This is Addendum #1 to a solicitation issued by Gwinnett County, Georgia for inspection and exercising of water and sewer valves on an annual contract (BL087-22). The project encompasses valve locating, inspection, exercising, valve box adjustment and replacement, GPS mapping, and related tasks for distribution and fire hydrant isolation valves ranging from 2 inches to 48 inches in diameter. Work will be performed across diverse terrain including major thoroughfares, streets, highways, rural roadways, and off-road easement areas adjacent to waterways. The County maintains a system of 57,606 distribution and fire hydrant isolation valves (6"-20"), of which 670 are classified as cannot-locate (CNL) distribution valves and 12,440 are CNL fire hydrant isolation valves. Approximately 5,000 CNA/CNE fire hydrant isolation valves will be assigned during the contract life. An estimated 6,010 valves are located in Gwinnett Department of Transportation roads and approximately 750 in state routes, though the County acknowledges these figures may not be precise.
The addendum addresses critical clarifications regarding concrete and asphalt repair requirements, payment terms, valve riser specifications, and contractor obligations. Sidewalk repairs must be replaced joint to joint and finished to match existing conditions, while driveway repairs shall extend to the first joint or not exceed the right-of-way boundary. Contractors will not be compensated for valve location efforts when a valve is identified as CNL. Valves receiving two consecutive CNL inspections will be removed from future assigned work. Drop-in valve risers meeting ASTM A48 specifications (Cast Iron, 5-1/4" shaft, 1-1/2" or 2-1/4" depth, Sigma VB26015/VB2602 or approved equivalent) are acceptable for raises of 6 inches or less, with pre-approval required for greater heights. The County expects vendors to submit competitive unit pricing that will be held throughout the contract term. All contractors must comply with OSHA, DOT, and MUTCD regulations. Acknowledgment of this addendum on the bid form is mandatory; failure to do so may render a bid non-responsive.
Text of this file
August 1, 2022
BL087-22
INSPECTION AND EXERCISING OF WATER AND SEWER VALVES ON AN ANNUAL CONTRACT
ADDENDUM #1
Q1. For valves requiring repairs under bid items 2.1C, 2.2C, 2.3C, and 2.4C in sidewalks, will the entire sidewalk section (typically 4’x5’ for internal roads and 5’x5’ for external roads) require replacement to meet the “existing joint to joint” section stated in Part 3.9 entitled (page 6), “Concrete Sidewalks/Driveways”?
A1. Yes, joint to joint and finished to match the existing sidewalk.
Q2. For driveways requiring repairs under bid items 2.1C, 2.2C, 2.3C, and 2.4C in driveways, what is the largest driveway apron section (sf) required replacement to meet the “existing joint to joint” section stated in Part 3.9 entitled (page 6), “Concrete Sidewalks/Driveways”?
A2. Driveways shall be replaced to the first joint. If no joint is present, the replacement will not exceed the Right of Way.
Q3. How many valves do you anticipate will need a blocking truck?
A3. “Contractors shall perform the work in compliance with OSHA; DOT; MUTCD and all other applicable safety regulations”.
Q4. Will back log repairs be added to any repair work orders created during assessment activities? If so, do you have an estimate of the number of back-log repairs?
A4. We have approximately 5,000 CNA/CNE fire hydrant isolation valves that will be assigned during the life of this contract.
Q5. Does Gwinnett County anticipate bringing in any new systems during the length of the new contract?
A5. No.
Q6. Can you estimate how many valves are in GDOT roads?
A6. We estimate approximately 6010 valves are located in Gwinnett DOT roads. However, this number may not be accurate as we do not confidently track this information.
Q7. Can you estimate how many valves in roads with a speed limit >45mph?
A7. We do not track this information.
Q8. Can you estimate how many valves are in state routes?
A8. We estimate approximately 750 valves are located in state roads. However, this number may not be accurate as we do not confidently track this information.
Q9. Will the contractor be paid for digging up concrete or asphalt when no asset is found?
A9. No payment shall be made for valve location efforts if the valve is identified by the Contractor as
CNL.
Addendum #1
BL087-22
Q10. How many valves will be part of the scope that have not had an assessment or repair meeting or exceeding the requirements of this scope A10. All assigned valves have had a previous inspection. We have approximately 5,000 CNA/CNE fire hydrant isolation valves that will be assigned during the life of this contract.
Q11. Will Gwinnett County consider unit prices of $1.00 to be acceptable and responsive, when it is clear that construction and/or repair related scope items cost more than $1.00. For example, the material costs alone for Items #3 and #4 for the previous contract (BL067-20) were more than $1.00, but unit pricing in that amount was accepted by the County.
A11. It is the intention of Gwinnett County to solicit an item for bid and expects the vendor to price the item competitively. Gwinnett County will hold the vendor to the submitted unit pricing for the life of the contract.
Q12. Since the Contractor cannot bill for CNLs, will Gwinnett County provide the total number of current
CNLs on record and the total number of valves in the system?
A12. We have 57,606 distribution and fire hydrant isolation valves (6”-20”). Of the 57,606, there are 670
CNL distribution valves and 12,440 CNL fire hydrant isolation valves.
Q13. For valves previously determined to be CNL under the previous contract, will Gwinnett County consider removing these from the assigned valves under the new contract?
A13. If a valve has two consecutive CNL inspections, the valve will not be issued in the assigned scope of work.
Q14. Please provide the County’s specifications and diagram for valve risers in/out of pavement and asphalt.
A14. Gwinnett County DWR allows drop in valve risers for valves that need to be raised 6” or less in or out of pavement. Drop in valve risers may be used for valves in excess of 6” with the pre-approval of the Gwinnett County DWR contract manager.
Q15. For valve risers 12-inches and less, will the County accept drop-in type risers? If so, does the
County have a specification for drop-in type risers?
A15. Gwinnett County DWR allows drop in valve risers for valves that need to be raised 6” or less in or out of pavement. Valve risers must meet ASTM A48; Cast Iron 5-1/4” shaft, 1-1/2” or 2-1/4” depth, Sigma VB26015/VB2602 or approved equivalent.
This addendum should be acknowledged on Bid Form, page 22. Failure to do so may result in your bid being deemed non-responsive.
Thank you, Shelley McWhorter, CPPB Purchasing Associate III
| August 1, 2022 |
| BL087-22 |
| INSPECTION AND EXERCISING OF WATER AND SEWER VALVES ON AN ANNUAL CONTRACT |
| ADDENDUM #1 |
| Q1. For valves requiring repairs under bid items 2.1C, 2.2C, 2.3C, and 2.4C in sidewalks, will the entire sidewalk section (typically 4’x5’ for internal roads and 5’x5’ for external roads) require replacement to meet the “existing joint to joint” section stated in Part 3.9 entitled (page 6), “Concrete Sidewalks/Driveways”? |
| A1. Yes, joint to joint and finished to match the existing sidewalk. |
| Q2. For driveways requiring repairs under bid items 2.1C, 2.2C, 2.3C, and 2.4C in driveways, what is the largest driveway apron section (sf) required replacement to meet the “existing joint to joint” section stated in Part 3.9 entitled (page 6), “Concrete Sidewalks/Driveways”? |
| A2. Driveways shall be replaced to the first joint. If no joint is present, the replacement will not exceed the Right of Way. |
| Q3. How many valves do you anticipate will need a blocking truck? |
| A3. “Contractors shall perform the work in compliance with OSHA; DOT; MUTCD and all other applicable safety regulations”. |
| Q4. Will back log repairs be added to any repair work orders created during assessment activities? If so, do you have an estimate of the number of back-log repairs? |
| A4. We have approximately 5,000 CNA/CNE fire hydrant isolation valves that will be assigned during the life of this contract. |
| Q5. Does Gwinnett County anticipate bringing in any new systems during the length of the new contract? |
| A5. No. |
| Q6. Can you estimate how many valves are in GDOT roads? |
| A6. We estimate approximately 6010 valves are located in Gwinnett DOT roads. However, this number may not be accurate as we do not confidently track this information. |
| Q7. Can you estimate how many valves in roads with a speed limit >45mph? |
| A7. We do not track this information. |
| Q8. Can you estimate how many valves are in state routes? |
| A8. We estimate approximately 750 valves are located in state roads. However, this number may not be accurate as we do not confidently track this information. |
| Q9. Will the contractor be paid for digging up concrete or asphalt when no asset is found? |
| A9. No payment shall be made for valve location efforts if the valve is identified by the Contractor as CNL. |
| Q10. How many valves will be part of the scope that have not had an assessment or repair meeting or exceeding the requirements of this scope |
| A10. All assigned valves have had a previous inspection. We have approximately 5,000 CNA/CNE fire hydrant isolation valves that will be assigned during the life of this contract. |
| Q11. Will Gwinnett County consider unit prices of $1.00 to be acceptable and responsive, when it is clear that construction and/or repair related scope items cost more than $1.00. For example, the material costs alone for Items #3 and #4 for the previous contract (BL067-20) were more than $1.00, but unit pricing in that amount was accepted by the County. |
| A11. It is the intention of Gwinnett County to solicit an item for bid and expects the vendor to price the item competitively. Gwinnett County will hold the vendor to the submitted unit pricing for the life of the contract. |
| Q12. Since the Contractor cannot bill for CNLs, will Gwinnett County provide the total number of current CNLs on record and the total number of valves in the system? |
| A12. We have 57,606 distribution and fire hydrant isolation valves (6”-20”). Of the 57,606, there are 670 CNL distribution valves and 12,440 CNL fire hydrant isolation valves. |
| Q13. For valves previously determined to be CNL under the previous contract, will Gwinnett County consider removing these from the assigned valves under the new contract? |
| A13. If a valve has two consecutive CNL inspections, the valve will not be issued in the assigned scope of work. |
| Q14. Please provide the County’s specifications and diagram for valve risers in/out of pavement and asphalt. |
| A14. Gwinnett County DWR allows drop in valve risers for valves that need to be raised 6” or less in or out of pavement. Drop in valve risers may be used for valves in excess of 6” with the pre-approval of the Gwinnett County DWR contract manager. |
| Q15. For valve risers 12-inches and less, will the County accept drop-in type risers? If so, does the County have a specification for drop-in type risers? |
| A15. Gwinnett County DWR allows drop in valve risers for valves that need to be raised 6” or less in or out of pavement. Valve risers must meet ASTM A48; Cast Iron 5-1/4” shaft, 1-1/2” or 2-1/4” depth, Sigma VB26015/VB2602 or approved equivalent. |
| This addendum should be acknowledged on Bid Form, page 22. Failure to do so may result in your bid being deemed non-responsive. |
| Thank you, |
| / |
| Shelley McWhorter, CPPB |
| Purchasing Associate III |