DDC_As_Built_Drawings_(2012).pdf
PDF 17 MB Posted
- Solicitation number
- ABL-15229
About this file
DDC As-built (2012)
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ_ABL-15229_Rev_1.pdf | ||
| SCA_WD_12.30.14.pdf | ||
| PLC_Specs.docx | DOCX document | |
| ABL-15229_Brand_Name.pdf | ||
| DDC_As_Built_Automated_Logic_Install(2014).pdf | ||
| RFQ_ABL-15229.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NO
LAST
UPDATE DESCRIPTION BUILDING
1 1/24/07 Title Page 2 1/24/07 Control System Architecture 3 1/24/07 Equipment Schedules
3A 1/24/07 Control Valve Schedule / Piping 4 1/24/07 Lab Penthouse
4A 1/24/07 Lab Penthouse Sequence of Operations 4B 1/24/07 Lab Penthouse Sequence of Operations 4C 1/24/07 Lab Penthouse Sequence of Operations 4D 1/24/07 Lab Penthouse AHU-101 / GEF-101 4E 1/24/07 Lab Penthouse AHU-102 / EF-105 / EF-106 4F 1/24/07 Lab Penthouse AHU-103 4G 1/24/07 Lab Penthouse Fume Hood Exhaust / EF-101, 102 4H 1/24/07 Lab Penthouse Fume Hood Exhaust / EF-103, 104 4I 1/24/07 Lab Penthouse Interface Panel (P1) 4J 1/24/07 Interface Panel (P1) Controller Details 4K 1/24/07 Interface Panel (P1) Controller Details 5 1/24/07 Lab Compressor Rm L205
5A 1/24/07 Lab Compressor Rm L205 Sequence of Operations 5B 1/24/07 Lab Compressor Rm L205 VF-103 / Efs 5C 1/24/07 Lab Compressor Rm L205 Gas Panels 5D 1/24/07 Lab Compressor Rm L205 Interface Panels (P2) 5E 1/24/07 Interface Panel (P2) Controller Details 6 1/24/07 Lab Boiler Room L120
6A 1/24/07 Lab Boiler Room L120 Sequence of Operations 6B 1/24/07 Lab Boiler Room L120 HX-101 / EF-114, 115 6C 1/24/07 Lab Boiler Room L120 Fuel System 6D 1/24/07 Lab Boiler Room L120 Pumps / HWS / VF-101, 102 6E 1/24/07 Lab Boiler Room L120 Interface Panel (P5) 6F 1/24/07 Interface Panel (P5) Controller Details 6H 1/24/07 Lab Air Valve / Reheat Control 6I 1/24/07 Lab Pressure / Fume Hood Control 6J 1/24/07 Lab SAV-113,14,126 & 127 Control 6K 1/24/07 Lab Area Control List by Area Served 7 1/24/07 Post Treatment Rm L014
7A 1/24/07 Post Treatment Rm L014 Sequence of Operations 7B 1/24/07 Post Treatment Rm L014 Equipment Control 7C 1/24/07 Post Treatment Rm L014 Equipment Control 7D 1/24/07 Post Treatment Rm L014 Interface Panel (P6) 7E 1/24/07 Interface Panel (P6) Controller Details 7F 1/24/07 Interface Panel (P9) Controller Details 8 1/24/07 Office Mech Rm 265
8A 1/24/07 Office Mech Rm 265 Sequence of Operations 8B 1/24/07 Office Mech Rm 265 AHU-201 / RF-201 8C 1/24/07 Office Area VAV Box Control (AHU-201) 8D 1/24/07 Office Mech Rm 265 Interface Panel (P3) 8E 1/24/07 Interface Panel (P3) Controller Details 9 1/24/07 Office Mech Rm 247
9A 1/24/07 Office Mech Rm 247 Sequence of Operations 9B 1/24/07 Office Mech Rm 247 Sequence of Operations 9C 1/24/07 Office Mech Rm 247 AHU-202 / RF-202 9D 1/24/07 Office Area VAV Box Control (AHU-202) 9E 1/24/07 Office Mech Rm 247 HWG-201 / HWS 9F 1/24/07 Office Mech Rm 247 Computer Rm A/C Unit 9G 1/24/07 Office Mech Rm 247 Interface Panel (P4) 9H 1/24/07 Interface Panel (P4) Controller Details 10 1/24/07 Filter Building Sequence of Operations
10A 1/24/07 Filter Building VF-301 10B 1/24/07 Filter Building Equipment 10C 1/24/07 Filter Building Equipment Wiring Details 10D 1/24/07 Filter Building Interface Panel (P7) 10E 1/24/07 Interface Panel (P7) Controller Details 11 1/24/07 Wet Well Bldg
11A 1/24/07 Wet Well Bldg VF-401, Sequence of Operations 11B 1/24/07 Wet Well Equipment 11C 1/24/07 Wet Well Bldg Interfce Panel (P8) 11D 1/24/07 Interface Panel (P8) Controller Details 12 1/24/07 UH / CUH / FT Sequence of Operations
12A 1/24/07 Unit Heaters / Cabinet Unit Heaters / Fintubes
CONTROL DRAWING INDEX
FILTER BUILDING 3
WET WELL
BUILDING 4
MISC.
ARCHITECTURE
AND SCHEDULES
LAB BUILDING 1
OFFICE BUILDING
13 1/14/11 Lab AHU Seawater H/C Seq of Ops-Phase 1 13A 1/14/11 Lab AHU Seawater H/C Seq of Ops-Phase 1 13B 1/14/11 Lab AHU Seawater H/C Seq of Ops-Phase 2&3 13C 1/14/11 Seawater Loop & Heat Pump Loop-Phase 1 13D 1/14/11 Building Loop-Phase 1 13E 1/14/11 Building Loop-Phase 2&3 13F 1/14/11 Network Controller Details CLS1&2
LAB BUILDING
LABORATORY AIR VALVES AND SPACE TEMPERATURE CONTROLS:
THE LACS SHALL CONTROL THE LABORATORY AIR VALVES, REHEAT COILS, EXHAUST-VS-
SUPPLY PRESSURIZATION OFFSETS AND SPACE TEMPERATURES AS SHOWN ON THE
DRAWINGS.
THE FOLLOWING POINTS ARE INCLUDED FOR MONITORING AND ALARMING VIA THE HVAC DDC
SYSTEM.
1. FUME HOOD EXHAUST FLOW FACE VELOCITY (M/s)
2. LABORATORY ROOM SUPPLY AIR FLOW (L/s)
3. LABORATORY ROOM GENERAL EXHAUST AIR FLOW (L/s)
4. FUME HOOD SASH POSITION (% OPEN)
5. FUME HOOD LOW FLOW (ALARM)
6. LABORATORY ROOM AIR OFFSET (IF APPLICABLE)
7. LABORATORY DIFFERENTIAL PRESSURE (IF APPLICABLE)
8. LABORATORY ROOM TEMPERATURE SETPOINT (DEG C)
THE LACS SYSTEM WILL ACCEPT CONTROL INPUTS FROM THE HVAC DDC SYSTEM AS FOLLOWS.
1. FUME HOOD EXHAUST FLOW FACE VELOCITY SETPOINT
2. LABORATORY ROOM AIR FLOW OFFSET SETPOINT ADJUSTMENT (IF APPLICABLE)
3. LABORATORY ROOM DIFFERENTIAL PRESSURE SETPOINT ADJUSTMENT (IF APPLICABLE)
4. LABORATORY ROOM TEMPERATURE SETPOINT ADJUSTMENT.
ROOM SYMBOL
DESV
SIZE
(in)
FS
(in) COIL
FLOW
(L/S) RH VALVE TAG
EXHAUST
SYMBOL
CDRS25
SIZE (in)
FS
(in)
HOOD
SYMBOL
CDRS25
SIZE (in)
FS
(in) XFRM PNL NOTES
BASEM ENT
L013 EAV-001 24 SS (Manually Balanced)
FIRST FLOOR
L101 SAV-101 16 16 RHC-102 0.18 VS2213-536-9-4 VR3 EAV-101 16 16 HAV-101 12 X1 Common HAV FS
EAV-101.1 10 12 HAV-102 12 20
HAV-103 12
L102 SAV-102 12 12 RHC-103 VS2213-536-9-3 VR2 EAV-102 12 12 HAV-104 12 X2 Common HAV FS
EAV-102.1 8 12 HAV-105 12 16
L103,104,105,106 SAV-103 6 6 X3
L132 SAV-114 12 RHC-113 0.09 VS2213-536-9-3 VR2 X3 VAV CONTROLLER
L107 SAV-104 14 14 RHC-104 0.14 VS2213-536-9-3 VR2 EAV-104 6 8 HAV-106 10 10 X4 HAV-106 is backdraft
FT-1 0.032 VT2415H23A020 EAV-105 16 12
L108 SAV-105 6 6 RHC-105 0.01 VS2213-536-9-2 VR1 X4
L109 SAV-106 8 8 EAV-106 X5 No damper on EAV-106 L110 EAV-106.1 No damper on EAV-106.1 L111 SAV-107 10 12 RHC-106 0.07 VS2213-536-9-2 VR1 EAV-107 HAV-107 X5 No damper on EAV/HAV-107
L114 SAV-108 10 12 RHC-107 0.07 VS2213-536-9-2 VR1 EAV-108 8 8 X6
EAV-108.1 6 6
L115 SAV-109 6 6 RHC-108 0.02 VS2213-536-9-2 VR1 EAV-109 6 6 X6
L116 SAV-110 12 12 RHC-109 0.07 VS2213-536-9-2 VR1 EAV-110 10 10 HAV-108.1 10 X7 HAV-108,108.1 are backdraft
HAV-108 10
L117 SAV-111 8 10 RHC-110 0.06 VS2213-536-9-2 VR1 EAV-111 8 X7 EAV-111 is VAV box
L123, 136 SAV-113 14 RHC-114 0.09 VS2213-536-9-3 VR2 X7 VAV CONTROLLER
L121,122,124,126,127 RHC-101 0.13 VS2213-536-9-3 VR2 EAV-127 10 (Manually Balanced)
SECOND FLOOR
L201 SAV-115 16 16 RHC-115 0.22 VS2213-536-9-4 VR3 EAV-115 16 16 HAV-109 10 X8 Common HAV FS
HAV-110 14
HAV-110.1 12 26
HAV-110.2 12
HAV-111 10
HAV-112 12 12 Separate HAV FS
L202 SAV-116 16 16 RHC-116 0.23 VS2213-536-9-4 VR3 EAV-116 16 16 HAV-113 14 14 X9
HAV-113.1 12
HAV-114 10 16
HAV-115 14 14
L232 SAV-128 10 RHC-127 0.09 VS2213-536-9-3 VR2 X9 VAV CONTROLLER
L203 SAV-117 16 16 RHC-117 0.27 VS2213-536-9-4 VR3 EAV-117 16 16 HAV-116 10 10 X10
HAV-117 10 10
L204 SAV-118 10 12 RHC-118 0.10 VS2213-536-9-3 VR2 EAV-118 10 X10 EAV-118 is VAV box L207 SAV-119 10 10 RHC-119 0.08 VS2213-536-9-3 VR2 EAV-119 10 X11 EAV-119 is VAV box
L234 SAV-127 10 RHC-128 0.09 VS2213-536-9-3 VR2 X11 VAV CONTROLLER
L208 SAV-120 12 12 RHC-120 0.13 VS2213-536-9-3 VR2 EAV-120 12 12 HAV-117.1 12 X12
EAV-120.1 14 14 HAV-117.2 12 18
L209 SAV-121 12 12 RHC-121 0.11 VS2213-536-9-3 VR2 EAV-121 10 10 HAV-118 12 12 X13 L210 SAV-122 12 12 RHC-122 0.12 VS2213-536-9-3 VR2 EAV-122 12 X13 EAV-122 is VAV box L211 SAV-123 16 16 RHC-123 0.23 VS2213-536-9-4 VR3 EAV-123 12 X14 EAV-123 is VAV box L212 SAV-124 16 16 RHC-124 0.23 VS2213-536-9-4 VR3 EAV-124 16 16 HAV-119 12 12 X14 L213 SAV-125 12 12 RHC-125 0.12 VS2213-536-9-3 VR2 EAV-125 12 X15 EAV-125 is VAV box
L214 SAV-129 8 14 X15
L215 SAV-130 10 12 EAV-129 12 X15 EAV-129 is VAV box L216,217,218,220,221 EAV-126 10 (Manually Balanced)
F202 RHC-130 0.30 VS2213-536-9-5 VR4
NOTE: All HAV's are stainless steel (SS)
SUPPLY AIR EXHAUST AIR VALVES HOOD AIR VALVES
PANEL 100VA 25VA TOTAL VA
1 1 7 275 2 1 6 250 3 1 3 175 4 1 7 275 5 1 6 250 6 1 7 275 7 2 8 400 8 1 9 325 9 2 7 375 10 1 8 300 11 2 3 275 12 1 6 250 13 1 7 275 14 1 7 275 15 1 8 300
18 99 4275
PANEL TRANSFORMER QUANTITIES
PANEL 100VA 25VA TOTAL VA Circuit
1 1 7 275 ELL7-39
2 1 8 300 ELL7-39
3 1 5 225 ELL7-39
4 1 7 275 ELL7-41
5 1 6 250 ELL7-41
8 1 9 325 ELL14-37
9 2 7 375 ELL14-37
10 1 8 300 ELL14-37
11 2 3 275 ELL14-37
12 1 6 250 ELL14-39
13 1 7 275 ELL14-39
14 1 7 275 ELL14-39
15 1 8 300 ELL14-39
Totals 15 88 3700
TRANSFORM ER PANELS
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L208 Flow Ctrl X12-2 25
SAV-120 X12-3 25
RHC-120 X12-1 100
EAV-120 X12-4 25
EAV-120.1 X12-5 25
HAV-117.1 X12-6 25
HAV-117.2 X12-7 25
FS FSx2 FS X12-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L209 Flow Ctrl X13-2 25
SAV-121 X13-3 25
RHC-121 X13-1 100
EAV-121 X13-4 25
HAV-118 X13-5 25
FS FS FS X13-1
L210 Flow Ctrl X13-6 25
SAV-122 X13-7 25
RHC-122 X13-1
EAV-122 X13-8 25
FS FS X13-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L211 Flow Ctrl X14-2 25
SAV-123 X14-3 25
RHC-123 X14-1 100
EAV-123 X14-4 25
FS FS X14-1
L212 Flow Ctrl X14-5 25
SAV-124 X14-6 25
RHC-124 X14-1
EAV-124 X14-7 25
HAV-119 X14-8 25
FS FS FS X14-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L213 Flow Ctrl X15-2 25
SAV-125 X15-3 25
RHC-125 X15-1 100
EAV-125 X15-4 25
FS FS X15-1
L214 Flow Ctrl X15-5 25
SAV-129 X15-6 25
FS X15-1
L215 Flow Ctrl X15-7 25
SAV-130 X15-8 25
EAV-129 X15-9 25
FS FS X15-1
L216,217,218,220,221 EAV-126
(Manually Balanced)
BASEM ENT
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA
L013 EAV-001
(Manual Damper)
FIRST FLOOR
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L101 Flow Ctrl X1-2 25
SAV-101 X1-3 25
RHC-102 X1-1 100
EAV-101 X1-4 25
EAV-101.1 X1-5
HAV-101 X1-6 25
HAV-102 X1-7 25
HAV-103 X1-8 25
FS FS x 2 FS X1-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L102 Flow Ctrl X2-2 25
SAV-102 X2-3 25
RHC-103 X2-1 100
EAV-102 X2-4 25
EAV-102.1 X2-5 25
HAV-104 X2-6 25
HAV-105 X2-7 25
FS FS x 2 FS X2-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L103,104,105,106 VAV Ctrl X2-8 25
SAV-103 (VAV Actuator)
L132 VAV Ctrl X2-9 25 SAV-114 (VAV Actuator)
RHC-113
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L107 Flow Ctrl X3-2 25
SAV-104 X3-3 25
RHC-104 X3-1 100
EAV-104 X3-4 25
EAV-105 X3-5 25
HAV-106 (Backdraft Dpr) FS FS x 2 X3-1
L108 VAV Ctrl X3-6 25 SAV-105 (VAV Actuator)
RHC-105 X3-6
FT-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L109 VAV Ctrl X4-6 25
SAV-106 (VAV Actuator)
L111 VAV Ctrl X4-7 25 SAV-107 (VAV Actuator)
RHC-106 X4-7
EAV-107 (no Dpr)
HAV-107 (no Dpr)
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L114 Flow Ctrl X4-2 25
SAV-108 X4-3 25
RHC-107 X4-1 100
EAV-108 X4-4 25
EAV-108.1 X4-5 25
FS FS x 2 X4-1
L115 VAV Ctrl X4-8 25 SAV-109 (VAV Actuator)
RHC-108 X4-8
EAV-109 (pwrd by VAV box)
FS X4-8
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L116 Flow Ctrl X5-2 25
SAV-110 X5-3 25
RHC-109 X5-1 100
EAV-110 X5-4 25
HAV-108.1 X5-5 25
HAV-108 X5-6 25
FS FS FS x 2 X5-1
L117 VAV Ctrl X5-7 25 SAV-111 (VAV Actuator)
RHC-110 X5-7
EAV-111 (pwrd by VAV box X5-7
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L136, 123 VAV Ctrl X5-8 25
SAV-113 (VAV Actuator)
RHC-114 X5-8
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA
L121,122,124,126,127 EAV-127
(Manually Balanced)
SECOND FLOOR
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L201 Flow Ctrl X8-2 25
SAV-115 X8-3 25
RHC-115 X8-1 100
EAV-115 X8-4 25
HAV-109 X8-5 25
HAV-110 X8-6 25
HAV-110.1 X8-7 25
HAV-110.2 X8-8 25
HAV-111 X8-9 25
HAV-112 X8-10 25
FS FS FSx3 X8-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L202 Flow Ctrl X9-2 25
SAV-116 X9-3 25
RHC-116 X9-1 100
EAV-116 X9-4 25
HAV-113 X9-5 25
HAV-113.1 X9-6 25
HAV-114 X9-7 25
HAV-115 X9-8 25
FS FS FSx3 X9-1
L232 VAV Ctrl X9-9 100 SAV-128 (VAV Actuator)
RHC-127
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L203 Flow Ctrl X10-2 25
SAV-117 X10-3 25
RHC-117 X10-1 100
EAV-117 X10-4 25
HAV-116 X10-5 25
HAV-117 X10-6 25
FS FS FSx2 X10-1 L204 Flow Ctrl X10-7 25
SAV-118 X10-8 25
RHC-118 X10-1
EAV-118 X10-9 25
FS FS X10-1
ROOM
SUPPLY
AIR CTRL
SUPPLY
ACT REHEAT
EXHAUST
ACT
HOOD
CTRL &
DPR ACT XFRM vA L207 Flow Ctrl X11-2 25
SAV-119 X11-3 25
RHC-119 X11-1 100
EAV-119 X11-4 25
FS FS X11-1
L234 VAV Ctrl X11-5 100 SAV-127 (VAV Actuator)
RHC-128
1) Seawater Waste System Controls And Operation:
a) Two ultrasonic level control systems are installed in the main Seawater Waste Collection Sump (one in each half of the sump) in the seawater equipment room to control the operation of the seawater waste treatment system. Both sumps shall normally be valved open and the level sensors shall be redundant. When a sump is closed for maintenance the plant operator shall disable the corresponding sensor via the MMI and the other level sensor shall be used to control the pumps.
b) The level sensors shall indicate high and low levels as outlined herein and shall be interlocked to various pumps as outlined below.
c) One low level sensor shall cut-out the seawater waste treatment pumping system (pumps Pmp-106, Pmp-107, & Pmp-108) and the other shall indicate a trouble alarm. The extreme high level sensor shall be a high water alarm and shall indicate an emergency alarm condition. The normal high water level sensor shall cut-in the lead pump for the seawater waste treatment system. The second high water sensor cuts-in the second pump. If the water level in the seawater waste collection sump continues to rise a third level shall cut-in the third (redundant) pump and shall indicate an emergency and trouble alarm. Essentially, the seawater waste treatment system comprises a pumped filtration and ozonation system that operates continuously between two levels in the collection sump. If the lead pump cannot keep up with the flow of contaminated seawater then the second pump cuts-in. All pumps cut out at the low level in the collection sump. Additionally, lag and standby pumps cut out 0.15 meter above low level. The control system shall include visual alarms. Elapsed runtime shall be monitored for each pump and the lead/lag/standby designations shall be reassigned accordingly on a weekly basis, except that PMP-108 shall always be lead. Lead pump operation may also be initiated by the operator thru the MMI. Pump-108 is VFD controlled, and it’s speed shall vary proportionally between lag start and lad stop set point in the seawater waste collection sump.
d) Backwash Surge Tank Pumps Pmp-110 & Pmp-111:
i) The DDC shall control pumps Pmp-110 & Pmp-111 in a primary/standby configuration and monitor the seawater backwash waste holding tank. The primary pump shall activate during off peak hours (between 8pm and 6am) and deliver post treatment backwash to the Site Packaged Waste Treatment System until the Backwash Waste Holding Tank is empty. Coordinate pump off peak runtime with the UAF Facility Lift Station and the Laboratory Sewage Ejector SE-101. Elapsed runtime shall be monitored for each pump and the lead/lag/standby designations shall be reassigned accordingly on a weekly basis. Lead pump operation may also be initiated by the operator thru the MMI.
ii) Upon primary pump failure an alarm shall activate and the standby pump shall be automatically energized.
Upon high level alarm the off peak operation sequence shall be overridden and the primary pump shall deliver post treatment backwash to the Site Packaged Waste Treatment System until the Backwash Waste Holding Tank is empty.
The sequence of operation of the seawater system is as described herein.
1) Operator Interface:
a) A PC computer workstation will be provided to monitor status of the seawater system as well as provide control as needed.
i) Typical status points monitored will be
(1) Wet Well Level
(2) VFD Pump Status, Speed, and Runtime, and Lead/Lag Position
(3) Unfiltered Seawater Supply Flow Rate and Flow Total
(4) Unfiltered Seawater Supply Pressure
(5) Opened / Closed Status of all monitored valves
(6) Individual Filter and Reservoir Levels
(7) Water Quality
(8) Backwash Circ Pump and Air Blower Status
(9) Waste Seawater Collection Tank and Backwash Surge Tank Levels
(10) Waste Seawater Pumps and Backwash Surge Pumps Status
(11) Filter Backwash Sequence Status
(12) Alarms as described
ii) Typical control points will be
(1) Seawater System On/Off
(2) Unfiltered Seawater Supply Flow Total Reset
(3) Unfiltered Seawater Supply Pump Runtime Reset
(4) Individual Filter Auto-Backwash Timeclock
(5) Manual Filter Backwash Control
(6) Reservoir Level Setpoints
(7) Active Reservoir Selection
(8) Individual Active Filter Selection
(9) Water Quality Alarm Setpoints
(10) Alarm Acknowledgement
(11) Backwash Surge Pump Off-Peak Schedule
A panel-mounted Operator Interface will be provided for redundant monitoring and control of the seawater system.
1) Main Filter House:
a) When the seawater system is on, a Filtered Seawater Supply Valve (MV13 or MV14) shall open for the active reservoir, selected by the plant operator thru the MMI. Either or both reservoirs may be selected.
b) When the seawater system is on a Seawater Filter Valve (SFV1a or SFV1b, typical of 6 filters) shall open for the active Gravity Sand Filters (selectable by the plant operator thru the MMI). Line a or line b valves shall be selected for the corresponding duplex supply line by monitoring the selection made by the operator with a switch at the Well Control Panel.
c) Ultrasonic level sensors are provided in the Gravity Sand Filters (LS5, LS6, LS7, LS8, LS9, and LS10). Levels shall be monitored in the active Gravity Sand Filters and if the level of seawater rises above an adjustable setpoint an alarm shall sound and the filter inlet valve shall close.
d) Ultrasonic level sensors are provided in the Filtered Seawater Reservoirs (LS11 and LS12) to provide rate control of the seawater supply pumps and to sound an alarm if the level of seawater in the active reservoir drops to a pre-determined level, to protect the distribution system from running dry. This condition will signify that the demand of unfiltered seawater exceeds the filtered seawater supply capability. If the level of seawater in the active reservoir rises to a pre-determined level an alarm shall also sound. These alarms will be announced and monitored.
e) There is a single backwash supply pump (PMP-301) that provides filtered seawater for backwashing the gravity sand filters. The on-off operation of this pump is controlled by the backwash controller that cycles the backwash procedure of each gravity sand filter. Operation of the pump shall be synchronized with the active FSW Reservoir BW Supply Valve (MV11 or MV12).
f) There is a rotary air blower that is used to scour the gravity sand filter beds prior to backwashing them with filtered seawater. The on-off operation of this air blower is controlled by the backwash controller as for the backwash pump.
g) All motor controls shall be the HOA (Hand-Off-Automatic) type that will allow any pump to be manually operated.
2) Gravity Sand Filter Backwash Control Sequence
a) The level of the active Filtered Seawater Reservoir shall be monitored. If the level is below a predetermined set point and no other Gravity Sand Filters are active when a backwash is called for, then initiation of a backwash sequence shall be inhibited and an alarm shall sound.
b) Each of the six gravity sand filters will be backwashed on a regular basis. The frequency of automatic backwashing each filter cell will be determined by the experience of the seawater system operating staff. The frequency of backwashing will vary seasonally. The backwashing procedures will be initiated by a timeclock controller. There will be an overriding ultrasonic level controller in the filter cells that will initiate the backwash cycle in the event that the time clock controller does not initiate the backwash cycle prior to the filters becoming dirty or clogged, requiring backwashing. The automatic backwash control system shall include manual override features to allow initiation or cancellation of the backwash cycles.
c) Each filter is supplied with unfiltered seawater from the main seawater supply pumps. There are two supply lines; one will be in use, the other will be either purged with fresh water to control the build-up of marine fouling organisms in the pipelines or it will be drained.
d) Each filter will have several electrically operated valves on the various piping connections to the filter, as follows:
i) Seawater Filter Valve 1a - on the influent line to the filter from the Seawater Supply Line 1.
ii) Seawater Filter Valve 1b - on the influent line to the filter from the Seawater Supply Line 2.
iii) Seawater Filter Valve 1c - on the filtered water discharge line to the Filtered Seawater Reservoirs.
iv) Seawater Filter Valve 1d - on the backwash waste line from the filter backwash drainage trough.
v) Seawater Filter Valve 1e - on the backwash water supply line from the backwash water supply pump and connected to the filtered water discharge line.
vi) Seawater Filter Valve 1f - on the air scour line from the air blower supply header.
vii) These valve designations repeat for filters 2 through 6.
e) A typical backwash sequence will be as follows:
i) Step 1
(1) All filter valves shall close.
(2) Reservoir BW Supply Valves shall be confirmed closed.
(3) Air Blower and Backwash Supply pump shall be confirmed off.
ii) Step 2
(1) The filter BW Outlet valve 1d shall open.
iii) Step 3
(1) The air blower shall start, and upon confirmation of sufficient pressure in the air scour supply line, the filter air scour inlet valve 1f shall open.
(2) This step shall continue for 2 minutes.
iv) Step 4
(1) The filter air scour inlet valve 1f shall close and then the air blower shall stop.
(2) The system shall pause for 2 minutes to allow air evacuation thru the filter air relief tube.
v) Step 5
(1) The filter BW Inlet valve 1e shall open.
(2) The active reservoir BW supply outlet valve shall open.
(3) When the filter BW Inlet valve and reservoir BW supply valve are confirmed open, the backwash circulation pump shall start.
(4) This step shall continue for 4 minutes.
1) Wet Well Pumphouse:
a) Each of the three main submersible turbine seawater supply pumps, Pmp-401, Pmp-402 and Pmp-403 has a capacity of 50.46 l/s. Two pumps will operate in a lead/lag configuration. The third pump will be (redundant) standby. Each pump will include a variable frequency drive to control the output (flow rate) of each pump. In the case of lead or lag pump failure; the failed pump shall de-energize, the standby pump shall activate and an alarm shall sound. The lead, lag and standby pumps shall alternate to equalize runtime. The pump with the least runtime shall be evaluated on a weekly basis and shall be switched to the lead pump, the pump with the most runtime shall be switched to the stand-by pump. Runtime / Lead pump evaluation may also be initiated by the operator thru the MMI.
b) A magnetic flow meter will be provided in each of the duplex raw seawater main lines to the filter house (FM1 & FM2). When the seawater system is on (selectable through the MMI) the active filters shall open and the lead seawater supply pump shall start. The output from the active main line magnetic flow meter (selected by the operator with a switch at the Well Control Panel) will be used to monitor the seawater delivery flow rate. The plant operator will select which reservoir to use through the MMI. Level sensors in the active Filtered Seawater Reservoir (FSWR1 or FSWR2) will regulate the lead and lag seawater pumps variable frequency drives and thus control the seawater delivery flow rates to maintain the level of the active reservoir to setpoint. If the lead pump is at 100% speed and the active FSW Reservoir cannot maintain its level setpoint the lag pump shall start and both pumps shall operate in unison to maintain the reservoir level setpoint. If the reservoir is at or above setpoint and both pumps are operating at or below 74% speed for a time interval of 15 minutes the lag pump shall stop. A pump shall be allowed to run at minimum speed and cause the active FSW Reservoir level to exceed the level set point and cause overflow. This system of control will match the flow rate of the main seawater supply pumps to the actual system flow demand.
c) There will be an ultrasonic level controller located in the wet well. This controller shall be setup to override the main reservoir level controller in the event that the water level in the wet well starts to drop below a predetermined level. In this event the ultrasonic controller will reduce the flow rate of the operating seawater supply pump to match the reduction of flow into the wet well. If the level of the seawater in the wet well continues to drop below a safe operating level (an alarm condition) then the controller shall shut off the operating submersible turbine pumps. When the level drops to this unsafe level the controller shall shut down the pump and an audible and visual alarm shall be activated. This alarm condition shall be recorded on the central control system.
All motor controls shall be the HOA (Hand-Off-Automatic) type that will allow any pump to be manually operated.
COMPONENTS
QTY PART NUMBER DESCRIPTION MANUF
1 1747-l551B SLC 5/05 - 16k A llen-Bradley 1 1747-M13 Flash Memory - 28k A llen-Bradley 2 1746-N2 Blank Slot Filler A llen-Bradley 1 1746-A7 7 Slot Rack A llen-Bradley 1 1746-P4 PS A llen-Bradley 1 1749-IN16 16 Discrete Input A llen-Bradley 1 1746-OW16 16 Relay Output Non-Isolated A llen-Bradley 1 1746-NI8 8 Analog Input Non-Isolated A llen-Bradley 1 1746sc-INO4i 4 Analog Output- Isolated Spectrum Controls 1 SDU-PMBRK UPS Mounting Bracket SOLA
1 SDU500 UPS SOLA
Phase I – Laboratory AHU Seawater Heating and Cooling
Scope of Work
Provide the following control, monitoring, alarm, and trending functions for the seawater heating and cooling system at the NOAA Ted Stevens Marine Research Institute in Juneau, Alaska.
This work requires coordination between Trane, the heat pump manufacturer, and Control Contractors, Inc (CCI), the existing building automation system (BAS) contractor. Provide all coordination and devices to interface between the BAS and the Trane controllers. CCI has primary responsibility to coordinate all required interfaces between the Trane controllers and the BAS.
Trane Control, Monitoring, and Alarm: Two Trane Model TRWD heat pumps, each with a Trane CH530 control panel. The CH530 panels interface with a Trane BCU control panel to provide the required sequence of control. The Trane controllers will control, monitor, and alarm the heat pumps. Provide all control devices that interface directly with the Trane controllers, except as specifically excluded.
BAS Control, Monitoring and Alarm: The BAS system is a Seibe Network 8000 system installed by CCI. The BAS will provide control, monitoring, and alarm of the seawater heating system. Provide all control devices that interface directly with the BAS, except as specifically excluded.
Provide a BAS graphic display of the seawater heating and cooling system showing control, monitoring and alarm functions. Interface with the Trane controllers to provide points they initiate.
Provide user adjustment of all setpoints from the graphic display or with links to a separate setpoint screen.
Display all points that are indicated in the points list on the control drawings.
Annunciate alarms that are indicated in the points list per existing building alarm protocol.
Government Furnished Equipment and Services: The government will provide the following:
Variable frequency drives: Provide interface requirements.
Motor starters and contactors
Automatic valves Wiring and conduits, including landing conductors in government furnished components such as starts and VFD’s. Landing conductors in contractor furnished equipment is the contractors’ responsibility.
Waste Seawater Pumps PMP-106/107/108
Trane Monitoring
Seawater discharge temperature.
Heat Pumps
Trane Control
Heat Pump Lead/Lag Control Disable the heat pumps when the waste seawater discharge temperature is below 30°F.
Provide lead/lag sequencing of the heat pumps with monthly switchover.
Lead Heat Pump Enable when the temperature in HPT-101 is more than 5°F below setpoint.
Disable when, for a continuous five minute period, the heat pump is operating at minimum output and the tank temperature is more than 5°F above the setpoint.
Lag Heat Pump Enable when the lead heat pump fails to operate when enabled.
Enable when the lead heat pump has operated at 100% for 10 continuous minutes, the HPT-101 temperature is more than 5°F below the setpoint, and the tank temperature is not rising.
During simultaneous lead/lag operation of the heat pumps, operate the lead heat pump at 100% output and modulate the lag heat pump to maintain the setpoint.
Disable when, for a continuous five minute period, the lag heat pump is operating at minimum output and the tank temperature is more than 3°F above the setpoint.
Source and Load Pumps: When a heat pump is enabled:
Enable the respective source pump.
Enable the respective load pump.
Verify source and load pump operation via a heat pump flow sensor for two minutes.
Enable the heat pump and operate per the heat pump lead/lag control sequence.
When the heat pump is disabled by the heat pump lead/lag control, maintain source and load flow for 1 minute, then:
Disable respective source.
Disable respective load pump.
Trane Monitoring: Monitoring the following points from a touch screen panel on the BCU.
Heat pump tank HPT-temperature Heat pump HP-101 percent output Heat pump HP-102 percent output Load pump PMP-119 percent speed Load pump PMP-120 percent speed
BAS Monitoring Heat pump tank HPT-1 temperature Heat pump HP-101 percent output Heat pump HP-102 percent output Load pump PMP-119 percent speed Load pump PMP-120 percent speed
Trane Alarms: Provide a general heat pump alarm when:
Any standard heat pump alarm occurs Temperature in HPT-101 more than 10°F above or below the setpoint Heat pumps disabled due to low waste seawater discharge temperature
BAS Alarms Heat pump general alarm
Source Pumps PMP-116 and PMP-117
Power is supplied to each pump through a separate magnetic starter with H-O-A switch. In the hand position, the pump operates. In the auto position, the Trane controller controls the pump.
Trane Control: Enable the pump as part of the respective heat pump operating sequence.
Load Pumps PMP-119 and PMP-120
Power is supplied to each pump through a separate VFD with H-O-A switch. In the hand position, the respective pump operates at 100% speed. In the auto position, the Trane Controller controls the pump.
Trane Control: Enable the pump as part of the respective heat pump operating sequence.
Modulate the pump from 215 gpm at full load to 100 gpm at minimum load. Determine speed associated with each flow rate during balancing.
Disable the respective heat pump operating sequence if the pump fails to operate when enabled.
Trane Monitoring Pump status Percent speed
BAS Monitoring Percent speed
Trane Alarm: Provide a general heat pump alarm when:
Incorrect pump speed VFD Alarm
Heat Pump Building Pumps PMP-121 and PMP-122
Power is supplied to each pump through a separate VFD with H-O-A switch. In the hand position, the respective pump operates at 100% speed. In the auto position, the BAS controls the pump.
BAS Control: Operate pumps in a lead/standby configuration with monthly switchover.
Enable the lead pump when heating/cooling coil HCC-101 and/or HCC-103 requires heating.
Enable and modulate the lag pump when lead pump fails to operate when enabled.
Modulate the pump VFD to maintain a pressure differential of 15psig, with a minimum speed of 30%.
BAS Monitoring
Speed status Differential pressure
BAS Alarms Pump failure when enabled Pump on when disabled Speed failure
Pressure differential is continuously more than 3psig above or below the setpoint for one minute.
Seawater Cooling System
Cooling HX Pump PMP-123
Power is supplied to the pump through a magnetic starter with H-O-A switch. In the hand position, the pump operates. In the auto position, the BAS controls the pump.
BAS Control: Enable the pump when heating/cooling coil HCC-101 and/or HCC-103 require cooling.
BAS Monitoring Pump status
BAS Alarm Pump failure when enabled Pump on when disabled
Cooling Pump PMP-118
Power is supplied to the pump through a VFD with H-O-A switch. In the hand position, the pump operates at 100% speed.
In the auto position, the BAS controls the pump.
BAS Control
Enable the pump and open automatic valve AV-2 and/or AV-4 when heating/cooling coil HCC-101 and/or HCC- 103 require cooling.
Modulate the pump speed to maintain a differential pressure of 14psig in the cooling supply and return mains with a minimum speed of 30%.
Disable pump and close valve(s) when both heat pumps are operating.
BAS Monitoring
Speed status Differential pressure
BAS Alarms
Pump failure when enabled Pump on when disabled Speed failure
Pressure differential is continuously more than 3psig above or below the setpoint for one minute.
Heating/Cooling Coil HCC-101
BAS Control: Provide sequential cooling to heating control, without overlap, of the following to maintain the AHU-101 supply air setpoint of 62°F.
Modulate automatic valve AV-2 in the seawater cooling supply to heating/cooling coil HCC-101.
Modulate the automatic valve in the heat recovery loop to heat recovery coil HRC-101A (existing control).
Modulate automatic valve AV-1 in the heat pump heating supply tp heating/cooling coil HCC-101.
Modulate the automatic valve in the heating supply to heating coil HC-101 (existing control).
BAS Monitoring: Display on the existing AHU-101 screen, with HCC-101 added.
Heat pump heating automatic valve AV-1 position Seawater cooling automatic valve AV-2 position
Heating/Cooling Coil HCC-103
Control: Provide sequential control, without overlap, of the following to maintain the setpoint in Lobby F102.
Modulate automatic valve AV-4 in the seawater cooling supply to heating/cooling coil HCC-103.
Modulate automatic valve AV-3 in the heat pump hearing supply to heating/cooling coil HCC-103.
Modulate the automatic valve in the heating supply to heating coil HC-103 (existing control).
Monitoring: Display on the existing AHU-103 screen, with HCC-101 added
Heat pump heating automatic valve AV-3 position
Seawater cooling automatic valve AV-4 position
New / Exist QTY TAG PART NUMBER MANUFACTURER DESCRIPTION
CABLE
(Type/Qty)
WIRING
DETAIL PANEL
PWR
TERM CTRL POINT
BO 1 SPEED STAT CLS2 AO-AO1
BO 1 CONTROL CLS2 AI-IN1
BO 1 ALARM CLS2 DI-IN2
N 1 CWA1 H-800 VERIS Sensor, Current, 0.5-200A, Solid-Core, NO, On/Off 1x1 CLS2 DI-IN4 N 1 R1FB3 RIBT24B FDI Relay, 20A, 1HP @ 120V, SPDT, On/Off 1x1 CLS2 DO-NO1 N 1 R1FB4 RIBT24B FDI Relay, 20A, 1HP @ 120V, SPDT, On/Off 1x1 CLS2 DO-NO2
SYSTEM DEVICES - SEAWATER LOOP AND HEATING PUMP LOOP DEVICE WIRING
Exist QTY TAG PART NUMBER MANUFACTURER DESCRIPTION
CABLE
(Type/Qty) CTRL POINT
BO 1 SPEED STAT CLS1 AO-AO2
BO 1 CONTROL CLS1 AI-IN3
BO 1 ALARM CLS1 DI-IN4
BO 1 SPEED STAT CLS1 AO-AO1
BO 1 CONTROL CLS1 AI-IN1
BO 1 ALARM CLS1 DI-IN2
BO 1 HAV4 (E)MZ1 AO3
BO 1 HAV5 (E)MZ1 AO4
BO 1 HAV6 (E)MZ7 AO3
BO 1 HAV7 (E)MZ7 AO4
N 1 PDH1 2301-025PD-3V-2D-B SETRA Sensor, Pressure, 0-25 psid, 3-Valve Manifold, 0-5Vd 1x2 CLS2 AI-IN6 N 1 PDH2 2301-025PD-3V-2D-B SETRA Sensor, Pressure, 0-25 psid, 3-Valve Manifold, 0-5Vd 1x2 CLS1 AI-IN6 N 1 R1FB1 RIBT24B FDI Relay, 20A, 1HP @ 120V, SPDT, On/Off 1x1 CLS1 DO-NO1 N 1 R1FB2 RIBT24B FDI Relay, 20A, 1HP @ 120V, SPDT, On/Off 1x1 CLS1 DO-NO2
SYSTEM DEVICES - BUILDING LOOP-PHASE I WORK DEVICE WIRING
Exist DWG FIELD DEVICE CTRL POINT SIGNAL OBJECT OBJ DESCRIPTION
BO C4 CLS1 AI-IN1 P121STAT PUMP STATUS
BO C4 CLS1 AI-IN3 P122STAT PUMP STATUS
N C4 PDH2 CLS1 AI-IN6 0-5Vdc HPHTGDP DIFFERENTIAL PRESSURE SWITCH
BO C4 CLS1 AO-AO1 P121SPED PUMP SPEED
BO C4 CLS1 AO-AO2 P122SPED PUMP SPEED
BO C4 CLS1 DI-IN2 P121ALRM PUMP ALARM
BO C4 CLS1 DI-IN4 P122ALRM PUMP ALARM
N C4 R1FB1 CLS1 DO-NO1 On/Off P121S/S PUMP START/STOP N C4 R1FB2 CLS1 DO-NO2 On/Off P122S/S PUMP START/STOP
POINT INFORMATION - CLS1
New / Exist DWG FIELD DEVICE CTRL POINT SIGNAL OBJECT OBJ DESCRIPTION
BO C3 CLS2 AI-IN1 P118STAT PUMP STATUS
N C4 PDH1 CLS2 AI-IN6 0-5Vdc SEACLDP DIFFERENTIAL PRESSURE SWITCH
BO C3 CLS2 AO-AO1 P118SPED PUMP SPEED
BO C3 CLS2 DI-IN2 P118ALRM PUMP ALARM
N C3 CWA1 CLS2 DI-IN4 On/Off P123STAT PUMP STATUS N C3 R1FB3 CLS2 DO-NO1 On/Off P118S/S PUMP START/STOP N C3 R1FB4 CLS2 DO-NO2 On/Off P123S/S PUMP START/STOP
POINT INFORMATION - CLS2