A1-Minimum Salient Characteristics.pdf

PDF 88 KB Posted

Attached to
Backflow Preventer Assemblies
Solicitation number
M0068126Q0096
Issued by

About this file

This document is a Minimum Salient Characteristics specification for backflow-prevention assemblies required by Marine Corps Air Station's Installation, Logistics and Environmental Department to comply with Arizona Department of Environmental Quality (ADEQ) cross-connection-control and backflow-prevention requirements under Arizona Administrative Code R18-4-215.

The contractor shall provide backflow-prevention assemblies meeting four primary requirements: (1) regulatory compliance with ADEQ standards; (2) appropriate protection levels based on hazard assessment, including Reduced Pressure Principle (RP) assemblies for actual or potential health hazards involving chemical, biological-process-water, or contamination hazards; Pressure Vacuum Breaker (PVB) assemblies for irrigation systems without backpressure or chemical injection; and Double Check Valve (DC) assemblies where hazard levels permit; (3) sizing and connections matching existing piping and system flow requirements with specific approved models listed by pipe diameter ranging from ½" to 6", including products from manufacturers Zurn-Wilkins, Apollo, FEBCO, and Watts with designated dimensional types; and (4) corrosion-resistant materials suitable for outdoor installation and potable-water service, with all components contacting potable water meeting applicable safe-drinking-water material requirements. The document provides a comprehensive list of 17 approved assembly configurations with corresponding dimension types referenced in attachments.

View the file

Other files

File Type Posted
D1-M0068126Q0096.pdf PDF
A1-B Backflow Spec sheets.pdf PDF
A1-Series 957RP Watts.pdf PDF
A1-Exhibit A-54 BACKFLOW ORDER.pdf PDF
A1-Series 009RP Watts.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DISTRIBUTION: DoW COMMUNITY ONLY

Minimum Salient Characteristics — Backflow-Prevention Assemblies

Marine Corps Air Station, Installation, Logistics and Environmental Department has a requirement to replace Backflow Preventers to comply with Arizona Department of Environmental Quality (ADEQ) cross-connection-control and backflow-prevention requirements under Arizona Administrative Code R18-4-215.

The contractor shall provide backflow-prevention assemblies that meet the following minimum salient characteristics:

1. Regulatory Compliance: Assemblies shall comply with applicable Arizona Department of Environmental Quality (ADEQ) cross-connection-control and backflow-prevention requirements under Arizona Administrative Code R18-4-215.

2. Required Protection Level: The assembly type shall provide the level of protection required for the identified cross-connection hazard and installation location:

• Reduced Pressure Principle (RP) Assembly: Required where the downstream system presents an actual or potential health hazard, including chemical, biological-process-water, or other contamination hazards.

• Pressure Vacuum Breaker (PVB) Assembly: Permitted only for irrigation systems that cannot create backpressure and do not use chemical injection or chemigation.

• Double Check Valve (DC) Assembly: Permitted only where the assessed hazard level and applicable water-system requirements allow its use.

3. Size and Connections: Assemblies shall be sized to match the existing piping and system flow requirements: [insert pipe diameter, connection type, flow rate, and pressure rating]. The assembly shall be compatible with the existing potable-water distribution system without requiring unplanned adapters or modifications:

• ½” 375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• ¾” 375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• 1” 375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• 1” RPLF4A Apollo, Dimensions Type “B” – see attachment

• 1” 975XLRP Zurn-Wilkins, Dimension Type “C” – see attachment

• 1-1/2”375XLRP Zurn-Wilkins, Dimension Type “A” – see attachment

• 1-1/2”975XLRP Zurn-Wilkins, Dimensions Type “C” – see attachment

• 2”375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• 2”825YRP FEBCO, Dimensions Type “D” – see attachment

• 2”765PVB FEBCO, Dimensions Type “E” – see attachment

• 2”975XLRP Zurn-Wilkins, Dimensions Type “C” – see attachment

DISTRIBUTION: DoW COMMUNITY ONLY

• 2-1/2”009RP Watts, Dimensions Type “F” – see attachment

• 3” 009RP Watts, Dimensions Type “F” – see attachment

• 4” 709DC Watts, Dimensions Type “I” – see attachment

• 4” 957RP Zurn-Wilkins, Dimensions Type “H” – see attachment

• 4” 375ARP Zurn-Wilkins, Dimensions Type “G” – see attachment

• 6” 375XLRP Zurn-Wilkins, Dimensions Type “J” – see attachment

4. Materials and Construction: Assemblies shall be constructed of corrosion-resistant materials suitable for outdoor installation and potable-water service.

Components in contact with potable water shall meet applicable safe-drinking-water material requirements.