Addendum #1 Complete Final - Saline Middle School Roofing Project-Sm.pdf
PDF 3 MB Posted
- Attached to
- Request for Proposal- Middle School Roofing
- Solicitation number
- RFP - SAL - 240000000530
- Issued by
- Washtenaw County, St. Louis City, Michigan
About this file
This document is an Addendum to the Request for Proposal for the Saline Middle School Solar-Integrated Roof project issued by the Saline Area Schools in Michigan. The addendum provides updates and clarifications to the original solicitation, including revisions to the project scope, bid submission details, and response to bidder questions.
The project involves the installation of a solar-integrated roof system for the Saline Middle School. Bidders can submit proposals for the entire roof area or separate bid categories covering half the roof. The bid due date remains unchanged at December 5, 2023 at 11:00 AM local time. The addendum includes details on scheduling site visits, obtaining the building permit, and compliance with Davis-Bacon wage requirements. It also provides additional information on the existing roof system composition and the installation of solar anchors and walkway pads. Bidders are asked to indicate if they can complete the project in one or two summers.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid Package - Saline Middle School Roofing Project.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM 1
Project: REVISED Saline Middle School Solar-Integrated Roof
Bid Due date: Tuesday, December 5, 2023, at 11:00 AM Local Time (unchanged)
I. General Information
1. For questions contact Mark Paulus at lecoleplanners3@gmail.com or (248) 880-6791.
2. Attached is the pre-bid meeting sign-in sheet from November 27, 2023.
3. Any bidder requesting to visit the site, contact Mark Paulus at lecoleplanners3@gmail.com or (248) 880-6791 to schedule a time. No bidder shall visit the building with scheduling with Mark Paulus.
4. Advertisement for Bids, Revise 1st paragraph. Saline Area Schools will be receiving bids for the following bid package: Saline Middle School Solar-Integrated Roof.
5. Front End/Request for Proposal, page 1, Revise 1st paragraph. The Saline Area Schools (also referred to as the District or SAS in these documents) will accept sealed bids for: Saline Middle School Solar-Integrated Roof.
6. Front End/Request for Proposal, all pages, revise header. Saline Middle School Solar- Integrated Roof – Bid.
7. Front End/Request for Proposal, page 12, add section Additional Work Scope. Include 8 Hours of coordination for the solar rebate application and other items.
8. Front End/Request for Proposal, page 14, add under unit pricing. Install only, provided by others, solar anchor. The number of anchors anticipated to be installed ranges between 192 and 675 over the entire roof. Attached is the solar anchor information.
9. Front End/Request for Proposal, page 14, add under unit pricing. Furnish and install additional walkway pads for the solar being installed by others. Based the unit pricing on approximately 5,000 square feet for each bid category.
10. Front End/Request for Proposal, pages 13-15. This is the proposal form that is being reissued to include the revisions of this addendum.
II. Questions and Answers
1Q. Is the contractor responsible for obtaining the building permit from the State?
1A. Yes, the contractor is responsible for obtaining the building permit from the State. The cost of the actual permit is part of the general allowance of $20,000.
2Q. Is this project governed by Davis Bacon wage determination?
2A. Yes, this project is governed by Davis Bacon wage determination, and attached is the wage determination.
3Q. Can you provide a drawing showing the deck construction between gypsum and metal?
3A. Attached to this addendum is a drawing showing this information.
4Q. Can you please provide the existing roof system in roof areas 8, 9, 10, and 11 that are complete removal?
4A. The bidder is still responsible for verifying but in support of the bidders based on the documents these areas are long-span metal deck, 1.5” thick isocyanurate insulation, ¾ wood fiberboard insulation, and asphalt BUR with gravel surface. Again, the bidder is still responsible to verify this information and include their findings in their base bid.
ADDENDUM 1
Project: REVISED Saline Middle School Solar-Integrated Roof
Bid Due date: Tuesday, December 5, 2023, at 11:00 AM Local Time (unchanged)
5Q. Does the bidder have to bid on the entire project?
5A. There are 2 bid categories that separate the roof area basically in half. The bidders can bid on each bid category, the entire roof, just one section, or each bid category with a note saying they would like to be awarded 1 category.
6Q. Does this work have to be completed in the summer of 2024?
6A. The bid documents say the bidder can complete this work in both 2024 and 2025. We are asking the bidder to note that on the bid form. We understand this is a large project and want to give the bidders flexibility.
7Q. Will you accept the manufacturers of Johns Manville and Duro-Last as voluntary alternates?
7A. Johns Manville and Duro-Last will be accepted as voluntary alternates as long as they meet the entire specification for all items.
END
SALINE AREA SCHOOLS Business Office Page 13 Saline Middle School Roofing Project - Bid
My signature certifies that the Proposal as submitted complies with all of the terms and conditions set forth in the Request for Proposal unless specifically enumerated as an exception as part of our Proposal.
COMPANY NAME: _____________________________________________________
ADDRESS: ___________________________________________________________
AUTHORIZED SIGNATURE: _____________________________________________
AUTHORIZED NAME (please print): _______________________________________
TITLE: ________________________________________ DATE: ________________
CELL PHONE #: ________________________ FAX #: ________________________
E-MAIL: _____________________________________________________________
The undersigned certifies that the bid contained meets or exceeds the attached specifications. Include the bond and allowances amount in price(s).
BID CATEGORY A SALINE MIDDLE SCHOOL: ROOF AREAS 1-14
Base Bid Amount: $ ____________________
3,000 Square Feet Allowance: Full Removal and Replacement including 3” ISO Insulation in Lieu of Removal of Existing Membrane & Providing Dens Deck & Membrane: $ ____________________
Allowance Amount: $ 20,000.00
Bond Amount: $ ____________________
Grand Total - $ ____________________
Schedule. Project completed in 1 or 2 Summers _____________________
BID CATEGORY B SALINE MIDDLE SCHOOL: ROOF AREAS 15-22
Base Bid Amount: $ ____________________
3,000 Square Feet Allowance: Full Removal and Replacement including 3” ISO Insulation in Lieu of Removal of Existing Membrane & Providing Dens Deck & Membrane: $ ____________________
Allowance Amount: $ 20,000.00
Bond Amount: $ ____________________
Grand Total - $ ____________________
Page 14 Saline Middle School Roofing Project - Bid
BID CATEGORIES A AND B SALINE MIDDLE SCHOOL: ALL AREAS 1-22
Deduct if Awarded Both Categories: $ ____________________
Unit Pricing
Unit Prices (provide unit prices below for adds/deducts)
Replace deteriorated 1” x 6” wood nailers (L.F.) $ ______________
Replace deteriorated 1” x 8” wood nailers (L.F.) $ ______________
Replace deteriorated 2” x 4” wood nailers (L.F.) $ ______________
Replace deteriorated 2” x 6” wood nailers (L.F.) $ ______________
Replace deteriorated 2” x 8” wood nailers (L.F.) $ ______________
Replace deteriorated 2” x 10” wood nailers (L.F.) $ ______________
Replace deteriorated 2” x 12” wood nailers (L.F.) $ ______________
Replace deteriorated 3/4” CDX plywood (S.F.) $ ______________
Replace 1-inch thick flat stock isocyanurate insulation (S.F.) $__ _______
Replace 1.5-inch thick flat stock isocyanurate insulation (S.F.) $__ _______
Replace 2-inch thick flat stock isocyanurate insulation (S.F.) $__ _______
Replace 3-inch thick flat stock isocyanurate insulation (S.F.) $__ _______
Replace deteriorated drain bowls with cast iron (each) $ ______________
Installation only of solar anchors (each) $ ______________
Furnish and install additional walkway pads (S.F.) $ ______________
Bid Questions
Acknowledge receipt of Addendums: ____________________________________
Do you agree to the schedule and terms of the schedule? Yes No
Bid Bond included? Yes No
Familial Disclosure Affidavit included? Yes No
Iran Linked Business Affidavit included? Yes No
Please state your warranty: _____________________________________________
Page 15 Saline Middle School Roofing Project - Bid
State any prompt payment terms: __________% ___________days.
Do you conduct background checks on your employees? Yes No
Are you on the Excluded Parties List, which excludes you from receiving Federal Contracts or certain sub contracts, pursuant to the provisions of 31 U.S.C. 6101, note E.O. 12549, E.O. 12689, 48 C.F.R. 9.404? Yes No Unknown
Provide your DUNS number, if you have one: ____________________________
At least three (3) references with contact person:
Company: __________________ Contact: __________________ Phone: __________
Company: __________________ Contact: __________________ Phone:___________
Company: __________________ Contact: __________________ Phone:___________
Page 16 Saline Middle School Roofing Project - Bid
CONSTRUCTION BID DISCLOSURE STATEMENT – FAMILIAL RELATIONSHIP
Pursuant to MCL 380.1267, a sworn and notarized statement disclosing any familial relationship that exists between the owner or any employee of the bidder and any member of the Saline Area Schools Board or the Saline Area Schools Superintendent must be accompanied with the bid. Bids without this disclosure statement will not be accepted.
The members of the Saline Area Schools Board are Jennifer Steben, Michael McVey, Kandace Jones, Brad Gerbe, Susan Estep, David Hayward, Jenney Miller, Tim Austin, and Lauren Gold.
The Saline Area Schools Superintendent is Dr. Stephen D. Laatsch
€ The Following are the familial relationships:
€ There are none.
STATE OF MICHIGAN )
) ss
COUNTY OF_____________)
The undersigned, authorized representative of bidder (insert name) does hereby acknowledge that bidder has read the foregoing disclosure statement and the statements herein contained are true.
Signature of Bidder Representative
Print Name
Title
Subscribed and sworn to before me this _____day of _________________, _______
Notary Public, ______________County, Michigan My commission expires: ____/____/________
Page 17 Saline Middle School Roofing Project - Bid
AFFIDAVIT OF COMPLIANCE – IRAN ECONOMIC SANCTIONS ACT
Michigan Public Act No. 517 of 2012
The undersigned, the owner or authorized officer of the below named contractor (the “Contractor”), pursuant to the compliance certification requirement provided in the Saline Area Schools (the “School District”) Request For Proposals For Saline Middle School Roofing Project (the “RFP”), hereby certifies, represents and warrants that the Contractor (including its officers, directors and employees) is not an “Iran linked business” within the meaning of the Iran Economic Sanctions Act, Michigan Public Act No. 517 of 2012 (the “Act”), and that in the event Contractor is awarded a contract as a result of the aforementioned RFP, the Contractor will not become an “Iran linked business” at any time during the course of performing the Work or any services under the contract.
The Contractor further acknowledges that any person who is found to have submitted a false certification is responsible for a civil penalty of not more than $250,000.00 or 2 times the amount of the contract or proposed contract for which the false certification was made, whichever is greater, the cost of the School District’s investigation, and reasonable attorney fees, in addition to the fine. Moreover, any person who submitted a false certification shall be ineligible to bid on a request for proposal for three (3) years from the date it is determined that the person has submitted the false certification.
CONTRACTOR:
Name of Contractor
By:
Its:
Date:
STATE OF )
)ss.
COUNTY OF ____________ )
This instrument was acknowledged before me on the _____ day of ________________, 20 , by __________________________.
, Notary Public
______________ County, __________
My Commission Expires:___________
Acting in the County of :___________
8850374.1 31354/151790
Project Name Project Address Project City, Project State Project ZIP
Anchor Products Guide Specification Ver: 20190426A
SECTION XX XX XX
BALLAST FREE, NON-PENETRATING, EQUIPMENT ATTACHMENTS
This is a guide specification intended for use by a design professional and is not suitable as a substitute for professional engineering design and/or documentation required by building code, contract or applicable law.
EQUIPMENT SECUREMENT OVER WATERPROOFING AND ROOFING SYSTEMS
The specification following this cover page is provided to assist the Design Professional in creating a performance specification for the securement of equipment to a waterproofing or roofing surface.
PLEASE NOTE: In the design and installation of equipment over waterproofing and or roofing systems, all parties involved must recognize that existing structural support system was designed based on the loads being applied uniformly. Attachment solutions such as the U-
Anchors, dependent upon the equipment being attached, may apply point loads (upward, downward, transverse or in all directions) to the deck or other structural elements. This design approach may not be feasible in all applications. The new equipment, as well as the effects of the new equipment, will add weight to the structure as well as possibly alter wind effects. In addition, as a result of adding the new equipment, additional weight will be imposed onto the structural requiring an engineering evaluation. Anchor Products highly recommends that an independent structural engineer conduct an investigation of the entire building structure to determine the adequacy of the structural elements to withstand these added loads. Identifying and determining these imposing loads is the responsibility of the system designer.
NOTE: This specification contains hidden text that offers helpful notes and instructions. To use this feature click the SHOW/HIDE button located on the Home menu in the Paragraph section.
Show / Hide Button
(COVER PAGE)
Project City, Project State Project ZIP
This is a guide specification intended for use by a design professional and is not suitable as a substitute for professional engineering design and/or documentation required by building code, contract or applicable law.
SECTION 07, 10, 13, 21, 22, 23, 26, 27, 48:
For best results, display hidden notes to specifier the button located on the Home menu in the Paragraph section.
PART 1 - GENERAL
1.1 SECTION INCLUDES
1.2 RELATED SECTIONS
A Non-ballasted, non-penetrating, rooftop attachment systems for:
1 Section 07 00 00 - Thermal & Moisture Protection.
2 Section 07 71 00 - Roof Specialties.
3 Section 07 72 00 - Roof Accessories.
4 Section 10 14 00 - Signage 5 Section 10 24 00 - Roof Screens 6 Section 13 10 00 - Lightning Protection 7 Section 21 00 00 - Fire Suppression.
8 Section 21 05 29 - Hangers & Supports for Fire Suppression Piping & Equipment 9 Section 21 05 48 - Vibration & Seismic Controls for Plumbing, Piping & Equipment 10 Section 22 00 00 - Plumbing.
11 Section 22 05 29 - Hangers & Supports for Plumbing, Piping & Equipment 12 Section 22 05 48 - Vibration & Seismic Controls Plumbing, Piping & Equipment.
13 Section 22 33 00 - Air Duct Accessories.
14 Section 23 00 00 - Heating, Ventilating & Air Conditioning (HVAC).
15 Section 23 05 29 - Hangers & Supports for HVAC.
16 Section 26 00 00 - Electrical.
17 Section 27 00 00 - Communications.
18 Section 48 14 00 - Solar Electric Power Generation Equipment
1.3 REFERENCES
A ASTM A 123/A 123M – Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products.
B ASTM A 153/A 153M – Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.
C ASTM D 1929 – Standard Test Method for Determining Ignition Temperature of Plastics.
D MSS SP-58 – Pipe Hangers and Supports: Materials, Design and Manufacture;
Manufacturers Standardization Society of the Valve and Fittings Industry.
E MSS SP-69 – Pipe Hangers and Supports: Selection and Application; Manufacturers Standardization Society of the Valve and Fittings Industry.
Project City, Project State Project ZIP
This is a guide specification intended for use by a design professional and is not suitable as a substitute for professional engineering design and/or documentation required by building code, contract or applicable law.
F 2015 IBC, Chapter 16, Section 1609 – Referenced from ASCE 7-16 Chapter 29 “Wind Loads on Building Appurtenances and Other Structures – Main Wind Force Resisting System (Directional Procedure)”
1.4 SYSTEM DESCRIPTION
A Secure rooftop equipment in all zones and regions on roof with an engineered U-Anchor Rooftop Attachment System designed for maintaining a watertight condition without damage to the roofing assembly. The anchor assembly shall consist of a flashing, weatherized steel plate, and a welded, threaded attachment meeting requirements for the specific application. The U-Anchor shall be manufactured by Anchor Products, LLC (see PART 2).
1 Coordinate additional design considerations for seismic and wind zones with the Structural Engineer
1.5 SUBMITTALS
A Submit under provisions of Section 01 30 00.
1 Product Data: Submit for all products proposed for use, describing physical characteristics and method of installation.
2 Shop Drawings: Show installation layout, sizes of units, and details of installation.
1.6 QUALITY ASSURANCE
A Manufacturer Qualifications:
1 Company specializing in manufacturing of rooftop attachments equipment, with a minimum of 10 years of documented experience.
B Installer Qualifications: Company approved by roofing manufacturer.
C Pre-Installation Meeting: After approval of submittals, but before beginning installation, conduct a meeting at the project site attended by the Architect, Contractor, Rooftop Equipment Installers, Installers of roofing, and mechanical, electrical equipment and other systems to be installed on rooftop attachments.
1 Purpose of meeting is to describe in detail the installation process and to establish agreement, coordination, and responsibilities.
2 Prepare detailed meeting report and distribute copies to the Architect and all attendees.
1.7 DELIVER, STORAGE, AND HANDLING
A Deliver all materials to project site in manufacturer's original packaging, marked with manufacturer's name, product model names and catalog numbers, identification numbers, and other related information.
B Store materials under cover until needed for installation.
Project City, Project State Project ZIP
This is a guide specification intended for use by a design professional and is not suitable as a substitute for professional engineering design and/or documentation required by building code, contract or applicable law.
1.8 WARRANTY
A See Section 01 78 00 - Closeout Submittals for additional warranty requirements.
B Warranty: 20-year limited warranty to repair or replace, at the option of the manufacturer, any products found to be structurally defective in material or workmanship.
1 Warranty is not valid if System has been modified, installed incorrectly, or not designed in accordance with manufacturer recommendations.
2 Terms and Conditions: Reference Warranty
PART 2 -PRODUCTS
2.1 MANUFACTURERS
A Acceptable Manufacturer:
1 Anchor Products, LLC i.e. U-Anchor Rooftop Attachments;
a P.O. Box 1551, Colleyville, TX 76034.
b Tel: (888) 575-2131 c www.AnchorP.com d Email: info@anchorp.com
B Requests for substitutions will be considered in accordance with provisions of Section 01 60 00.
2.2 ROOFTOP ANCHOR
A Rooftop Attachment System: Engineered, attachment system specifically designed for installation without the need for exposed roof penetrations, ballast or flashings, and without causing damage to the roofing membrane.
B Provide rooftop anchors with the following:
1 Matching waterproofing type and brand.
2 Documentation of acceptance of attachment solution by roofing manufacturer issuing project guarantee.
3 Documentation of a direct path of attachment from decking through attached equipment
4 Engineering certification stating no potential path for potential water into or through the attachment assembly. Seals, gaskets, sealant and other non-permanent, non-structural solutions are not acceptable.
C Provide the following:
1 U-Anchor 2200 Liquid Applied for use with Reinforced Liquid Applied Systems 2 U-Anchor 2400 Single Ply for use with PVC, TPO, KEE and EPDM 3 U-Anchor 2600 Asphalt for use with APP or SBS Modified Bitumen roof Built Up
Asphalt Systems
Project City, Project State Project ZIP
This is a guide specification intended for use by a design professional and is not suitable as a substitute for professional engineering design and/or documentation required by building code, contract or applicable law.
4 U-Anchor 2800 Coatings for use with roof assemblies coated with One-Part Acrylic Coatings, as well as One-Part and Two-Part Urethane Coatings.
D Provide supporting accessories to complete the proper installation of any rooftop items that are designed as a system and are provided by the rooftop equipment attachment supplier with a sole source warranty:
1 Industrial Process Equipment 2 Guy Lines/Guide Wires 3 Pipe Supports/Hangers 4 Ductwork 5 Plumbing 6 Life Safety a Tie-offs b Safety Railing
7 Snow Retention 8 Visual Screens 9 Signage 10 Walkway, Crossover & Equipment Platform Access 11 Electrical Conduit and Fuse Boxes 12 Lightning Protection Equipment 13 Surveillance Equipment 14 Exterior Lighting 15 Gas and Chemical Lines 16 Photovoltaic and Solar Hot Water systems
PART 3 - EXECUTION
3.1 EXAMINATION
A Verify that roofing system is complete and that roof surfaces are smooth, flat, and ready to receive work of this section.
B Consult the manufacturer’s recommendations and follow all requirements explicitly for installation of adhesive or coating flashing.
3.2 PREPARATION
A Clean surfaces of roof in areas to receive portable support bases.
1 Sweep loose gravel from gravel surfaced roofs.
2 Remove dirt, dust, oils, and other foreign materials.
B Use care in handling portable support system components during installation, to avoid damage to roofing, flashing, equipment, or related materials.
3.3 INSTALLATION OF U-ANCHOR
Project City, Project State Project ZIP
This is a guide specification intended for use by a design professional and is not suitable as a substitute for professional engineering design and/or documentation required by building code, contract or applicable law.
A Prepare the roof surface by removing all loose debris and clean the area in accordance with the roofing manufacturer recommendation.
B Place the anchor over the roof membrane and align as per engineering requirements using the notched alignment marks on each side of the membrane cover. (following all roof manufacturer specific installation requirements)
C Locate bases at spacing indicated by engineering design.
1 Accurately locate and align bases.
2 Provide complete and adequate support of all piping, ducting, and conduit; whether or not all required devices are shown.
D The use of wood for creating equipment supports is not permitted.
E Consult roofing manufacturer of existing or new roofing system for the type of isolation pads required between the roof and base any equipment that may be in contact with the roof surface.
3.4 FIELD QUALITY CONTROL
A When requested by the Architect, provide a factory-trained representative of the manufacturer to visit the site while the work is in progress to assure that the installation conforms to the manufacturers design and installation requirements.
3.5 CLEANING AND PROTECTION
A Remove all packaging, unused fasteners, adhesive and other installation materials from the project site.
B Remove adhesive from exposed surfaces of supports and bases, and leave the work area in clean condition.
C Provide protection as required, leaving the work area in undamaged condition at the time of completion of work.
END OF SECTION
U-ANCHOR™ |
Anchor Products LLC.
PO Box 1551 Colleyville, TX 76034
888-575-2131 www.anchorp.com info@anchorp.com
Secured Mounting Solutions™
* Specified option is standard. Custom options may be available for additional charge. Lead times may apply depending on roofing manufacturer and product availability.
All representations herein are premised on proper installation and use of approved components. Failure to properly install or use of unapproved components voids all Anchor Products representations.
Anchor Products systems are included in many roofing manufacturers’ guarantees!
Please contact us for more information.
U-ANCHOR™ | U2000-PVC
Welded Solution For Fully Adhered Single-Ply Roofing Systems
Product Specifications Bolts
• 3/8”-16 x 1.5” Bolt*
• Material Type: 304 Stainless Steel
Plate (encapsulated between the membranes)
• Outer Diameter: 5.5”
• Steel Thickness: 0.047” (1.194mm)
• Material Type: Galvanized Steel G90
Target Membrane
• Manufacturer: Brand or Non-Brand Specific*
• Color: Default White*
• Length: 15.75”
• Width: 15.75”
• Thickness: Default 60 mil*
Patents
• Visit www.anchorp.com/patents
Packaging Specifications
• Sold Individually OR Full Box Quantity
• Individual Weight: Approx. 1.1875 lbs
• Full Box Quantity: 10 units
• Box Weight: Approx. 17 lbs
• Box Dimensions: 17” x 11” x 17”
• Full Pallet Quantity: 30 boxes
• Pallet Dimensions: 48” x 40” x 67”
Description The U-Anchor 2000-PVC is a lightweight rooftop attachment system consisting of a thermoplastic target membrane and an U-Anchor 2000 series plate. The plate is factory welded to the target membrane and a matching thermoplastic cover membrane is applied over the plate and is welded to the target membrane, encapsulating the plate, followed by a separator disk.
The U2000-PVC provides a watertight, warranted attachment solution for PVC roofing systems.
The U2000-PVC is ideal for roof assemblies that are difficult to fasten to, and provides additional tax incentives for qualifying rooftop solar installations.
Additionally, the U2000-TPO acts as an effective expansion joint at each rooftop attachment point and minimizes stress to roof components.
Advantages
• Extremely strong and lightweight.
• Fast installation, approximate rate of 12 per man hour.
• Installs on any flat or low slope surface.
U-Anchor Attachment The U2000-PVC is attached to a fully adhered roofing system by hot air welding around the perimeter edge consistent with the specified roofing manufacturer’s hot air welding specifications.
(Alternative options available for mechanically attached roof assemblies.)
Location and spacing of each U2000-PVC is dictated by project specific engineering.
Equipment Attachment To securely mount your rooftop equipment to the U-Anchor, after its installed, the connection nut must be tightened to approximately 20-25 ft.-lbs.
Use a calibrated torque wrench during install to ensure appropriate results are achieved.
Refer to product documentation for detailed installation and component requirements.
Testing Results are based on plate performance only.
• Shear and Tension values vary dependent upon roof assembly.
• Contact engineering for specific values.
Tested in accordance with ICC AC467 Individual roof deck assembly tests available upon request as application specific results may vary.
Warranty
• 20 Year Limited Material Only Warranty.
Subject to terms and conditions.
BackFront
If required, apply seam sealant in accordance with the roofing manufacturer’s specifications.Probe the seam to make sure the membrane is welded properly.
If required, apply seam sealant in accordance with the roofing manufacturer’s specifications.
STEP 2
Clean the roof surface with the manufacturer’s recommended cleaner.
Using the manufacturer’s written specifications, hot air weld the perimeter edge of the cover membrane using a 2-inch roller to achieve a minimum 2-inch weld around the perimeter.
STEP 1
Align the U-Anchor according to the engineered design. Most designs are transferred to the roof surface with chalk lines.
*Avoid using Permanent chalk - such as red chalk.
U-ANCHOR INSTALLATION
U2000-PVC, TPO, KEE, TPA Roof Membranes
888-575-2131www.anchorp.com
The following instructions are meant to be utilized by an experienced and professional roofing contractor using the proper equipment, techniques, and safety protocols – not just the average handyman. Each installation should always follow the specified roofing manufacturer’s written specification.
888-575-2131
SOLAR
SOLUTION GUIDE
Roofing Experience: A Vital Necessity
Anchor Products evolved out of the roofing industry.
We started as roofers that focused on understanding and mastering all types of low slope, single-ply commercial roofing, and with that knowledge, we created the perfect mounting solutions for
Solar Installers. Our Solutions allow solar professionals to mount a photovoltaic system to the roof with the utmost confidence, while providing reliability that the system will remain in place and assure that no damage will be done to the roof.
Partner with us for our reliable solutions. Because we are roofers first, the roof surface that you are making installations on stays protected, every single time.
Solar Mounting Solutions So Simple, They Are Brilliant.
Key Reasons Using U-Anchor Matters for Solar Array Installations
U-Anchor is the Right Choice
U2400 is a lightweight rooftop attachment system consisting of a U-Anchor 2000 Series plate and the same cover membrane of your roof. The membrane is factory heat-welded to the top of the plate. It provides a watertight, manufacturer-accepted attachment for mechanically attached and fully adhered single-ply membranes. U2400 is available for EPDM, KEE, PVC and TPO roofing materials.
The U-Anchor installs easily in minutes, saving you time and manpower while reinforcing the strength of your solar panels.
Efficient Installation Not only is the installation quick, it is very cost effective. The installation of the U-Anchor system results in reduced cost in labor, maintenance and liability. A win-win all the way around.
Superior Strength Each U-Anchor shows exceptional resistance to both tension and shear. The attachment provides unparalleled securement for your solar panel system against high winds, seismic events or any other natural hazards.
Universal Application For All Roof Types This system can be safely attached to commercial grade TPO, PVC, EPDM, Asphalt and coated roofs. The U-Anchor is a non-penetrating securement method. Accepted by all major North American roofing manufacturers.
Lightweight U-Anchor is lighter and adds significantly less weight to the roof than other methods. Transportation and handling of the U-Anchor system is much easier than the industry standard methods used today.
Simplified Engineering With Consistent Design The U-Anchor is a fully-designed attachment system, tested and proven to provide a consistent performance in strength, regardless of weather and other natural occurrences. It provides a better solution for commercial rooftop systems.
U-Anchors combine strength, efficiency and versatility across the spectrum of solar installations.
KEE
KEE
EPDM
APP
U2000 SERIES
5.5" x 5.5" Galvanized Steel Plate
U2400
U2800
U2600
PVC
PVC
TPO
TPO
SBS
SBS Torch
Coatings
Anatomy of the U-Anchor*
*U2400 shown above
Membrane Separator: heat-welded to the cover membrane to protect it from mounting-rack brackets.
Cover Membrane: heat-sealed to the center of the solid plate.
Stainless Steel Bolt: welded to the plate with no possible path for water intrusion.
Solid Lightweight G90 Galvanized Steel Plate: anchor with rolled edges to protect the roof.
2 Anchor Products Solar Solutions Guide anchorp.com | 888.575.2131 anchorp.com | 888.575.2131 3
Comparing a Fully Anchored™ System to a Ballasted System vs.vs.
Solid Plate Technology is Superior to Compression Seals
Traditional ballast may still be a popular method, however Fully Anchored™ is the fastest growing solution in the market.
When choosing roof attachment securement for your solar investment, whether it’s a ballasted solar array or the fully attached U-Anchor securement from Anchor Products, you must consider performance, cost, ease of installation, and protection of the roof surface.
Compression seal technology is vulnerable to leaking. U-Anchor solid plate solutions are not. It is just that simple.
COMPRESSION SEAL ISSUES:
A doughnut hole in the base compression seal is an opening in the attachment, where water can collect and can create a water path leading to a leak.
Vibrations and movement cause the fasteners that secure the compression seal pieces to back out, compromising the seal and allowing for catastrophic leaks.
Wind loads apply tension to a compression seal, pulling its components apart and allowing water to get under the seal.
Bolts, compression seals and caulk require invasive inspections and necessary maintenance, which are not included in warranty coverage.
Frequent inspections and constant maintenance require adjustments to hardware and components, which often lead to downtime and possibly interruption of business.
BALLAST ISSUES:
Ballast is considered an overburden to the roof and manufacturers will not cover damages caused by the effects of ballast.
Ballast can be ineffective in high wind or seismic event scenarios, as they can be blown from their placement and damage rooftop equipment, as well as the roof surface.
Ballast blocks typically weigh 30 lbs. each, putting unnecessary weight on the crew and the structure itself, which causes more damage over time.
U-ANCHOR SOLUTION:
U-Anchors can be included in the warranty of the roof, and are allowed as a “roof-friendly” solution by all manufacturers.
U-Anchors fastened to the roof will prohibit all movement and will eliminate issues caused by vibrations, preventing stress on the racking, array, connections, conduit and roof membrane.
U-Anchors weigh less than a pound, and in turn, offset thousands of pounds of ballast. They are easy to load and will not damage the roof. A quick installation makes them more time efficient as well.
The U-Anchor stands out when it comes to holding strength, efficiency and cost. If you’re still not sure, have our team do a cost analysis and walk you through the installation process. We will demonstrate why the U-Anchor is the superior choice for securing your solar array.
COMMON COMPRESSION SEAL U-2400 ANCHOR
U-ANCHOR SOLUTION:
Fully-adhered U-2000 Solutions are heat-welded to the roof, which forms a non-penetrating waterproof protective shield.
U-2000 Anchors are engineered as an integrated rooftop component and are unaffected by vibration or movement.
When installed properly, U-2000 Series anchors are part of the roof. They will not come apart and water cannot get in.
The U-Anchor is the ONLY solution included in some roofing manufacturers’ guarantee. No maintenance is required to uphold the Anchor Products warranty.
No maintenance means no downtime. No worries.
LEAK ENTRY POINT
AFTER FATIGUE
NO SEAL REQUIRED –
NO LEAK PATH
4 Anchor Products Solar Solutions Guide anchorp.com | 888.575.2131 anchorp.com | 888.575.2131 Anchor Products Solar Solutions Guide 5
PROVEN RELIABLE:
Shedd Aquarium
CHICAGO, ILLINOIS
Chicago’s blustery lake winds and extreme temperatures are no match for the strength and reliability of the U-Anchor Solutions.
PROVEN STRONG:
Westin Dawn Resort
ST. MAARTEN
The U-Anchor proved its strength by withstanding gale-force winds of Category 5 Hurricane, Irma, as our mounting racks remained intact with only debris damage.
PROVEN COMPLIANT:
Mandalay Bay
LAS VEGAS, NEVADA
The U-Anchor continues to set standards by exceeding code with its tested, cost effective, non-penetrating solutions as demonstrated atop this iconic desert destination.
PROVEN SECURE:
iPark Hudson
YONKERS, NEW YORK
Flying debris damaged some of the solar panels at this exclusive office park during Superstorm Sandy, but the U-Anchor did not falter in those high winds, protecting that rooftop investment.
BY THE NUMBERS:
ANCHOR PRODUCT
SOLUTION
U-ANCHOR
U2800-COATINGS™
SOLAR PANELS 913
PROJECT SIZE 264 KW
INSTALLED BY INNOVATIVE
BY THE NUMBERS:
ANCHOR PRODUCT
SOLUTION U-ANCHOR 2000
PROJECT SIZE 900 kW
MODULES INSTALLED 913
INSTALLED BY SXW WIND POWER
HURRICANES SURVIVED 3 (CATEGORY
1, 4, 5)
BY THE NUMBERS:
ANCHOR PRODUCT
SOLUTION U-ANCHOR 2000
SOLAR PANELS 21,325
PROJECT SIZE 6.4 MWp
INSTALLED BY SUNORA ENERGY
SOLUTIONS
BY THE NUMBERS:
ANCHOR PRODUCT
SOLUTION U-ANCHOR 2000
PROJECT SIZE 1.22 MW
SOLAR PANELS 3,700
ROOF AREA 110,000 SQ FT
HURRICANES SURVIVED 2 (CATEGORY
1, 4)
More Than Just Solar Attachments
WE HAVE ALL THE SOLUTIONS FOR ANY OF YOUR ROOFING NEEDS:
There is no solar array system project too big or too small for us to help you with your attachment needs. Utilize the U-Anchor and AP Solutions to secure your conduit, junction boxes, combiner boxes, batteries and electrical boxes, and many other rooftop equipment securement needs. Our team will help find the perfect anchor and solution to fit the needs of your project.
MEP ELECTRICALLIGHTNING
PROTECTION
ACCESSGUARDRAIL FALL SAFETY EQUIPMENT
SECUREMENT
SNOW
RETENTION
SOLARPIPE/CONDUIT
SUPPORT
INVERTER
BOXES
6 anchorp.com | 888.575.2131 anchorp.com | 888.575.2131 Anchor Products Solar Solutions Guide 7
Custom Orders Built To Your Needs We will help you customize a proven solution for your solar installation.
Why Anchor Products Anchor Products was first-to-market with a seamless, non-penetrating solar attachment in 2014, and it remains the only manufacturer of lightweight, watertight anchors for solar and all other commercial rooftop equipment.
Anchor Products – reinforcing your trust in our ease of installation, superior strength, universal use and our roof-friendly application to remain code compliant.
• Simple Installation – Installation made easy to anchor your rooftop equipment to the roof’s surface safely and easily.
• Superior Strength – The strength of the U-Anchor and its Solutions is first class and is able to resist high levels of tension and shear to provide securement in high winds or seismic events.
• Rooftop Compatibility – Anchor Products secures equipment and accessories for TPO, PVC, EPDM, Asphalt and coated roofs, and matches your roof’s color and material..
• Roof-Friendly and Code Compliant – The U-Anchor is a non-penetrating securement method. Accepted by major North American roofing manufacturers. This method is code compliant to maintain the integrity of the roof’s warranty.
Let us help you find your Solution and educate you on the benefits of the Solar Investment Tax Credit.
Roofing projects that include solar installation are eligible for the Solar Investment Tax Credit— plus bonus depreciation on the roof. Ask us how the Solar Tax Credit can work for you.
If your solar installation includes conduits, junction boxes, combiner boxes, batteries or electrical boxes – or any combination – Anchor Products will work with you to design a solution that fulfills your securement needs.
Put the Anchor Products advantage to work for you.
Contact us today to learn how:
888-575-2131 or info@anchorp.com
Fewer U-Anchors and touchpoints are needed to secure your solar array and equipment versus less effective securement options.
Anchor Products proudly provides the U-Anchor rooftop solar securement system for the membrane roof solar array atop the famed Shedd Aquarium in the Windy City.
Anchor Products proudly provides the U-Anchor rooftop solar securement system for the membrane roof solar array atop the famed Shedd Aquarium in the Windy City.
info@anchorp.com
P.O. Box 1551 | Colleyville, TX 76034
888.575.2131 www.anchorp.com
"General Decision Number: MI20230100 10/27/2023
Superseded General Decision Number: MI20220100
State: Michigan
Construction Type: Building
County: Washtenaw County in Michigan.
BUILDING CONSTRUCTION PROJECTS (does not include single family homes or apartments up to and including 4 stories).
Note: Contracts subject to the Davis-Bacon Act are generally required to pay at least the applicable minimum wage rate required under Executive Order 14026 or Executive Order 13658.
Please note that these Executive Orders apply to covered contracts entered into by the federal government that are subject to the Davis-Bacon Act itself, but do not apply to contracts subject only to the Davis-Bacon Related Acts, including those set forth at 29 CFR 5.1(a)(2)-(60).
|If the contract is entered |. Executive Order 14026 | |into on or after January 30, | generally applies to the | |2022, or the contract is | contract. | |renewed or extended (e.g., an |. The contractor must pay | |option is exercised) on or | all covered workers at | |after January 30, 2022: | least $16.20 per hour (or | | | the applicable wage rate | | | listed on this wage | | | determination, if it is | | | higher) for all hours | | | spent performing on the | | | contract in 2023. | |If the contract was awarded on|. Executive Order 13658 | |or between January 1, 2015 and| generally applies to the | |January 29, 2022, and the | contract. | |contract is not renewed or |. The contractor must pay all| |extended on or after January | covered workers at least | |30, 2022: | $12.15 per hour (or the | | | applicable wage rate listed| | | on this wage determination,| | | if it is higher) for all | | | hours spent performing on | | | that contract in 2023. |
The applicable Executive Order minimum wage rate will be adjusted annually. If this contract is covered by one of the Executive Orders and a classification considered necessary for performance of work on the contract does not appear on this wage determination, the contractor must still submit a conformance request.
Additional information on contractor requirements and worker protections under the Executive Orders is available at http://www.dol.gov/whd/govcontracts.
Modification Number Publication Date 0 01/06/2023 1 02/03/2023 2 04/07/2023 3 07/21/2023 4 09/01/2023 5 09/08/2023 6 10/20/2023 7 10/27/2023
ASBE0025-003 06/01/2021
Townships of Ann Arbor, Augusta, Lodi, Northfield, Pittsfield, Salem, Saline, Scio, Superior, Webster, Ypsilanti & York
Rates Fringes
ASBESTOS WORKER/HEAT & FROST
INSULATOR........................$ 35.41 32.91
ASBE0047-001 07/01/2023
Townships of Bridgewater, Dexter, Freedom, Lims, Lyndon, Manchester, Sharon & Sylvan
Rates Fringes
ASBESTOS WORKER/HEAT & FROST
INSULATOR........................$ 36.62 19.78
* BOIL0169-001 06/01/2023
Rates Fringes
BOILERMAKER......................$ 39.95 35.38
* BRMI0009-010 08/01/2023
Rates Fringes
BRICKLAYER.......................$ 39.24 27.68
TILE FINISHER....................$ 28.58 21.34
TILE SETTER......................$ 38.99 23.31
CARP0687-001 06/01/2021
Rates Fringes
CARPENTER, Includes Drywall Hanging, Form Work, and Metal Stud Installation................$ 35.16 29.22
CARP1045-001 06/01/2020
Rates Fringes
CARPENTER (Floor Layer - Carpet, Resilient, & Vinyl Flooring)........................$ 30.60 24.58
CARP1102-002 06/01/2020
Rates Fringes
MILLWRIGHT.......................$ 35.30 34.10
ELEC0252-010 06/01/2021
Rates Fringes
ELECTRICIAN......................$ 47.46 27%+12.25
ENGI0324-017 06/01/2023
Rates Fringes
OPERATOR: Power Equipment
GROUP 1....................$ 47.49 25.35
GROUP 2....................$ 46.29 25.35
GROUP 3....................$ 44.79 25.35
GROUP 4....................$ 44.49 25.35
GROUP 5....................$ 43.67 25.35
GROUP 6....................$ 42.81 25.35
GROUP 7....................$ 41.84 25.35
GROUP 8....................$ 40.13 25.35
GROUP 9....................$ 31.79 25.35
FOOTNOTES:
Tower cranes: to be paid the crane operator rate determined by the combined length of the mast and the boom. If the worker must climb 50 ft. or more to the work station, $.25 per hour additional.
Derrick and cranes where the operator must climb 50 ft. or more to the work station, $.25 per hour additional to the applicable crane operator rate.
POWER EQUIPMENT OPERATOR CLASSIFICATIONS
GROUP 1: Crane with boom and jib or leads 400' or longer
GROUP 2: Crane with boom and jib or leads 300' or longer
GROUP 3: Crane with boom and jib or leads 220' or longer
GROUP 4: Crane with boom and jib or leads 140' or longer
GROUP 5: Crane with boom and jib or leads 120' or longer
GROUP 6: Regular crane operator, and concrete pump with boom operator
GROUP 7: Backhoe/Excavator/Trackhoe, bobcat/skid Loader, broom/sweeper, bulldozer, grader/blade, highlift, hoist, loader, roller, scraper, tractor & trencher
GROUP 8: Forklift & extend-a-boom forklift
GROUP 9: Oiler
IRON0025-019 06/01/2022
Rates Fringes
IRONWORKER
REINFORCING.................$ 31.43 34.77
STRUCTURAL..................$ 34.85 40.42
LABO0334-005 06/01/2023
Rates Fringes
LABORER: Landscape & Irrigation
GROUP 1.....................$ 25.97 8.60
GROUP 2.....................$ 23.75 8.60
CLASSIFICATIONS
GROUP 1: Landscape specialist, including air, gas and diesel equipment operator, lawn sprinkler installer, skidsteer (or equivalent)
GROUP 2: Landscape laborer: small power tool operator, material mover, truck driver and lawn sprinkler installer tender
LABO0499-005 08/01/2022
Rates Fringes
LABORER
Common or General; Grade Checker; Sandblaster........$ 30.66 14.70 Mason Tender - Brick;
Mason Tender - Cement/Concrete.............$ 31.21 14.70 Pipelayer...................$ 31.02 14.70
PAIN0022-003 06/01/2022
Rates Fringes
PAINTER: Brush and Roller.......$ 32.85 20.41 PAINTER: Drywall Finishing/Taping.................$ 32.85 20.41 PAINTER: Spray..................$ 26.86 17.66
PAIN0357-002 06/01/2023
Rates Fringes
GLAZIER..........................$ 38.66 20.98
PAID HOLIDAYS: New Year's Day, Decoration Day, Fourth of July, Labor Day, Thanksgiving Day and Christmas Day;
provided that the employee has worked the last full regular scheduled work day prior to the holiday, and the first full regular scheduled work day following the holiday, provided the employee is physically able to work.
PLAS0514-006 06/01/2018
Rates Fringes
CEMENT MASON/CONCRETE FINISHER...$ 31.47 13.81
PLUM0190-004 06/01/2023
Rates Fringes
PIPEFITTER (Including HVAC Pipe Installation; Excluding HVAC System Installation)........$ 46.88 23.70 PLUMBER, Excludes HVAC Pipe and Unit Installation............$ 44.31 23.70
ROOF0070-001 05/08/2023
Rates Fringes
ROOFER...........................$ 39.67 18.85
SFMI0704-001 08/01/2023
Rates Fringes
SPRINKLER FITTER (Fire Sprinklers)......................$ 49.72 32.00
SHEE0080-001 06/01/2022
Rates Fringes
SHEET METAL WORKER, Includes HVAC Duct and Unit Installation.....................$ 47.64 26.15
TEAM0247-001 06/01/2023
Rates Fringes
TRUCK DRIVER
GROUP 1
Flatbed; Pickup; Dump & Tandem.....................$ 29.82 0.70+a+b
GROUP 2
Semi.......................$ 29.97 0.70+a+b
GROUP 3
Lowboy.....................$ 30.07 0.70+a+b
PAID HOLIDAYS: New Year's Day, Memorial Day, Independence Day, Labor Day, Thanksgiving Day and Christmas Day. If any of the above holidays fall on a Sunday, the following
Monday shall be considered the holiday and, if work is performed, the rate shall be double time.
FOOTNOTE:
a. $456.70 per week, plus $67.10 per day.
* SUMI2011-025 02/01/2011
Rates Fringes
IRONWORKER, ORNAMENTAL...........$ 18.48 7.93
TRUCK DRIVER: Tractor Haul Truck............................$ 13.57 ** 1.18
WELDERS - Receive rate prescribed for craft performing operation to which welding is incidental.
** Workers in this classification may be entitled to a higher minimum wage under Executive Order 14026 ($16.20) or 13658 ($12.15). Please see the Note at the top of the wage determination for more information.
Note: Executive Order (EO) 13706, Establishing Paid Sick Leave for Federal Contractors applies to all contracts subject to the Davis-Bacon Act for which the contract is awarded (and any solicitation was issued) on or after January 1, 2017. If this contract is covered by the EO, the contractor must provide employees with 1 hour of paid sick leave for every 30 hours they work, up to 56 hours of paid sick leave each year.
Employees must be permitted to use paid sick leave for their own illness, injury or other health-related needs, including preventive care; to assist a family member (or person who is like family to the employee) who is ill, injured, or has other health-related needs, including preventive care; or for reasons resulting from, or to assist a family member (or person who is like family to the employee) who is a victim of, domestic violence, sexual assault, or stalking. Additional information on contractor requirements and worker protections under the EO is available at https://www.dol.gov/agencies/whd/government-contracts.
Unlisted classifications needed for work not included within the scope of the classifications listed may be added after award only as provided in the labor standards contract clauses (29CFR 5.5 (a) (1) (ii)).
The body of each wage determination lists the classification and wage rates that have been found to be prevailing for the cited type(s) of construction in the area covered by the wage determination. The classifications are listed in alphabetical order of ""identifiers"" that indicate whether the particular rate is a union rate (current union negotiated rate for local), a survey rate (weighted average rate) or a union average rate (weighted union average rate).
Union Rate Identifiers
A four letter classification abbreviation identifier enclosed in dotted lines beginning with characters other than ""SU"" or ""UAVG"" denotes that the union classification and rate were prevailing for that classification in the survey. Example:
PLUM0198-005 07/01/2014. PLUM is an abbreviation identifier of the union which prevailed in the survey for this classification, which in this example would be Plumbers. 0198 indicates the local union number or district council number where applicable, i.e., Plumbers Local 0198. The next number, 005 in the example, is an internal number used in processing the wage determination. 07/01/2014 is the effective date of the most current negotiated rate, which in this example is July 1, 2014.
Union prevailing wage rates are updated to reflect all rate changes in the collective bargaining agreement (CBA) governing this classification and rate.
Survey Rate Identifiers
Classifications listed under the ""SU"" identifier indicate that no one rate prevailed for this classification in the survey and the published rate is derived by computing a weighted average rate based on all the rates reported in the survey for that classification. As this weighted average rate includes all rates reported in the survey, it may include both union and non-union rates. Example: SULA2012-007 5/13/2014. SU indicates the rates are survey rates based on a weighted average calculation of rates and are not majority rates. LA indicates the State of Louisiana. 2012 is the year of survey on which these classifications and rates are based. The next number, 007 in the example, is an internal number used in producing the wage determination. 5/13/2014 indicates the survey completion date for the classifications and rates under that identifier.
Survey wage rates are not updated and remain in effect until a new survey is conducted.
Union Average Rate Identifiers
Classification(s) listed under the UAVG identifier indicate that no single majority rate prevailed for those classifications; however, 100% of the data reported for the classifications was union data. EXAMPLE: UAVG-OH-0010 08/29/2014. UAVG indicates that the rate is a weighted union average rate. OH indicates the state.