A6 Full Specs.pdf

PDF 63 KB Posted

Attached to
Small Business Set Aside for Replacement of 10 Network UPS's per attachments.
Solicitation number
N61331-24-T-JC06
Issued by

About this file

This document outlines a small business set aside solicitation by the Department of the Navy Naval Sea Systems Command for the replacement of ten network uninterruptible power supply (UPS) units. The Navy seeks quotes by Thursday, February 1, 2024 at 11:00 AM Central Time for the supply of five 1,500-watt and five 1,920-watt rack mount UPS units meeting the specifications provided in the attached file. Quotes should be emailed to jessica.d.clark27.civ@us.navy.mil and include the offeror's Commercial and Government Entity code and lead time. Offerors must be able to invoice using the Wide Area Workflow system, and shipping costs should be included in the pricing or listed as a separate line item. The work will be performed at the Naval Surface Warfare Center in Panama City, Florida.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GOVERNMENT POINT OF ENTRY (GPE) ANNOUNCEMENT

FOR

REPLACEMENT OF 10 NETWORK UPS'S

The Naval Surface Warfare Center, Panama City Division, (NSWC PCD), Panama City, FL is seeking vendors to award a firm-fixed price purchase order. The procurement is for

Replacement of 10 Network UPS's.

1) Provide five 1,500-watt rack mount UPS. Specifications shall meet or exceed the following characteristics:

2) Qty: 5

1,500-Watt Rack Mount UPS Characteristics

Battery Type Valve Regulated Lead Acid (VRLA)

Runtime at Full Load 4.9 minutes at 1350W

Runtime at Half Load 14 minutes at 675W

Expandable Runtime Yes

DC System Voltage 36V

Battery Recharge Rate (Included Batteries) Less than 4.5 hours from 10% to 90%

Battery Replacement Description Hot-swappable, user replaceable batteries

Input Voltage 120V AC

3) Provide five 1,920-watt rack mount UPS. Specifications shall meet or exceed the following characteristics:

4) Qty: 5

1,920-Watt Rack Mount UPS Characteristics

Battery Type Valve Regulated Lead Acid (VRLA)

Runtime at Full Load 4.5 minutes at 1920W

Runtime at Half Load 12 minutes at 960W

Expandable Runtime Yes

DC System Voltage 48V

Battery Recharge Rate (Included Batteries) Less than 4.5 hours from 10% to 90%

Battery Replacement Description Hot-swappable, user replaceable batteries

Input Voltage 120V AC

UPS Systems shall be shipped to:

Naval Surface Warfare Center, Panama City Division (NSWC PCD) 110 Vernon Avenue Building 399 Panama City, FL 32407

NAICS Code 335999 applies. Small Business Size Standard is 600 employees. FSC is 6150.