A401 PARTIAL PLAN BASEMENT AT EL 157FT Rev1.pdf
PDF 156 KB Posted
- Solicitation number
- 36C24224Q0863
About this file
This document appears to be a partial plan for a basement renovation at the James J. Peters VA Medical Center in Bronx, NY as part of an Energy Savings Performance Contract (ESPC) project. The plan details the demolition and construction of an electric substation room, pump room, and corridor at elevation 157 feet, including the installation of a 48" x 48" exhaust fan. The plan also includes typical firestopping details for wall and floor penetrations.
The related federal contract opportunity is for the emergency rental of a chiller at the James J. Peters VA Medical Center, solicitation number 36C24224Q0863. The Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 2 is the procuring agency. The plan appears to be an attachment to this solicitation, providing design details for the chiller plant improvements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
36.5
37.4
38.5
D D.4 D.7
S-401
16' - 0"
9' - 4 3/8"4' - 0" 7 5/8"
/8
6" CONC SLAB
ELECTRIC
SUBSTATION
ROOM
GK-08
CORRIDOR
GK-07
PUMP ROOM
GK-02
REMOVE EXISTING DOUBLE
DOOR AND FRAME. SEE
STRUCTURAL DRAWINGS FOR
OPENING ENLARGEMENT
REQUIREMENTS. INSTALL NEW
DOOR, FRAME AND HARDWARE.
UNEXCAVATED
SEE STRUCTURAL DRAWINGS
FOR MASONRY WALL DETAILS
SEE THIS DRAWING FOR TYPICAL
FIRE STOPPING DETAILS
A-401
LOUVER L-1 48"X48"
BOTTOM OF LOUVER AT
11'-4"
A-401
A
4' - 0"2' - 0"
EXHAUST FAN
EF-1 BOTTOM AT 13'-4"
OPENING SIZE 24"X24"
8" 6' - 4" 8" 4' - 0 1/4" 4' - 3 3/4"
8" 3' - 4"
NEW CMU WALL OR EXISTING
CONCRETE WALL
SLWEEVE OPTIONAL
INSTALL PER UL SYSTEM C-AJ-1226
USE HILTI FS-ONE MAX FIRESTOP SEALANT
METAL PIPE
MAX. DIA.
STEEL PIPE (SCH 10
OR HEAVER
30"
COPPER PIPE
STEEL CONDUIT
EMT
30"
6"
6"
4"
CAST IRON PIPE
TYPE
INSTALL PER UL SYSTEM C-AJ-1226
USE HILTI FS-ONE MAX FIRESTOP SEALANT
METAL PIPE
MAX. DIA.
STEEL PIPE (SCH 10
OR HEAVER)
30"
COPPER PIPE
STEEL CONDUIT
EMT
30"
6"
6"
4"
CAST IRON PIPE
TYPE
INSTALL PER UL
SYSTEM HW-D-0045
USE HILTI CP 606
FLEXIBLE FIRESTOP
SEALANT
8" CMU WALL
FULLY GROUTED CORES
AT LINTEL
8" CMU
2-4x3 1/2x1/4 ANGLES
FULLY GROUTED CORES
WIRE MESH
LOUVER L-1, 48"X48"
L1 1/2X 1 1/2X1/8
CLIP ANGLE AS
RECOMMENDED BY
LOUVER MANUFACTURER
SEALANT
SEALANT
HEAD DETAIL EFH-1
SCALE: 1-1/2"=1'-0"
EXHAUST FAN EF-1
FULLY GROUTED CORES
AT LINTEL
#5 BAR VERTICAL
GROUT CORE
JAMB DETAIL EFJ-1
SCALE: 1-1/2"=1'-0"
8" CMU
SEALANT BOTH
SIDES TYPICAL 2-4x3 1/2x1/4 ANGLES
0 1'2"4"
0 1'2"4"
SILL DETAIL EFJ-1
SCALE: 1-1/2"=1'-0"
EXHAUST FAN EF-1
EXHAUST FAN EF-1
FULLY GROUTED CORES
WIRE MESH
SEALANT BOTH
SIDES TYPICAL
SEALANT BOTH
SIDES TYPICAL
0 1'2"4"
SEALANT BOTH
SIDES TYPICAL
LOUVER L-1 48"X48"
#5 BAR VERTICAL
GROUT CORES
L1 1/2X1 1/2X1/8 CLIP ANGLE SPACED
AS RECOMMENDED BY LOUVER
MANUFACTURER
AREA OF WORK
36.1
B.6 E.4 o n e e ig h th in c h o n e fo o t 1 th re e q u a rt e rs in c h o n e fo o t
O'BRIEN & GERE ENGINEERS, INC
S A
V E
D
IT IS A VIOLATION OF LAW FOR ANY PERSON,
LICENSED ENGINEER, TO ALTER THIS DOCUMENT.
UNLESS ACTING UNDER THE DIRECTION OF A
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED.
INACCURACIES IN THE STATED SCALE MAY BE INTRODUCED
WHEN DRAWINGS ARE REPRODUCED BY ANY MEANS.
USE THE GRAPHIC SCALE BAR TO DETERMINE THE ACTUAL SCALE.
DRAWING IS NOT SCALABLE IF NO SCALE BAR IS PRESENT.
o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e in c h o n e fo o t
IF
T H
IS
S H E E T
IS
N O T x
F U L L
S
IZ
E U S E
G R A P H
IC
S C A L E S
DESCRIPTION DATE
8825 STANFORD BLVD, SUITE 210
COLUMBIA, MD 21045
PHONE: (443) 276−8288 FAX: (443) 276−8301
www.ameresco.com
AMERESCO
Green Clean Sustainable
DESIGN CHANGE APPROVED CONSULTANT FIRM STAMP
Medical Center Director Approval
Associate Director Approval
Chief Nurse Executive / Chief of Staff Approval
PCC Director Approval
Drawing Title
Chief Engineer Approval
Safety Manager Approval
Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
Dwg. Of
Office of Facility
Management Service
/4 /2
:2
:1
A M
A-401
09/26/18 MRH JJA
BINGHAMTON, NY
PARTIAL PLAN GROUND FLOOR AT EL 157'-0"
X
B in g h a m to n S v r\
P ro je c ts
\A m e re s c o
.3
\6
.V a
-B ro n x -C h p
-1 \D o c s \D
W G
\R e v it \6
A m e re s c o
B ro n x V
A
S tr u c tu ra l.
rv t
VISN 2 ESPC PROJECT
ECM - 2: CHILLER PLANT
IMPROVEMENTS
JAMES J. PETERS VA MEDICAL CENTER
BRONX, NY 10468
66169
1/4" = 1'-0"
GROUND FLOOR PLAN AT 157'-0"
2' 4'2'04'
PLAN
NORTH
TRUE
NORTH
NOT TO SCALE
TYPICAL WALL PENETRATION FIRE STOPPING DETAIL
NOT TO SCALE
TYPICAL FLOOR PENETRATION FIRESTOPPING DETAIL
NOT TO SCALE
TYPICAL FIRE STOPPING AT TOP OF WALL
EXISTING CONCRETE SLAB
ON METAL DECK
NOTES
1. COORDINATE WITH MECHANICAL AND ELECTRICAL DRAWINGS FOR
FOR LOCATION OF CONDUITS AND PIPING
2. FIELD VERIY LOCATION OF EXISTING PIPES AND CONDUITS
1 1/2" = 1'-0"A-401
1 SECTION
0 1'2"4"
1 1/2" = 1'-0"
TYPICAL EXHAUST FAN DETAIL
1 1/2" = 1'-0"A-401
A DETAIL
0 1'2"4"
A B
D
C
NOT TO SCALE
KEY PLAN
IMPROVEMENTS
ECM-2: CHILLER PLANT
ISSUED FOR CONSTRUCTION 09/26/18
FIELD MODIFICATIONS 11/30/18