This Addendum #1 Appendix F is an inspection report prepared for the Douglasville - Douglas County Water and Sewer Authority (DDCWSA) regarding the West Banks Mill Tank, a 500,000-gallon elevated welded steel storage tank located on West Banks Mill Road in Winston, Georgia. The inspection was conducted on December 5, 2017, following the tank's removal from service for cleaning and comprehensive interior and exterior evaluation. The tank, constructed in 2003 by Caldwell Tanks, Inc., is supported by six welded steel columns with concrete pedestal foundations and features a 60-inch diameter welded steel riser with a torospherical bowl design. The inspection assessed the structural integrity, coating condition, accessories, site conditions, and overall maintenance requirements of the facility, with the tank receiving a low ranking on the maintenance priority list based on the generally excellent condition of the interior coating system and structural components.
The inspection identified specific rehabilitation recommendations organized into three categories: exterior surfaces requiring pressure washing and overcoating with epoxy intermediate and urethane finish coats at an estimated cost of $68,600; accessories modifications including drain line rerouting ($6,500), altitude valve vault painting ($1,200), siphon pipe installation ($4,000), and fence repair ($1,500); and site maintenance consisting of fallen tree removal and fence repair ($1,500) and trim overgrowth ($250). The engineer's opinion of total probable construction costs, including bonds, insurance, mobilization, contingency, engineering and inspection, and inflation allowances, totaled $284,891. The inspection documented minor coating failures, mildew growth, and corrosion at specific locations, with less than five spots of interior floor corrosion and excellent coating adhesion throughout most of the structure, supporting the assessment that the tank was in generally good operational condition despite some cosmetic and maintenance concerns requiring attention.
Text of this file
West Banks Elevated Tank – December 2017 1
WEST BANKS MILL
500,000 Gallon Elevated Tank
West Banks Elevated Tank – December 2017 2
I. Introduction
On December 5, 2017 the West Banks Mill Tank was taken out of service, cleaned, and a complete interior and exterior inspection was performed. Once the inspection was complete, the tank was disinfected in accordance with AWWA recommendations and put back into service. The following is a summary of the inspection. Also included in the inspection report is a list of recommended rehabilitation work, a construction cost estimate, historical maintenance records, and a recommended maintenance ranking compared to other water storage tanks in the Douglasville – Douglas County Water and Sewer Authority (DDCWSA) water system.
II. General B. 500,000 gallon elevated tank
C. Welded steel construction
D. Located on West Banks Mill Road 0.04 miles east of the intersection of Tyree
Road and West Banks Mill Road.
E. Elevated torospherical bowl supported by six (6) welded steel columns with tie rods.
F. 60 inch diameter welded steel riser
G. Concrete pedestal foundations
III. Observations
A. Exterior Coating
The coating on the exterior of the tank is generally in good condition. Adhesion of all layers of the coating system, inter-coat and substrate, appeared to be excellent on the riser and columns. Adhesion on the tank bowl appeared to be excellent between the steel, prime coat, and intermediate coat. The adhesion of the finish coat on the bowl appeared to be poor.
The coating system on the bowl around the balcony had an average dry film thickness of 16.7 mils. Most of the exterior of the tank/support columns had a thin layer of mildew growth and the protective coatings are chalking (deterioration of epoxy binder). The exterior coating exhibited a few areas of coating failure, mostly limited to the lower portions of the column legs and column anchor plates. Several areas of the tank appeared to have a secondary coating covering up areas of graffiti.
B. Column Foundations and Anchor Bolts
All six (6) of the tank column foundations were inspected. Concrete foundations appeared to be in good condition, with the exception to minor spalling on Column 5. Minor
West Banks Elevated Tank – December 2017 3 corrosion was observed at the interface of the column anchor plate and the grout bearing pad in several locations. Tie rods and turnbuckles were observed and appeared to be in good condition, with the exception of light mildew along their length and minor corrosion at rub points where the tie rods cross.
C. Interior Coating
The interior coating system is generally in excellent condition with less than five (5) locations of spot corrosion on the floor. Coating thickness was tested resulting in an average measured thickness of 15.0 mils. The coating on the interior of the riser appeared to be in good condition. Coating adhesion on the tank interior appeared to be excellent between all layers. One area was observed to be experiencing minor pitting (approximately 1/16” deep) and was repaired with Aquatapoxy prior to disinfection.
D. Exterior Accessories
The tank is equipped with a column ladder and fixed bowl ladder. The column ladder extends to the outside edge of the tank balcony and is structurally sound. The column ladder is equipped with a cable safety climb system and a lockable ladder shield. SCADA communication cables/conduit are attached to the column ladder and appear to be in good condition. The bowl ladder is also equipped with a cable safety climb system and antenna cables are securely attached to the ladder.
The tank bowl balcony is 36-inches wide and has a 42-inch tall handrail. The balcony has drainage holes that prevent water from pooling on the balcony; however, there does appear to be a few areas where new drainage holes need to be drilled. Two (2) antennas are mounted to the balcony handrail. One additional antenna is mounted adjacent to the tank vent. Abandoned stainless steel antenna mast anchor plates are located adjacent to the antenna. The tank vent is a round type which is equipped with an insect screen.
The bowl roof hatch is a 30-inch square opening with a hinged and lockable cover.
An additional 24-inch bolted access hatch is located on the roof adjacent to the vent. It is in good condition, but is not equipped with hinges. The tank is not equipped with obstruction lighting.
The riser is equipped with a 24-inch diameter binged, flanged manway. The manway appears to be in good condition with the exception of the corroded bolts.
West Banks Elevated Tank – December 2017 4
E. Interior accessories
The tank bowl is equipped with one interior ladder which is in good condition and is equipped with a rigid rail safety climbing system. A safety grate is installed at the top of the riser and appeared to be in good condition.
The tank riser has a 12-inch inlet/outlet pipe with deflector plate and a drain line.
The piping inside the riser appears to be in good condition. The inlet/outlet pipe is equipped with a removable silt stop assembly and deflector plate that extends 18 inches off the riser floor.
An 8-inch overflow pipe extends up column 3 penetrating the tank balcony and then the sidewall of the tank. The overflow pipe is supported at intervals along its length and discharges on a concrete splash pad on grade. The overflow pipe is equipped with a flap valve and screen.
F. Site
The tank site was clean and well maintained. The tank drain is routed to the southwest corner of the site and discharges via a riser pipe and flap valve approximately 4 feet above grade. The tank eventually drains off into the woods and onto residential property to the east of the tank site. The resident located south of the tank site has mentioned to
DDCWSA personnel that the water runs onto his property from the drain line, but it does not create damage as long as it flows at low volume.
Site fencing is in good condition. There are two (2) locations where a tree has fallen across the site fence. The fence is topped with 3-strand barbed wire. A double leaf gate provides access to the site.
IV. Maintenance Priority
Based on observations described herein, and specifically based on the overall condition of the interior of the tank, the West Banks Mill Tank has been assigned a low ranking on the maintenance priority list.
West Banks Elevated Tank – December 2017 5
V. Recommendations
Rehabilitation recommendations include:
A. Exterior Surfaces
• Pressure wash and overcoat existing tank with an epoxy intermediate coat and urethane finished coat.
• Mechanically clean areas of spot corrosion prior to coating application.
B. Accessories
• Re-route drain line below grade and off site. Daylight the drain line and terminate with flap valve.
• Paint altitude valve vault piping and valves.
• Install a siphon pipe in the tank to facilitate draining the lower portion of the tank bowl.
C. Site
• Remove fallen trees and repair site fence.
VI. Historical Improvements, Repairs and Inspections
Item Date Year Constructed 2003
Washout, cleaning and inspection 2014
Washout, cleaning and inspection 2017
West Banks Elevated Tank – December 2017 6
Figure 1 - Riser Manway
Figure 2 - Electrical Cabinet
West Banks Elevated Tank – December 2017 7
Figure 3 - Column No. 1 with Ladder
Figure 4 – Typical Column Foundation
West Banks Elevated Tank – December 2017 8
Figure 5 – Corrosion at Riser Baseplate
Figure 6 – Damage to Coating on Column
West Banks Elevated Tank – December 2017 9
Figure 7 – Typical Anchor Bolt Connection
Figure 8 – Typical Tie Rod Turn Buckle
West Banks Elevated Tank – December 2017 10
Figure 9 – Corrosion on Tie Rod
Figure 10 - Inlet/Outlet Pipe & Drain Line with Deflector Plates
West Banks Elevated Tank – December 2017 11
Figure 11 – Coating Cracking on Riser
Figure 12 – Column Ladder at Bowl Balcony
West Banks Elevated Tank – December 2017 12
Figure 13 – Exterior Mildew
Figure 14: Corrosion on Tank Balcony Handrail
West Banks Elevated Tank – December 2017 13
Figure 15: Drainage in Balcony Floor
Figure 16: Antenna on Balcony
West Banks Elevated Tank – December 2017 14
Figure 17: Exterior Bowl Ladder w/ Safety Climb
Figure 18: Tank Vent and Antenna
West Banks Elevated Tank – December 2017 15
Figure 19: Antenna Anchor Plates (Not Used)
Figure 20: 30-inch Square Roof Hatch
West Banks Elevated Tank – December 2017 16
Figure 21: Additional 24-inch Diameter Access Hatch
Figure 22: Bowl Ladder, Antenna, and Roof Vent
West Banks Elevated Tank – December 2017 17
Figure 23: Overflow Pipe and Interior Roof Plates
Figure 24: Typical Tank Interior
West Banks Elevated Tank – December 2017 18
Figure 25: Riser Safety Grate
Figure 26: Roof Structure
West Banks Elevated Tank – December 2017 19
Figure 27: Interior Bowl Ladder and Rail Safety Climb
Figure 28: Spot Corrosion on Tank Interior Floor
West Banks Elevated Tank – December 2017 20
Figure 29: Tank Site Looking Southwest
Figure 30: Tank Drain
West Banks Elevated Tank – December 2017 21
Figure 31: Drain w/ Flap Valve and Screen
Figure 32: Tree Damage on Site Fence
West Banks Elevated Tank – December 2017 22
Figure 33: Rain Gauge
Figure 34: Site Entrance
West Banks Elevated Tank – December 2017 23
Figure 35: West Banks Mill Road at Tank Site (looking South)
Figure 36: West Banks Mill Road Tank Site (looking East)
West Banks Elevated Tank – December 2017 24
Figure 37: West Banks Mill Road Tank Site (looking East)
Figure 38: West Banks Mill Road Tank
West Banks Elevated Tank – December 2017 25
END OF REPORT
West Banks Elevated Tank – December 2017 26
THIS PAGE IS INTENTIONALLY LEFT BLANK
APPENDIX A
Construction Cost Estimate
Item No. Quantity Unit Description Unit Cost Total Cost
Exterior
1 19,600 SF Pressure Wash, Spot Prime and Overcoat 3.50$ 68,600$
Interior
1 10,000 SF Abrasive Blast and New Coating System 12.00$ 120,000$
Accessories
1 1 LS Re-route Drain Line and Install Flap Valve 6,500.00$ 6,500$
1 1 LS Paint Altitude Valve Vault Piping and Valves 1,200.00$ 1,200$
1 1 LS Repair Damaged Fence and Remove Fallen Tree 1,500.00$ 1,500$
1 1 LS Interior Bowl Siphon Pipe 4,000.00$ 4,000$
Site
1 1 LS Trim Overgrowth from Fence 250.00$ 250$
Subtotal 202,050$
Bonds and Insurance (2.5%) 5,051$
Mobilization (5%) 10,103$
Construction Contingency (10%) 20,205$
SUBTOTAL 237,409$
Engineering and Inspection (15%) 35,611$
Inflation (5%) 11,870$
OPINION OF TOTAL COST 284,891$
WEST BANKS MILL TANK RECONDITIONING
ENGINEER'S OPINION OF PROBABLE CONSTRUCTION COSTS
APPENDIX B
Field Inspection Report
17037
12/5/2017
Cloudy, 60
9273 West Banks Mill
Rd.
50'
Ht. to Bottom 121'
Ht. to Overflow 158'
Construction Welded Steel
Column 4: Appears to have graffiti painted over, minor chipping of protective coating on base plate, slight mildew growth, small areas of spot corrosion on column; Overall good condition
Column 5: Appears to have graffiti painted over, minor chipping of protective coating on base plate, slight mildew growth, small areas of spot corrosion on column, minor spalling of concrete on foundation;
Overall good condition
Column 6: Appears to have graffiti painted over (major cracking of top coat), minor chipping on column, slight mildew growth; Overall good condition
Tie Rod/Turnbuckle Condition: Minor mildew growth, overall in good condition. Minor corrosion at rub points where tie rods cross.
Miscellaneous Comments: Additional security measures include ladder shield and bottom section of ladder removed. Concrete spalling on foundation corner of Column 5.
Column Ladder
Ladder Location: Column 1, Communication cables are attached to the ladder
SUPPORT COLUMN(S)
Number of Columns/Legs: 6
Coating Condition (Location and Millage): Coating Thickness: 8.4 - 17.5 mils, Avg. 13.5 mils, Intercoat adhesion is good; Coating adhesion to steel substrate is excellent. Good condition w/ only a few areas of small areas of coating failure.
Column 1: Access Ladder, Slight mildew growth, Conduit attached to back of ladder, Spot corrrosion on tie rod anchor tabs and small area of column; Overall good condition
Column 2: Slight mildew growth, Slight spot corrosion on tie rod anchor tabs and small location on column. Overall good condition
Column 3: Minor chipping to protective coating on base plate, slight mildew growth, amall areas of spot corrosion on column, supplemental grounding system attached to column, overall good condition.
Overflow pipe connected to leg with welded tabs, splash pad at bottom.
Foundation/Base Plate/Anchor Bolt Condition
Zone 1402
Elevated Leg
1402.00'
500,000 Gallons
Safety System: Cable climbing system
Rung Spacing: 12" Ladder Width: 16"
Capacity
Contractor
Serial Number
Erected (Date)
TANK INSPECTION FIELD REPORT
ELEVATED WATER TANK
Weather:
Address:
NAMEPLATE INFORMATION
Water System:
Tank Name:
Press. System:
Type:
Datum:
Krebs Job No:
Date:
Diameter
S 5331
Caldwell Tanks, Inc.
DDCWSA
West Banks Mill
Riser Foundation/Base Plate/Anchor Bolt Condition: Concrete and grout foundation excellent condition;
Minor corrossion on base plate where coating has failed; Anchor bolts are in good condition
Riser Manway
Miscellaneous Appurtenances(Antennas, Safety Devices): One antenna at vent and additional base plates which are not in use
Coating Condition (Location and Millage): Good condition; Coating Thickness 10.7 - 23.8 mils, Avg. 16.7 mils on sides of bowl; Coating Thickness 10.7 - 24.9 mils, Avg. 15.2 mils on top of bowl. Coating failure exhibited on balcony handrail at numerous locations. Minor chalking over most of the tank
Level Indicator Assembly
Type: None Operational:
Type: None Operational:
Obstruction Lighting
Roof Vent
Type: Round Vent Insect Screening: Yes
Size: 42" diameter Top, 30" diameter neck
Fixed/Rotating: Fixed
Safety System: Cable climbing system
Rung Spacing: 12" Ladder Width: 16"
Roof Hatch
Size: 30" Square Hinged: Yes Lockable: Yes
Riser Diameter: 60"
4" Raised Curb Surrounding Opening: Yes 2" Overhang on Hatch Cover: Yes
Balcony
Width: 36"
Positive Drainage: Yes
Handrail Height: 42"
Bowl Ladder
Bowl General Condition: Generally in good condition, minor chalking, place on bowl where graffiti coverup coating was applied, mildew present
BOWL, EXTERIOR
Riser Ladder
Safety System: Rail climbing system Ladder Width: 16"
Rung Spacing: 12"
Coating Condition (Location and Millage): Good condition, small spot failure on manway and coating cracking on column near manway penetration. Coating Thickness: 11.9 - 20.1 mils, Avg. 15.4 mils, Intercoat adhesion is good, Coating adhesion to steel substrate excellent.
Miscellaneous Comments: 8" drain connection with 5" non-removable silt stop and deflector plate
Opening Size: 24" diameter
Type (Hinged/Flanged): Flanged, with external hinge
RISER
Riser Type(Wet/Dry): Wet
Rectifier Type:
Wiring Condition:
Rectifier Location
Enclosure Condition:
Rung Spacing: 12"
Mounting System: Welded at roof with floor bracket
Ladder Width: 16"
Riser Opening Safety System: Yes, steel grating
Cathodic Protection
No. of Anodes: Anode Condition:
Overflow Piping
Size: 8", extends exterior of tank down column 3 to splash pad. Included flap valve
Weir/Overflow Structure: Flared inlet
Condition: Good, some rust bleed at flanged connection/flap valve
MISCELLANEOUS SITE CONDITIONS
Overflow/Drain Piping
Size: 8"
Flap Valve: Yes Discharge to: Pipe extended four feet above grade
Sample Tap: Yes in altitude valve vault
Coating Condition (Location and Millage): Excellent; Coating Thickness 10.8 - 19.8 mils, Avg. 15.0.
Adhesion between all layers is excellent. Areas of spot corrosion were repaired with Aquatapoxy.
Metal Pitting (Location and Depth): One location of pitting. Approx. 1/16" deep. Repaired in place with
Aquatapoxy.
Miscellaneous Comments: No corrosion observed on the interior of the wet riser.
Interior Ladder
Safety System: Safety rail
Silt Stop Drain Assembly
Height: 18" Removable: No
Condition: Good with deflector plate
BOWL, INTERIOR
Inlet/Outlet Piping
Size: 12"
Condition: Good
Bowl General Condition: Excellent condition with less than 5 locations of spot corrosion on interior floor.
Miscellaneous Comments: Communication cables attached to bowl ladder. Two SCADA antennas mounted to handrail (Katherien Scala). One separate 24" bolted access hatch on roof by vent - good condition, no hinges but chain is attached to hatch. Adhesion on bowl roof & at balcony is good on prime
& intermediate coating but top coat is brittle.
Location of Samples Taken: None Taken - information from last rehab project available
Interior -
Exterior -
Site Grading/Drainage: Good; away from tank
Access Road Condition: Gravel/grass, good condition
Miscellaneous Site Comments: Two locations of tree damage. See site plan.
Fencing:
Height: 7' Type: Metal Security Wire: Yes
Condition: Good Gate Type: Double Leaf
COATING SAMPLES
APPENDIX C
Site Plan
SHEET TITLE
SHEET NO.
DATE
PROJECT NO.
SCALE
17037
12/05/17
DESKTOP-992NOGD 4:33:20 PM P:\bham\Douglasville\17037_WestBanksMill_BeulahTank\Drawings\W. Banks Mill\WestBanksMillTank-S1 - 2017 Inspection.dgn12/18/2017
K
R E
B S E
N G
IN
E E
R
IN
G
, IN
C
NO SCALE
DOUGLASVILLE, GEORGIA
WATER AND SEWER AUTHORITY
DOUGLASVILLE - DOUGLAS COUNTY
S1
SITE PLAN
V
V
V
V
LADDER
GATE
OVERFLOW
W E
S T B
A N
K S M
IL
L R
D
12"W
VAULT
VALVE
ALTITUDE
ABOVE GARAGE
TANK DRAIN
TREES
TREES
PAD
SPLASH
ELEVATED STORAGE TANK
WEST BANKS MILL 500,000 GALLON
TREE DAMAGE
#1
#2
#3
#4
#5
#6
APPENDIX D
Aerial Photo of Site
SHEET TITLE
SHEET NO.
DATE
PROJECT NO.
SCALE
17037
12/05/17
BHM-ENGL-17 12:19:04 PM P:\bham\Douglasville\17037_WestBanksMill_BeulahTank\Drawings\W. Banks Mill\WestBanksMillTank-T1 - 2017 Inspection.dgn12/11/2017
K
R E
B S E
N G
IN
E E
R
IN
G
, IN
C
NO SCALE
DOUGLASVILLE, GEORGIA
WATER AND SEWER AUTHORITY
DOUGLASVILLE - DOUGLAS COUNTY
T1
AERIAL PHOTO
ELEVATED STORAGE TANK
WEST BANKS MILL 500,000 GALLON
| 17037_WestBanksReport_171205.pdf |
| APPENDIX A.pdf |
| 17037_WBMestimate_171205.pdf |
| APPENDIX B.pdf |
| 17037_WestBanksMillInspectionReport_171205.pdf |
| APPENDIX C.pdf |
| WestBanksMillTank-S1.pdf |
| APPENDIX D.pdf |
| WestBanksMillTank-T1 - 2017 Inspection.pdf |
Other files
| File | Type | Posted |
|---|---|---|
| IFB#274 Addendum #1 | — | |
| Addendum #1 Appendix G | — | |
| IFB#274 Ad West Banks Mill | — | |
| Addendum #1 Appendix E | — | |
| Award Information | — |