Addendum 1 MTMS HVAC Controls RFP Sept 25 2024.pdf

PDF 22 MB Posted

Attached to
RFP for HVAC Controls
Solicitation number
RFP-CADI-240000003164-2
Issued by
Wexford County, Burt CDP, Michigan

About this file

This document is an Addendum for a Request for Proposals (RFP) issued by the Metropolitan Transportation Management System (MTMS) for HVAC Controls. The addendum provides updates and clarification to the original RFP.

The RFP requests proposals for the installation, configuration, and maintenance of HVAC controls for various facilities managed by MTMS. The project overview includes upgrading and integrating the HVAC control systems across multiple sites. Proposals are due by September 25, 2024. A mandatory pre-proposal conference was held on September 10, 2024 for all interested bidders. The contract term is for 5 years with an option to renew for an additional 5 years.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR PROPOSAL - HVAC Controls Cadillac Area Public Schools September 25, 2024

ADDENDUM 1

PUBLISHED SEPTEMBER 25, 2024

November 2022 VAV-PRC016E-EN

Product Catalog VariTrane™ Round Inlet/Round Outlet Model VRRF

©2022 Trane VAV-PRC016E-EN

Introduction The installed base of ducted HVAC systems is very vast and highly variable. No matter the system, retrofit and upgrading is inevitable. The retrofit terminal units discussed in this catalog are utilized for upgrading existing ducted HVAC systems, most notably in the area of controls. Using Trane’s vast knowledge of air volume control and unit controls, Round Inlet/Round Outlet Retrofit (VRRF) Terminal Units are used to improve energy efficiency and reduce overall operating cost in existing systems. Often VRRF units are used in the following applications:

• Bypass/replace existing mechanical regulator (air valve)

• Upgrade building and/or unit controls (e.g. Pneumatic to BACnet®) with or without replacing the mechanical regulator (air valve)

• Convert Constant Air Volume System to Variable Air Volume System

• Convert pressure dependent Variable Air Volume System to pressure independent Variable Air

Volume System (e.g. Trane VariTrac™)

• Convert Multizone (Dual Duct) Systems to Variable Air Volume System The VRRF terminal unit is also very beneficial for non-retrofit or new applications. This unit allows for great controllability, keeping occupied spaces comfortable in a very compact footprint. For those applications where space is at premium, but controls functionality is not, the VRRF terminal unit is ideal.

Copyright This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

• Added Symbio™ 500 unit controls information in Model Number chapter.

• Added Symbio™ 500 controller image in Controls chapter.

• Updated Mechanical Specifications chapter.

VAV-PRC016E-EN 3

Features and Benefits Construction

Agency Certifications UL-Listed Products AHRI Certified Performance American Society of Heating, Refrigerating and Air-conditioning Engineers

(ASHRAE)

Air Conditioning and Refrigeration Institute (AHRI) Underwriter’s Laboratory (UL) 1995 National Fire Protection Association (NFPA)

Application Considerations Flow Measurement and Control Retrofit Systems

Selection Procedure Trane Select Assist™ Air Valve Selection Acoustics Controls

Model Number

General Data

Performance Data Air Pressure Drop Acoustics Data

Controls Tracer Building Automation System

Electrical Data

Jobsite Connections

Dimensional Data

Weights

Table of Contents

4 VAV-PRC016E-EN

Mechanical Specifications Agency Listing Air Valve Direct Digital Controls Control Options Trane Hot Water Valves

Table of Contents

VAV-PRC016E-EN 5

Features and Benefits

Construction The basic unit consists of a sheet metal casing with an air damper which is used to modulate the air being delivered into the occupied zone. The unit is designed to modulate either cooling or heating air between the temperatures of 40 and 140°F. Primary air enters the air valve through its round inlet and sent into the air valve cylinder and exits from the round outlet. This air could be sent strait to the diffusers or in conjunction with a VAV unit that is being retrofitted.

Standard Features

• Available in 8 sizes (0- 4,000 cfm) for simple easy install in round ductwork

• Available for installation in both vertical or horizontal airflow

• Optional adapter plate for easy integration with legacy Trane VAV units

• Optional LEED wrap for preventing contamination during the construction phase

• Optional Factory mounted, wired, tested and commissioned pressure independent controls

– DDC (Comm3 or Comm 4), LonTalk, BACnet Communication

– Trane Air-Fi Wireless Communication

• Additional Factory mounted, wired, tested options

– Modulating Actuator

– Power Fuse

– Controls Transformer

– Toggle Disconnect Switch

– Relay Kits

– Duct Temperature Sensor

– Two-position or modulating hot water valves

Note: Two-position and modulating hot water valves ship separate from unit for field installation and connection to unit via wire harness provided.

6 VAV-PRC016E-EN

Agency Certifications There are numerous regulations and standards in the industry that determine the construction and performance parameters for terminal units. Some of the more important of those standards and regulations are listed below, along with a brief description of what each one addresses.

UL-Listed Products All VariTrane™ units are listed in accordance with UL -1995 as terminal units. This listing includes the terminal with electric heaters. Additionally, all insulation materials pass UL 25/50 smoke and flame safety standards.

AHRI Certified Performance All VariTrane™ units are AHRI certified. AHRI 880 guarantees the pressure drop, flow performance, and acoustical performance provided is reliable and has been tested in accordance with industry accepted standards. AHRI 885 uses AHRI 880 performance and applies accepted industry methods to estimate expected “NC” sound levels within the occupied space.

American Society of Heating, Refrigerating and Air-conditioning Engineers (ASHRAE)

ASHRAE - Standard 41.1 ASHRAE - Standard 41.2 ASHRAE - Standard 41.3 These standards specify methods for temperature measurement (41.1), laboratory airflow measurement (41.2), and pressure measurement (41.3). While none of these standards specifically discusses air terminals, they discuss topics that are aspects of terminal box systems. Therefore, some engineers will include these standards in their specifications as a primer on accepted measurement techniques.

ASHRAE - Standard 62.1 ASHRAE - Standard 111 This standard calls out procedures to be followed for testing and balancing HVAC systems. It includes descriptions of the equipment used, procedures followed, and field changes that must be made when a system is balanced.

Air Conditioning and Refrigeration Institute (AHRI) AHRI Standard 880 This standard sets forth classifications, performance testing requirements, and test results reporting requirements for air terminal units. The standard contains very detailed procedures that are to be followed for the testing and certification program associated with this standard. The operating characteristics tested include discharge and radiated sound power, wide-open pressure drop, and fan motor amp draw.

AHRI Standard 885-2008 This document provides a procedure to estimate sound pressure levels in an occupied space. The standard accounts for the amount of sound pressure in the space due to the air terminal, diffusers and their connecting low pressure ductwork. While sound generated from the central system fan and ductwork may be a significant factor in determining the sound pressure level in the room, this standard does not address those factors. It focuses solely on the terminal and items downstream of it. This standard is related to AHRI-880 by using sound power determined using AHRI-880 methodology as a starting point for the AHRI-885 procedure.

Underwriter’s Laboratory (UL) 1995 Underwriter’s Laboratory is an independent testing agency that examines products and determines if those products meet safety requirements. Equipment manufacturers strive to meet UL guidelines and

VAV-PRC016E-EN 7

obtain listing and classifications for their products because customers recognize UL approval as a measure of a safely designed product. terminals are listed per UL-1995, Heating and Cooling Equipment. The terminals are listed as an entire assembly.

National Fire Protection Association (NFPA)

NFPA 70

This standard is also known as the National Electrical Code (NEC). The Code gives standards for installation of wiring and electrical equipment for most types of commercial and residential buildings. It is often referred to in air terminal specifications when fan-powered boxes, electric heat or electric controls are included.

NFPA 90A

This standard does not speak directly to air terminals but does discuss central system considerations pertaining to a fire and/or smoke condition. The standard discusses safety requirements in design and construction that should be followed to keep the air-handling system from spreading a fire or smoke.

The standard specifies practices that are intended to stop fire and smoke from spreading through a duct system, keep the fire-resistive properties of certain building structures (fire walls, etc.) intact, and minimize fire ignition sources and combustible materials.

Agency Certifications

8 VAV-PRC016E-EN

Application Considerations Flow Measurement and Control

One of the most important characteristics of a VAV terminal unit is its ability to accurately sense and control airflow. The VariTrane™ terminal unit was developed with exactly that goal in mind. The patented, multiple-point, averaging flow ring measures the velocity of the air at the unit primary air inlet.

The differential pressure signal output of the flow ring provides the terminal unit controller a measurement of the primary airflow through the inlet. The terminal unit controller then opens or closes the inlet damper to maintain the controller airflow setpoint.

Flow Measurement Most of these terminal units contain a differential pressure airflow measurement device, mounted at the primary air inlet, to provide a signal to the terminal unit controller. Numerous names exist for the differential pressure measurement device—flow sensor, flow bar, flow ring. The differential pressure measured at the inlet varies according to the volumetric flow rate of primary air entering the inlet.

The total pressure and the static pressure are measurable quantities. The flow measurement device in a VAV terminal unit is designed to measure velocity pressure. Most flow sensors consist of a hollow piece of tubing with orifices in it. The VariTrane™ air valve contains a flow ring as its flow measuring device.

The flow ring is two round coils of tubing. Evenly spaced orifices in the upstream coil are the high-pressure taps that average the total pressure of air flowing through the air valve. The orifices in the downstream ring are low-pressure taps that average the air pressure in the wake of flow around the tube. By definition, the measurement of static pressure is to occur at a point perpendicular to the airflow.

The low-pressure taps on the VariTrane™ flow ring measure a pressure that is parallel to the direction of flow but in the opposite direction of the flow. This “wake pressure” that the downstream ring measures is lower than the actual duct static pressure. The difference between the “wake pressure” and the static pressure can be accounted for so that the above relationship between flow and differential pressure remain valid. The difference also helps create a larger pressure differential than the velocity pressure.

Since the pressures being measured in VAV terminal unit applications are small, this larger differential allows transducers and controllers to measure and control at lower flow settings than would otherwise be possible.

The average velocity of air traveling through the inlet is expressed in the equation:

FPM = 1096.5

VP

DENS

Where:

• FPM = Velocity of air in feet per minute

• 1096.5 = A constant

• VP = The velocity pressure of the air expressed in inches of water

• DENS = The density of the air expressed in pounds per cubic foot Often, the density is assumed to be a constant for dry air at standard conditions [68°F (20°C)] and sea level pressure of 14.7 psi (101.4 kPa). These conditions yield the following commonly used equation:

FPM = 4005 VP

The amount of air traveling through the inlet is related to the area of the inlet and the velocity of the air:

AIRFLOW (cubic feet per minute, cfm) = AREA (square feet) x AVERAGE VELOCITY (feet per minute)

Accuracy The multiple, evenly spaced orifices in the flow ring of the VariTrane™ terminal unit provide quality measurement accuracy even if ductwork turns or variations are present before the unit inlet. For the most accurate readings, a minimum of 1½ diameters, and preferably 3 diameters, of straight-run

VAV-PRC016E-EN 9

ductwork is recommended prior to the inlet connection. The straight-run ductwork should be of the same diameter as the air valve inlet connection. If these recommendations are followed, and the air density effects mentioned below are addressed, the flow ring will measure primary airflow within ±5% of unit nominal airflow.

Figure 1. Air pressure measurement orientations

Air Density Effects Changes in air density due to the conditions listed below sometimes create situations where the standard flow sensing calibration parameters must be modified. These factors must be accounted for to achieve accuracy with the flow sensing ring. Designers, installers, and air balancers should be aware of these factors and know of the necessary adjustments to correct for them.

Elevation At high elevations the air is less dense. Therefore, when measuring the same differential pressure at elevation versus sea level the actual flow will be greater at elevation than it would be at sea level. To calculate the density at an elevation other than standard conditions (most manufacturers choose sea level as the point for their standard conditions), you must set up a ratio between the density and differential pressure at standard conditions and the density and differential pressure at the new elevation.

Standard Conditions∆P DENS Standard Conditions

∆P New Conditions DENS New Conditions=

Since the data from the manufacturer is published at standard conditions, this equation should be solved for the differential pressure at standard conditions and the other quantities substituted to determine the ratio for the differential pressure measured at the new conditions.

Duct Pressure and Air Temperature Variations While changes in these factors certainly affect the density of air, most operating parameters which systems need keep these effects very small. The impact on accuracy due to these changes is less than one half of one percent except in very extreme conditions. Extreme conditions are defined as those systems with inlet static pressures greater than 5 in. wg (1245 Pa) and primary air temperatures greater than 100°F (37.8°C). Since those types of systems occur so infrequently, we assume the effects of duct pressure and air temperature variations to be negligible.

10 VAV-PRC016E-EN

Linearity With the increased use of DDC controls instead of pneumatic controls, the issue of linearity is not as great as it once was. The important aspect of flow measurement versus valve position is the accuracy of the controller in determining and controlling the flow. Our units are tested for linearity and that position versus airflow curve is downloaded and commissioned in the factory to ensure proper control of the unit.

Retrofit Systems It is very important to understand how the VRRF terminal unit should be applied depending upon the retrofit application. This will ensure that the performance of the system is maintained. This section outlines the most common retrofit applications.

Bypass/Replace Existing Mechanical Regulator (Air Valve) Figure 2. Horizontal installation — Trane air valve removed

Existing Legacy Single Duct Unit

Duct

Adapter

Basic RIRO Unit (Shown without insulation for detail)

Figure 3. Horizontal installation — air valve remains

Old duct left in place

Existing Legacy Single Duct Unit

Basic RIRO Unit (Shown without insulation for detail)

Old air valve left in place

VAV-PRC016E-EN 11

Figure 4. Vertical installation

Existing Legacy Single Duct Unit

Basic RIRO Unit (Shown without insulation for detail)

Old duct left in place

Old air valve left in place

Upgrade Building and/or Unit Controls Figure 5. Upgrade building and/or unit controls

Existing Legacy Single Duct Unit

Convert Constant Air Volume System to Variable Air Volume System Conversion of the existing systems requires the VRRF product as well as retrofit of the existing air handler or rooftop to deliver variable air volume

12 VAV-PRC016E-EN

Figure 6. Constant air volume to variable air volume

Zone 1

Duct

VRRF

Zone 2

Convert Pressure Dependent Variable Air Volume System to Pressure Independent Variable Air Volume

Installation of new, or conversion of existing pressure dependent Variable Air Volume system to pressure independent Variable Air Volume System (e.g. Trane VariTrac™) utilizes VRRF to replace the existing VariTrac™ zone dampers and bypass damper.

Figure 7.

HVAC Unit

RIRO Bypass Damper

Tracer® Concierge™

RIRO Zone Damper

Zone SensorTrane® Air-Fi™ Zone Sensor

Trane® Air-Fi™ Wireless Communication

VAV-PRC016E-EN 13

Convert Legacy Trane Analog Controls to DDC (Comm3 or Comm4), LonTalk®, BACnet® Communication

• Trane Air-Fi® wireless is especially beneficial for this application. The legacy analog controls were non-communicating.

• For wiring diagrams and installation instructions refer to Installation, Operation, and Maintenance manual (VAV-SVN09*-EN)

Convert Multizone (Dual Duct) Systems to Variable Air Volume System Figure 8. Multizone (dual duct) to variable air volume

Duct

Duct

Remove Existing Controller

Cold

Hot

VRRF

14 VAV-PRC016E-EN

Selection Procedure This section describes the catalog selection of VRRF VAV terminal units with a specific example. A computer selection program, Trane Official Product Selection System (TOPSS™), is also available to aid in selection of VAV terminal units. Selection of VRRF VAV terminal units can involve three elements:

• Air Valve Selection

• Acoustics

• Controls

Trane Select Assist™ Trane Select Assist™ is an online tool used to determine properly sized VariTrane™ VAV terminal unit and resulting performance data for specific input specifications. In addition to selection of VAV terminal unit configuration selections, Trane Select Assist also includes most other Trane products, allowing user to select all required equipment within the one program.

Within the tool, required fields are denoted by red shading, and for VAV terminal units include maximum and minimum airflows, control type, and unit model. (Models with reheat have additional required fields.) The user has the option of viewing information for an individual selection on one screen, or as a schedule with all VAV units required for the specific application.

Trane Select Assist also calculates sound power data for the selected terminal unit. Input is either maximum individual sound level for each octave band, or maximum NC value. Trane Select Assist will calculate acoustical data subject to default or user-supplied sound attenuation data.

Schedule View: The program has many time saving features such as:

• Copy/paste from spreadsheets like Microsoft® Excel

• Easily arrange fields to match your schedule

• Time-saving templates to store default settings The use can also export the schedule view to Excel for modification or inclusion in engineering drawings as a schedule. Details regarding the program, its operation, and instructions on obtaining a copy are available from your local Trane sales office.

Air Valve Selection The wide-open static pressure and airflows are found in the performance data section of the catalog. To select an air valve, locate the required design cooling airflow for your terminal unit type and find the smallest air valve size that has a pressure drop equal to or lower than the maximum wide-open static pressure requirement.

Example: Cooling Only VCCF Terminal Unit

• Design cooling airflow: 1700 cfm

• Maximum wide open Air pressure drop: 0.25 in. wg

• Minimum cooling airflow: 850 cfm From the performance data charts, select a valve size 12, which has a wide-open static pressure drop of

0.01 in. wg Check the minimum and maximum cfm desired with the minimum and maximum cfm allowed in the table in the general data section. The maximum setting of 1700 cfm is within the acceptable range. The desired minimum setting of 850 cfm is acceptable for the cooling only box desired. Note that if an electric reheat box was selected, the minimum cfm would be dependent upon the kW of the electric heater. (See Electric Heat Unit Selection.)

Acoustics The acoustical data found in the VAV catalog is used to determine sound the terminal unit will generate.

Locate the table for the VAV terminal unit of interest. Sound power data and an equivalent NC level for an AHRI 885-2008 transfer function is listed.

VAV-PRC016E-EN 15

Example: VRRF, Size 12 (See air valve selection)

• Cooling Airflow: 1700 cfm

• Maximum inlet static pressure: 1.5 in. wg Interpolation gives sound power data of:

Octave Band 2 3 4 5 6 7 NC

Discharge Sound Power 77 70 67 63 64 60 30

Radiated Sound Power 46 53 54 53 52 50 29

The NC level above is determined by using either the catalog’s AHRI 885-2008 (mineral fiber for radiated sound) transfer function for the conditions shown in the acoustics table. A different transfer function could be applied as conditions dictate.

The maximum NC level is NC-30. If the maximum NC level was exceeded, it would have been necessary to reselect the next larger unit size.

Controls Proper control type selection is crucial to VRRF application. In most instances, the control type will need to match the exisiting building control system type. For example, VariTrac™ communicating via Comm3/ Comm4 will require the UCM control type. See more detail in the Controls portion of the catalog.

Selection Procedure

16 VAV-PRC016E-EN

Model Number

Digit 1, 2, 3, 4 — Unit Type

VRRF = VariTrane Round Inlet and Outlet (Retrofit)

Digit 5, 6 — Primary Air Valve

04 = 4in Inlet (225 cfm) 05 = 5in Inlet (350 cfm) 06 = 6in Inlet (500 cfm) 08 = 8in Inlet (900 cfm) 10 = 10in Inlet (1400 cfm) 12 = 12in Inlet (2000 cfm) 14 = 14in Inlet (3000 cfm) 16 = 16in Inlet (4000 cfm) 0A = 4in Inlet (225 cfm) — Control Box Only 0B = 5in Inlet (350 cfm) — Control Box Only 0C = 6in Inlet (500 cfm) — Control Box Only 0D = 8in Inlet (900 cfm) — Control Box Only 0E = 10in Inlet (1400 cfm) — Control Box Only 0F = 12in Inlet (2000 cfm) — Control Box Only 0G = 14in Inlet (3000 cfm) — Control Box Only 0H = 16in Inlet (4000 cfm) — Control Box Only G0 = Control Box Only (200 cfm) G1 = Control Box Only (250 cfm) G2 = Control Box Only (300 cfm) G3 = Control Box Only (350 cfm) G4 = Control Box Only (400 cfm) G5 = Control Box Only (450 cfm) G6 = Control Box Only (500 cfm) G7 = Control Box Only (600 cfm) G8 = Control Box Only (650 cfm) G9 = Control Box Only (700 cfm) GA = Control Box Only (800 cfm) GB = Control Box Only (1000 cfm) GC = Control Box Only (1050 cfm) GD = Control Box Only (1200 cfm) GE = Control Box Only (1300 cfm) GF = Control Box Only (1400 cfm) GG = Control Box Only (1500 cfm) GH = Control Box Only (1600 cfm) GI = Control Box Only (1700 cfm) GJ = Control Box Only (1800 cfm) GK = Control Box Only (2000 cfm) GL = Control Box Only (2100 cfm) GM = Control Box Only (2300 cfm) GN = Control Box Only (2400 cfm) GP = Control Box Only (2800 cfm) GQ = Control Box Only (3000 cfm) GR = Control Box Only (3100 cfm) GS = Control Box Only (3200 cfm) GT = Control Box Only (3400 cfm) GU = Control Box Only (4000 cfm) GV = Control Box Only (5200 cfm)

Digit 7, 8 — Design Sequence

** = Factory Assigned

Digit 9, 10, 11, 12 — Unit Controls

ENCL = Shaft Only in Enclosure DD00 = Trane Actuator Only DD01 = UCM4 Cooling Only Control DD02 = UCM4 N.C. On/Off Hot Water DD03 = UCM4 Prop Hot Water DD04 = UCM4 Staged On/Off Elec Heat DD05 = UCM4 Pulse Width MOD Elec Heat DD07 = UCM4 N.O. On/Off Hot Water DD11 = VV550 DDC Controller, Cool Only DD12 = VV550 DDC Ctrl to Operate N.C. On/Off Water Valve DD13 =VV550 DDC Ctrl to Operate Prop Water Valve DD14 = VV550 DDC Ctrl On/Off Electric Heat DD15 = VV550 DDC Ctrl w/Pulse Width Modulation DD16 = VV550 DDC Controller Ventilation Flow DD17 = VV550 DDC Ctrl to Operate N.O. On/Off Water Valve DD19 = VV550 DDC Controller with Flow Tracking DD20 = VV550 DDC Vent Flow Control l to Operate N.C. Water Valve DD21 = VV550 DDC - Vent Flow w/ On/Off Elec Heat DD22 = VV550 DDC Vent Flow control to operate prop water valve DD33 = VV550 DDC Vent Flow control to operate N.O. On/Off water valve DD41 = UC400 DDC - Basic (No water or electric heat) DD42 = UC400 DDC - Basic (Water heat - N.C. - 2 position) DD43 = UC400 DDC - Basic (Water heat- Modulating) DD44 = UC400 DDC - Basic (Electric heat-staged) DD45 = UC400 DDC - Basic (Electric heat-PWM) DD46 = UC400 DDC - Ventilation flow - Cooling only DD47 = UC400 DDC - Basic (Water heat- N.O.- 2 position) DD49 = UC400 DDC - Flow Tracking (Cooling only) DD50 = UC400 DDC - Ventilation Flow (Water heat- N. C. - 2 position DD51 = UC400 DDC - Ventilation Flow (Electric heat- staged) DD52 = UC400 DDC - Ventilation Flow (Water heat-Modulating) DD63 = UC400 DDC - Ventilation Flow (Water heat- N.O. - 2 position) DD71 = UC210 DDC - Basic (No water or electric heat) DD72 = UC210 DDC - Basic (Water heat- N.C. - 2 position) DD73 = UC210 DDC - Basic (Water heat- Modulating) DD74 = UC210 DDC - Basic (Electric heat-staged) DD75 = UC210 DDC - Basic (Electric heat-PWM) DD76 = UC210 DDC - Ventilation flow- cooling only DD77 = UC210 DDC - Basic (Water heat- N.O. - 2 position)

Digit 9, 10, 11, 12 — Unit Controls (continued) DD79 = UC210 DDC - Flow Tracking (Cooling only) DD80 = UC210 DDC - Ventilation Flow (Water heat

- N. C. - 2 position) DD81 = UC210 DDC - Ventilation Flow (Electric heat-staged) DD82 = UC210 DDC - Ventilation Flow (Water heat-Modulating) DD93 = UC210 Ventilation Flow (Water heat- N.O. - 2 position) SE41 = Symbio™ 500 DDC - Basic (Cooling Only) SE42 = Symbio™ 500 DDC - Basic (Water heat - N.C. - 2 position) SE43 = Symbio™ 500 DDC - Basic (Water heat- Modulating) SE44 = Symbio™ 500 DDC - Basic (Electric heat-staged) SE45 = Symbio™ 500 DDC - Basic (Electric heat-

PWM)

SE46 = Symbio™ 500 DDC - Ventilation Flow (No Reheat) SE47 = Symbio™ 500 DDC - Basic (Water heat - N.O. - 2 position) SE49 = Symbio™ 500 DDC - Flow Track (Cooling only) SE50 = Symbio™ 500 DDC - Ventilation Flow (N.C.

- 2 position) SE51 = Symbio™ 500 DDC - Ventilation Flow (Electric heat-staged) SE52 = Symbio™ 500 DDC - Ventilation Flow (Water heat-Modulating) SE63 = Symbio™ 500 DDC - Ventilation Flow (Water heat - N.O.- 2 position) SE71 = Symbio™ 210e DDC - Basic (Cooling only) SE72 = Symbio™ 210e DDC - Basic (Water heat - N.C. - 2 position) SE73 = Symbio™ 210e DDC - Basic (Water heat- Modulating) SE74 = Symbio™ 210e DDC - Basic (Electric heat-staged) SE75 = Symbio™ 210e DDC - Basic (Electric heat-

PWM)

SE76 = Symbio™ 210e DDC - Ventilation Flow (No Reheat) SE77 = Symbio™ 210e DDC -Basic (Water heat - N.O. - 2 position) SE79 = Symbio™ 210e DDC - Flow Track (Cooling only) SE80 = Symbio™ 210e DDC - Ventilation Flow (N.

C. - 2 position) SE81 = Symbio™ 210e DDC - Ventilation Flow (Electric heat-staged) SE82 = Symbio™ 210e DDC - Ventilation Flow (Water heat-Modulating) SE93 = Symbio™ 210e DDC - Ventilation Flow (Water heat - N.O. - 2 position)

VAV-PRC016E-EN 17

Digit 9, 10, 11, 12 — Unit Controls (continued) SY71 = Symbio™ 210 DDC - Basic (Cooling only) SY72 = Symbio™ 210 DDC - Basic (Water heat - N.C. - 2 position) SY73 = Symbio™ 210 DDC - Basic (Water heat- Modulating) SY74 = Symbio™ 210 DDC - Basic (Electric heat-staged) SY75 = Symbio™ 210 DDC - Basic (Electric heat-

PWM)

SY76 = Symbio™ 210 DDC - Ventilation Flow (No Reheat) SY77 = Symbio™ 210 DDC - Basic (Water heat - N.O. - 2 position) SY79 = Symbio™ 210 DDC - Flow Track (Cooling only) SY80 = Symbio™ 210 DDC - Ventilation flow (N.C.

- 2 position) SY81 = Symbio™ 210 DDC - Ventilation Flow (Electric heat-staged) SY82 = Symbio™ 210 DDC - Ventilation Flow (Water heat-Modulating) SY93 = Symbio™ 210 DDC - Ventilation Flow (Water heat - N.O. - 2 position)

Digit 13 — Transformer

0 = No Transformer 1 = 120/24 Volt (50 VA) 2 = 208/24 Volt (50 VA) 3 = 240/24 Volt (50 VA) 4 = 277/24 Volt (50 VA) 5 = 480/24 Volt (50 VA) 6 = 347/24 Volt (50 VA) 7 = 575/24 Volt (50 VA) 8 = 380/24 Volt (50 VA)

Digit 14 — Disconnect Switch

0 = No Power Disconnect W = With Power Disconnect Switch

Digit 15 — Power Fuse

0 = No Fusing W = With Power Fuse

Digit 16 — Unit Orientation

H = Horizontal Airflow V = Vertical Airflow (up or down)

Digit 17 —Wireless Sensor Options

0 = No Wireless Receiver (Wired Sensor Only) 3 = Air-Fi® Wireless Comm Interface (FM)

Digit 18 — Outlet Adapters

0 = None D = Adapter (C, D, or E Style)

Digit 19 — Relay Kit

0 = None W = With one or more relay kits

Digit 20 —Water Valve

0 = None

Digit 21 — Zone Sensor

0 = None A = DDC Sensor Only B = DDC Sensor, Ext Adj, Comm Jack C = DDC Sensor, NSB, Comm Jack D = DDC Sensor, Ext Adj, NSB, Comm Jack E = Digital Display Zone Sensor M = Air-Fi® WCS/SD (Display) N = Air-Fi® WCS/SB (Base)

Digit 22— Factory Installed Solution

0 = None W = Factory-Mounted DTS 1 = Factory-Installed DTS 2 = HW Valve Harness 3 = Both DTS/HW Valve Harness

Digit 23 — Actuator

0 = None A = Standard Actuator B = Belimo Actuator G = Trane Analog Actuator (UC210 or UC400 only)

Digit 24 — Special Options

0 = None S = Special Options

Model Number

18 VAV-PRC016E-EN

General Data

Table 1. Primary airflow control factory settings — I-P

Control Type Air Valve Size (in.) Maximum Valve (cfm) Maximum Controller (cfm) Minimum Controller (cfm) Constant Volume

(cfm)

Direct Digital Control/ UCM, VV550, Symbio™ 210, Symbio™ 210e, Symbio™ 500, UC210, and UC400

4 225 25-225 0,25-225 25-225

5 350 40-350 0,40-350 40-350

6 500 60-500 0,60-500 60-500

Direct Digital Control/ UCM, VV550, Symbio™ 210, Symbio™ 210e, Symbio™ 500, UC210, and UC400

8 900 105-900 0,105-900 105-900

10 1400 165-1400 0,165-1400 165-1400

12 2000 240-2000 0,240-2000 240-2000

Direct Digital Control/ UCM, VV550, Symbio™ 210, Symbio™ 210e, Symbio™ 500, UC210, and UC400

14 3000 320-3000 0,320-3000 320-3000

16 4000 420-4000 0,420-4000 420-4000

24 x 16 8000 800-8000 0,800-8000 800-8000

Table 2. Primary airflow control factory settings — SI

Control Type Air Valve Size (in.) Maximum Valve L/s Maximum Controller L/s Minimum Controller L/s Constant Volume L/s

Direct Digital Control/ UCM, VV550, Symbio™ 210, Symbio™ 210e, Symbio™ 500, UC210, and UC400

4 106 12-106 0,12-106 12-106

5 165 19-165 0,19-165 19-165

6 236 28-236 0,28-236 28-236

Direct Digital Control/ UCM, VV550, Symbio™ 210, Symbio™ 210e, Symbio™ 500, UC210, and UC400

8 425 50-425 0,50-425 50-425

10 661 77-661 0,77-661 77-661

12 944 111-944 0,111-944 111-944

Direct Digital Control/ UCM, VV550, Symbio™ 210, Symbio™ 210e, Symbio™ 500, UC210, and UC400

14 1416 151-1416 0,151-1416 151-1416

16 1888 198-1888 0,198-1888 198-1888

24 x 16 3776 378-3776 0,378-3776 378-3776

VAV-PRC016E-EN 19

Performance Data Air Pressure Drop

Table 3. Air pressure drop (in. wg)

Inlet Size

I-P SI

Airflow (cfm) Cooling Only Airflow (L/s) Cooling Only

50 0.01 25 3

100 0.01 50 3

150 0.01 70 3

225 0.01 105 3

100 0.01 45 3

200 0.01 95 3

300 0.01 140 3

350 0.02 165 4

100 0.01 45 3

250 0.05 120 13

350 0.1 165 26

500 0.22 235 55

200 0.01 95 3

400 0.02 190 4

600 0.04 280 9

900 0.08 420 21

500 0.01 235 3

800 0.01 375 3

1100 0.01 520 3

1400 0.01 660 3

800 0.01 375 3

1200 0.01 565 3

1600 0.01 755 3

2000 0.01 940 3

1500 0.01 700 3

2000 0.01 945 3

2500 0.01 1180 3

3000 0.01 1415 3

2000 0.01 940 3

2500 0.01 1180 3

3000 0.01 1415 3

4000 0.01 1885 3

20 VAV-PRC016E-EN

Acoustics Data Table 4. Discharge sound power (dB) — 0.5, 1.0 and 1.5 in. inlet pressures

Inlet Size

(in) Cfm L/s

0.5" Inlet Pressure ∆Ps

1.0" Inlet Pressure ∆Ps

1.5" Inlet Pressure ∆Ps

2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

80 38 66 61 54 48 43 36 67 65 61 54 49 45

120 57 69 66 57 51 44 38 73 70 63 57 51 47

150 71 70 69 58 52 45 39 76 74 65 59 52 48 77 76 69 62 56 53

225 106 69 68 61 56 49 45 76 77 68 61 55 50

130 61 64 58 52 47 43 39 66 64 58 54 50 47

200 94 66 58 52 48 44 41 71 66 60 55 50 50

250 118 65 58 52 49 44 41 73 67 61 55 50 50 76 70 66 59 55 55

350 165 65 58 53 48 44 41 74 66 61 56 51 51

200 94 66 61 54 50 47 43 69 65 60 56 54 51

300 142 68 63 57 54 50 46 72 69 64 58 55 53

400 189 69 64 59 56 51 48 74 70 66 60 57 56 76 74 69 63 60 59

500 236 71 66 62 59 55 52 75 71 67 63 59 57

350 165 66 58 52 49 47 41 70 62 56 54 52 49

520 245 67 62 55 53 50 45 73 68 60 57 55 52

700 330 71 64 58 56 53 49 75 70 65 60 58 57 78 74 68 63 61 59

900 425 73 64 61 60 56 52 78 70 68 63 60 60

550 260 61 55 51 47 45 41 67 59 55 54 53 50

820 387 66 59 55 50 49 45 72 63 59 55 56 53

1100 519 71 62 59 53 53 48 76 67 63 57 58 56 79 70 65 60 61 60

1400 661 73 65 62 58 56 52 79 71 66 61 60 58

800 378 60 53 52 50 49 43 64 58 56 55 55 52

1200 566 64 57 55 52 53 46 69 62 60 57 58 54

1600 755 68 60 59 55 56 50 74 65 63 59 61 56 76 69 66 62 63 60

2000 944 71 63 62 60 58 53 77 69 66 63 63 58

1100 519 60 54 53 50 48 43 64 59 57 55 53 50

1600 755 64 58 58 53 51 46 68 62 62 57 56 53

2100 991 67 60 61 56 54 49 72 65 65 60 59 55 75 68 68 63 62 59

3000 1416 72 64 66 62 59 55 77 69 70 65 63 59

1400 661 64 58 55 53 52 48 67 64 60 58 58 56

2100 991 66 61 58 55 55 51 70 67 64 60 60 59

2800 1321 69 63 61 58 57 54 73 69 66 63 62 61 76 71 70 66 65 64

4000 1888 73 68 67 64 62 58 78 72 70 66 65 62

Notes:

1. All data are measured in accordance with Industry Standard ARI 880-2011.

2. Data at 1.5in inlet pressure constitutes AHRI 880–2011 standard rating conditions. Data at 0.5, 1.0, 2.0 and 3.0in are application ratings. These ratings are outside the scope of the certification program.

3. All sound power levels, dB re: 10-12 Watts.

4. Where ∆Ps is the inlet static pressure minus discharge static.

VAV-PRC016E-EN 21

Table 5. Discharge sound power (dB) – 2.0 and 3.0 in. inlet pressures

Inlet Size (in) Cfm L/s

2.0" Inlet Pressure ∆Ps

3.0" Inlet Pressure ∆Ps

2 3 4 5 6 7 2 3 4 5 6 7

80 38 68 67 66 60 56 54 68 69 68 63 60 58

120 57 73 73 70 64 58 56 73 74 73 67 63 61

150 71 77 77 72 65 60 57 76 78 75 69 64 62

225 106 81 83 76 68 62 59 83 86 79 72 67 64

130 61 66 70 65 59 57 55 67 68 67 61 61 60

200 94 72 72 69 60 58 57 73 74 74 64 62 62

250 118 77 72 70 62 58 58 76 74 75 66 63 63

350 165 81 75 70 63 58 59 81 78 75 68 63 63

200 94 70 68 66 61 60 58 71 70 68 64 65 63

300 142 76 73 69 63 62 60 76 74 72 67 66 64

400 189 79 76 72 66 63 62 80 77 75 69 67 66

500 236 80 77 74 68 64 64 82 79 77 71 68 67

350 165 74 65 61 59 59 56 75 67 63 61 62 61

520 245 76 73 65 62 61 59 78 75 67 64 65 63

700 330 80 76 69 65 63 61 81 79 72 68 67 66

900 425 82 76 74 68 65 64 84 79 78 71 68 67

550 260 70 65 59 58 59 58 73 68 62 61 64 63

820 387 76 68 64 61 62 61 78 71 67 64 65 65

1100 519 80 72 67 63 63 63 83 75 71 66 66 67

1400 661 84 76 70 64 64 64 86 78 73 68 68 68

800 378 69 65 60 60 61 58 71 70 64 63 65 63

1200 566 74 67 66 63 64 61 76 72 69 66 67 65

1600 755 78 70 68 65 66 63 80 74 72 69 70 67

2000 944 82 73 71 67 68 64 83 76 74 71 71 68

1100 519 69 66 62 59 60 58 71 70 64 62 64 63

1600 755 73 67 68 62 62 60 76 71 72 65 66 64

2100 991 77 70 70 65 64 62 80 73 76 68 67 66

3000 1416 83 75 75 69 67 65 86 77 78 72 71 69

1400 661 72 70 67 63 64 63 74 73 71 67 68 67

2100 991 74 71 70 66 66 65 76 75 73 70 69 68

2800 1321 78 73 72 68 67 66 80 76 76 72 71 70

4000 1888 83 77 74 71 70 68 86 79 78 75 73 72

Notes:

1. All data are measured in accordance with Industry Standard ARI 880-2011.

2. Data at 1.5in inlet pressure constitutes AHRI 880–2011 standard rating conditions. Data at 0.5, 1.0, 2.0 and 3.0in are application ratings. These ratings are outside the scope of the certification program.

3. All sound power levels, dB re: 10-12 Watts.

22 VAV-PRC016E-EN

Table 6. Radiated sound power (dB) — 0.5, 1.0 and 1.5 in. inlet pressures

Inlet Size

(in) Cfm L/s

0.5" Inlet Pressure ∆Ps

1.0" Inlet Pressure ∆Ps

1.5" Inlet Pressure ∆Ps

2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

80 38 40 43 47 45 45 43 41 46 50 49 50 49

120 57 43 44 48 48 46 43 43 49 53 51 51 50

150 71 44 45 48 48 47 44 45 49 53 52 52 50 45 52 59 56 56 54

225 106 45 48 49 50 50 46 48 52 54 53 54 51

130 61 39 41 45 43 41 37 39 43 49 50 49 46

200 94 40 41 43 42 39 36 41 45 49 50 49 47

250 118 40 41 43 42 39 36 43 45 49 49 48 46 44 48 51 52 53 52

350 165 39 43 47 47 44 40 43 47 49 49 47 46

200 94 41 45 45 42 40 37 41 46 49 49 49 46

300 142 40 44 45 45 43 41 43 48 49 48 48 47

400 189 40 47 48 48 47 45 41 49 50 50 50 48 45 51 52 52 53 51

500 236 41 50 51 51 50 47 43 51 52 52 53 51

350 165 39 43 48 46 44 39 40 45 50 50 50 46

520 245 40 45 47 46 44 39 43 48 52 51 50 48

700 330 41 46 48 47 45 41 47 51 53 51 50 48 47 53 55 54 54 52

900 425 44 49 50 50 48 46 45 51 54 52 51 49

550 260 39 42 47 46 45 40 42 45 50 51 51 48

820 387 41 45 48 47 45 40 44 47 52 52 51 49

1100 519 43 47 49 48 45 41 47 50 53 52 51 48 49 52 56 55 55 53

1400 661 44 49 51 49 47 43 48 51 54 53 52 48

800 378 40 46 47 47 45 40 40 48 50 50 50 48

1200 566 41 47 47 47 44 39 43 50 52 51 51 47

1600 755 42 49 48 48 46 41 44 51 51 51 50 46 45 53 54 53 52 50

2000 944 44 49 50 51 48 43 46 53 53 53 52 48

1100 519 39 46 50 46 43 38 40 48 53 49 47 45

1600 755 40 47 51 47 44 40 42 51 55 51 49 47

2100 991 43 49 50 47 45 41 45 52 55 51 50 48 47 55 58 55 53 52

3000 1416 47 55 55 50 46 43 50 58 59 53 50 48

1400 661 42 48 51 50 48 44 43 51 54 54 53 51

2100 991 43 49 51 50 49 45 45 52 55 55 55 53

2800 1321 46 51 53 52 49 46 48 55 56 56 55 54 50 57 59 59 59 58

4000 1888 49 56 55 55 54 51 51 56 58 57 57 54

Notes:

1. All data are measured in accordance with Industry Standard ARI 880-2011.

2. Data at 1.5in inlet pressure constitutes AHRI 880–2011 standard rating conditions. Data at 0.5, 1.0, 2.0 and 3.0in are application ratings. These ratings are outside the scope of the certification program.

3. All sound power levels, dB re: 10-12 Watts.

VAV-PRC016E-EN 23

Table 7. Radiated sound power (dB) — 2.0 and 3.0 in. inlet pressures

Inlet Size (in) Cfm L/s

2.0" Inlet Pressure ∆Ps

3.0" Inlet Pressure ∆Ps

2 3 4 5 6 7 2 3 4 5 6 7

80 38 42 52 57 51 54 55 42 55 61 55 57 58

120 57 43 52 57 54 57 56 43 55 61 56 58 60

150 71 45 53 58 57 58 57 45 56 61 57 59 61

225 106 49 56 59 58 59 59 49 58 63 61 62 63

130 61 39 45 51 53 54 53 41 46 53 55 57 57

200 94 41 48 53 54 56 55 42 48 54 56 58 58

250 118 44 49 53 54 56 56 44 50 55 56 58 59

350 165 48 52 53 54 55 54 48 54 56 57 58 58

200 94 41 49 52 52 55 55 42 51 55 55 57 58

300 142 43 51 54 54 56 55 43 53 56 56 58 59

400 189 48 53 54 53 54 54 48 55 57 55 57 58

500 236 46 53 54 54 56 55 51 57 58 56 57 58

350 165 41 47 52 52 54 53 42 49 55 54 56 56

520 245 44 50 55 55 57 55 45 52 56 57 60 59

700 330 48 54 57 56 57 55 49 56 59 59 61 60

900 425 50 56 58 57 57 55 52 57 61 59 59 59

550 260 45 49 53 54 56 55 45 50 53 55 58 59

820 387 47 51 56 57 58 57 48 52 57 58 60 61

1100 519 49 53 57 56 57 56 50 54 59 59 61 61

1400 661 51 54 57 57 57 56 53 56 60 59 60 60

800 378 41 48 53 56 55 54 41 48 53 55 58 57

1200 566 44 52 57 56 57 56 45 52 57 58 59 58

1600 755 47 54 56 55 55 53 49 57 60 60 60 59

2000 944 50 55 56 56 56 54 51 58 60 59 59 58

1100 519 41 48 54 52 51 50 43 51 56 53 52 53

1600 755 44 52 57 55 53 53 47 54 58 55 54 56

2100 991 47 56 60 56 55 54 50 57 62 58 56 57

3000 1416 54 60 61 56 55 54 54 61 65 61 60 60

1400 661 43 52 56 59 58 57 44 52 58 60 61 60

2100 991 46 54 59 61 61 60 48 56 60 62 63 63

2800 1321 50 57 61 61 62 61 52 58 63 64 64 64

4000 1888 54 61 63 62 62 62 55 62 65 66 65 65

Notes:

1. All data are measured in accordance with Industry Standard ARI 880-2011.

2. Data at 1.5in inlet pressure constitutes AHRI 880–2011 standard rating conditions. Data at 0.5, 1.0, 2.0 and 3.0in are application ratings. These ratings are outside the scope of the certification program.

3. All sound power levels, dB re: 10-12 Watts.

24 VAV-PRC016E-EN

Table 8. Sound noise criteria (NC) - valve only

Inlet Size (in) CFM L/s

Discharge Inlet Pressure (∆Ps) Radiated Inlet Pressure (∆Ps)

0.5” 1.0” 1.5” 2.0” 3.0” 0.5” 1.0” 1.5” 2.0” 3.0”

80 38 22 25 27 30 21 24 32 36

120 57 26 31 34 36 22 27 32 36

150 71 30 36 38 39 40 22 27 34 33 36

225 106 28 39 46 50 23 28 34 38

130 61 20 24 31 29 19 23 25 27

200 94 22 29 34 36 16 23 27 28

250 118 21 31 35 36 36 16 23 25 27 30

350 165 21 32 41 41 21 23 27 31

200 94 19 24 27 30 19 23 26 30

300 142 21 28 33 34 19 23 28 31

400 189 23 30 34 37 38 22 24 26 28 32

500 236 25 31 38 40 25 26 28 33

350 165 19 24 29 30 22 24 26 30

520 245 20 28 33 36 21 26 30 31

700 330 25 30 35 37 40 22 27 30 32 34

900 425 28 34 39 42 24 28 33 36

550 260 – 18 22 27 21 24 27 28

820 387 16 24 29 32 22 26 31 32

1100 519 23 29 33 34 38 23 27 31 32 34

1400 661 25 33 39 42 25 28 32 35

800 378 – 16 23 28 21 24 28 28

1200 566 – 20 26 31 21 26 32 32

1600 755 19 26 29 31 34 22 25 28 31 35

2000 944 22 30 37 38 24 27 31 35

1100 519 – 16 24 29 24 27 28 31

1600 755 – 19 25 30 25 30 32 33

2100 991 17 24 27 30 34 24 30 33 35 37

3000 1416 24 30 38 42 30 34 36 40

1400 661 – 21 28 32 25 28 32 33

2100 991 18 25 30 34 25 30 34 35

2800 1321 20 27 30 32 36 27 31 34 36 38

4000 1888 26 32 38 42 30 33 38 40

Notes:

1. “—” represents NC levels below NC15.

2. NC values are calculated using modeling assumptions based on AHRI 885–98–02 addendum.

3. Data at 1.5in inlet pressure constitutes AHRI 880–2011 standard rating conditions. Data at 0.5, 1.0, 2.0 and 3.0in are application ratings. These ratings are outside the scope of the certification program.

VAV-PRC016E-EN 25

Controls Tracer Building Automation System

Tracer® Building Automation Systems ensure comfort within your building.

Building controls have a bigger job description than they did a few years ago. It’s no longer enough to control heating and cooling systems and equipment. Sophisticated buildings require smarter technology that will carry into the future. Tracer controls provide the technology platform – mobile, easy-to-use, cloud-based, scalable and open - for the next generation of data-driven, technology-enabled services that are creating high performance buildings.

With a Trane Tracer® Building Automation System, you’ll:

• Reduce operating costs through energy management strategies.

• Consistently provide occupant comfort.

• Enjoy reliable operation with standard, pre-engineered, and pretested applications.

• Easily troubleshoot and monitor either on site or from a remote location.

• Reduce installation time and simplify troubleshooting.

Whether factory-mounted or field-installed, Trane offers a wide range of controllers to suit virtually any application. These units are compatible with a variety of building types and can be used for new construction or renovation. Through extensive usability testing internally and with building operators, we’ve designed our controls for real world ease of use.

Tracer BACnet Controllers Trane offers a full line of programmable BACnet® controllers designed for simple integration into any system which can communicate via the BACnet® protocol. These controllers are factory-downloaded, commissioned, and shipped ready to be installed.

UC210 BACnet® Controller

Symbio™ 210 BACnet® Controller Symbio™ 210e BACnet® Controller Symbio™ 500 Controller

UC400 BACnet® Controller

26 VAV-PRC016E-EN

Tracer VV550 LonTalk® Controllers Trane offers a full line of LonTalk® controllers designed for simple integration into ANY system which can communicate via the LonTalk® Space Comfort Control (SCC) protocol. These controllers are also completely factory-commissioned.

Trane VAV DDC UCM Controller DDC (communicating electronic)—DDC controllers provide system-level data used to optimize overall system performance. Variables such as occupied/unoccupied, minimum and maximum airflows and temperature, valve position, ventilation fraction, and so on are available on a simple Trane Comm3/4 protocol twisted-shielded wire pair.

Note: One of many Trane DDC Control options which are factory-installed, wired, calibrated, and fully tested before shipment.

Trane DDC controllers provide Trane-designed solid-state electronics intended specifically for temperature and ventilation control in space comfort applications. DDC control capabilities include:

• Pressure-independent (PI) operation—Provides airflow required by the zone temperature sensor to maintain occupant comfort. The controller automatically adjusts valve position to maintain required airflow. Minimum and maximum airflow is factory-set and field-adjustable.

• Factory-set airflow and temperature setpoints.

Air-Fi® Wireless System For more detailed information on Air-Fi® Wireless systems and devices, see:

• BAS-SVX40*–EN Air-Fi® Wireless Installation, Operation, and Maintenance

• BAS-PRD021*–EN Air-Fi® Wireless Product Data Sheet

• BAS-SVX55*–EN Air-Fi® Wireless Network Design Best Practices

VAV-PRC016E-EN 27

Air-Fi® Wireless Communications Interface (WCI)

A factory-installed Air-Fi® Wireless Communications Interface (WCI) provides wireless communication between the Tracer® SC, Tracer® UC210/UC400, Symbio™ 210/Symbio™ 210e/ Symbio™ 500 VAV unit controllers and optionally, Air-Fi® Wireless Communication sensors.

The Air-Fi® WCI’s wireless mesh network is the perfect alternative to a wired communication link. Eliminating the low-voltage wire between the zone sensor and the terminal unit controller, and between the unit controllers and the system controller will:

• Reduced installation time and associated risks.

• Completion of projects with fewer disruptions.

• Easier and more cost-effective re-configurations, expansions, and upgrades.

Note:WCI is not compatible with the Trane VAV UCM or

Tracer® VV550 LonTalk® controller.

Air-Fi® Wireless Communication Sensor (WCS)

The Wireless Communications Sensor (WCS) communicates wirelessly to a Tracer® BACnet® unit controller that has an Air- Fi® WCI installed. AWCS is an alternative to a wired sensor when access and routing of communication cable are issues. It also allows flexible mounting and relocation. Also available are a non-display version of the WCS with a temperature setpoint knob, an occupancy / CO2 sensor / zone temperature version of the WCS, and a relative humidity (RH) sensor add-on daughter board accessory.

Factory-installed vs. Factory-commissioned The terms factory-installed and factory-commissioned are often used interchangeably. Trane takes great pride in being the industry leader in factory-commissioned DDC controllers. The following table differentiates these concepts.

Factory-commissioned controllers provide the highest quality and most reliable units for your system.

Additional testing verifies proper unit operation including occupied/unoccupied airflow and temperature setpoints, communication link functionality, and output device functionality. The benefits of factory-commissioning are standard on VariTrane™ terminal units with Trane DDC controls. This means that factory-commissioned quality on VariTrane™ units is now available on ANY manufacturer’s control system that can communicate using the LonMark® Space Comfort Control (SCC) protocol or the BACnet® protocol. (See Controls section for complete listing of variables which are communicated.)

Table 9. Factory-installed vs. factory-commissioned

Factory-installed Factory-commissioned

Transformer installed (option) X X

Wires terminated in reliable/consistent setting X X

Controller mounted X X

Electric heat contactors and fan relay wired X X

Controller addressing and associated testing — X

28 VAV-PRC016E-EN

Table 9. Factory-installed vs. factory-commissioned (continued)

Factory-installed Factory-commissioned

Minimum and Maximum airflows settings (occupied/unoccupied) — X

Minimum and Maximum temperature setpoints (occupied/unoccupied) — X

Minimum ventilation requirements — X

Heating offset — X

Trane Air-Fi® wireless communications modules (WCI) X X

Trane Air-Fi® Wireless Communications Sensor (WCS) — —

Duct temperature sensor X X

Pre-wired water valve harness X X

VAV-PRC016E-EN 29

Electrical Data VRRF units are available with optional class 2, 50VA, 50/60Hz unit controls transformer available in the following line voltages:

• 120 VAC

• 208 VAC

• 240 VAC

• 277 VAC

• 347 VAC

• 380 VAC

• 480 VAC

• 575 VAC

30 VAV-PRC016E-EN

Jobsite Connections Reference VariTrane™ Round Inlet/Round Outlet (VRRF) Installation, Operation and Maintenance guide (VAV-SVN09*-EN) for detailed jobsite connections. See below for some common installations.

Figure 9. Common VRRF installations

Basic RIRO Unit (Shown without insulation for detail)

Old duct left in place 6” minimum

Old air valve left in place

Existing Legacy Single Duct Unit

Electric Heater

Metal strap hangers secured to building structure

Metal strap hangers secured to building structure

Basic RIRO Unit (Shown without insulation for detail)

Old duct left in place 6” minimum

Old air valve left in place

Existing Legacy Single Duct Unit

Installation of Typical Vertical RIRO

Installation of Basic RIRO Unit Using Hanger Straps

Minimum 1 1/2 duct diameters of straight duct on air terminal inlet

Installation of Basic RIRO Unit without Adapter to Single Duct Unit w/ Electric Heat using Hanger Straps

Installation of Basic RIRO Unit with Adapter to Single Duct Unit w/ Hot Water Heat using Hanger Straps

Metal strap hangers secured to building structure

Duct

Basic RIRO Unit (Shown without insulation for detail)

Minimum 1 1/2 duct diameters of straight duct on air terminal inlet

Metal strap hangers secured to building structure

Minimum 1 1/2 duct diameters of straight duct on air terminal inlet

Basic RIRO Unit (Shown without insulation for detail)

Adapter

Existing Legacy Single Duct Unit

Hot Water Coil (Typically Remains)

Metal strap hangers secured to building structure

VAV-PRC016E-EN 31

Dimensional Data Figure 10. Unit dimensions

14 .70"

5.00"

.38" B

9.50"

C

A (dia)

Table 10. Unit dimensions (in.)

Damper Size A B(a) C Nominal CFM Unit Weight (lb) Adapter Panel Weight (lb)

0 (Control Box Only)(b) n/a n/a n/a 4.75 n/a

4(c) 4.000 21 13 225 21 0.5

5(c) 5.000 21 13 350 21 0.5

6 5.875 21 13 500 20 0.5

8 7.875 21 15 900 22 0.8

10 9.875 21 17 1400 24 1.4

12 11.875 21 19 2000 25 1.6

14 13.875 21 21 3000 27 1.6

16 15.875 21 23 4000 30 1.9

(a) Table values do not include adapter. The adapter increases B dimension by 2.50 in.

(b) Control box dimensions on the Size 0 unit are the same as those shown in graphic above for all VRRF units that include damper.

(c) Size 4 and 5 require a reducer that will increase the B dimension. One or two reducers may be required depending on application. (Not shown in diagram.)

32 VAV-PRC016E-EN

Weights Table 11. Unit weights

Damper Size (in.) Unit Weight (lb) Adapter Panel Weight (lb)

0 (Control Box Only) 4.75 —

4 21 1.6

5 21 1.6

6 20 1.6

8 22 2.1

10 24 2.6

12 25 3.3

14 27 3.7

16 30 4.3

VAV-PRC016E-EN 33

Me…