Date (rev.00): 16.05.2018

By (rev00): NJ

Sheet no.: 1

Rev. ( / date / by): 00/16.05.2018/NJ

Project No.: A101400A

Customer ref.: PO no 30236-000/GIS-6019

Shipowner: In-Mar Systems, Inc / Gulf Island Shipyard

Shipyard: Gulf Island Shipyard

Hull no.: 6019

Type of vessel: Tug

Vessel name: NA

Vessel Class ABS

Fi-Fi Class FIFI 1

PROJECT ITEM NO. 01

CONTENTS

Item No: Qty Type Description Sheet No

01 2 112A-21-08 FFS1200-400V-LB-DF-110P m3/h / 9,1 bar 2

Rev. by:

Revision history (01 onwards, first issue = blank):

Revision / date: Change:

DATA SHEETS

Monitors

Date (rev.00): 16.05.2018

By (rev00): NJ

Sheet no.: 2

Rev. ( / date / by): 00/16.05.2018/NJ

ITEM NO. 01 FFS1200-400V-LB-DF-110P

General information Quantity 2 Monitor series 112A-21-08 Operation Electrical operation Manufacturer FFS

Design Criteria Fluid Sea Water Flange standard DN200 DiN PN16 Pressure class PN 16

Technical data Dual Flow function Yes Nozzle type Pelton Deflector Yes Capacity Full 1200 m3/h Throw length -Capacity Full >120 m Reaction force -Capacity Full 13650 N Capacity Reduced 300 m3/h Throw length -Capacity Reduced NA m Reaction force -Capacity Reduced NA N Inlet pressure 9,1 bar Power supply operation 440V AC/ 60Hz/ 3 phas Weight 197 kg Protection class IP 56 Elevation max - 20 / +80 deg Azimuth max +/- 150 deg

Materials Body and branch pipe Ni-Al-Bronze Nozzle AISI 316L Other parts AISI 316L /GRP / POM(plastic)

Surface Treatment Base Primer Coating RAL 3002 Red

Documentation Certificate ABS Throw curve FFS1200_300 LB-TC/FFS-329 Electrical wiring diagram A101400_ C1/C2/C3 Dimensional drawing FFS1200DimLB eller 112A-21-08?

Assembly drawing w/partslist NA Instruction manual FFS-659 & FFS-665 Data sheet FFS-240

A101400A

DATA SHEETS

Monitors

FFS 1200LB

SINGLE / DUAL FLOW MONITOR

FFS-240rev02

Product subjected to technical changes without prior notice

Fire Fighting Systems AS

Tykkemyr 27

1597 Moss

NORWAY

Tel: +47 69 24 49 90 e-mail: ffs@fifisystems.com www.fifisystems.com

Description The FFS single/dual flow monitors offer a unique combination of high performance in relation to weight and dimensions. The units are extremely robust and require minimal maintenance.

The monitor flow channels are designed using the latest technology in fluid engineering.

In this way low pressure loss is achieved, and the throw characteristics are well within

FI-FI 1 requirements.

The monitors are manufactured and performance tested in Scandinavia in accordance with the highest quality standards.

Material for main castings is nickel-aluminium-bronze with superb strength and corrosion resistance. Stainless steel (AISI 316L) and composites are used for smaller components. Ball bearings for elevation and horizontal movements are made from high grade stainless steel and permanently grease filled. They are sealed from both internal water pressure and atmosphere by O-rings. The monitor is protected by a lightweight

GRP cover, which can easily be removed.

The dual flow mechanism is operated by water pressure. The components are well protected against external damage as integrated parts of the castings.

The vertical and horizontal movements are operated by electrical motors via gearboxes.

All gears are completely sealed from the surroundings, thus eliminating accidental contact. Robust hand wheels made from composites and stainless steel provide manual back-up operation for the monitor movements.

FFS 1200LB

SINGLE / DUAL FLOW MONITOR

FFS-240rev02

Product subjected to technical changes without prior notice

F F S

Dimensions

Technical data 1 bar = 0,1 Mpa = 14,5 psi

Weight (standard execution)

Weight (long barrel execution)

170 kg

180 kg

Nominal capacity

Reduced capacity

Elevation sector

Horizontal sector

Horizontal/elevation operation

Dual flow

Spray deflector

Limit switches

Inlet pressure

Static pressure testing

Power supply

Inlet flange

Materials in internal wetted parts

Monitor cover

Seals

Coating

1200 m³/hour

300 m³/hour

-20° to +80°

300° (Option 360°)

Electrical with manual override

On/off or stepless electrical operation

Remote electrical operation

Easily adjustable

Selected from performance curve

Factory tested at 1.5x max working pressure

220-240V, 380-440V/3 phase/50 or 60 Hz + 24VDC

DN200/PN16 (DIN 2526 Form E)

Stainless steel / bronze /composites

Glass fibre reinforced polyester

Moulded nitrile O-rings

External red colour coating (RAL 3002)

FFS-329

Rev.01

N-1597 MOSS

Fax: +47 69 24 49 95

FI-FI MONITOR THROW CURVE

MODEL: FFS1200/300 LB

SEA WATER FLOW: 1200 and 300 m3/h

HORIZONTAL RANGE AT OPTIMAL WIND CONDITIONS

1200 m3/h

300 m3/h

6 7 8 9 10 11 12 13

Pressure (bar)

T h ro w

L e n g th m

Installation and Maintenance

1597 Moss

Norway

Tel: +47 69 24 49 90

E-mail: ffs@fifisystems.com

Doc no: FFS-659 rev03 Original instructions

Fire Water Monitor

FFS 3600

FFS 2400

FFS 1200

FFS 600

Manufacturer

Tykkemyr 27, 1597 Moss, Norway Phone: +47 69244990

Internet: www.fifisystems.com mailto:ffs@fifisystems.com http://www.fifisystems.com/

Norway

Table of Contents

1. PICTOGRAMS SHOWN ON MONITOR 3

2. IMPORTANT SAFETY INFORMATION AND WARNINGS 4

3. COMPANY PRESENTATION 5

4. DESCRIPTION FFS FIRE WATER MONITOR 6

4.1. Fire water monitor main components (remotely controlled) 7

4.2. Fire water monitor main components (manually controlled) 8

4.3. Identity plate 8

4.4 Noise levels 9

4.5. Work area/sector 9

5. SAFETY PRECAUTIONS 10

5.1. Transport 10

5.2. Installation 10

5.3. Before using monitor 10

5.4. Using monitor 10

5.5. After using monitor 10

5.6. During maintenance 10

6. INSPECTION/ MAINTENANCE 11

7. LIFTING INSTRUCTIONS 12

7.1. Sizes FFS 1200 series and smaller 12

7.2. Sizes FFS 2400 series and larger 13

8. GENERAL INFORMATION FOR INSTALLATION 14

8.1. Mechanical installation 15

8.2. Installation on mobile units 16

8.3. Electrical installation 17

8.3.1. Special conditions (CE, ATEX, etc.) 17

9. ADJUSTING LIMIT-SWITCHES 18

10. START-UP AND COMISSIONING 19

11. TROUBLESHOOTING 20

12. DECLARATION OF CONFORMITY CE/ATEX (IF APPLICABLE) 21

13. APPENDIX 1 – WIRING DIAGRAM CE/ATEX (IF APPLICABLE) 22

14. APPENDIX 2 – ELECTRICAL DATA CE/ATEX (IF APPLICABLE) 23

1. Pictograms shown on monitor

Attention and caution.

Do not stand in front of the monitor while running.

Read and understand user manual.

Bonding point.

Lifting point.

2. Important Safety Information and Warnings

Pay attention to the various important warnings listed below.

Warning! Means potential risk of serious damage to personnel or objects.

Modifications and operation of the monitor performed by unauthorized personnel disclaims FFS responsibility of any personal injury or property damage.

Product development is continuously updating, so products may be subjected to technical changes without prior notice.

More details regarding the various issues are given in the following pages of this manual.

Warning! Make sure the monitor nozzle is pointing in safe direction before starting the system.

Warning! Keep safe distance from the high velocity water jet coming from fire water monitor nozzle.

Warning! Operator must always have clear view of the total fire water monitor working area during operation.

Warning! Make sure power supply is disconnected and water supply is shut off before doing any repair or maintenance work.

Warning! Use proper safety gear when handling fire water monitor.

Warning! It is the customer responsibility that fire water monitor foundation and support are properly engineered.

3. Company presentation

Fire Fighting Systems (FFS) is the leading designer, maker and supplier of complete systems for external fire-fighting in the marine market. FFS provide complete packages comprising all services and equipment exclusive piping required for installations onboard tugs, offshore vessels, fire boats and work boats in accordance with all class societies. FFS also provide complete systems for onshore fire-fighting on tank farms, refineries, industrial plants, jetties etc.

FFS Design uses the latest technology to achieve a lean and green profile to each product as well as the complete system.

Product range comprises pumps with drivers, gearboxes, fire water monitors, foam mixers, deluge systems, remote control systems and all related equipment for a complete package.

For land-based systems FFS can deliver everything from single units to complete systems with performance guarantee based on our in-house engineering. Our wide range of pumps and monitors can deliver from 5000 l/min up to 80.000 l/min of foam or water. A wide range of pump drivers can be delivered for mobile or fixed installations. Complete equipped mobile units or fixed installations can also be delivered.

The monitors are manufactured and tested in our factory in accordance with the highest quality standards.

FFS production is based on the highest standard available. A strongly motivated workforce is trained to secure the quality required for safety systems at sea and onshore in high technology environments under

ISO9001 QA conditions.

FFS Service engineers are available from our global network.

4. Description FFS fire water monitor

This instruction provides information of FFS manufactured fire water monitor models: FFS 600, FFS 1200, FFS 2400 and FFS 3600. The name corresponds to the monitors nominal working capacity, FFS 600 equals 600m3/h, but the capacity may vary depending on nozzle size. All models can be delivered in several different types. The actual unit(s) supplied may not include all features described in this instruction.

FFS monitors offer a unique combination of high performance in relation to weight and dimensions. The units are extremely robust and require minimal maintenance.

The monitor flow channels are designed using the latest technology in fluid engineering. Hence, low pressure loss is achieved, and the throw characteristics are well within marine Fi-Fi 1, 2 and 3 requirements.

Material for main castings is nickel-aluminum-bronze with superb strength and corrosion resistance.

Stainless steel (AISI 316L) and composites are used for smaller components. The monitor is painted with red color coating (RAL 3002). Ball bearings for elevation and horizontal movements are made from high grade stainless steel and permanently grease filled. They are sealed from both internal water pressure and atmosphere by O-rings. The monitor is normally protected by a lightweight cover, which can easily be removed.

The vertical and horizontal movements are operated by electrical motors via gearboxes. All gears are completely sealed from the surroundings, thus eliminating accidental contact. Robust hand wheels made from composites and stainless steel providing manual back-up operation for the monitor movements.

The various models in the FFS monitor range can also be supplied as manually operated monitors.

In these cases, the rotation and elevation of monitor is done by two hand wheels connected to shafts via gear wheels. All additional function can also be operated manually by hand wheel. The gears are self-locking for any horizontal, elevation or additional functions.

Monitors can be equipped with various nozzles:

Standard: Monitors with solid jet for long distance fire-fighting. Nozzle is equipped with a deflector to spread the water jet.

Jet-Screen: Monitors with possibility to either have a hollow jet for long distance fire-fighting, or a wide conical screen that can be used either for self-protection as well as short distance fire-fighting.

Monitors can be equipped as Single, Dual or Stepless Flow type. Dual Flow offers a reduced water flow-setting at typical foam fire-fighting applications. Stepless Flow offer an adjustable flow-setting between reduced and full flow-setting.

For safety precautions, installation and maintenance, see relevant chapters.

4.1. Fire water monitor main components (remotely controlled)

Deflector

Lifting points

Limit-switch rotation Handwheel rotation

Standard nozzle

Gearmotor rotation

Junction box

Safety switch

Id-plate

Inlet flange

Solenoid valve

Dual/Stepless flow

Handwheel elevation

Gearmotor elevation

Limit-switch elevation

Cover

Jet-Screen nozzle

4.2. Fire water monitor main components (manually controlled)

4.3. Identity plate

Handwheel elevation

Handwheel rotation

Handwheel deflector

Lever

Dual flow

Test-pressure at factory

Monitor type

Serial number

Year of manufacture

Working pressure

Monitor model

Monitor weight

Flow

Capacity

Certification number

Optional information

CE/ATEX

marking

(if applicable)

4.4 Noise levels

The noise levels are based on testing according to the European Norm SS-EN ISO 11201.

4.5. Work area/sector

Note!

With manually operated monitors, and remotely operated monitors in manual override, it is possible to rotate the monitor 360°. Be highly aware of any obstacles as people, buildings etc. in the surroundings when in use.

If the monitor is mounted on a platform, mobile unit etc., make sure to add clearance according to laws and regulations outside the monitors work area to prevent risk of crushing.

General dimensions of the monitor are stated in the order specific documentation.

When the fire water monitor is in operation, the water impact area must be carefully observed by the operator. The maximum throw length is stated in the order specific documentation. Note that the water impact force can be very dangerous to personnel, as well as potentially causing serious damage to objects and structures. Many monitors therefore have the option of reducing the direct impact force by activating the actuator to spread the water jet, or activating the screen function to get a wide conical screen. In these cases, the spray pattern will also cover a larger area.

Limit-switches (if used) are provided and needs to be set individually in each specific case, to limit monitors operating sector for remotely operation.

Type FFS 600 FFS 1200 FFS 2400 FFS 3600

Nominal water capacity (m3/h) 600 1200 2400 3600

A-weighted emission sound pressure level at workstation (dBA)

72,5 74,0 72,5 73,5

5. Safety precautions

This instruction must be followed closely. In addition, monitor operation manual, local safety and work protection regulations are to be taken into consideration. Ensure that all operators are properly trained and understand this instruction and operation manual before use to prevent accidents.

Installation instructions and setting of operating sectors must be followed and completed prior to running the fire water monitor in remote control mode.

Be sure that no person come in contact with the water jet under any circumstances.

5.1. Transport

Equipment supplied by FFS shall only be transported if it is prevented, hindered and limited to risks of damage to life, health, property, goods or the environment that may occur. Center of gravity (CG) is marked on the crate. Make sure to handle it correctly. Lifting equipment must be connected to the monitor before being released from the crate to prevent risk of tipping over.

5.2. Installation

The installation must be performed by qualified personnel and must comply with the instructions described in chapter 8.

Only approved and certified lifting equipment to be used for lifting operation. Make sure to follow the lifting instructions described in chapter 7.

5.3. Before using monitor

The system integrator / end user is required to do a risk assessment to inform and prevent any security risks. Make sure that the work area is cleared.

5.4. Using monitor

Keep away from moving parts of the monitor to avoid injuries. Do not stand in front of the monitor before the valve for the water supply is closed (risk of high waterjet/water pressure), serious risk of injury or death may occur.

5.5. After using monitor

Make sure the monitor is ready to be used on short notice and that all functions are in good working order.

Make sure that any observed deviations are reported and corrected. Contact Fire Fighting Systems AS if needed.

5.6. During maintenance

Maintenance must be performed by qualified personnel. Make sure that the power supply is disconnected and that the water supply is shut off before doing any repair or maintenance work.

Symbol for CG

6. Inspection/ Maintenance

If service or maintenance is performed, original spare parts supplied by FFS must be used. Inform FFS monitors serial number when ordering spare parts.

Contact: spareparts@fifisystems.com

If service or maintenance has been performed on the monitor, it must be operated remotely and without water before it can be set in to duty. This is to ensure that the monitor is within its operating sectors.

Make sure that the power supply is disconnected and that the water supply is shut off before doing any

Detailed inspection of the monitor is recommended to be carried out monthly;

Inspect the monitor carefully for improper or unauthorized adjustments etc. or any signs of damages or other deviations. Check for visible damages on coating, repair if needed.

The oil level of the gear-motors is not necessary to check; permanent lubrication is provided.

All bearings are permanently grease filled so re-lubrication is NOT needed.

On manual monitors, it is recommended to re-grease the threaded rod for deflector mechanism on a regular basis.

The monitor must be operated electrically or manually on a regular basis, at least once a month to ensure that the monitor is in good working order and to prevent load damages. All functions of the monitor are required to be operated. Operation check can be done with or without water supply (it is recommended to do it with water supply on). This is carried out by running the monitor to its end stops (6x), Rotation (2x), Elevation (2x), Deflector (2x), all additional functions are also required to be operated.

7. Lifting instructions

Start by removing cover (if applicable) to access the lifting points (remember to mount cover after lifting).

Only use approved and certified lifting gear for performing lifting operation.

When lifting the monitor either from the crate or onto the monitor standpipe, never attach lifting gear to the monitor nozzle. This could cause damage to the unit.

7.1. Sizes FFS 1200 series and smaller

Available equipment: 2 soft slings + lifting device suitable for weights according to id-plate.

A lifting instruction is also permanently attached to the monitor nozzle.

Use soft slings around the monitor body as shown below. If necessary, the hand wheel for nozzle elevation can be rotated to adjust the monitor centre of gravity during lifting.

7.2. Sizes FFS 2400 series and larger

Available equipment: Lifting gear + lifting device suitable for weights according to id-plate.

Attach lifting gear to the lifting points, as shown below.

Use all three lifting points at the same time. If necessary, the hand wheel for elevation can be rotated to adjust the monitor centre of gravity during lifting.

Lifting points x3

8. General information for installation

The monitor foundation and standpipe must be dimensioned in each specific case depending upon the actual installation. Monitors can be installed on mobile units as well as permanent installations. Guidelines for foundation/standpipe design shall be applicable to rules and regulations regarding requirements for stress and deformation calculations of mechanical equipment.

Design and production of foundation/standpipe, must be performed by personnel with relevant engineering competence. When building the foundation/platform/standpipe make sure that there are no objects within the monitors operating area.

The order specific documentation gives input to foundation-calculations by providing information of weights, dimensions, reaction forces and other relevant data of the various monitor sizes. The image below is showing a typical arrangement for monitor foundation/standpipe.

When installing monitor FFS 2400 or FFS 3600 it is recommended that the FFS supplied docking bracket is mounted. The docking bracket is to be mounted outside the monitors normal operating sector.

Standpipe

Valve

Monitor

Reducer

8.1. Mechanical installation

Make sure the customer supplied standpipe has correct dimensions and is designed according to monitor weight and reaction force. The counter-flange surface must be flat and free from burrs and scratches to secure good sealing function. Check flatness of flange before monitor is lifted into position.

If a shut-off valve is installed just before the monitor, the swing-out for the disc must not interfere with the monitor inlet flange. A concentric butterfly-valve is recommended installed min 0,5m before the monitor.

Make sure the complete piping system from pump inlet to fire water monitor is free from any internal debris. This may cause serious damage to monitor internal parts at high water velocities.

The monitor is intended to be mounted on a vertical standpipe. Check to see that the interface flange on the standpipe matches the inlet flange on monitor base.

Place a standard gasket on the standpipe flange and make sure that the correct number of fasteners are available. Make sure that the gasket is in place between the two flanges before the bolts are inserted. Use high quality gasket material suitable for fire water service. The gasket dimensions must be according to pressure class and nominal flange dimension.

Lift the monitor onto the standpipe by use of suitable lifting slings and a crane according to lifting instruction described in chapter 7. Do not detach the lifting equipment before the monitor is fastened securely onto the standpipe.

All data and installations must be verified by the customer to ensure correct and safe installation.

Minimum requirements for flange bolts: Class 8.8.

The flange bolts shall be tightened in steps to avoid tilting of flange and in cross-sequence up to the recommended torque according to bolt class and size.

8.2. Installation on mobile units

When mounting a monitor on a mobile unit, pay special attention to the monitors high reaction force. The reaction force is stated in the order specific documentation.

The monitors FFS 2400 and FFS 3600 are supplied with a docking bracket as part of standard delivery.

The bracket should be mounted to the surrounding structure and will unload the gravity forces generated by the monitor nozzle. This is recommended on mobile units like trucks, trailers, boats etc. since vehicle movements can cause stress to gear wheels carrying the monitor nozzle. This can potentially reduce the lifetime of the gear motors.

The support bracket is delivered with 4 pre-drilled mounting holes.

Example of docking bracket below.

Docking bracket

8.3. Electrical installation

Before installing the monitor, make sure that the sign plate data corresponds to the power supply and operating condition and that the installation complies with the manufactures recommendations.

Install the electrical junction box in centre of horizontal operation sector and at the opposite side of the nozzle allowing the flexible cable to move freely in both directions. Use two of the flange bolts to fasten the bracket.

If limit-switches are to be used, direction of monitor movement must be confirmed. Make sure that monitor rotation to left is connected via left limit switch, rotation to right is connected via right limit switch, elevation upwards is connected via upper limit switch, and elevation downwards via lower limit switch.

Limit-switches use Normally Closed (NC) contacts that break the control circuit when switch is activated.

How to adjust the limit-switches are described in chapter 9.

8.3.1. Special conditions (CE, ATEX, etc.)

All external electrical connections are to be connected according supplied wiring diagram attached as

Appendix 01 and inside cover of the junction box.

Data for the electrical equipment mounted on the monitor is to be found attached as Appendix 02.

The supplier of the control system for the monitor must arrange installation according to local laws and regulations. The monitor is equipped with a safety switch near the junction box. This is to disconnect control system when doing mechanical maintenance or manual operation.

For all other electrical work on the monitor, power supply must be switched off and secured.

Bonding must be provided. Bonding point is located on the monitor inlet flange, marked with a blue decal.

The potential-equalizing connections to the monitor and surrounding installation must be sized with a suitable cross-section area and made in compliance with local laws and regulations.

To make the monitor ATEX-compliant, the limit switches must be connected through EX-barriers in the control system

9. Adjusting limit-switches

If limit-switches are to be used, adjusting the operating sectors must be followed and completed prior to running the monitor.

Remove the monitor cover (if applicable). Unscrew the black lids on the limit-switches, turn by hand.

Inside the limit-switches there are two sensors (micro-switch or inductive switch) together with adjustable cams, one for each direction (left, right, up, down).

The outer cam must be pushed down and rotated into position, and the inner cam must be pulled up and rotated into position. Make sure that cams are firmly in its position after adjustment.

Orient the nozzle in each maximum direction.

Start by setting the relevant cam so the top of the cam is on the opposite side if the sensor. Rotate cam until sensor is activated:

Left: outer sensor, rotate cam clockwise

Right: inner sensor, rotate cam counter clockwise

Up: outer sensor, rotate cam clockwise

Down: inner sensor, rotate cam counter clockwise

Confirm that all directions are properly adjusted by running the monitor remotely. Small adjustments may be necessary on the cams.

Mount lids on limit-switches and monitor cover (if applicable).

Adjustable cams

Outer sensor

Inner sensor

10. Start-up and comissioning

Read operation manual before starting the monitor.

Keep away from moving parts of the monitor to avoid injuries.

1 Remove monitor cover (if applicable).

2 Check that all bolts and screws that have been adjusted or relocated are firmly fixed. Follow the instructions given in this chapter.

3 Check the equipment against material specification and order confirmation to ensure that voltage rating etc. is corresponding to the available power connection. Check also the water capacity and pressure rating.

4 If limit-switches are to be used, check that the settings of operating sectors are corresponding to the safe areas of operation. Study instructions in chapter 9.

5 After adjustment, a new functional test without water is recommended before monitor is tested with water.

6 Run the system according to instructions given in operation manual. Make sure there are no water leakage.

7 Verify that the maximum pressure of the monitor is not exceeded.

8 If foam concentrate has been used, flush the monitor with fresh water afterwards.

11. Troubleshooting

The monitor is made to meet the highest requirements for reliability. If the operations and maintenance instructions are followed properly, malfunction or deviating performance should not be expected. If any trouble is encountered, this guide can be of use.

Observation:

Monitor does not move or moves slowly/unevenly during remote control operation.

1 Check power supply to control circuits.

2 Check if motor protection is tripped.

3 Make sure the monitor is not positioned in any extreme position (limit-switches activated).

4 Check for foreign objects in monitors inlet and main body.

5 Check flange for flatness, and that flange bolts are evenly torqued.

6 Check functionality of electrical control system.

7 Run the monitor in manual operation mode to exclude possibility of mechanical failure.

If none-of the above suggested investigations lead to any conclusion, contact FFS for consultation.

Observation:

Monitor does operate, but outside the pre-set operation sector during remote control operation.

Stop operating the monitor immediately since permanent mechanical damage may occur!

1 This problem may occur if service or repair has been performed and the phase on the terminals on the

3-phase electrical system has been changed. In this case, the directions of rotation for the electrical motor may have changed; up become down and/or left becomes right.

2 Check if the limit-switches are correctly set or if they are damaged.

Operation Manual

1597 Moss

Norway

Tel: +47 69 24 49 90

Doc no: FFS-665 rev02 Original Instructions

Fire Water Monitor

FFS 3600

FFS 2400

FFS 1200

FFS 600

Pictograms shown on monitor

Attention and caution.

Do not stand in front of the monitor while running.

Read and understand user manual.

Bonding point.

Lifting point.

Important Safety Information and Warnings:

Pay attention to the various important warnings listed below.

Warning! Means potential risk of serious damage to personnel or objects.

Modifications and operation of the monitor performed by unauthorized personnel disclaims FFS responsibility of any personal injury or property damage.

More details regarding the various issues are given in the following pages of this manual.

Warning! Make sure the monitor nozzle is pointing in safe direction before starting the system.

Warning! Keep safe distance from the high velocity water jet coming from fire water monitor nozzle.

Warning! Operator must always have clear view of the total fire water monitor working area during operation.

Warning! Make sure power supply is disconnected and water supply is shut off before doing any

Warning! Use proper safety gear when handling fire water monitor.

Warning! It is the customer responsibility that fire water monitor foundation and support are properly engineered.

Operation

How to operate depends on if the monitor is remotely or manually controlled. The general procedure is very much the same, so read the general instruction together with instruction regarding either remotely or manually controlled.

General

Do not stand in front of the monitor before the valve for the water supply is closed (risk of high waterjet/ water pressure).

Control system must be operated in such a way that max. water pressure is not exceeded. That means correct pump speed in relation to opening/closing of valves, numbers of water consumers in use etc.

Installation instructions and setting of operating sectors must be followed and completed prior to running the monitor.

If docking station is used, the monitor needs to be manually operated into its normal working sector before starting.

Monitor start up

1 Orient the nozzle of the monitor in such a direction that the water jet cannot cause injury or damage.

2 Activate the water supply.

3 Fill up the piping system up to the monitor slowly to prevent any water hammering. This can typically be done by having a small by-pass pipe from pump, running the pump at very low speed or having a small valve opening. The water shall be seen flowing out of nozzle before main valve can be opened and/or pump speed increased. Note that water hammer can cause serious damage to the equipment and pose risk to personnel.

4 Orientation of the jet can now easily and accurately be operated.

Monitor shut off

1. De-activate the water supply slowly.

2. Orient the monitor into the desired park position.

3. If risk for subzero weather condition, the nozzle shall be directed downwards below horizontal level to drain the monitor.

After use

Make sure the monitor is ready to be used on short notice, and that all functions are in good working order.

Make sure that any observed deviations are reported and corrected.

Remotely controlled monitor

Make sure that the manual crank handle on the handwheels are folded in before remote operation

Make sure no personnel can be in accidental contact with moving parts when switching between manual and remote fire water monitor control.

The electric remote control can be done from a fixed or remote control panel. For details see separate documentation from the control system supplier.

Manual override mode

The manual override mode serves as a backup possibility of the monitor in case of a power supply failure of the control circuits. This can be used with or without water supply to the monitor.

Activating manual override

1. Make sure power supply is disconnected by using the safety switch located near the junction box.

2. Release the crank handles located inside the hand wheels of the gear-motors; these are spring loaded and must be folded out.

3. The monitor is now ready to be operated manually. To alter the orientations of the monitor, turn the hand wheel accordingly.

4. If dual flow; locate the solenoid valve under the monitor nozzle. To regulate the flow, the valve is equipped with a manual override. Press the grey knob and rotate 90° to inner position.

Deactivating manual override

1. To prepare the monitor for electric remote control, make sure that the monitor is in normal working sector defined by the limit-switches.

2. Crank handles must be folded into the hand wheel in their standby fold in position.

3. Connect the power supply by using the safety switch near the junction box.

4. Activate the monitor control system if that is included in the local procedures.

Manually controlled monitor

The manually operated monitor is operated by hand-wheels and levers.

To move the monitors orientation, turn hand-wheels located at elevation gear and rotation gear. Direction of rotation on hand-wheels versus monitor movement varies from model to model.

If dual flow, the regulation of the flow is operated by a lever on the dual flow valve located under the monitor nozzle. Turn lever right to full flow, downwards to reduced flow, and left to stop in any position between full and reduced.

If deflector, the movement of the deflector is operated by a hand-wheel located at the monitor nozzle. Turn counter-clockwise to engage deflector, and clockwise to disengage deflector.

If Jet-Screen, the alteration between jet- and screen-function is operated by a hand-wheel located at the monitor nozzle. Turn counter-clockwise to engage jet-function, and clockwise to engage screen-function.

A101400A Item 01 Monitor
A101400A Monitor Datasheet
FFS-240 FFS1200LB Single/Dual Flow Monitor Datasheet
FFS-329 Fi-Fi Monitor Throw Curve FFS1200/300LB
FFS1200LB Water Monitor Dimensional Drawing
Installation and Maintenance Instructions - Fire Water Monitor
Table of Contents
1. Pictograms shown on Monitor
2. Important Safety Information and Warnings
3. Company presentation
4. Description FFS Fire water monitor
4.1. Fire water monitor main components (remotely controlled)
4.2. Fire water monitor main components (remotely controlled)
4.3. Identity plate
4.4. Noise levels
4.5. Work area/sector
5. Safety precautions
5.1. Transport
5.2. Installation
5.3. Before using monitor
5.4. Using monitor
5.5. After using monitor
5.6. During maintenance
6. Inspection / Maintenance
7. Lifting instructions
7.1. Sizes FFS 1200 series and smaller
7.2. Sizes FFS 2400 series and larger
8. General information for installation
8.1. Mechanical installation
8.2. Installation on mobile units
8.3. Electrical installation
8.3.1. Special conditions (CE, ATEX, etc.)
9. Adjusting limit-switches
10. Start-up and commissioning
11. Troubleshooting
Operation Manual - Fire Water Monitor
Pictograms shown on monitor
Important Safety Information and Warnings
Operation
General
Monitor start up
Monitor shut off
After use
Remotely controlled monitor
Manual override mode
Activating manual override
Deactivating manual override

Manually controlled monitor