5/8" x16-5/8" VITREOUS CHINA UNDERCOUNTER MOUNT SINK.

REFER TO ARCHITECTURAL AND INTERIOR DRAWINGS FOR MOUNTING HEIGHTS AND

COUNTERTOP REQUIREMENTS. COLOR SHALL BE WHITE. PROVIDE WITH GRID STRAINER;

CHROME PLATED P-TRAP WITH ESCUTCHEON, LOOSE KEY STOP VALVES WITH

COMPRESSION FITTINGS AND WATER SUPPLIES AND RISERS; TRUEBRO HANDILAV GUARD

INSULATION KIT.

MANUFACTURER & CATALOG NO.: AMERICAN STANDARD 0618.000

DESCRIPTION: LAVATORY TRIM - SENSOR ACTIVATED ELECTRONIC HAND WASHING FAUCET

WITH 0.35 GPM SPRAY AND ASSE-10170 IN SPOUT THERMOSTATIC MIXING VALVE. HARD

WIRED TRANSFORMER AND GRID STRAINER; CHROME PLATED P-TRAP WITH ESCUTCHEON,

LOOSE KEY STOP VALVES WITH COMPRESSION FITTINGS AND WATER SUPPLIES AND

RISERS. LOW VOLTAGE CABLING AND ASSOCIATED CONDUIT SHALL BE PROVIDED BY

PLUMBING CONTRACTOR.

MANUFACTURER & CATALOG NO.: SLOAN EAF-200-ITM

MB-1

DESCRIPTION: MOP BASIN - MOLDED STONE, 24" X 24" X 10", WHITE WITH BLACK ACCENTS, STAINLESS STEEL DRAIN WITH COMBINATION DOME STRAINER AND LINT BASKET, 3" OUTLET.

STAINLESS STEEL WALL GUARDS VINYL BUMPER GUARD ON EXPOSED SIDES. MOP HANGER,

HOSE AND HOSE BRACKET. CAULK BETWEEN MOP BASIN AND WALL WITH SILICONE BASED

CAULK. DEEP SEAL TRAP. MOUNT 18" FLOOR TO HOSE BRACKET. MOUNT 54" FLOOR TO MOP

HANGER.

MANUFACTURER & CATALOG NO.: FIAT MSB-2424, WILLIAMS MTB-2424, SWAN MS-2424, ZURN

Z-1996-24, PROFLO PFMB2424S

TRIM - TWO HANDLE EXPOSED MIXING FAUCET, SINGLE WING HANDLES, POLISHED CHROME

PLATED, 3/4" HOSE THREAD SPOUT WITH INTEGRAL VACUUM BREAKER, WALL BRACE, PAIL

HOOK, INTEGRAL STOPS AND INTEGRAL CHECK VALVES. MOUNT 36" FLOOR TO FAUCET.

MANUFACTURER & CATALOG NO.: CHICAGO FAUCET 897-CRCF, DELTA 28T9.

SH-1

DESCRIPTION: 3 PERSON BEACH COLUMN SHOWER FITTED WITH TWO SHOWERS AND ONE

FOOT RINSE. CENTRAL RISING VENT WITH SUPPLIES FROM BELOW. COLUMN DRAIN FLANGE

WITH 15 DRAIN HOLES SHALL BE 14 GAUGE TYPE 304 STAINLESS STEEL WITH 16 GAUGE

COLUMN TUBE. MOUNT TO CONCRETE WITH FIVE 5/16-18 STAINLESS STEEL HEX HEAD

BOLTS. DRAIN FITTINGS ARE CAST IRON COATED WITH RUST PREVENTATIVE. 3" SANITARY, 2"

VENT WITH 1/2" DOMESTIC WATER CONNECTIONS.

MANUFACTURER & CATALOG NO.: BRADLEY MODEL COL-3B TYPE H W/ DOME GRATE DRAIN

TD-1

DESCRIPTION: 3-3/8" WIDE REVEAL TRENCH DRAIN SYSTEM, 3" THROAT. TOTAL 48" LENGTH

LINEAR TRENCH DRAIN WITH DRAIN FLANGE. INCLUDE COUPLINGS BOTTOM CONNECTION

AND RUBBER GASKETS, REMOVEABLE GRATE, 3" DRAIN HOLE, REMOVEABLE FABRICATED

304 STAINLESS STEEL SLOTTED GRATE, RUBBER MEMBRANE.

MANUFACTURER & CATALOG NO.: CARMEN 927531-F

PLUMBING FIXTURE LIST CONT.

NOTES:

1. SANITARY RISER UP IN WALL TO ANY FIXTURE SHALL BE A MINIMUM OF 2".

2. SIZES SHOWN ARE MINMUMS. SIZES SHOWN ON THE DRAWINGS THAT ARE LARGER THAN THE SIZES LISTED IN THE SCHEDULES SHALL

DICTATE THE ROUGH-IN SIZE.

3. BACK TO BACK WATER CLOSETS SHALL HAVE A 4" WASTE TO A CARRIER WITH A 2" VENT, AND A 1-1/2" CW CONNECTION.

4. BACK TO BACK 3" FLOOR DRAINS SHALL HAVE A 3" SANITARY AND A 1-1/2" VENT.

* TRAP PRIMER CONNECTION

*1/2" *0.25"

ADD-002 11/24/26

S

S a

"WP"

a,b,c,...

JUNCTION BOX AS REQUIRED OR AS NOTED.

PHASE

CONDUCTOR

NEUTRAL

GROUND

LC1-1

CEILING OUTLET AND LIGHTING FIXTURE AS SCHEDULED.

SYMBOL DESCRIPTIONDESCRIPTIONSYMBOL

WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE. INSTALL

18 INCHES ABOVE FINISHED FLOOR TO CENTER, UNLESS

NOTED OTHERWISE.

WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE. INSTALL

ABOVE COUNTER TOP, UNLESS NOTED OTHERWISE. COORDINATE

THE REQUIRED HEIGHT ABOVE COUNTER TOP WITH ARCHITECT

AND ALL OTHER INSTALLATION IN AREA PRIOR TO ROUGH-IN.

NUMBER INDICATES MOUNTING HEIGHT ABOVE FINISHED

FLOOR TO BOTTOM OF OUTLET BOX WHEN SHOWN NEXT

TO SYMBOL.

+42"

SYMBOL INDICATES FIXTURE TYPE WHEN SHOWN ON LIGHTING

PLANS AND SITE ELECTRICAL PLANS ADJACENT TO FIXTURE

SYMBOL. REFER TO LIGHTING FIXTURE SCHEDULE FOR FIXTURE

REQUIREMENTS.

"GFI"

OUTLET BOX AND 20A, SINGLE POLE SWITCH. MOUNT AT 46 INCHES

ABOVE FINISHED FLOOR TO CENTER, UNLESS NOTED OTHERWISE.

LOCATE WITHIN 8" OF STRIKE SIDE OF DOOR, UNLESS NOTED

OTHERWISE. LOWER CASE LETTER INDICATES CIRCUIT SWITCHED.

NOMENCLATURE INDICATES GROUND FAULT

INTERRUPTER TYPE RECEPTACLE WHEN SHOWN PLANS

ADJACENT TO SYMBOL.

OUTLET AND EXIT LIGHT FIXTURE AS SCHEDULED OR NOTED.

ARROWS INDICATE DIRECTION ARROWS REQUIRED.

OCCUPANCY SENSOR. THE LETTER(S) DESIGNATION NEXT TO

THE SYMBOL (IF SHOWN) INDICATE SWITCHING ZONES TO BE

CONTROLLED VIA THE OCCUPANCY SENSOR. IF A LETTER

DESIGNATION IS NOT SHOWN, THE OCCUPANCY SENSOR SHALL

CONTROL ALL LIGHTING FIXTURES WITHIN THE ROOM. SEE

OCCUPANCY SENSOR CONTROL WIRING DIAGRAMS, AND

DETAILS, SHEET E101, FOR ADDITIONAL REQUIREMENTS.

LOWER CASE LETTERS INDICATE SWITCHING ARRANGEMENT

WHEN SHOWN NEXT TO OR WITHIN SYMBOL ON PLANS.

OCCUPANCY SENSOR SWITCH. MOUNT AT 46 INCHES ABOVE

FINISHED FLOOR TO CENTER, UNLESS NOTED OTHERWISE.

LOCATE WITHIN 8" OF STRIKE SIDE OF DOOR, UNLESS NOTED

OTHERWISE.

CEILING OUTLET AND LIGHTING FIXTURE AS SCHEDULED.

CEILING OUTLET AND LIGHTING FIXTURE AS SCHEDULED.

a

O

ELECTRICAL LEGEND - POWERELECTRICAL LEGEND - LIGHTING

J J

WALL OUTLET (WHERE REQUIRED) AND LIGHTING FIXTURE AS

SCHEDULED.

NOMENCLATURE INDICATES WEATHER RESISTANT

RECEPTACLE IN WEATHERPROOF WHILE IN-USE DIECAST

ALUMINUM ENCLOSURE WHEN SHOWN ON PLANS ADJACENT

TO SYMBOL.

HOMERUN TO PANEL INDICATED. PREFIX INDICATES PANEL

NOMENCLATURE. NUMBERS INDICATE CIRCUIT NUMBERS.

CIRCUIT. NUMBER OF CROSSBARS INDICATE QUANTITY OF

CONDUCTORS REQUIRED. MINIMUM CONDUIT SIZE SHALL BE

3/4 INCH TRADE SIZE. MINIMUM SIZE CONDUCTORS SHALL BE

12 AWG.

"WR" NOMENCLATURE INDICATES WEATHER RESISTANT

RECEPTACLE WHEN SHOWN ON PLANS ADJACENT TO SYMBOL.

"EX" NOMENCLATURE INDICATES EXISTING DEVICE WHEN

SHOWN ON PLANS ADJACENT TO SYMBOL.

L11-17

UNLESS NOTED OTHERWISE, NOMENCLATURE SHOWN NEXT

TO DEVICE SYMBOL INDICATES THE PANEL AND BRANCH

CIRCUIT WHICH SHALL BE USED TO FEED THE DEVICE.

PANEL ID

CKT. NO.

"TR" NOMENCLATURE INDICATES TAMPER RESISTANT RECEPTACLE

WHEN SHOWN ON PLANS ADJACENT TO SYMBOL.

WALL OUTLET WITH TYPE OF RECEPTACLE AS NOTED.

MOUNT 18 INCHES ABOVE FINISHED FLOOR TO CENTER,

UNLESS NOTED OTHERWISE.

GENERAL DEMOLITION NOTES:

GD1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE

SITE TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS. THESE

REMOVAL DRAWINGS SHALL SERVE TO AID THE CONTRACTOR IN HIS

EVALUATION OF THE EXTENT OF REMOVALS, BUT SHALL NOT BE HELD

TO BE ALL INCLUSIVE.

GD2. FOR FURTHER REQUIREMENTS WITH REGARD TO EXTENT OF

REMOVALS, SEE THE NEW CONSTRUCTION PLANS WHICH ILLUSTRATE

THE ADJACENT NEW CONSTRUCTION.

GD3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS

REQUIRED FOR THE INSTALLATION OF NEW WORK, WHETHER OR NOT

IT IS SPECIFICALLY INDICATED OR NOTED IN THESE DOCUMENTS.

GD4. ALL CONDUIT RUNS TO REMOVED EQUIPMENT SHALL HAVE ALL

CONDUCTORS REMOVED, UNLESS CONDUCTORS ARE REQUIRED TO

SERVE EXISTING EQUIPMENT TO REMAIN.

GD5. REMOVAL OF EMPTY CONDUIT SHALL BE REQUIRED ONLY IF

SUCH CONDUIT INTERFERES WITH THE NEW CONSTRUCTION AND/OR IF

INDICATED TO BE DISCONNECT AND REMOVED COMPLETE BACK TO

SOURCE OF FEED.

GD6. IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN

MUST BE RELOCATED OR REMOVED DUE TO OTHER DEMOLITION OR

DUE TO INTERFERENCE WITH NEW EQUIPMENT INSTALLATION, THE

CIRCUITS SHALL BE MODIFIED IN A MANNER WHICH SHALL ENSURE

PROPER OPERATION OF THE EQUIPMENT AFTER THE CONSTRUCTION

IS COMPLETE. CONTRACTOR SHALL USE THE SAME GAUGE AND TYPE

OF CONDUCTOR, AND THE SAME CONDUIT SIZE AS EXISTING TO MAKE

ALL REQUIRED CIRCUIT MODIFICATIONS.

GD7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER

DISPOSAL OF ALL EQUIPMENT REMOVED.

GD8. OWNER RESERVES THE FIRST RIGHT OF REFUSAL OF REMOVED

EQUIPMENT.

GD9. THE CONTRACTOR SHALL COORDINATE DISRUPTION OF

SERVICES WITH THE OWNER. DISRUPTIONS OF SERVICES SHALL BE

KEPT TO A MINIMUM. DISRUPTIONS SHALL ONLY OCCUR AFTER

RECEIVING OWNER PRIOR APPROVAL.

GD10. THE CONTRACTOR SHALL REFER TO THE MECHANICAL,

PLUMBING, AND ARCHITECTURAL PLANS FOR ADDITIONAL

REQUIREMENTS ON EQUIPMENT AND AREAS REQUIRING

DISCONNECTIONS AND REMOVALS.

GD11. IT IS NOT THE INTENT OF THIS DRAWING TO SHOW ALL EXISTING

ELECTRICAL DEVICES, EQUIPMENT, AND ITEMS TO BE DISCONNECTED

AND REMOVED. THIS DRAWING DOES NOT SHOW ALL ELECTRICAL

DEVICES, EQUIPMENT, AND ITEMS TO BE DISCONNECTED AND

REMOVED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING

THE PROJECT AREAS TO BECOME FAMILIAR WITH THE EXISTING

CONDITIONS AND TO DETERMINE THE AMOUNT OF REMOVALS.

LIGHTING FIXTURE SCHEDULE

MANUFACTURERDESCRIPTION

TYPE

FIXTURE SERIES

LAMP

LITHONIA

LEDS 4000K

(90,000 HRS WITH

81% LUMEN

MAINTENANCE)

80 CRI

CSVT-L48-AL03-MVOLT- SWW3 80CRI

SERIES

LITHONIA

LED RED

ECRG RD SERIES

WATTS

MOUNTING

FIXTURE

VOLTAGE

120/277

(MULTI-

VOLT)

44W

(NOMINAL

FIXTURE

INPUT

WATTS)

SUSPENDED

/ CHAIN

120/277

(MULTI-

VOLT)

AS

REQ'D

CEILING

REMARKSSYMBOL

F1H

4' VAPER TIGHT LED STRIP FIXTURE WITH

STAINLESS STEEL LATCHES & 301 STAINLESS

MOUNTING HARDWARE. SWITCHED TO HIGH

LUMEN OUTPUT.

[FIXTURE LUMEN OUTPUT ~ 5000 LUMENS]

EX1R

EXIT LIGHTING FIXTURE, SINGLE-FACED, WHITE

HOUSING, RED LETTERS. PROVIDE WITH BATTERY

BACK UP SYSTEM TO ILLUMINATE SIGN ON LOSS OF

NORMAL POWER SOURCE FOR A MINIMUM OF 90

MINUTES WITH SELF-DIAGNOSTICS FUNCTIONALITY.

PROVIDE WITH INTEGRAL LIGHT HEADS FOR

EGRESS ILLUMINATION.

ISOLITE

DUAL-LITE LED

BUG-6W-WH-SD SERIES

EV4D-02WAL SERIES

120/277

(MULTI-

VOLT)

6W

(NOMINAL

FIXTURE

INPUT

WATTS)

WALL

EMB1

LED THERMOPLASTIC EMERGENCY LIGHTING UNIT

WITH TWO LED FIXTURE HEADS, INTEGRAL

BATTERY BACK-UP WITH HIGH OUTPUT LITHIUM

IRON PHOSPHATE BATTERIES CAPABLE OF 90

MINUTES OF OPERATION ON LOSS OF NORMAL

POWER SOURCE. PROVIDE WITH SELF-

DIAGNOSTICS.

(END OF LIGHTING FIXTURE SCHEDULE)

LITHONIA ELM4L SERIES

CONTRACTOR SHALL DETERMINE BEST INSTALLATION HARDWARE

SELECTION BASED ON INSTALLATION MATERIALS AND SURFACES.

CONTRACTOR SHALL DETERMINE IF WET LOCATION FITTINGS OUT BOTH

ENDS OPTION IS REQUIRED FOR INSTALLATION.

BEACON

LEDS 5000K

(50,000 HRS WITH

70% LUMEN

MAINTENANCE)

90+ CRI

RWL1-48L-15-5K7-4W-UNV

120/277

(MULTI-

VOLT)

15W

(NOMINAL

FIXTURE

INPUT

WATTS)

WALLF3

LOW PROFILE LED WALL LUMINAIRE SCONCE WITH

DIE-CAST HOUSING.

FIXTURE LUMEN OUTPUT ~ 2000 LUMENS]

DUAL-LITE EVCURWD4 SERIES

COMPASS CCRG SERIES

COOPER APVT SERIES

KURTZON WL-SEG SERIES

EX1L

PROVIDE CHEVRONS AS INDICATED.

ELITE LIGHTING

LEDS 4000K

(50,000 HRS WITH

70% LUMEN

MAINTENANCE)

90+ CRI

RL675-1100L-DIMTR-120-27K/30K/35K/40K/

50K-90-WH/RL-ACC-SLIM-6-ROUGHPLATE

SERIES

120/277

(MULTI-

VOLT)

14W

(NOMINAL

FIXTURE

INPUT

WATTS)

RECESSEDF2

6” ROUND MULTI-CCT & OUTPUT LED SLIM DISK

WITH DIE CAST ALUMINUM BODY & TRIM, ROUND

FLAT LENS WITH WHITE TRIM. PROVIDE WITH

ROUGH-IN PLATE AS REQUIRED FOR

INSTALLATION.

FIXTURE LUMEN OUTPUT ~ 1000 LUMENS]

CONTRACTOR SHALL DETERMINE BEST INSTALLATION HARDWARE

SELECTION BASED ON INSTALLATION MATERIALS AND SURFACES.

CONTRACTOR SHALL FIELD SET / SELECT COLOR TEMPERATURE AND

FIXTURE OUTPUT IN FIELD PER MFG INSTALLATION INSTRUCTIONS.

SUBSTITUTIONS BY ARCHITECT AND ENGINEER APPROVAL ONLY.

SUBSTITUTIONS BY ARCHITECT AND ENGINEER APPROVAL ONLY.

HALO HLB6LSFS5 SERIES

NLS

TRC-LWM-1-T4FTW-16L-35-50K8-UNV-WSM-

D-STANDARD FINISH-CTG SERIES

SURE-LITE LPXC25R3SD

SURE-LITE SELHP100R3SD

BEGHELLI USA BS100LED-4-HT-LO-WT40-120-277V

LIGHTOLIER

FD2-6R-SLM-Z10-SCT-U-W-

DSANCPR468 SERIES

ILP SWS-2L-U-50-T4 SERIES

BEGHELLI USA EPC-ATR

BEGHELLI USA BBXSEWHTAT

JUNO

WF6-ALO20-SWW5-90CRI-MW-M6

SERIES

LITHONIA ARC1 LED-P2-50K-MVOLT SERIES

R e d

W h t

Wht

Blk/Orn Blue

Blue

Relay (if req'd)

Normally Closed

Photocell (if req'd)

Common

Normally Open

Auto Dimming Ctrl (if req'd)

7-Brn

8-Vio

6-Gry

5-Blu

4-Vio w/ Wht stripe

3-Blk

2-Wht

1-Red

SWITCH "a" N

SWITCH "b"

Power Pack

Additional Occupancy

Sensor (qty. as shown on Lighting Plans)

3-WAY

SWITCH

3-WAY

SWITCH

4-WAY

SWITCH

UNSWITCHED HOT CONDUCTOR.

SWITCHED HOT CONDUCTOR.

Occupancy

Sensor

LIGHTING CONTROL DIAGRAM - TYPICAL FOR ROOMS WITH SINGLE OR

MULTIPLE CONTROL SWITCHES & OCCUPANCY SENSORS

NO SCALE

7-Brn

8-Vio

6-Gry

5-Blu

4-Vio w/ Wht stripe

3-Blk

2-Wht

1-Red

B lk

Relay (if req'd)

Relay (if req'd)

Relay (if req'd)

Normally Closed

Photocell (if req'd)

Common

Normally Open

Auto Dimming Ctrl (if req'd)

Relay (if req'd)

Relay (if req'd)

GENERAL LIGHTING CONTROL NOTES:

A. OCCUPANCY SENSOR DESIGNS ARE BASED ON PRODUCTS BY ACUITY LIGHTING CONTROLS. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY

DESIGN CHANGES REQUIRED TO USE PRODUCTS BY ANOTHER MANUFACTURER.

B. CEILING MOUNT SENSOR LOCATIONS ARE BASED ON SENSOR SWITCH CM PDT9 SERIES OCCUPANCY SENSOR.

C. IT IS NOT THE INTENT OF THIS DRAWING TO SHOW, NOR DOES THIS DRAWING SHOW EVERY CONFIGURATION OF LIGHTING CONTROL DIAGRAM REQUIRED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL LIGHTING CONTROL PER THE LIGHTING CONTROL SYSTEM

MANUFACTURER'S REQUIREMENTS.

OPERATION & PROGRAMMING NOTE: OCCUPANCY SENSORS SHALL ALLOW LIGHTING FIXTURES TO BE "TURNED ON" VIA THE LIGHTING CONTROL SWITCHES WHEN OCCUPANCY HAS BEEN DETECTED. THE LIGHTING FIXTURES SHALL REMAIN "ON" UNTIL AREA HAS BEEN FOUND TO BE "UNOCCUPIED" FOR THE PROGRAMMED TIME PERIOD (OR WHENEVER THE LIGHTING CONTROL SWITCH HAS BEEN TURNED "OFF". COORDINATE "ON" DURATION TIME PERIODS FOR EACH TYPE OF ROOM WITH OWNER PRIOR TO INSTALLATION OF THE

OCCUPANCY SENSORS.

NOTE: CONTROL DIAGRAM IS TYPICAL FOR ALL SPACES WITH ONE OR MORE

SWITCHES AND ONE OR MORE OCCUPANCY SENSORS, UNLESS NOTED OTHERWISE.

NOTE: SWITCH CONFIGURATIONS SHOWN FOR WIRING

REFERENCE ONLY. SWITCH CONFIGURATION FOR A

PARTICULAR SPACE SHALL BE A COMBINATION OF THE

ABOVE TYPES OF SWITCHES, QUANTITY AS INDICATED

ON THE LIGHTING PLANS.

R E

NI

G

NEAN L

OI

S

E

S

F O R P

E

KENTU

C

K Y

FO

ET

A T S

D

ESNE

L I C

CRAIG

34886

AJ

SON

A&E FILE NO.

DRAWING DATE

DRAWN BY

CHECKED BY

DECA LOG #

DRAWING INFORMATION

DRAWING NO.

AS BUILT DATE

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKY

ACCOUNT NO.

670-CBRB-PF28-00

PHASE

RTA DATE

RTA

09/08/2026

09/08/2026

/2 /2

:3

:3

A M

E101BJH

09/08/2026

2505-196

JMC

ELECTRICAL LEGEND

-1

P E

N N

Y R

IL

E

F O

R E

S T

B E

A C

H R

E S

T R

O O

M B

U

IL

D

IN

G

PENNYRILE FOREST BEACH RESTROOM BUILDING

ADD-001 11/17/26

ADD-002 11/23/26

Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM