This document is an Addendum (Addendum No. Two) for an HVAC Upgrades project for Kentucky State Police Post 3 in Bowling Green, Kentucky, issued by the Commonwealth of Kentucky's Department for Facilities and Support Services, Division of Engineering and Contract Administration. The addendum, dated July 1, 2025, provides several key modifications to the original bid documents, including specific instructions for work schedules, demolition activities, and drawing revisions. Notably, the contractor must schedule attic work with the owner at least 48 hours in advance, complete duct cleaning after 5:00 pm or at night when building occupancy is lower, and replace several original drawings with revised versions dated 06/27/25.
The addendum includes technical details such as instructions for installing an attic access hatch using a Fakro Model DRL Flat Roof Hatch with an LML aluminum folding access ladder, sawcutting existing metal deck and concrete roof structure, and options for using existing lighting fixtures. The owner will relocate stored materials from the mechanical room, and the contractor has specific requirements for working in the attic, including heat considerations and timing of work. The document is part of a comprehensive HVAC upgrade project that involves mechanical, electrical, and structural modifications to the Kentucky State Police facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Final_RFB_785_2500000731_4_SO_FORM.PDF | ||
| Final_RFB_785_2500000731_1_SO_FORM.PDF | ||
| Addendum 1.pdf | ||
| Final_RFB_785_2500000731_3_SO_FORM.PDF | ||
| Final_RFB_785_2500000731_2_SO_FORM.PDF | ||
| Addendum 3.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMONWEALTH OF KENTUCKY
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
INVITATION TO BID NO: RFB-267-25
FOR: HVAC Upgrades
Kentucky State Police- Post 3 Bowling Green, Kentucky
DATE: July 1, 2025
RFB-785-2500000731
ADDENDUM NO. Two (2)
BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING
UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.
Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.
END OF ADDENDUM
Invitation to Bid No. RFB-267-25 For: HVAC Upgrades
Kentucky State Police- Post 3 Bowling Green, Kentucky
Janis Wilhoite, Statewide Procurement Analyst II Division of Engineering and Contract Administration
POST 3 – HVAC UPGRADES
KENTUCKY STATE POLICE
BOWLING GREEN, KENTUCKY
MARCUM NO. 24619
ACCOUNT NO. 520-CBZ6-BG02-00
ADDENDUM 2.00
JULY 1, 2025
The following Addendum Items shall be made part of the Contract Documents for the referenced project.
2.01 Refer to Section 10000.4 – Daily Work Times. Work schedules for work to be completed in the attic can be adjusted due to the heat potential in the attic.
Contractor shall schedule with the Owner at minimum 48 hours prior to work commencing.
2.02 Refer to Section 10000.4 – Daily Work Times. Duct cleaning work shall be completed during afternoons after 5:00pm or at night when building occupancy is lower. This work shall not occur between 6:00am and 5:00pm.
2.03 Refer to Drawing DME1.1. Omit this drawing in its entirety and replace with the attached Drawing DME1.1 Revision 1 dated 06/27/25.
2.04 Refer to Drawing ME1.1. Omit this drawing in its entirety and replace with the attached Drawing ME1.1 Revision 1 dated 06/27/25.
2.05 Refer to Drawing ME4.1. Omit this drawing in its entirety and replace with the attached Drawing ME4.1 Revision 1 dated 06/27/25.
2.06 Refer to Drawing ME5.1. Omit this drawing in its entirety and replace with the attached Drawing ME5.1 Revision 1 dated 06/27/25.
2.07 Refer to Drawing ME1.1, Mechanical Construction Tag Note 9. Contractor shall saw cut existing metal deck and concrete roof structure between existing bar joists for installation of attic access hatch with pull down ladder. Attic access shall be equal to Fakro Model DRL Flat Roof Hatch, deck mount, R-value 8.3, with Model LML aluminum folding access ladder to be adjusted for the deck height; five year warranty. At the opening in the existing roof, the Contractor shall furnish and install framing per the attached detail on Sketch XH01.
2.08 Refer to Drawing ME1.1. There are existing lighting fixtures in the attic. The
Contractor shall have the option to make existing lighting fixtures operational in lieu of providing temporary lighting for construction lighting.
2.09 Refer to Drawings DME1.1 and ME1.1. The Owner will relocate all stored materials from mechanical room.
Attachments:
1. Drawing DME1.1, Revision 1
2. Drawing ME1.1, Revision 1
3. Drawing ME4.1, Revision 1
4. Drawing ME5.1, Revision 1
5. Sketch XH01
END OF ADDENDUM 2.00
A.A.
16x14 SA x1
SA
12Ø SA
x1
SA
20x14 SA14x10 SA x1
SA
18x14 SA14x10 SA10x10 SA8x10 SA8x8 SA
4-2
VVT 3-2
VVT
5-3
VVT
4-3
VVT 3-3
VVT
2-3
VVT
1-3
VVT
2-4
VVT
3-4
VVT
1-4
VVT
1-4
VVT
BP-4
VVT
1-2
VVT
2-2
VVT
BP-3 VVT
12x10 SA
3-1
VVT
T T T
T
T
T
T
T T
T
T
T
TT
T
2-1
VVT
1-1
VVT
EF
EF
EF
RH
IU
IU
IU
EF
EF
EF
EF
R
EF R
EF
REF
REF
DISPATCH
VEST.
ADMIN. OFFICE
OFFICE
103OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
EVIDENCE
OFFICE
OFFICE
RADIO
TECH
EVIDENCE
CONFERENCE
WOMENS
MENS
VEST.
OFFICE
118 FILE STOR.
MECH. /
STOR.
WOMENS
123 LOUNGE
IDF
CORRIDOR
JAN.
RESTROOM
OFFICE
OFFICE
OFFICE
MENS
VEST.
OU
OU
OU
OU
IU
IU
(TYP.)
(TYP.)
STOR.
T
PANTRY
OFFICE
T
CF CF
14x12 SA
12 12
17 7
CF
10x10 SA
(TYP.)
(TYP.)
VVT
CU CU CU CU
(TYP.)
EUH
2 2
5 5 x1
SA
(TYP.)
(TYP.)
N G
GFIGFI
WP
L
WH
(TYP)
F F F
F
SS
NORTH
PROJECT
SCALE: 1/8" = 1'-0"
DEMOLITION FLOOR PLAN
A
B
C
17 18 19 20
F
D
E
G
H
J
K
L
N
M
O
P
R
1 2 43 5 6 87 9 10 11 12 13 14 15 16
DECA LOG #
DRAWING NO.
AS BUILT DATE
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKYACCOUNT NO.
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
A&E FILE NO. 24619
DRAWING DATE 05/07/2025
DRAWN BY
CHECKED BY
PHASE RTA
RTA DATE
DRAWING INFORMATION
KSP POST NO. 3 - HVAC UPGRADES
3119 NASHVILLE ROAD, BOWLING GREEN KY
520-CBZ6-BG02-00
05/23/2025
Paducah, KY Office
2301 McCracken Blvd Paducah, KY 42001
270-444-9274 MarcumEngineering.net
BA/MM
BY/AD DME1.1
MECH-ELEC DEMOLITION PLAN
MECHANICAL
DEMOLITION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
1 CONTRACTOR SHALL REMOVE EXISTING BYPASS DAMPER AND ASSOCIATED
DUCTWORK BACK TO MAIN AND CAP.
2 CONTRACTOR SHALL MANUALLY OPEN EXISTING VVT DAMPER AND FIX IN THE
FULL OPEN POSITION.
3 REMOVE EXISTING EXHAUST FAN. PROTECT DUCTWORK FOR REUSE.
4 CAP EXISTING DUCT OFF FOR ZONE 1 DUCT MODIFICATIONS.
CONTRACTOR SHALL REMOVE EXISTING FURNACES, REFRIGERANT PIPING,
DISCONNECT GAS PIPING, CONDENSING UNITS, ETC. PROTECT SUPPLY
DUCTWORK FOR REUSE WHERE INDICATED.
REMOVE ALL EXISTING THERMOSTATS, CONTROLS, WIRING, ETC. IN ITS ENTIRETY.
INSTALL BLANK COVER PLATE ON WALL BOXES. COLOR SHALL BE MATCH
EXISTING ELECTRICAL DEVICE COVER PLATES.
7 EXISTING DUCTLESS MINI SPLIT SYSTEM TO REMAIN.
8 REMOVE EXISTING DIFFUSER AND FLEXIBLE DUCTWORK BACK TO SHEETMETAL
DUCT. PROTECT SHEET METAL DUCT FOR REUSE, UNLESS OTHERWISE NOTED.
9 REMOVE EXISTING RETURN AIR GRILLE AND ANY ASSOCIATED SOUND TRAP IN ITS
ENTIRETY. INSTALL NEW CEILING TILE IN ITS LOCATION TO MATCH EXISTING.
10 REMOVE EXISTING DIFFUSER, FLEXIBLE DUCT, AND DUCT TAKEOFF TO MAIN AND
CAP.
11 REMOVE SECTION OF DUCTWORK AS INDICATED IN ITS ENTIRETY. PROTECT
REMAINING DUCTWORK FOR RESUSE. REFER TO NEW WORK PLAN.
12 REMOVE EXISTING DIFFUSER, FLEXIBLE DUCT, ETC. IN ITS ENTIRETY. INSTALL
NEW CEILING TILE IN ITS LOCATION TO MATCH EXISTING.
REMOVE EXISTING CONCENTRIC VENT FLUES THROUGH WALL AND ALL
ASSOCIATED COMBUSTION AIR INTAKE AND FLUE BACK TO EACH FURNACE
INCLUDING ALL HANGERS AND SUPPORTS.
14 PROTECT EXISTING OUTSIDE AIR LOUVER AND DUCTWORK FOR REUSE.
DISCONNECT FROM EXISTING RETURN AIR CONNECTIONS.
REMOVE EXISTING FURNACE, REFRIGERANT PIPING, DISCONNECT GAS PIPING,
CONDENSING UNITS, ETC. IN ITS ENTIRETY. REMOVE SUPPLY AIR DUCT TO
EXTENTS SHOWN. PROTECT REMAINING SUPPLY AIR DUCT FOR REUSE.
16 REMOVE EXISTING RETURN AIR DUCT IN ITS ENTIRETY. PATCH OPENINGS IN
MECHANICAL ROOM WALLS TO MATCH EXISTING.
17 EXISTING ATTIC ACCESS OPENING ABOVE LAY-IN CEILING.
18 REMOVE EXISTING DUCTLESS SPLIT UNIT, REFRIGERANT PIPING, ETC. IN ITS
ENTIRETY.
19 REMOVE EXISTING EXHAUST FAN AND ASSOCIATED DUCTWORK IN ITS ENTIRETY.
PROTECT EXISTING LOUVER FOR REUSE.
20 CONTRACTOR SHALL REMOVE EXISTING WATER HEATER AND ASSOCIATED PIPES
UP TO CEILING SPACE PROTECT PIPING FOR REUSE.
DEMO NATURAL GAS PIPING BRANCHES FROM FURNACES BACK TO MAIN.
PROTECT EXISTING NATURAL GAS MAIN PIPING FOR REUSE. MODIFY GAS PIPING
AS NECESSARY TO PERFORM NEW WORK.
22 DEMO EXISTING UNIT HEATER AND ASSOCIATED COMPONENTS IN ITS ENTIRETY.
ELECTRICAL
DEMOLITION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
CONTRACTOR SHALL REMOVE AND DISCONNECT ALL WIRE AND CONDUIT FROM
THE FURNACE BACK TO THE NEAREST JUNCTION BOX. REMOVE 1P20A BREAKER
FROM PANEL B1 CIRCUIT 1,2,3,AND 4.
CONTRACTOR SHALL REMOVE AND DISCONNECT ALL WIRE AND EXPOSED
CONDUIT FROM THE ELECTRICAL DISCONNECT BACK TO THE PANEL. REMOVE
3POLE BREAKER FROM PANEL B1 CIRCUIT (5,7,9), (11,13,15),(16,18,20) AND
(26,28,30). DISCONNECT AND REMOVE CONDUIT ATTACHED TO THE OUTSIDE
BRICK WALL.
CONTRACTOR SHALL DISCONNECT AND REMOVE WIRE AND CONDUIT FROM
EXHAUST FAN BACK TO THE NEAREST JUNCTION BOX. CONTRACTOR SHALL
DISCONNECT AND REMOVE WIRE FROM LIGHT SWITCH TO EXHAUST FAN.
4 CONTRACTOR SHALL REMOVE AND DISCONNECT THE HVAC CONTROLS IN THEIR
ENTIRETY BACK TO SOURCE.
5 NO ELECTRICAL WORK TO BE COMPLETED IN AREA.
6 CONTRACTOR SHALL DISCONNECT WIRE FROM UNIT. REMOVE WIRE AND CONDUIT
BACK TO SOURCE IN ITS ENTIRETY ALONG WITH LOCAL DISCONNECT.
CONTRACTOR SHALL DISCONNECT AND REMOVE WIRE AND CONDUIT FROM
EXHAUST FAN BACK TO THE NEAREST JUNCTION BOX. CONNECTION TO LIGHT
SWITCH AND CIRCUIT SHALL REMAIN.
8 REMOVE WIRE AND CONDUIT FROM EXHAUST FAN BACK TO SOURCE. REMOVE
SWITCH CONTROL WITH INTERLOCKS IN THEIR ENTIRETY.
9 DISCONNECT POWER FROM EXISTING WATER HEATER. PROTECT CONNECTIONS
FOR RE-USE.
10 DISCONNECT AND REMOVE WIRE FROM AC UNIT TO DISCONNECT.
CONTRACTOR SHALL DISCONNECT WIRE FROM UNIT. REMOVE WIRE AND CONDUIT
BACK TO SOURCE IN ITS ENTIRETY ALONG WITH LOCAL DISCONNECT. REMOVE
2P25 BREAKER AND REPLACE WITH BLANK COVER.
12 EXISTING RECEPTACLE SHALL STAY IN PLACE AND ACTIVE. PROTECT DURING
DEMOLITION.
REMOVE EXISTING UNIT HEATER IN ITS ENTIRETY INCLUDING WIRE AND EXPOSED
CONDUIT BACK TO THE PANEL. PLACE BLANK FACEPLATE OVER EXPOSED
OPENING.
CONTRACTOR SHALL DISCONNECT WIRE FROM UNIT. REMOVE WIRE AND CONDUIT
BACK TO NEAREST JUNCTION BOX IN ITS ENTIRETY ALONG WITH LOCAL
DISCONNECT.
Addendum 2.0
4" COMPACTED CA-6
SEE SITE PLAN FOR WIDTH
FINISHED GRADE
4" THICK CONCRETE SLAB 4500
PSI MIN. COMPRESSIVE
STRENGTH REINFORCED W/ 6X6
- W1.4XW1.4 W.W.F. (BROOM
FINISH)
NOTE: TOOLED CONSTRUCTION JOINTS SHALL BE
MADE ON MAXIMUM JOINT SPACING TO SIDEWALK
WIDTH RATIO OF 1:1 (TYP.) EXPANSION JOINTS @
MAXIMUM 100' INTERVALS.
THICKENED SIDEWALK EDGE
WHERE NOTED ON THE DRAWINGS
NOTE:
1. CONTROL JOINTS SHALL BE MADE ON MAXIMUM JOINT SPACING TO
SIDEWALK WIDTH RATION OF 1:1 (TYP.)
2. CONTROL JOINTS IN OTHER PEDESTRIAN CONCRETE AREAS SHALL BE
PER PLAN AND NOT TO EXCEED 10'.
CONTROL JOINT (DEPTH = 1/4 SLAB
THICKNESS).
2 SCALE: N.T.S.
CONCRETE CONTROL JOINT1 SCALE: N.T.S.
FLUSH CONCRETE SIDEWALK
1.
0'
X X X X X X X X X X
CIVIL
DEMOLITION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
1 EXISTING CONCRETE PATIO AND SIDEWALK TO REMAIN AND BE PROTECTED.
2 REMOVE EXISTING SHRUBS INCLUDING ALL ROOT BALLS, ROOTS, ETC. IN THEIR
ENTIRETY.
REMOVE EXISTING GRAVEL, WEED BARRIER, AND SOILS TO 12" BELOW EXISTING
GRADE. REMOVE 4" CORRUGATED DRAINAGE PIPE FROM CENTER OF AREA AND
CAP BELOW GRADE.
6/27/25
A.A.
16x14 SA x1
S
A
14x10 SA
18x14 SA10x10 SA
12x10 SA
DISPATCH
VEST.
ADMIN. OFFICE
101OFFICE
103OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
EVIDENCE
OFFICE
OFFICE
RADIO
TECH
EVIDENCE
CONFERENCE
WOMENS
MENS
VEST.
OFFICE
FILE STOR.
MECH. /
STOR.
WOMENS
123 LOUNGE
IDF
CORRIDOR
JAN.
RESTROOM
OFFICE
OFFICE
OFFICE
MENS
VEST.
STOR.
PANTRY
OFFICE
14x12 SA
10x10 SA
RH
IU
IU
OU
OU
IU
CF CF CF
S-2
S-2
S-2
S-3
S-3
S-3 310 S-2
S-1
S-1
S-1
S-1
S-1
S-2
S-2
S-1
S-2 165 S-2
S-2
S-2
S-2
S-1
S-1
S-3
S-3
16x14 SA
16x14 SA
Ø
S A
S-1 50 10 x1
S A
S-2
S-2
6x
S A
S-1 x1
S
A12x10 SA
16x14 SA x1
S
A
S-1
S-2 x1
S
A
10x10 SA
14x16 RA12x14 RA
14x16 RA
6x
R A
6x
R A x1
R
A
14x16 RA14x14 RA12 x1
R
A
8x10 RA
8x
R A
8x
R A
R-1
R-1
R-1
R-1
R-1
R-1
R-1
R-1
R-1
R-1 x1
R
A
10x8 RA
R-1
6x
R A
R-1
12x12 RA 10x10 RA
6x6 RA
6x6 RA
8x8 RA
R-1
R-1
R-1
S-1
S-1
10x12 RA
12x12 RA 6x6 RA
10x12 RA10x12 RA
R-1
R-1
R-1
6 7
8 7
AHU
HP
L
R-1
R-1
EF
EF
4 EF
EF
EF
EF
HP
HP
HP
HP
10x10 EA 12x12 OAL
X
10x10 SA
16x16 RA
S-4
S-4
OU
IU
D
SS
16x14 SA
R E
F
R E
F
B-2
PANTRY
MAIN
E
M M M
M
HP
HP
HP
HP
REF
REF
WH
F
F
F
F
MECH. /
STOR.
(TYP.)
(TYP.)
L
A.A.
DISPATCH
VEST.
ADMIN. OFFICE
101OFFICE
103OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
EVIDENCE
OFFICE
OFFICE
RADIO
TECH
EVIDENCE
CONFERENCE
WOMENS
MENS
VEST.
OFFICE
FILE STOR.
MECH. /
STOR.
WOMENS
123 LOUNGE
IDF
CORRIDOR
JAN.
RESTROOM
OFFICE
OFFICE
OFFICE
MENS
VEST.
STOR.
PANTRY
OFFICE
(TYP)
2 2
EPEP EPEP EPEP EPEP3
4 5
6 6 6
6 6
SS 8
OSOS
OSOS
OSOS
OSOS
OSOS
EPEP
EPEP
EPEPEPEP
EPEPEPEP
EPEP
EPEP
EPEP
EPEP
B1-5,7 B1-11,13
B1-16,18 B1-26,28
EPEP EPEP EPEP
EPEP
B1-2
B1-4
B1-1
B1-3
AHU
HP
EF
EF
4 EF
EF
EF
EF
HP
HP
HP
HP
F
F
F
F
B-1 B-2
MAIN
E
PANTRY
MAIN
E
10~
GFIGFI
WP
B1-24
WH-1
MECH. /
STOR.
OU
IU
EPEP
EPEP
SS
NORTH
PROJECT
SCALE: 1/8" = 1'-0"
MECH FLOOR PLAN
A
B
C
17 18 19 20
F
D
E
G
H
J
K
L
N
M
O
P
R
1 2 43 5 6 87 9 10 11 12 13 14 15 16
DECA LOG #
DRAWING NO.
AS BUILT DATE
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKYACCOUNT NO.
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
A&E FILE NO. 24619
DRAWING DATE 05/07/2025
DRAWN BY
CHECKED BY
PHASE RTA
RTA DATE
DRAWING INFORMATION
KSP POST NO. 3 - HVAC UPGRADES
3119 NASHVILLE ROAD, BOWLING GREEN KY
520-CBZ6-BG02-00
05/23/2025
Paducah, KY Office
2301 McCracken Blvd Paducah, KY 42001
270-444-9274 MarcumEngineering.net
BA/MM
BY/AD ME1.1
MECH-ELEC FLOOR PLAN
MECHANICAL
CONSTRUCTION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
RETURN AIR DUCT TO RISE FROM UNIT CONNECTION AND INTO ATTIC. SAWCUT
OPENING IN EXISTING CEILING/ROOF FOR DUCT TO PASS THROUGH INTO ATTIC
SPACE AND. COORDINATE LOCATION OF OPENING WITH EXISTING CONDITIONS
AND STRUCTURE.
2 DUCT MAINS ROUTED IN ATTIC.
SUPPLY AIR DUCT TO RISE TO ATTIC SPACE THROUGH EXISTING OPENING DUCT
INSULATION SHALL BE CONTINUOUS THROUGH OPENING. MODIFY OPENING AS
REQUIRED FOR NEW DUCTSIZE.
4 INSTALL 10x10 SA CONNECTION ON TOP OF DUCT AND CONNECT TO EXISTING
DUCT IN ATTIC.
5 INSTALL 12x10 SA CONNECTED TO EXISTING 12x10 SA DUCT ROUTED AND CONNECTED TO EXISTING 20x14 SA.
INSTALL 10x8 RA THROUGH EXISTING ROOF/CEILING TO ATTIC. CONTRACTOR
SHALL SAW CUT OPENING TO ALLOW INSULATION TO PASS THROUGH
CONTINUOUS.
INSTALL 8x8 RA THROUGH EXISTING ROOF/CEILING TO ATTIC. CONTRACTOR
SHALL SAW CUT OPENING TO ALLOW INSULATION TO PASS THROUGH
CONTINUOUS.
INSTALL 12x10 RA THROUGH EXISTING ROOF/CEILING AT ATTIC. CONTRACTOR
SHALL SAW CUT OPENING TO ALLOW INSULATION TO PASS THROUGH
CONTINUOUS.
9 MAINTAIN AREA CLEAR OF DUCTWORK FOR ACCESS TO ATTIC.
ROUTE NEW NATURAL GAS PIPING FROM FURNACES TO EXISTING PIPING
BRANCHES. MODIFY EXISTING PIPING ROUTING AS NECESSARY TO PERFROM
NEW WORK.
FURNISH AND INSTALL WATER HEATER. LOCATE WHERE PREVIOUS UNIT WAS
REMOVED. RECONNECT TO EXISTING PIPING AT CEILING. REFER TO DETAILS
FOR ADDITIONAL REQUIREMENTS.
ROUTE FURNACE CONDENSATE PIPING TO MECHANICAL ROOM FLOOR DRAIN.
MAINTAIN ADEQUATE SLOPE FOR PIPING. REFER TO DETAILS FOR MORE
INFORMATION.
NORTH
PROJECT
SCALE: 1/2" = 1'-0"
MECHANICAL ROOM FLOOR PLAN
ELECTRICAL
CONSTRUCTION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
PROVIDE AND INSTALL WIRE AND EMT CONDUIT FROM NEAREST JUNCTION BOX
TO RECONNECT EXHAUST FAN TO EXISTING CIRCUIT. SEE M5.1 EQUIPMENT
CONNECTION SCHEDULE FOR WIRE, CONDUIT AND BREAKER SIZE.
PROVIDE AND INSTALL WIRE AND EMT CONDUIT FROM NEAREST JUNCTION BOX
TO RECONNECT FURNACE TO EXISTING WIRE AND CIRCUIT. PROVIDE CIRCUIT
BREAKER OF SIMILAR TYPE TO PANEL B CIRCUITS 1,2,3, AND 4. SEE M5.1
EQUIPMENT CONNECTION SCHEDULE FOR WIRE, CONDUIT AND BREAKER SIZE.
PROVIDE AND INSTALL A DISCONNECT SWITCH FOR CONDENSING UNIT. USE THE
SAME LOCATION FROM THE REMOVED DISCONNECT. PATCH AND SEAL ANY
EXPOSED OPENING. CONNECT DISCONNECT TO CONDENSING UNIT. SEE M5.1
EQUIPMENT CONNECTION SCHEDULE FOR WIRE, CONDUIT, DISCONNECT SIZE.
PROVIDE AND INSTALL A CIRCUIT BREAKER OF SIMILAR TYPE IN PANEL B1
CIRCUIT( 5,7) IN PLACE OF THE REMOVED 3 POLE BREAKER. PLACE A BLANK
COVER OVER THE REMAINING OPEN SPOT. UPDATE THE PANEL SCHEDULE.
PROVIDE AND INSTALL WIRE AND EMT CONDUIT FROM PANEL B1 TO DISCONNECT.
SEE M5.1 EQUIPMENT CONNECTION SCHEDULE FOR WIRE, CONDUIT BREAKER
SIZE.
PROVIDE AND INSTALL A 2P CIRCUIT BREAKER OF SIMILAR TYPE IN PANEL B1 IN
PLACE OF THE REMOVED 3 POLE BREAKER. PLACE A BLANK COVER OVER THE
REMAINING OPEN SPOT. UPDATE THE PANEL SCHEDULE. PROVIDE AND INSTALL
WIRE AND EMT CONDUIT FROM PANEL B1 TO DISCONNECT. SEE M5.1 EQUIPMENT
CONNECTION SCHEDULE FOR WIRE, CONDUIT BREAKER SIZE.
6 NO ELECTRICAL WORK TO BE COMPLETED IN AREA.
7 RECONNECT INDOOR AND OUTDOOR UNIT TO EXISTING WIRE AND CIRCUIT.
8 EXISTING LIGHT SWITCH SHALL CONTINUE TO CONTROL EXHAUST FAN AND
LIGHTS.
PROVIDE, INSTALL AND CONNECT A LINE VOLTAGE, CEILING MOUNTED
OCCUPANCY SENSOR TO CONTROL EXHAUST FAN. LIGHTS SHALL CONTINUE TO
BE CONTROLLED BY LIGHT SWITCH IN ROOM.
PROVIDE AND INSTALL ALL WIRE AND EMT CONDUIT FROM SOURCE BACK TO
EQUIP. PROVIDE AND INSTALL A 3P BREAKER OF SIMILAR KIND. MOVE CIRCUIT
BREAKERS AS NEEDED TO PROVIDE SPACE FOR BREAKER IF IT DOES NOT
ALREADY EXIST. SEE ME5.1 FOR BREAKER SIZE AND WIRE SIZE.
11 PROVIDE AND INSTALL ALL WIRE AND EMT CONDUIT FROM SOURCE BACK TO
EQUIP. SEE ME5.1 FOR BREAKER SIZE AND WIRE SIZE.
PROVIDE AND INSTALL A SURFACE MOUNT RECEPTACLE IF NO SERVICE OUTLET
IS ALREADY PRESENT WITHIN 25'. CORE DRILL THROUGH WALL TO CONTINUE
CIRCUIT TO PANEL.
PROVIDE AND INSTALL WIRE AND CONDUIT FROM NEAREST JUNCTION BOX BACK
TO THE WATER HEATER. REPLACE BREAKER WITH SIMILAR KIND 2P30.SEE
DRAWING ME5.1 FOR WIRE AND CONDUIT SIZE.
PROVIDE AND INSTALL WIRE AND RMT CONDUIT FROM NEAREST JUNCTION BOX
TO RECONNECT SPLIT HEAT PUMP TO EXISTING CIRCUIT. SEE M5.1 EQUIPMENT
CONNECTION SCHEDULE FOR WIRE, CONDUIT AND BREAKER SIZE. REPLACE
CURRENT BREAKER WITH A 2P30 OF SIMILAR KIND IN PANEL.
PROVIDE AND INSTALL A DISCONNECT SWITCH FOR SPLIT HEAT PUMP UNIT. USE
THE SAME LOCATION FROM THE REMOVED DISCONNECT. PATCH AND SEAL ANY
EXPOSED OPENING. CONNECT DISCONNECT TO SPLIT HEAT PUMP. SEE M5.1
EQUIPMENT CONNECTION SCHEDULE FOR WIRE, CONDUIT, DISCONNECT SIZE.
NORTH
PROJECT
SCALE: 1/8" = 1'-0"
ELEC FLOOR PLAN
A
ME1.1
A
ME1.1
DUCT RUN-OUT
SCHEDULE
CFM RANGE SIZE
0 - 100 6"Ø
101 - 200 8"Ø 201 - 375 10"Ø 376 - 600 12"Ø
CIVIL
CONSTRUCTION TAG NOTES
(APPLIES TO THIS DRAWING ONLY)
1 EXISTING PATIO AND SIDE WALK TO REMAIN AND BE PROTECTED.
CONTRACTOR SHALL BACKFILL AREA UNDER 14'X18' CONCRETE PAD WITH
MINIMUM 12" OF COMPACTED DGA TO OBTAIN CORRECT ELEVATION. CONCRETE
PAD SHALL BE 4" THICK AND SLOPE 1% WAY FROM THE BUILDING. ELEVATION
SHALL MATCH EXISTING PATIO TOP OF CONCRETE.
INSTALL #4 REBAR ON 18" CENTERS ALONG CONNECTION OF NEW PAD TO
EXISTING PATIO. REBAR SHALL BE DOWELLED INTO EXISTING PATIO 6" AND
CENTERED IN EXISTING CONCRETE THICKNESS.
4 INSTALL THICKENED SLAB ALONG THE EDGE WHERE INDICATED.
REPAIR ALL GRADES. REMOVE ROCKS AND DEBRIS. SEED, STRAW, AND
ESTABLISHED NEW GRASS TO MATCH EXISTING.
Addendum 2.0 6/27/25
A
B
C
17 18 19 20
F
D
E
G
H
J
K
L
N
M
O
P
R
1 2 43 5 6 87 9 10 11 12 13 14 15 16
DECA LOG #
DRAWING NO.
AS BUILT DATE
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKYACCOUNT NO.
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
A&E FILE NO. 24619
DRAWING DATE 05/07/2025
DRAWN BY
CHECKED BY
PHASE RTA
RTA DATE
DRAWING INFORMATION
KSP POST NO. 3 - HVAC UPGRADES
3119 NASHVILLE ROAD, BOWLING GREEN KY
520-CBZ6-BG02-00
05/23/2025
Paducah, KY Office
2301 McCracken Blvd Paducah, KY 42001
270-444-9274 MarcumEngineering.net
BA/MM
BY/AD ME4.1
MECH-ELEC DETAILS
FURNACE INSTALLATION DETAIL
NO SCALE
UNION
SUPPLY
AIR DUCT
COMBUSTION
AIR INTAKE
EXHAUST
VENT
REFRIGERANT
COIL
REFRIGERANT PIPING
INSULATE LINES PER
SPECIFICATIONS
RETURN AIR DUCT
P-TRAP REFER TO DETAIL
CONTROL WIRING IN CONDUIT
FURNACE
FILTER RACK
GAS MAIN
PIPING
GAS PIPING. REFER
TO PLUMBING
DRAWINGS.
FULL SIZE
GAS COCK
DIRT LEG
CAP
REDUCED TO UNIT
CONNECTION SIZE
CONCRETE MAINTENANCE
PAD. REFER TO HVAC NOTES
FOR REQUIREMENTS.
MCONTROL DAMPER CONTROL
WIRING INTERLOCKED WITH
WALL MOUNT CO2 SENSOR
MANUAL
VOLUME
DAMPER
OUTSIDE AIR DUCT
CONTROL DAMPER
FULL-SIZE CONDENSATE DRAIN
ROUTE TO OPEN RECEPTACLE.
REFER TO PLUMBING DRAWINGS
NOTE:
ORIENTATION AND CONNECTION POINTS
MAY VARY. REFER TO HVAC PLANS AND
SCHEDULES.
CONTRACTOR SHALL FURNISH AND
PLACE CONCRETE SPLASH BLOCK
2"
SLEEVE AND SEAL COPPER CONDENSATE
DRAIN PIPING THRU WALL AND TURN
DOWN TO WITHIN 6" OF GRADE
TERMINATE CONDENSATE IN
SPLASH BLOCK ON GRADE
CONDENSATE DRAIN TERMINATION DETAIL
NO SCALE
SEE CONDENSATE
DRAIN TRAP DETAIL
TRANSITION FROM PVC
TO COPPER PRIOR TO
WALL PENETRATION
B D
A C
CONDENSATE DRAIN TRAP DETAIL
NO SCALE
HVAC
UNIT
1" PVC LINE OR MATCH CONN. SIZE
IF GREATER THAN 1"
ROUTE CONDENSATE DRAIN TO HEADER, FLOOR DRAIN, OR
GRADE AS INDICATED ON DRAWINGS
NOTE:
1. "RUNNING" TRAPS ARE NOT ACCEPTABLE.
2. EXTERNAL TRAP NOT REQUIRED IF INTERNAL TRAP IS PROVIDED BY EQUIPMENT MANUFACTURER.
PIPE PLUG (TYP.)
UNION
SLOPE
SLOPETEE (TYP.)
POSITIVE UNIT PRESSURE
C= 1" + FAN TSP
D= 1" MTN.
NEGATIVE UNIT PRESSURE
A= 1/2 (B)
B= 1" + FAN TSP
HORIZONTAL INSTALLATION
SIDE VIEW
HORIZONTAL PIPE
VERTICAL INSTALLATION
REFRIGERANT PIPE SUPPORT DETAIL
NO SCALE
CEILING. REFER TO
ARCHITECTURAL
DRAWINGS.
SECURE PIPE
SUPPORT TO
WALL.
WALL. REFER TO
ARCHITECTURAL AND
STRUCTURAL
DRAWINGS.
SECURE TO
STRUCTURE.
12" MIN.
SCH. 40 PVC PIPE
(TYPICAL)
REFRIGERANT PIPING
AND INSULATION
CONTINUOUS
THROUGH SLEEVE
SECURE PIPE SLEEVE
TO SUPPORT
SECURE TO
STRUCTURE.
UNI-STRUT OR OTHER
APPROVED PIPE CLAMP
ALL-THREAD
ROD
INSULATION
CONTINUOUS
THROUGH
SLEEVE (TYP.)
UNI-STRUT OR OTHER
APPROVED SUPPORT
REFRIGERANT PIPING
AND INSULATION
SECURE PIPE SLEEVE
TO SUPPORT
CARBON STEEL, STRUT
MOUNT, INSULATION
COUPLING CLAMP EQUAL
TO KLO-SHURE INSULATION
COUPLINGS
VERTICAL INSTALLATION
WALL. REFER TO
ARCHITECTURAL AND
STRUCTURAL
DRAWINGS.
OPTIONAL
STRUT MOUNT
SADDLE-SHAPED
PIPE SUPPORT
SECURE PIPE SLEEVE
TO SUPPORT
REFER TO PLANS FOR
QUANTITY OF LINE SETS
CONDENSING UNIT SPLIT SYSTEM
NO SCALE
REFRIGERANT SUPPLY & RETURN
LINES TO A/C COIL
4" HOUSE KEEPING PAD
COIL WITH GRILLE
CONDENSING OUTDOOR UNIT
ELECTRICAL CONNECTION TO
WEATHERPROOF FUSED
DISCONNECT BY ELECTRICIAN
SUSPEND EXHAUST FAN
FROM STRUCTURE WITH
THREADED ROD AND
VIBRATION ISOLATORS.
CEILING EXHAUST FAN WITH REMOVEABLE
EXHAUST GRILLE FOR ACCESS TO AND SERVICE
OF BLOWER ASSEMBLY.
DUCTWORK - SEE PLANS
FOR SIZE.
CEILING MOUNTED EXHAUST FAN DETAIL
NO SCALE
FLEX CONNECTOR
BACKDRAFT DAMPER
LAY-IN OR GYP.
CEILING ASSEMBLY
RETURN-AIR GRILLE PLENUM DETAIL
NO SCALE
NOTE:
1. FLEXIBLE DUCT SHALL NOT
BE USED TO CONNECT
GRILLES TO DUCT.
RETURN AIR DUCT
(SEE PLAN FOR SIZE)
RETURN AIR DUCT
(SEE PLAN FOR SIZE)
FULL SIZE INTERNALLY
INSULATED PLENUM
CEILING (SEE
ARCHITECTURAL)
RETURN AIR GRILLE
(SEE SCHEDIULE)
" M
IN
L
W
45°
L = 1/4 W
(4" MIN.)
RECTANGLE TAKE-OFF
NOTE:
SPIN-INS, RAKE-OFFS,
EXTRACTORS, SPLITTERS, ETC.
WILL NOT BE ACCEPTED
UNLESS OTHERWISE NOTED.
AIR FLOW
SUPPLY AIR TRUNK DUCT
SUPPLY AIR DUCT TAKE-OFF CONNECTION DETAIL
NO SCALE
TAPE VAPOR BARRIER OF
FLEXIBLE DUCT TO METAL
DUCT OR DIFFUSER BACK
VAPOR BARRIER WITH FOIL
BACK TAPE
VOLUME DAMPER W/
HANDLE STAND-OFF
EXTERNALLY INSULATED ROUND
DUCT (SEE PLAN FOR SIZE AND
LENGTH OF RUN)
1" GASKETED FLANGE
45° TAKE-OFF
CONNECT FLEXIBLE
DUCT TO FITTING W/
METAL CLAMP
CEILING DIFFUSER
WITH DIFFUSER BACK
INSULATION (SEE PLAN
FOR SIZE AND TYPE)
INSULATED FLEXIBLE
DUCT 5'-0" MAX LENGTH
SEE PLAN FOR SIZE
LONG RADIUS, HARD
ELBOW TO BE INSTALLED
BEFORE FLEXIBLE DUCT
ATTACH 1/4" SELF-LOCKING
PLASTIC CABLE TIE WITH
TWO(2) SHEETMETAL
SCREWS TO SHEETMETAL
DUCTWORK
ROUND TAKE-OFF
AIR FLOW
SUPPLY AIR TRUNK DUCT
ELECTRICAL EQUIPMENT LABEL/IDENTIFICATION
NO SCALE
3"
LETTERING SIZE = 12 PT.
2"
EQUIPMENT DESIGNATION:
SERVED BY:
CIRCUIT NO:
LOCATION:
LOAD SERVED
VOLTAGE:
AF
W
LAMICOID EQUIPMENT LABEL
EQUIPMENT
ENCLOSURE
ARC FLASH WARNING
LABEL
SHOCK HAZARD WARNING
SIGN
LAST METHOD IS TO SURFACE
MOUNT WIREMOLD AND BOX TO
FINISHED INTERIOR WALL. THIS
METHOD SHALL BE USED ONLY IF THE
OTHER TWO METHODS ARE NOT
POSSIBLE.
EXISTING WALL
FINISHED FLOOR
CONDUIT ROUTING/INSTALLATION
THIRD METHOD DETAIL
NO SCALE
FIRST METHOD IS TO EMBED DEVICE
HANDY BOX AND CONDUIT INTO NEW
OR EXISTING INTERIOR WALL WHERE
POSSIBLE
NEW OR EXISTING WALL
FINISHED FLOOR
SURFACE MOUNT CONDUIT IN UTILITY
AREA AND THEN THROUGH WALL TO
BOX
SURFACE MOUNT
CONDUIT/WIREMOLD AND HANDY BOX
TO FINISHED INTERIOR WALL. THIS
METHOD SHALL BE USED ONLY IF THE
FIRST METHOD IS NOT POSSIBLE.
EXISTING WALL
FINISHED FLOOR
UTILITY AREA SIDE WHEN AVAILABLE
(IE: STORAGE,
MECHANICAL/ELECTRIC EQUIPMENT
ROOMS AND JANITORIAL AREAS)
CONDUIT ROUTING/INSTALLATION
FIRST METHOD DETAIL
NO SCALE
CONDUIT ROUTING/INSTALLATION
SECOND METHOD DETAIL
NO SCALE
COLD WATER IN
THERMAL EXPANSION
TANK
COLD WATER
SHUT-OFF VALVE
HOT WATER OUT
TEMPERATURE
AND PRESSURE
HOT WATER
WATER HEATER
DIELECTRIC UNION (TYP.)
SHUT-OFF VALVE
CHECK VALVE
THERMOMETER
RELIEF VALVE
ELECTRIC WATER HEATER DETAIL
NO SCALE
4" THICK CONCRETE
MAINTENANCE PAD
16 GAUGE GALVANIZED
AUXILIARY DRAIN PAN
INSTALL FOR ALL
INSTALLATION ABOVE
CEILINGS OR ON EQUIP.
MEZZANINES ABOVE
CEILINGS
RUN RELIEF VALVE
PIPING TO FLOOR
DRAIN, MOP SINK OR
TO WITHIN 6" OF
OUTSIDE GRADE
INSTALL DRAIN LINE WITH
SHUT-OFF VALVE ROUTE
LINE TO SUITABLE DRAIN
WHERE POSSIBLE
NOTE:
WHEN WATER HEATERS ARE INSTALLED
IN PARALLEL, THE PIPES FROM THE TEE
TO EACH WATER HEATER SHALL BE OF
EQUAL LENGTH FOR BOTH COLD AND
HOT WATER PIPE.
INDOOR WALL MOUNTED
MINI SPLIT UNIT BY M.C.
CEILING SYSTEM
SPREADER BAR BY E.C.
WIRING AND EMT CONDUIT EXTENDING
TO OUTDOOR UNIT, ROUTE WITH PIPING
ABOVE CEILING, BY E.C.
30 AMP, 600 VOLT, DOUBLE POLE,
SINGLE PHASE AC MANUAL MOTOR
CONTROLLER, SUITABLE AS
MOTOR DISCONNECT, TOGGLE,
INDUSTRIAL GRADE, WHITE WITH
WHITE FACE PLATE, FLUSH IN
CEILING, BY E.C. (LEVITON CAT. #
MS302-DSW OR EQUAL)
M.C. CABLE BY E.C. ROUTED
TO UNIT WITH PIPING
COORDINATE
SURFACE MOUNTED
PIPING AND CABLE
COVER BY M.C.
NOTE:
a. COORDINATE ALL WORK WITH M.C.
b. LABEL TOGGLE SWITCH WITH
OUTDOOR UNIT DESIGNATION
WHEN PIPING ENTERS FROM BACK,
EXTEND MC THROUGH 2-PIECE SURFACE
MOUNTED RACEWAY FROM CEILING TO
UNIT, ALLOW SPACE FOR T'STAT WIRING
INDOOR MINI-SPLIT DETAIL
NO SCALE
Addendum 2.0 6/27/25
AutoCAD SHX Text
A
B
C
17 18 19 20
F
D
E
G
H
J
K
L
N
M
O
P
R
1 2 43 5 6 87 9 10 11 12 13 14 15 16
DECA LOG #
DRAWING NO.
AS BUILT DATE
FRANKFORT, KENTUCKY
DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION
DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES
FINANCE AND ADMINISTRATION CABINET
COMMONWEALTH OF KENTUCKYACCOUNT NO.
DATEDESCRIPTION OF REVISIONS
REVISION HISTORY OF THIS DRAWING
DATEDESCRIPTION OF REVISIONS
A&E FILE NO. 24619
DRAWING DATE 05/07/2025
DRAWN BY
CHECKED BY
PHASE RTA
RTA DATE
DRAWING INFORMATION
KSP POST NO. 3 - HVAC UPGRADES
3119 NASHVILLE ROAD, BOWLING GREEN KY
520-CBZ6-BG02-00
05/23/2025
Paducah, KY Office
2301 McCracken Blvd Paducah, KY 42001
270-444-9274 MarcumEngineering.net
BA/MM
BY/AD ME5.1
MECH-ELEC SCHEDULES
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
ITEM # DESCRIPTION VOLTAGE/PHASE
ELEC. DATA CONDUCTORS LOCAL DISCONNECTING MEANS
REMARKS/
NOTESLOAD UNITS MCA MOCP CONDUIT LINE NEU GND N.F.D.S. SIZE F.D.S. SIZE FUSE SIZE ENCL
NEMA
F-1 FURNACE 115/1 - - 9.6 1P15 3/4" #12 #12 #12 BREAKER - - - A,D,H
F-2 FURNACE 115/1 - - 11.5 1P15 3/4" #12 #12 #12 BREAKER - - - A,D,H
F-3 FURNACE 115/1 - - 11.5 1P15 3/4" #12 #12 #12 BREAKER - - - A,D,H
F-4 FURNACE 115/1 - - 11.5 1P15 3/4" #12 #12 #12 BREAKER - - - A,D,H
HP-1 AIR COOLED HEAT PUMP 208/1 - - 20.4 2P30 3/4" #10 - #10 2P30 - - 3R A,C
HP-2 AIR COOLED HEAT PUMP 208/1 - - 20.4 2P30 3/4" #10 - #10 2P30 - - 3R A,C
HP-3 AIR COOLED HEAT PUMP 208/1 - - 20.4 2P30 3/4" #10 - #10 2P30 - - 3R A,C
HP-4 AIR COOLED HEAT PUMP 208/1 - - 20.4 2P30 3/4" #10 - #10 2P30 - - 3R A,C
HP-5 AIR COOLED HEAT PUMP 208/3 - - 11.0 3P15 3/4" #12 - #12 3P30 - - 3R A,G,F
WH-1 WATER HEATER 208/1 4500 WATTS - 2P30 3/4" #10 - #10 BREAKER - - - -
IU-1 SPLIT HEAT PUMP UNIT 208 / 1 - - 2.1 2P30 1 / 2" #10 - #10 2P30 - - NEMA 3 I,J
OU-1 SPLIT HEAT PUMP UNIT 208 / 1 - - 2.1 2P30 1 / 2" #10 - #10 2P30 - - NEMA 3R I,J
AHU-1 SPLIT AIR HANDLING UNIT 208/1 - - 41.0 2P45 3/4" #6 - #10 2P60 - - 3 A,F,G
VENTILATION EQUIPMENT CONNECTION SCHEDULE
ITEM # DESCRIPTION VOLTAGE/PHASE
ELEC. DATA CONDUCTORS UNIT OPERATION
CONTROL
REMARKS/NOTES
LOAD UNITS MCA MOCP CONDUIT LINE NEU GND OCC SWITCH
EF-1 EXHAUST FAN 115/1 13 WATTS - 1P20 3/4" #12 #12 #12 X - A,B,E
EF-2 EXHAUST FAN 115/1 39 WATTS - 1P20 3/4" #12 #12 #12 X - A,B,E
EF-3 EXHAUST FAN 115/1 13 WATTS - 1P20 3/4" #12 #12 #12 X - A,B,E
EF-4 EXHAUST FAN 115/1 13 WATTS - 1P20 3/4" #12 #12 #12 X - A,B,E
EF-5 EXHAUST FAN 115/1 7 WATTS - 1P20 3/4" #12 #12 #12 - X A,B,E
EF-6 EXHAUST FAN 115/1 13 WATTS - 1P20 3/4" #12 #12 #12 X - A,B,E
MECHANICAL AND VENTILATION GENERAL NOTES:
THE INFORMATION ABOVE SHALL BE COORDINATED WITH THE MECHANICAL EQUIPMENT AS TAGGED ACTUAL EQUIPMENT REQUIREMENTS SHALL TAKE PRESIDENCE OVER THE LISTED INFORMATION. CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT REQUIRED TO PLACE EQUIPMENT IN SERVICE. EQUIPMENT MANUFACTURER SHALL BE RESPONSIBLE FOR VARIATIONS IN ELECTRICAL FIELD CONNECTIONS DUE TO EQUIPMENT SUBSTITUTIONS - MODIFY OVERCURRENT, DISC. SW, WIRE SIZE ETC, AS NECESSARY.
2 THIS SCHEDULE INCLUDES, BUT IS NOT LIMITED TO, THE EQUIPMENT FOUND ON THIS PROJECT, COORDINATE WITH ALL TRADES AND PROVIDE MANUFACTURERS MINIMUM REQUIREMENTS TO ALL EQUIPMENT INSTALLED. THIS SCHEDULE IS NOT TO IMPLY QUANTITY OF EQUIPMENT, REFER TO CONSTRUCTION DOCUMENTS OF RESPECTIVE TRADE FOR LOCATION AND QUANTITIES.
3 STARTER/MOTOR SWITCH/DISCONNECT SHALL BE LOCATED ADJACENT TO UNIT IN ACCORDANCE WITH N.E.C. ARTICLE #110 & #440 - MAINTAIN WORKING CLEARANCES.
4 ALL FIELD WIRING TO UNITS SHALL BE PROPERLY SUPPORTED PER NEC AND ENCLOSURES SHALL BE PROPERLY RATED FOR THE INSTALLATION CONDITIONS. PROPERLY BOND AND GROUND.
5 CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF ANY EQUIPMENT SHIPPED LOOSE WITH UNIT, SUCH AS CONTROLS - INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
6 EC SHALL FURNISH AND INSTALL ALL RACEWAY AND BOXES AS REQUIRED FOR THE MC FURNISHED CONTROLS. COORDINATE WITH MC BEFORE INSTALLATION.
7 EC SHALL FURNISH AND INSTALL ALL RACEWAY AND BOXES AS REQUIRED FOR THE MC FURNISHED LINE VOLTAGE CONTROLS. EC TO RECEIVE DEVICES, FURNISH AND INSTALL ALL WIRING AND CONDUIT. LINE
VOLTAGE DEVICE SHALL BE INSTALLED BY EC. COORDINATE WITH MC BEFORE INSTALLATION.
UNIT OPERATION CONTROL:
OCC. UNIT SHALL BE CONTROLLED BY ZONE LIGHT CONTROL. COORDINATE INTERCONNECTION OF FAN TO LIGHTING POWER CIRCUIT WITH THE ELECTRICAL CONTRACTOR
SWITCH SWITCH - UNIT SHALL BE CONTROLLED BY INDEPENDENT PILOT LIT SWITCH. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL PILOT LIGHT SWITCH. SWITCH SHALL BE ILLUMINATED WHEN FAN IS ENERGIZED.
SPECIAL NOTES:
A UNIT PROVIDED WITH THERMAL OVERLOAD PROTECTION.
B PROVIDE UNIT WITH FACTORY WIRED, PLUG-TYPE DISCONNECT.
C ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ELECTRICAL DISCONNECTS FOR UNIT(S).
D EQUIPMENT SHORT-CIRCUIT CURRENT RATING (SCCR) SHALL BE EQUAL TO, OR GREATER THAN THE MINIMUM AS SCHEDULED. EQUIPMENT NAME PLATE SHALL INCLUDE SCCR IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE 2017 440.4(B). SCCR SHALL BE PROVIDED FOR ENGINEERING REVIEW ON EQUIPMENT SHOP DRAWING SUBMITTALS.
E ELECTRICAL CONTRACTOR SHALL INSTALL SPEED CONTROLLER FOR FAN. HVAC CONTRACTOR SHALL PROVIDE CONTROLLER. FIELD COORDINATE LOCATION OF CONTROLLER ADJACENT TO UNIT.
F ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ELECTRICAL DISCONNECTS SWITCH WITH A SINGLE POINT CONNECTION.
G EQUIPMENT SHORT-CIRCUIT CURRENT RATING (SCCR) SHALL BE EQUAL TO, OR GREATER THAN THE MINIMUM AS SCHEDULED. EQUIPMENT NAME PLATE SHALL INCLUDE SCCR IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE 2017 440.4(B). SCCR SHALL BE PROVIDED FOR ENGINEERING REVIEW ON EQUIPMENT SHOP DRAWING SUBMITTALS.
H LOCAL CIRCUIT BREAKER SHOULD SERVE AS A DISCONNECTING MEANS FOR UNIT.
I ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ELECTRICAL DISCONNECT SWITCH FOR INDOOR AND OUTDOOR UNIT.
J INDOOR UNIT SHALL BE POWERED BY OUTDOOR UNIT.
FURNACE SCHEDULE
MARK MFG. MODEL TYPE CONFIG.
SIZE
(TONS)
SUPPLY
AIRFLOW
(CFM)
MAX OA
AIRFLOW
(CFM)
EXT. S.P.
(IN H2O) DRIVE
FAN DATA NATURAL GAS FIRED FURNACE DATA
COND. UNIT REMARKS AND
ACCESSORIES MARKMOTOR
(HP)
VOLTAGE/
PHASE
MCA
(AMPS)
MOCP
(AMPS)
INPUT
(MBH)
OUTPUT
(MBH)
MIN. EFF.
FLUE
SIZE
(INCHES)
F-1 YORK Y92E VERTICAL 3.0 1,000 100 0.75 DIRECT 1/2 115 / 1 8.8 15 60.0 58.0 97% 3 HP-1 SEE BELOW F-1
F-2 YORK Y92E VERTICAL 3.0 1,200 120 0.75 DIRECT 1/2 115 / 1 8.8 15 80.0 77.0 97% 3 HP-2 SEE BELOW F-2
F-3 YORK Y92E VERTICAL 3.0 1,200 120 0.75 DIRECT 1/2 115 / 1 8.8 15 80.0 77.0 97% 3 HP-3 SEE BELOW F-3
F-4 YORK Y92E VERTICAL 3.0 1,200 120 0.75 DIRECT 1/2 115 / 1 8.8 15 80.0 77.0 97% 3 HP-4 SEE BELOW F-4
REMARKS AND ACCESSORIES
1 PROVIDE UNIT WITH A MINIMUM TEN (10) YEAR HEAT EXCHANGER WARRANTY AND A ONE (1) YEAR PARTS AND LABOR WARRANTY.
2 PROVIDE UNIT WITH MATCHING CASED DX COOLING COIL BY FURNACE MANUFACTURER. PROVIDE A FACTORY INSTALLED, INTERNALLY MOUNTED TXV FOR DX COOLING COIL.
3 PROVIDE UNIT WITH A FACTORY-FABRICATED, HINGED FILTER RACK FLANGE-MOUNTED TO THE UNIT RETURN TO ACCEPT STANDARD NOMINAL SIZE (12" X 24" OR 24" X 24"), 2" THICK, MERV 13 AIR FILTERS. UNIT SHALL HAVE A GASKETED DOOR AND RAILS FOR EASY FILTER CHANGING. (BLC INDUSTRIES CLEAN-LINE SERIES 05FB OR APPROVED EQUAL). PROVIDE AN EXTRA SET OF REPLACEMENT FILTERS UPON PROJECT SUBSTANTIAL COMPLETION.
4 MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.
5 PROVIDE UNIT WITH VARIABLE SPEED, CONSTANT AIRFLOW ECM MOTOR.
6 PROVIDE UNIT WITH DRAIN SENSOR THAT SHUTS DOWN THE INDOOR UNIT ANY TIME A CLOGGED CONDENSATE DRAIN IS DETECTED IN THE DRAIN PAN.
7 PROVIDE UNIT SUITABLE FOR SEALED COMBUSTION OPERATION.
8 ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL NON-FUSED ELECTRICAL DISCONNECT SWITCH.
9 MECHANICAL CONTRACTOR SHALL PROVIDE UNIT WITH MANUFACTURER'S 7-DAY PROGRAMMABLE THERMOSTAT.
10 MECHANICAL CONTRACTOR SHALL SIZE AND PROVIDE UNIT WITH A NEEDLE-POINT IONIZATION DEVICE (GLOBAL PLASMA SOLUTIONS OR EQUAL). DEVICE SHALL BE PROVIDED AT 24V, POWERED AND CONTROLLED BY THE UNIT. IONIZATION DEVICE SHALL BE
ENERGIZED WHEN THE SUPPLY FAN FOR THE UNIT IS OPERATIONAL.
11 PROVIDE UNIT WITH MANUFACTURER'S HORIZONTAL CONCENTRIC VENT KIT.
12 COMBUSTION INTAKE AND FLUE VENT PIPING MATERIAL AND INSTALLATION SHALL BE PER MANUFACTURER'S REQUIREMENTS.
13 PROVIDE UNIT WITH 2-STAGE AUXILIARY NATURAL GAS HEAT. AUXILIARY NATURAL GAS HEAT SHALL ONLY BE ENERGIZED WHEN HEAT PUMP OPERATIONS ARE INADEQUATE TO MAINTAIN TEMPERATURE SET POINT DURING HEATING CONDITIONS.
CARRIER, DAIKIN, TRANE, YORK, OR APPROVED EQUAL
AIR COOLED HEAT PUMP UNIT SCHEDULE
MARK MFG. MODEL SIZE
WEIGHT
(LBS.)
TOTAL
COOLING
CAP.
(MBH)
SENSIBLE
COOLING
CAP.
(MBH)
EER @
DESIGN
HEATING
CAP.
(MBH)
HOT GAS
REHEAT
CAP.
(MBH)
HSPF @
DESIGN
VOLTAGE/
PHASE
MCA
(AMPS)
MOCP
(AMPS)
SCCR
(KA) SERVICE REMARKS AND
ACCESSORIES MARK
HP-1 YORK YH6 36 270 35.4 26.8 11.7 18.6 -- 8.1 208 / 1 20.4 30 -- F-1 1-11,16 HP-1
HP-2 YORK YH6 36 270 35.4 26.8 11.7 18.6 -- 8.1 208 / 1 20.4 30 -- F-2 1-11,16 HP-2
HP-3 YORK YH6 36 270 35.4 26.8 11.7 18.6 -- 8.1 208 / 1 20.4 30 -- F-3 1-11,16 HP-3
HP-4 YORK YH6 36 270 35.4 26.8 11.7 18.6 -- 8.1 208 / 1 20.4 30 -- F-4 1-11,16 HP-4
HP-5 AAON CFA 002 370 21.3 14.0 22.2 13.9 11.5 -- 208 / 3 11.0 15 10 AHU-1 1-10,12-16 HP-5
REMARKS AND ACCESSORIES:
1 PROVIDE UNIT WITH AT MINIMUM ONE (1) YEAR PARTS WARRANTY, ONE (1) YEAR LIMITED LABOR WARRANTY, AND FIVE (5) YEAR COMPRESSOR WARRANTY.
2 COOLING CAPACITIES ARE BASED ON 95 Fdb OUTDOOR AMBIENT TEMPERATURE AND 75 Fdb INDOOR TEMPERATURE.
3 HEATING CAPACITIES ARE BASED ON 0 Fdb OUTDOOR AMBIENT TEMPERATURE AND 70 Fdb INDOOR TEMPERATURE.
4 PROVIDE UNIT WITH LOW PRESSURE SWITCH, HIGH PRESSURE SWITCH, CRANKCASE HEATER, SUCTION PRESSURE TRANSDUCER, AND EVAPORATOR FREEZE THERMOSTAT.
5 PROVIDE UNIT WITH FACTORY INSTALLED THERMAL EXPANSION VALVE (TXV), REVERSING VALVE, AND FILTER DRYER.
6 PROVIDE UNIT WITH AT MINIMUM TWO-STAGE COMPRESSOR.
7 PROVIDE UNIT WITH HAIL GUARD ON CONDENSER COIL(S).
8 PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.
9 PROVIDE UNIT WITH REFRIGERANT HAVING A GLOBAL WARMING POTENTIAL LESS THAN 700 IN ACCORDANCE WITH CURRENT US EPA REGULATIONS.
10 FURNISH AND INSTALL REFRIGERANT PIPING SIZED AND ROUTED PER MANUFACTURER'S RECOMMENDATIONS.
11 HEAT PUMP UNIT SHALL BE FURNISHED BY FURNACE MANUFACTURER.
12 EQUIPMENT SHORT-CIRCUIT CURRENT RATING (SCCR) SHALL BE EQUAL TO, OR GREATER THAN THE MINIMUM AS SCHEDULED. EQUIPMENT NAME PLATE SHALL INCLUDE SCCR IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE 2017 440.4(B). SCCR
SHALL BE PROVIDED FOR ENGINEERING REVIEW ON EQUIPMENT SHOP DRAWING SUBMITTALS.
13 UNIT SHALL BE FURNISHED BY INDOOR HEAT PUMP AIR HANDLING UNIT MANUFACTURER.
14 PROVIDE UNIT WITH FULLY MODULATING HOT GAS REHEAT COIL AND CONTROL.
15 PROVIDE UNIT WITH ELECTRICAL PHASE LOSS PROTECTION.
16 ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ELECTRICAL DISCONNECT.
HP-1/2/3/4: CARRIER, DAIKIN, TRANE, YORK, OR APPROVED EQUAL / HP-5: AAON, UNITED COOL AIR, SAMSUNG, OR APPROVED EQUAL
LOUVER SCHEDULE
MARK MFG. DESCRIPTION MODEL/
TYPE
SIZE
(INCHES)
AIRFLOW
(CFM)
FREE
AREA
(SQ. FT.)
FACE
VELOCITY
(FPM)
PRESSURE
DROP
(IN. H2O)
TYPE OF FRAME
AND MOUNTING
MOUNTING
HEIGHT
(FT-IN)
SERVICE REMARKS AND
ACCESSORIES MARK
L-1 GREENHECK FIXED BLADE LOUVER ESD-435 24 X 16 X 4 400 0.99 404 0.03 CHANNEL 9'-4" AHU-1 INTAKE SEE BELOW L-1
REMARKS AND ACCESSORIES:
1 MOUNTING HEIGHT MEASURED FROM BOTTOM OF LOUVER TO TOP OF FINISHED FLOOR. CONTRACTOR SHALL COORDINATE LOUVER INSTALLATION WITH SOLDIER COURSE BRICK BAND AND EXISTING EXHAUST
LOUVER ELEVATION.
2 SIZES ARE SPECIFIED AS: FIRST FIGURE-WIDTH, SECOND FIGURE-HEIGHT, AND THIRD FIGURE- DEPTH.
3 PROVIDE UNIT WITH EXTENDED SILL.
4 PROVIDE UNIT IN ALUMINUM CONSTRUCTION.
5 PROVIDE UNIT WITH ALUMINUM BIRD SCREEN.
6 PROVIDE UNIT WITH FACTORY APPLIED, 2-COAT, 70% KYNAR FINISH. COLOR TO BE SELECTED BY OWNER.
7 INSTALL UNIT IN 18 GAUGE SHEETMETAL WALL SLEEVE.
8 CONTRACTOR SHALL FURNISH AND INSTALL LOOSE LINTEL AT OPENING FOR LOUVER.
GREENHECK, NCA, RUSKIN, UNITED ENERTECH, OR APPROVED EQUAL
Addendum 2.0 6/27/25
SPLIT HEAT PUMP SYSTEM EQUIPMENT SCHEDULE
INDOOR
UNIT
MARK
MFG. MODEL
NUMBER DESCRIPTION AREA SERVED
NOMINAL
(TONS)
APPROX. UNIT
WEIGHT
(LBS.)
MIN. REFRIG.
EQUIVALENT
LINE
LENGTH
(FT.)
MAX.
AIRFLOW
(CFM)
RATED
COOLING
CAPACITY
(MBH)
SEER2
RATED
HEATING
CAPACITY
(MBH)
HSPF2 VOLTAGE /
PHASE
MCA
(AMPS)
OUTDOOR
UNIT MARK MFG. MODEL
NUMBER
APPROX.
UNIT
WEIGHT
(LBS.)
ELECTRICAL DATA
REMARKS AND
ACCESSORIES
SYSTEM
MARKVOLTAGE /
PHASE
MCA
(AMPS)
MOCP
(AMPS)
SCCR
(kA)
IU-1 LG KNSAP361A HIGH WALL RADIO TECH 113 3.0 45 75 1,095 33.0 20.0 35.2 8.5 208 / 1 0.6 OU-1 LG KUSAP361A 150 208 / 1 23.0 30 5 SEE BELOW IU/OU-1
REMARKS AND ACCESSORIES:
1 PROVIDE UNIT WITH AT MINIMUM FIVE (5) YEAR PARTS WARRANTY, ONE (1) YEAR LIMITED-LABOR WARRANTY AND SEVEN (7) YEAR COMPRESSOR WARRANTY.
2 COOLING CAPACITIES BASED ON 95 F AMBIENT AIR TEMPERATURE AND 80 F db/67 F wb INDOOR AIR TEMPERATURE.
3 HEATING CAPACITIES BASED ON 47 F db AMBIENT AIR TEMPERATURE AND 70 F db/60 F wb INDOOR AIR TEMPERATURE.
4 MAINTAIN MANUFACTURER'S MINIMUM RECOMMENDED CLEARANCES.
5 FURNISH AND INSTALL REFRIGERANT PIPING SIZED AND ROUTED PER THE MANUFACTURER'S RECOMMENDATIONS. USE OF LINE SETS IS NOT ACCEPTABLE. TOTAL EQUIVALENT FOOTAGE OF LINE LENGTHS SHALL NOT EXCEED THE MANUFACTURER'S REQUIREMENTS OR THE ABOVE
SPECIFIED LENGTH, WHICHEVER IS LESS.
6 PROVIDE UNIT WITH REFRIGERANT HAVING A GLOBAL WARMING POTENTIAL LESS THAN 700 IN ACCORDANCE WITH CURRENT US EPA REGULATIONS.
7 ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ELECTRICAL DISCONNECTS FOR INDOOR AND OUTDOOR UNITS.
8 INDOOR UNIT SHALL BE POWERED BY OUTDOOR UNIT.
9 PROVIDE UNIT WITH WASHABLE, ANTI-MICROBIAL, LONG-LIFE AIR FILTER.
10 PROVIDE UNIT WITH MANUFACTURER'S WIRED PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING ALL UNIT FUNCTIONS. WIRELESS REMOTE CONTROLLER IS NOT ACCEPTABLE.
11 PROVIDE UNIT WITH LOW AMBIENT COOLING AND HEATING KIT CAPABLE OF OPERATION TO 0 Fdb.
CARRIER, DAIKIN, LG, MITSUBISHI, TRANE, OR APPROVED EQUAL
Sheet No.
Sheet Title
Checked By:
Drawn By :
Issue Date:
Project No.:
XH01
ATTIC OPENING
STRUCTURAL
SUPPORT
24619
6/30/2025
BCA
BCA
KS
P P
OS
T 3
- H
VA
C
UP
GR
AD
ES
N
AS
HV
ILL
E
RO
AD
, B
OW
LIN
G
GR
EE
N, K
EN
TU
CK
Y
DO NOT REPRODUCE
This document contains confidential information and is an instrument of service and property of the Engineer. It shall not be used on other projects or for the extension of this project without the Engineer's written approval.
Paducah, KY Office 2301 McCracken Blvd, Paducah, KY 42001 270-444-9274 / MarcumEngineering.net
MAIN RAIL
END REACTION
(TYP.)
CROSS RAIL
END REACTION
(TYP.)
QUICKFRAME ADJUSTABLE FRAME
ROOF FRAMING
RE: PLAN
ROOF FRAMING
RE: PLAN
SEE "FIELD REINFORCEMENT
OF BAR JOIST AT CONCENTRATED
LOADS" DETAIL FOR ADD'L
REQUIRED REINFORCING
QUICKFRAMES ADJUSTABLE STEEL ROOF FRAMES:
UNLESS SPECIFICALLY EXCLUDED ON PLAN, CONTRACTOR MAY PROVIDE THE FOLLOWING 12 GAGE (30 KSI) QUICKFRAMES OR 16 GAGE (30 KSI) ADJUSTABLE FRAMES AT MISCELLANEOUS OPENINGS IN STEEL ROOF FRAMING WHERE THE ROOF LIVE LOAD OR SNOW LOAD DOES NOT EXCEED 20 PSF AND THE TOTAL LOAD TO THE FRAME DOES NOT EXCEED THE LOADS SHOWN BELOW. USE THESE ADJUSTABLE FRAMES FOR OPENINGS REQUIRED BY SKYLIGHTS OR
MECHANICAL ROOFTOP UNITS.
CROSS RAIL END REACTION SHALL NOT EXCEED 1000 LBS.
MAIN RAIL END REACTION SHALL NOT EXCEED 1750 LBS.
THE TOTAL FRAME LOADS SHOWN BELOW INCLUDE A 20% INCREASE FOR MECHANICAL UNITS PER IBC SECTION 1607.8.2
AND AN INDUSTRY STANDARD UNBALANCED MECHANICAL LOADING OF 2/3 AND 1/3.
MECHANICAL LOADS
12 GAUGE FRAME
FRAME SPAN
FRAME
MAX. CROSS RAIL
OPENING SPAN
TOTAL
LOAD(LBS)
4'-0" 4'-0" 5'-0" 5'-0" 6'-0" 6'-0" 7'-0" 7'-0" 8'-0" 8'-0"
48" 96" 48" 96" 48" 96" 48" 96" 48" 96"
16 GAUGE FRAME
FRAME SPAN
FRAME
MAX. CROSS RAIL
OPENING SPAN
TOTAL
LOAD(LBS)
4'-0" 4'-0" 5'-0" 5'-0" 6'-0" 6'-0" 7'-0" 7'-0" 8'-0" 8'-0"
48" 96" 48" 96" 48" 96" 48" 96" 48" 96"
THE TOTAL FRAME LOADS SHOWN BELOW REFLECT THE MAXIMUM LOAD THE FRAME CAN CARRY WHEN ALL WEIGHT IS PLACED EVENLY ON THE MAIN RAILS AND DISTRIBUTED EVENLY BETWEEN ALL FOUR SUPPORT RAILS
EVENLY DISTRIBUTED LOADS
12 GAUGE FRAME
FRAME SPAN
FRAME
MAX. CROSS RAIL
OPENING SPAN
TOTAL
LOAD(LBS)
4'-0" 4'-0" 5'-0" 5'-0" 6'-0" 6'-0" 7'-0" 7'-0" 8'-0" 8'-0"
48" 96" 48" 96" 48" 96" 48" 96" 48" 96"
16 GAUGE FRAME
FRAME SPAN
FRAME
MAX. CROSS RAIL
OPENING SPAN
TOTAL
LOAD(LBS)
4'-0" 4'-0" 5'-0" 5'-0" 6'-0" 6'-0" 7'-0" 7'-0" 8'-0" 8'-0"
48" 96" 48" 96" 48" 96" 48" 96" 48" 96"
THESE QUICKFRAMES, OR THE OPENING THEY SPAN, SHALL NOT BE PLACED SO AS TO INTERFERE WITH THE REQUIREMENTS OF OTHER STRUCTURAL ELEMENTS (I.E. DRAG STRUTS, PURLINS, SUBPURLINS, ANGLES, ETC.) WITHOUT
THE PRIOR APPROVAL OF THE STRUCTURAL ENGINEER.
QUICKFRAMES ADJUSTABLE FRAMES SHALL BE AS MANUFACTURED BY QUICKFRAMES, A DIVISION OF SOYKO INDUSTRIES 480-464-1500 WWW.QUICKFRAMES.COM AND SHALL BE INSTALLED PER MANUFACTURER'S
RECOMMENDATIONS.
TYPICAL DETAIL
11 ADJUSTABLE FRAME FOR ROOF OPENINGS
| Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings. |
| END OF ADDENDUM |