Addendum 01_Part2.pdf

PDF 5 MB Posted

Attached to
751/22068. MAA; Mio DNR Field Office - Partial Demo & Reno
Solicitation number
RFQ - 171 - 230000000138
Issued by
Oscoda County, Milan City, Michigan

About this file

This document is an asbestos report and analytical laboratory report for the Mio DNR Field Office project in Oscoda County, Michigan. The report summarizes the findings of asbestos testing performed on various building materials, including floor tiles, pipe joint covers, and wall panels. The analysis identified several materials containing asbestos, including 3% chrysotile in floor tiles, 20% chrysotile in hard surfaces, and 10% chrysotile in pipe joint covers. The report provides details on the sampling, analysis, and results for 75 samples collected from the site.

The related state and local contract opportunity is for the partial demolition and renovation of the Mio DNR Field Office. The project is located in Oscoda County, Michigan. The bid attachments must be uploaded to the SIGMA VSS system, and questions should be emailed to the project manager. The bid submission deadline is 2:00 p.m. Approved emailed submissions will be handled on a case-by-case basis. The contract term is not specified.

View the file

Other files

File Type Posted
Specificiations_22068.MAA.pdf PDF
Addendum 02.pdf PDF
Advertisment_22068.MAA.pdf PDF
Addendum 01_Part1.pdf PDF
Drawings_22068.MAA.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix C Photograph Log

PHOTOGRAPH LOG

General Pictures of Building 80951

West Wing Addition

Radio Tower & Utilities

General Roofing Materials

Asbestos Pipe Joints / Pipe Cover - Fiberglass

Vinyl Floor Tiles

Transite (wall covering)

General Pictures for Understanding of Building Construction

Appendix D Analytical Report(s)

Thursday, May 06, 2021

DNR Mio Field Office 191 S Mt. Tom Road, Mio, MI 48647/Project Identification:

Fibertec Project Number: A01457

3125 Sovereign Drive

9C

Environmental Consulting & Tech., Inc. - Lansing

Lansing, MI 48911

Mr. Mike Hebert

Thank you for selecting Fibertec Environmental Services as your analytical laboratory. The samples you submitted have been analyzed in accordance with NELAC standards and the results compiled in the attached report. Any exceptions to NELAC compliance are noted in the report. These results apply only to those samples submitted. Please note TO-15 samples will be disposed of 7 calendar days after the reporting date. All other samples will be disposed of 30 days after the reporting date.

Dear Mr. Hebert, Submittal Date: 04/26/2021

If you have any questions regarding these results or if we may be of further assistance to you, please contact me at (517) 699-0345.

Sincerely, For Daryl P. Strandbergh Laboratory Director

Enclosures

By Sue Ricketts at 9:21 AM, May 06, 2021

1914 Holloway Drive Holt, MI 48842 T: (517) 699-0345

11766 E. Grand River Brighton, MI 48116 T: (810) 220-3300

8660 S. Mackinaw Trail Cadillac, MI 49601 T: (231) 775-8368 lab@fibertec.us

F: (517) 699-0388

F: (810) 220-3311

F: (231) 775-8584

DCSID: G-610.19 (10/01/19) RSN: A01457-210506091831

Laboratory Sample Number: A01457-018

Analytical Laboratory Report A01457

Order:

Page:

Date: 05/06/21

Client Identification: Environmental Consulting & Tech., Inc. - Lansing

Client Project Name: DNR Mio Field Office

Client Project No: NA

Sample Description: 80951 Paint Interior

Sample No:

Sample Matrix: Paint Chip

Collect Date:

Chain of Custody: 195166

Collect Time: 13:30

Laboratory Project Number: A01457

Sample Comments:

Q: Qualifier (see definitions at end of report) NA: Not ApplicableDefinitions:

04/13/21

: Parameter not included in NELAC Scope of Analysis.‡

Analysis

Reporting Limit Parameter(s) Result

Preparation

UnitsQ Dilution

Aliquot ID: Lead Content (Paint) Paint ChipMatrix:A01457-018

P. Date P. Batch A. Date A. Batch Init.

Description: 80951 Paint InteriorMethod: EPA 0200.2/EPA 6020A

%1. 0.13 0.00042 100 04/30/21 PT21D30B 05/03/21 T421E03ALead CJA

1914 Holloway Drive Holt, MI 48842 T: (517) 699-0345

11766 E. Grand River Brighton, MI 48116 T: (810) 220-3300

8660 S. Mackinaw Trail Cadillac, MI 49601 T: (231) 775-8368 lab@fibertec.us

F: (517) 699-0388

F: (810) 220-3311

Laboratory Sample Number: A01457-020

Analytical Laboratory Report A01457

Order:

Page:

Date: 05/06/21

Client Identification: Environmental Consulting & Tech., Inc. - Lansing

Client Project Name: DNR Mio Field Office

Client Project No: NA

Sample Description: Paint Ext.

Sample No:

Sample Matrix: Paint Chip

Collect Date:

Chain of Custody: 195168

Collect Time: 17:10

Laboratory Project Number: A01457

Sample Comments:

Q: Qualifier (see definitions at end of report) NA: Not ApplicableDefinitions:

04/22/21

: Parameter not included in NELAC Scope of Analysis.‡

Analysis

Reporting Limit Parameter(s) Result

Preparation

UnitsQ Dilution

Aliquot ID: Lead Content (Paint) Paint ChipMatrix:A01457-020

P. Date P. Batch A. Date A. Batch Init.

Description: Paint Ext.Method: EPA 0200.2/EPA 6020A

%1. 2.3 0.0038 190000 05/04/21 T421E04F 05/04/21 T421E04FLead CJA

1914 Holloway Drive Holt, MI 48842 T: (517) 699-0345

11766 E. Grand River Brighton, MI 48116 T: (810) 220-3300

8660 S. Mackinaw Trail Cadillac, MI 49601 T: (231) 775-8368 lab@fibertec.us

F: (517) 699-0388

F: (810) 220-3311

Spike recovery or precision unusable due to dilution.

Definitions/ Qualifiers:

The analyte was detected in the associated method blank.

The analyte was detected at a concentration greater than the calibration range, therefore the result is estimated.

The concentration is an estimated value.

The analyte was not detected at or above the reporting limit.

Matrix Interference has resulted in a raised reporting limit or distorted result.

Results reported on a wet-weight basis.

Value reported is outside QC limits

A:

B:

E:

J:

U:

X:

W:

Analytical Laboratory Report A01457

Order:

Page:

Date: 05/06/21 Laboratory Project Number: A01457

Exception Summary:

Modified MethodM:

Analysis Locations:

All analyses performed in Holt.

T104704518-19-8 (TX)

Accreditation Number(s):

1914 Holloway Drive Holt, MI 48842 T: (517) 699-0345

11766 E. Grand River Brighton, MI 48116 T: (810) 220-3300

8660 S. Mackinaw Trail Cadillac, MI 49601 T: (231) 775-8368 lab@fibertec.us

F: (517) 699-0388

F: (810) 220-3311

3130 Old Farm Lane, Suite 1 Commerce Twp., MI 48390

877-665-3373

Asbestos Laboratory Report

Prepared Exclusively For:

Fibertec Inc.

1914 Holloway Drive Holt, MI 48842 517-699-0345

Project: A01457 Lab # A20071 Report Date: 04/30/21 Sampled: 04/13/21 Received: 04/28/21 Analyzed: 04/30/21

Report Prepared For:

Project Name:

Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

IMS Laboratory, LLC IMS Laboratory, LLC operates a state-of-the-art environmental laboratory, specializing in full service microbial, asbestos and radon analyses. We maintain the highest levels of quality and personalized service in the industry. Our analytical staff includes only Certified Indoor Air Quality Professionals, Ph.D.

Microbiologists, Mycologists, Microbiologists, and Biochemists. Our team's extensive experience in indoor air quality sampling techniques, microbial identification, and analytical interpretation allows us to offer our clients expert personalized service and has made IMS Laboratory an industry leader.

IMS Laboratory is accredited through the American Industrial Hygiene Association (AIHA) for both viable and nonviable fungal identification and through the National Voluntary Laboratory Accreditation Program (NVLAP) for bulk asbestos. To maintain quality control and quality assurance, we use standardized procedures approved under strict AIHA and NVLAP guidelines. Client data information is compiled and stored in a specially designed computer management system for secure, redundant data and the ability to comply with AIHA and NVLAP quality system requirements. A portion of this quality system includes inter-analyst comparisons and statistical quality control using blind duplicate analyses and process blanks. Laboratory data is provided in compliance with AIHA and NVLAP policy modules and ISO 17025:2017 guidelines.

This data is intended for use by professionals having the necessary knowledge of the testing methods to interpret them accurately.

- 2 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, and limitations that apply to this report carefully.

Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Asbestos Report Summary Test Method: Polarized Light Microscopy (PLM)

75 Samples Analyzed 6 Samples Containing >1% Asbestos

Greater than 1% Asbestos Client ID Lab Number Description Asbestos

80951-2FT-1 A20071 - 1 Floor Tile Chrysotile 3% 80951-HS-1 A20071 - 17 Hard Surfaces (Holes-?Transite) / Second Floor Chrysotile 20% 80951-1FT-1 A20071 - 27 Floor Tile Chrysotile 5% 80951-JC-1-1 A20071 - 61 Pipe Joint Cover Chrysotile 10% 80951-JC-2-1 A20071 - 64 Pipe Joint Cover Chrysotile 10% 80951-JC-3-1 A20071 - 67 Pipe Joint Cover Chrysotile 10%

- 3 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Certificate of Laboratory Analysis Test Method: Polarized Light Microscopy (PLM)

EPA 600/R-93/116 and/or EPA - Appendix E to Subpart E of 40 CFR Part 763;

Interim Method for the Determination of Asbestos in Bulk Insulation Samples

Project: A01457

Prepared For Fibertec Inc. IMS Lab No. A20071 1914 Holloway Drive Date Collected: 04/13/21 Holt, MI 48842 Date Received: 04/28/21 517-699-0345 Date Analyzed: 04/30/21 Date Reported: 04/30/21

Client ID Lab No.

Client Description Sample Color(s)

Laboratory Attributes

Fibrous Components Non-Fibrous Components

Asbestos Type / Percent

80951-2FT-1

A20071 - 1

Floor Tile Gray Heterogeneous Non-Friable Non-Fibrous

3% Chrysotile 97% Matrix Chrysotile 3%

Note on 1: No mastic observed on tile.

80951-2FT-2

A20071 - 2A

Floor Tile Not Tested - Positive Stop #

80951-2FT-2

A20071 - 2B

Mastic* Yellow Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-2FT-3

A20071 - 3A

Floor Tile Not Tested - Positive Stop #

80951-2FT-3

A20071 - 3B

Mastic* Yellow Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-2FT-4

A20071 - 4A

Floor Tile Not Tested - Positive Stop #

80951-2FT-4

A20071 - 4B

Mastic* Yellow Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-2FT-5

A20071 - 5A

Floor Tile Not Tested - Positive Stop #

80951-2FT-5

A20071 - 5B

Mastic* Yellow Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

*Material description provided by laboratory.

- 4 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Client ID Lab No.

Client Description Sample Color(s)

Laboratory Attributes

Fibrous Components Non-Fibrous Components

Asbestos Type / Percent

80951-SP-1

A20071 - 6A

Surface Material White Brown

Heterogeneous Friable Fibrous

90% Cellulose 10% Matrix No Asbestos Detected

80951-SP-1

A20071 - 6B

Glue* Yellow Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-SP-2

A20071 - 7

Surface Material White Brown

Heterogeneous Friable Fibrous

90% Cellulose 10% Matrix No Asbestos Detected

Note on 7: No glue observed.

80951-SP-3

A20071 - 8

Surface Material White Brown

Heterogeneous Friable Fibrous

90% Cellulose 10% Matrix No Asbestos Detected

Note on 8: No glue observed.

80951-WW-CT-1

A20071 - 9

Ceiling Tile / New Wing

White Gray

Heterogeneous Non-Friable Non-Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-WW-CT-2

A20071 - 10

Ceiling Tile / New Wing

White Gray

Heterogeneous Non-Friable Non-Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-WW-CT-3

A20071 - 11

Ceiling Tile / New Wing

White Gray

Heterogeneous Non-Friable Non-Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-WW-CT-4

A20071 - 12

Ceiling Tile / New Wing

White Gray

Heterogeneous Non-Friable Non-Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-WW-CT-5

A20071 - 13

Ceiling Tile / New Wing

White Gray

Heterogeneous Non-Friable Non-Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-3-CT-1

A20071 - 14

Ceiling Tile White Gray

Heterogeneous Friable Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-3-CT-2

A20071 - 15

Ceiling Tile White Gray

Heterogeneous Friable Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-3-CT-3

A20071 - 16

Ceiling Tile White Gray

Heterogeneous Friable Fibrous

35% Cellulose 35% Fiberglass

30% Matrix No Asbestos Detected

80951-HS-1

A20071 - 17

Hard Surfaces (Holes-?Transite) / Second Floor

Gray Heterogeneous Non-Friable Fibrous

20% Chrysotile 80% Matrix Chrysotile 20%

80951-HS-2

A20071 - 18

Hard Surfaces (Holes-?Transite) / Second Floor

Not Tested - Positive Stop #

80951-HS-3

A20071 - 19

Hard Surfaces (Holes-?Transite) / Second Floor

Not Tested - Positive Stop #

*Material description provided by laboratory.

- 5 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Client ID Lab No.

Client Description Sample Color(s)

Laboratory Attributes

Fibrous Components Non-Fibrous Components

Asbestos Type / Percent

80951-HS-4

A20071 - 20

Hard Surfaces (Holes-?Transite) / Second Floor

Not Tested - Positive Stop #

80951-HS-5

A20071 - 21

Hard Surfaces (Holes-?Transite) / Second Floor

Not Tested - Positive Stop #

80951-AI-1

A20071 - 22

Attic Insulation (Blow In)

Gray Heterogeneous Friable Fibrous

98% Cellulose 2% Matrix No Asbestos Detected

80951-AI-2

A20071 - 23

Attic Insulation (Blow In)

Gray Heterogeneous Friable Fibrous

98% Cellulose 2% Matrix No Asbestos Detected

80951-AI-3

A20071 - 24

Attic Insulation (Blow In)

Gray Heterogeneous Friable Fibrous

98% Cellulose 2% Matrix No Asbestos Detected

80951-AI-4

A20071 - 25

Attic Insulation (Blow In)

Gray Heterogeneous Friable Fibrous

98% Cellulose 2% Matrix No Asbestos Detected

80951-AI-5

A20071 - 26

Attic Insulation (Blow In)

Gray Heterogeneous Friable Fibrous

98% Cellulose 2% Matrix No Asbestos Detected

80951-1FT-1

A20071 - 27

Floor Tile Brown Heterogeneous Non-Friable Non-Fibrous

5% Chrysotile 95% Matrix Chrysotile 5%

Note on 27: No mastic observed on tile.

80951-1FT-2

A20071 - 28A

Floor Tile Not Tested - Positive Stop #

80951-1FT-2

A20071 - 28B

Mastic* Black Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-1FT-3

A20071 - 29A

Floor Tile Not Tested - Positive Stop #

80951-1FT-3

A20071 - 29B

Mastic* Black Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-1FT-4

A20071 - 30A

Floor Tile Not Tested - Positive Stop #

80951-1FT-4

A20071 - 30B

Mastic* Black Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-1FT-5

A20071 - 31A

Floor Tile Not Tested - Positive Stop #

80951-1FT-5

A20071 - 31B

Mastic* Black Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

*Material description provided by laboratory.

- 6 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Client ID Lab No.

Client Description Sample Color(s)

Laboratory Attributes

Fibrous Components Non-Fibrous Components

Asbestos Type / Percent

80951-SP-1

A20071 - 32A

Surface Material Beige White

Heterogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-SP-1

A20071 - 32B

Mastic* Tan Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-SP-2

A20071 - 33A

Surface Material Beige White

Heterogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-SP-2

A20071 - 33B

Mastic* Tan Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-SP-3

A20071 - 34A

Surface Material Beige White

Heterogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-SP-3

A20071 - 34B

Mastic* Tan Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-PC-1

A20071 - 35

Surface Material Brown Yellow

Heterogeneous Friable Fibrous

20% Cellulose 75% Fiberglass

5% Matrix No Asbestos Detected

80951-PC-2

A20071 - 36

Surface Material Brown Yellow

Heterogeneous Friable Fibrous

20% Cellulose 75% Fiberglass

5% Matrix No Asbestos Detected

80951-PC-3

A20071 - 37

Surface Material Brown Yellow

Heterogeneous Friable Fibrous

20% Cellulose 75% Fiberglass

5% Matrix No Asbestos Detected

80951-1-CT-1

A20071 - 38

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-1-CT-2

A20071 - 39

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-1-CT-3

A20071 - 40

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-1

A20071 - 41

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-2

A20071 - 42

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-3

A20071 - 43

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-4

A20071 - 44

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

*Material description provided by laboratory.

- 7 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Client ID Lab No.

Client Description Sample Color(s)

Laboratory Attributes

Fibrous Components Non-Fibrous Components

Asbestos Type / Percent

80951-2-CT-5

A20071 - 45

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-6

A20071 - 46

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-7

A20071 - 47

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-8

A20071 - 48

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-2-CT-9

A20071 - 49

Ceiling Tile White Brown

Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

80951-WP-1B

A20071 - 50

Wall Panel Brown Heterogeneous Non-Friable Fibrous

96% Cellulose 4% Matrix No Asbestos Detected

80951-WP-2B

A20071 - 51

Wall Panel Brown Heterogeneous Non-Friable Fibrous

96% Cellulose 4% Matrix No Asbestos Detected

80951-WP-3B

A20071 - 52

Wall Panel Brown Heterogeneous Non-Friable Fibrous

96% Cellulose 4% Matrix No Asbestos Detected

80951-WP-1

A20071 - 53

Wall Panel Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

Note on 53: No joint compound observed.

80951-WP-2

A20071 - 54

Wall Panel Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

Note on 54: No joint compound observed.

80951-WP-3

A20071 - 55A

Wall Panel Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

80951-WP-3

A20071 - 55B

Joint Compound* White Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-WP-4

A20071 - 56A

Wall Panel Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

80951-WP-4

A20071 - 56B

Joint Compound* White Homogeneous Non-Friable Non-Fibrous

100% Matrix No Asbestos Detected

80951-WP-5

A20071 - 57

Wall Panel Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

Note on 57: No joint compound observed.

*Material description provided by laboratory.

- 8 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Client ID Lab No.

Client Description Sample Color(s)

Laboratory Attributes

Fibrous Components Non-Fibrous Components

Asbestos Type / Percent

80951-2WB-1

A20071 - 58

Wall Board Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

80951-2WB-2

A20071 - 59

Wall Board Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

80951-2WB-3

A20071 - 60

Wall Board Gray Brown

Heterogeneous Non-Friable Fibrous

12% Cellulose 88% Matrix No Asbestos Detected

80951-JC-1-1

A20071 - 61

Pipe Joint Cover Gray Heterogeneous Friable Fibrous

10% Chrysotile 10% Cellulose 25% Fiberglass

55% Matrix Chrysotile 10%

80951-JC-1-2

A20071 - 62

Pipe Joint Cover Not Tested - Positive Stop #

80951-JC-1-3

A20071 - 63

Pipe Joint Cover Not Tested - Positive Stop #

80951-JC-2-1

A20071 - 64

Pipe Joint Cover Gray Heterogeneous Friable Fibrous

10% Chrysotile 20% Cellulose 50% Fiberglass

20% Matrix Chrysotile 10%

80951-JC-2-2

A20071 - 65

Pipe Joint Cover Not Tested - Positive Stop #

80951-JC-2-3

A20071 - 66

Pipe Joint Cover Not Tested - Positive Stop #

80951-JC-3-1

A20071 - 67

Pipe Joint Cover Gray Yellow

Heterogeneous Friable Fibrous

10% Chrysotile 15% Cellulose 50% Fiberglass

25% Matrix Chrysotile 10%

80951-JC-3-2

A20071 - 68

Pipe Joint Cover Not Tested - Positive Stop #

80951-JC-3-3

A20071 - 69

Pipe Joint Cover Not Tested - Positive Stop #

ARM-1

A20071 - 70

Asphaltic Roofing Material

Black Heterogeneous Non-Friable Fibrous

15% Fiberglass 85% Matrix No Asbestos Detected

ARM-2

A20071 - 71

Asphaltic Roofing Material

Black Heterogeneous Non-Friable Fibrous

15% Fiberglass 85% Matrix No Asbestos Detected

ARM-3

A20071 - 72

Asphaltic Roofing Material

Black Heterogeneous Non-Friable Fibrous

15% Fiberglass 85% Matrix No Asbestos Detected

ARM-4

A20071 - 73

Asphaltic Roofing Material

Black Heterogeneous Non-Friable Fibrous

15% Fiberglass 85% Matrix No Asbestos Detected

- 9 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Client ID Lab No.

Client Description Sample Color(s)

Laboratory Attributes

Fibrous Components Non-Fibrous Components

Asbestos Type / Percent

ARM-5

A20071 - 74

Asphaltic Roofing Material

Black Heterogeneous Non-Friable Fibrous

15% Fiberglass 85% Matrix No Asbestos Detected

WW-Under Roof-1 A20071 - 75

Brown Fiberboard Roofing / New Wing

Brown Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

WW-Under Roof-2 A20071 - 76

Brown Fiberboard Roofing / New Wing

Brown Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

WW-Under Roof-3 A20071 - 77

Brown Fiberboard Roofing / New Wing

Brown Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

WW-Under Roof-4 A20071 - 78

Brown Fiberboard Roofing / New Wing

Brown Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

WW-Under Roof-5 A20071 - 79

Brown Fiberboard Roofing / New Wing

Brown Heterogeneous Friable Fibrous

95% Cellulose 5% Matrix No Asbestos Detected

IMS Laboratory, LLC is accredited through the National Voluntary Laboratory Accreditation Program (NVLAP). Data is provided in compliance with NVLAP policy modules and ISO 17025:2017 guidelines.

04/30/21 Marty Eakin, Asbestos Laboratory Manager

- 10 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Glossary Actinolite - This form of asbestos was not commonly used commercially, but can be found occasionally in some building products.

Amosite - This form of asbestos was commonly used in ceiling tiles, cement sheets, pipe insulation, and in many different types of thermal insulation products.

Anthophyllite - This form of asbestos was not commonly used commercially, but can be found occasionally in some building products.

Asbestos - Any of six naturally occurring silicate minerals (Chrysotile, Amosite, Crocidolite, Tremolite, Actinolite, and Anthophyllite). Inhalation of these minerals can cause asbestosis and certain types of cancer. Because of asbestos' fireproofing and other desirable properties, these minerals can be found in many different types of building materials.

Chrysotile - This is the most commonly used form of asbestos and can be found today in many building components including floors, roofs, ceilings, walls and insulation cement materials, piping and sealants of residential and commercial buildings. It was also used in automobile brake pads, linings and blocks, clutch plates and gaskets.

Crocidolite - This form of asbestos has been used in some building products including cement, pipe insulation and spray-on coatings.

Fibrous - Any material that contains, consists of, or resembles fibers.

Friable - Any material that can be crumbled, pulverized, or reduced to powder by the pressure of an ordinary human hand. Friable asbestos containing materials are dangerous because they allow asbestos fibers to get into the air where they can be inhaled.

Heterogeneous - A mixture that consists of two or more substances. It is non-uniform and the different components of the mixture can be seen.

Homogeneous - A substance which has uniform composition and properties throughout.

Non-Fibrous - Any material that does not contain fibers.

Non-Friable - Any material that cannot be pulverized under hand pressure.

Tremolite - This form of asbestos was not commonly used commercially, but can be found in some roofing materials, insulation products (including vermiculite), paints, sealants, and talc powders.

- 11 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, Report Date:

Lab Number:

Fibertec Inc.

A01457 04/30/21 A20071

Warranties, Legal Disclaimers, and Limitations Stereoscopic microscopy and polarized light microscopy coupled with dispersion staining is the analytical technique used for sample identification. The percentage of each component is visually estimated by volume. The detection limit for this method is <1% by visual estimation and 0.25% by 400 point counts or 0.1% by 1,000 point counts. The samples were analyzed as submitted by the client and may not be representative of the larger material in question. IMS Laboratory, LLC ("IMS") will discard all samples after 7 days.

Matrix interference and/or resolution limits may yield false results in certain circumstances. Suspect floor tiles containing less than 1% asbestos should be tested with SEM or TEM. Many vinyl floor tiles have been manufactured using greater than 1% asbestos. Often the asbestos was milled to a fiber size below the detection limit of polarized light microscopy. Therefore, a "No Asbestos Found" reading on vinyl floor tile does not necessarily exclude the presence of asbestos. TEM provides a more conclusive form of analysis for vinyl floor tiles.

This certificate of analysis relates only to the samples tested, as recieved by IMS and, to insure the integrity of the results, may only be reproduced in full. IMS is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials.

Unless otherwise noted in the body of this report, the condition of samples upon receipt was acceptable.

This report is generated by IMS at the request of, and for the exclusive use of, the IMS client named on this report. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the U.S. Government.

Project Name, Project Number, Sampling Date, Material Descriptions, Sampling Locations and Volume have been provided to IMS by the client and may affect the validity of the results. This report applies only to the samples taken at the time, place and location referenced in the report and received by IMS. Please be aware that property conditions, inspection findings and laboratory results can and do change over time relative to the original sampling due to changing conditions and many other factors. IMS does not furnish, and has no responsibility for, the inspector or inspection service that performs the inspection or collects the test samples. It is the responsibility of the end-user of this report to select a properly trained professional to conduct the inspection and collect appropriate samples for analysis and interpretation. Neither IMS, nor its affiliates, subsidiaries, suppliers, employees, agents, contractors and attorneys ("IMS related parties") are able to make and do not make any determinations as to the safety or health condition of a property in this report. The client and client's customer are solely responsible for the use of, and any determinations made from, this report, and no IMS related party shall have any liability with respect to decisions or recommendations made or actions taken by either the client or the client's customer based on the report.

IMS hereby expressly disclaims any and all representations and warranties of any kind or nature, whether express, implied or statutory, related to the testing services or this report including, but not limited to, damages for loss of profit or goodwill regardless of the negligence (either sole or concurrent) of IMS and whether IMS has been informed of the possibility of such damages, arising out of or in connection with IMS's services or the delivery, use, reliance upon or interpretation of test results by client or any third party. In no event will IMS be liable for any special, indirect, incidental, punitive, or consequential damages of any kind regardless of the form of action whether in contract, tort (including negligence), strict product liability or otherwise, arising from or related to the testing services or this report.

IMS accepts no legal responsibility for the purposes for which the client uses the test results. IMS will not be held responsible for the improper selection of sampling devices even if we supply the device to the user. The user of the sampling device has the sole responsibility to select the proper sampler and sampling conditions to insure that a valid sample is taken for analysis. Additionally, neither this report nor IMS makes any express or implied warranty or guarantee regarding the inspection or sampling done by the inspector, the qualifications, training or sampling methodology used by the inspector performing the sampling and inspection reported herein, or the accuracy of any information provided to IMS serving as a basis for this report. The total liability of IMS related to or arising from this report to a client or any third party, whether under contract law, tort law, warranty or otherwise, shall be limited to direct damages not to exceed the fees actually received by IMS from the client for the report. The invalidity or unenforceability, in whole or in part, of any provision, term or condition herein shall not invalidate or otherwise affect the enforceability of the remainder of these provisions, terms and conditions. Client shall indemnify IMS and its officers, directors and employees and hold each of them harmless for any liability, expense or cost, including reasonable attorney's fees, incurred by reason of any third party claim in connection with IMS's services, the test result data or its use by client.

- End of Lab Report Number A20071 -

Powered by TCPDF (www.tcpdf.org)

- 12 -

This report has been prepared by IMS Laboratory, LLC at the request of and for the exclusive use of Fibertec Inc. Read the important terms, conditions, http://www.tcpdf.org

March 25, 2020

Ms. Sharon Conley Facility & Equipment Coordinator MDNR-Forest Resources Division

RE: Asbestos Sampling Former Hanger Building MDNR Mio Field Office 191 South Mt. Tom Road Mio, Michigan Sagasser & Associates, Inc. Project #12002

Sagasser & Associates, Inc. has collected asbestos sampled from the former hanger building located on the Mio Field Office at 191South Mt. Tom Road in Mio, Michigan (Site). The purpose of the asbestos sampling was to determine the presence and percentage of asbestos mineral fibers in the identified suspect asbestos containing siding material of the former hanger building prior to renovation. Sagasser & Associates, Inc.

completed the sampling using the standard asbestos sampling protocol/techniques to minimize the creation of airborne fibers and standard sampling protocols for the collection of suspect samples.

General views of Site building with transite siding.

General interior view of site building.

Three (3) bulk samples were collected from the transite siding and submitted for analysis by polarized light microscopy (PLM) by EPA Method 600/R-93/116 at SanAir Technologies Laboratory in Cincinnati, Ohio. Since bulk sample TS-1 was determined to contain 18% chrysotile asbestos, the two other bulk samples were not analyzed.

TRANSITE

TRANSITE

Asbestos Sampling Report Project #12002 2 Former Hanger - Mio Field Office – Mio, Michigan

Per the NESHAP requirements, cementitious asbestos containing material (ACM) (transite panels) must be removed prior to renovation by a licensed abatement contractor.

The NESHAP agency and MIOSHA Asbestos Program overseeing the Site needs to be notified in writing of the intention to remove/demolish 10 days prior to the renovation.

Limitations and Exceptions

Sagasser & Associates, Inc. has performed the proposed scope of services using due care in accordance with good and customary practices, as ordinarily exercised by other reputable members of the profession under similar circumstances. Maps and sketches are provided for informational purposes and should not be considered surveys or engineering studies.

No sampling of metal, wood, materials identified as fiberglass or foam insulation, or materials not typically identified as suspect asbestos containing was conducted. Additionally, no sampling of any electrical wiring/ components was conducted and should be presumed to contain asbestos if identified. Sagasser & Associates, Inc. collected three samples of each identified miscellaneous materials and instructed the laboratory to analyze each sample set to the first positive samples. Thereby, not all of the bulk samples collected and submitted for laboratory analysis were analyzed and Sagasser & Associates, Inc. makes no representation as to the asbestos content of untested samples.

Additionally, areas/materials deemed to be not accessible without involving significant demolition activities and/or compromising the structural integrity of the building, were hidden, or unsafe were not assessed and Sagasser & Associates, Inc. makes no representation as to the presence or absence of asbestos containing materials in those areas/materials.

Closing

Sagasser & Associates, Inc. sincerely appreciated the opportunity to provide our consulting services. If you have any questions regarding the contents of this report or require additional information, please contact our office at your convenience.

Respectfully Submitted, Scot Egleston Kevin D. Sagasser, P.E.

Environmental Scientist Senior Project Engineer (Accreditation Number - A16147)

Attachments

Laboratory Analytical Report

SanAir ID#: 20004492

Project #: 12002

Project Name: DNR Garage - Mio

Report Date: 2/6/2020

Analysis Report prepared for Sagasser & Associates, Inc.

Dear Scot Egleston, We at SanAir would like to thank you for the work you recently submitted. The 3 sample(s) were received on Thursday, January 30, 2020 via FedEx. The final report(s) is enclosed for the following sample(s): TS -1.1, TS -1.2, TS -1.3.

These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.

Sincerely, Matthew Daigneault Asbestos Laboratory Manager SanAir Technologies Laboratory

Final Report Includes:

- Cover Letter

- Analysis Pages

- Disclaimers and Additional Information

Sample conditions:

- 3 samples in Good condition.

11709 Chesterdale Rd., Cincinnati, OH 45246 | 513.438.6006 | Fax: 804.897.1177 | www.SanAir.com | IAQ@SanAir.com

12002Project Number:

P.O. Number:

Project Name: DNR Garage - Mio

1/28/2020Collected Date:

1/30/2020 11:10:00 AMReceived Date:

2/6/2020 12:52:33 PM

20004492 SanAir ID Number

FINAL REPORT

Sagasser & Associates, Inc.Name:

Address: 699 South Wisconsin Avenue

Gaylord, MI 49735

989-732-5800Phone:

Analyst: Poeppelman, Dustin

Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

TS -1.1 / 20004492-001

Transite

Grey Non-Fibrous

Homogeneous

82% Other 18% Chrysotile

TS -1.2 / 20004492-002

Transite

Not Analyzed

TS -1.3 / 20004492-003

Transite

Not Analyzed

Analyst:

Analysis Date: 2/6/2020 Date: 2/6/2020

Approved Signatory:

12002Project Number:

P.O. Number:

Project Name: DNR Garage - Mio

1/28/2020Collected Date:

1/30/2020 11:10:00 AMReceived Date:

2/6/2020 12:52:33 PM

20004492 SanAir ID Number

FINAL REPORT

Sagasser & Associates, Inc.Name:

Address: 699 South Wisconsin Avenue

Gaylord, MI 49735

989-732-5800Phone:

Disclaimer

The final report cannot be reproduced, except in full, without written authorization from SanAir. Fibers smaller than 5 microns cannot be seen with this method due to scope limitations. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample and information provided by the client. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government.

Samples are held for a period of 60 days.

For NY state samples, method EPA 600/M4-82-020 is performed.

Polarized- light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.

Asbestos Certifications NVLAP lab code 600227-0

Rhode Island Certification Number: PLM00144