A1-Minimum Salient Characteristics.pdf

PDF 88 KB Posted

Attached to
Backflow Preventers
Solicitation number
M00681BackflowPreventers
Issued by

About this file

This document is a specification for minimum salient characteristics of backflow-prevention assemblies required by Marine Corps Air Station's Installation, Logistics and Environmental Department to comply with Arizona Department of Environmental Quality (ADEQ) cross-connection-control and backflow-prevention requirements under Arizona Administrative Code R18-4-215.

The contractor must provide backflow-prevention assemblies that meet four key requirements: (1) regulatory compliance with ADEQ standards; (2) appropriate protection levels based on cross-connection hazard type, including Reduced Pressure Principle (RP) assemblies for health hazards, Pressure Vacuum Breaker (PVB) assemblies for irrigation systems without chemical injection, and Double Check Valve (DC) assemblies where hazard levels permit; (3) proper sizing and connections matching existing piping and flow requirements; and (4) corrosion-resistant materials suitable for outdoor installation and potable-water service, with components meeting safe-drinking-water material requirements. The specification includes 19 specific assembly configurations ranging from ½ inch to 6 inches in diameter, with approved manufacturers including Zurn-Wilkins, Apollo, FEBCO, and Watts, each with designated dimension types (A through J) referenced in attachments.

View the file

Other files

File Type Posted
A1-Series 957RP Watts.pdf PDF
A1-Backflow Spec sheets.pdf PDF
A1-Series 009RP Watts.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DISTRIBUTION: DoW COMMUNITY ONLY

Minimum Salient Characteristics — Backflow-Prevention Assemblies

Marine Corps Air Station, Installation, Logistics and Environmental Department has a requirement to replace Backflow Preventers to comply with Arizona Department of Environmental Quality (ADEQ) cross-connection-control and backflow-prevention requirements under Arizona Administrative Code R18-4-215.

The contractor shall provide backflow-prevention assemblies that meet the following minimum salient characteristics:

1. Regulatory Compliance: Assemblies shall comply with applicable Arizona Department of Environmental Quality (ADEQ) cross-connection-control and backflow-prevention requirements under Arizona Administrative Code R18-4-215.

2. Required Protection Level: The assembly type shall provide the level of protection required for the identified cross-connection hazard and installation location:

• Reduced Pressure Principle (RP) Assembly: Required where the downstream system presents an actual or potential health hazard, including chemical, biological-process-water, or other contamination hazards.

• Pressure Vacuum Breaker (PVB) Assembly: Permitted only for irrigation systems that cannot create backpressure and do not use chemical injection or chemigation.

• Double Check Valve (DC) Assembly: Permitted only where the assessed hazard level and applicable water-system requirements allow its use.

3. Size and Connections: Assemblies shall be sized to match the existing piping and system flow requirements: [insert pipe diameter, connection type, flow rate, and pressure rating]. The assembly shall be compatible with the existing potable-water distribution system without requiring unplanned adapters or modifications:

• ½” 375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• ¾” 375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• 1” 375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• 1” RPLF4A Apollo, Dimensions Type “B” – see attachment

• 1” 975XLRP Zurn-Wilkins, Dimension Type “C” – see attachment

• 1-1/2”375XLRP Zurn-Wilkins, Dimension Type “A” – see attachment

• 1-1/2”975XLRP Zurn-Wilkins, Dimensions Type “C” – see attachment

• 2”375XLRP Zurn-Wilkins, Dimensions Type “A” – see attachment

• 2”825YRP FEBCO, Dimensions Type “D” – see attachment

• 2”765PVB FEBCO, Dimensions Type “E” – see attachment

• 2”975XLRP Zurn-Wilkins, Dimensions Type “C” – see attachment

DISTRIBUTION: DoW COMMUNITY ONLY

• 2-1/2”009RP Watts, Dimensions Type “F” – see attachment

• 3” 009RP Watts, Dimensions Type “F” – see attachment

• 4” 709DC Watts, Dimensions Type “I” – see attachment

• 4” 957RP Zurn-Wilkins, Dimensions Type “H” – see attachment

• 4” 375ARP Zurn-Wilkins, Dimensions Type “G” – see attachment

• 6” 375XLRP Zurn-Wilkins, Dimensions Type “J” – see attachment

4. Materials and Construction: Assemblies shall be constructed of corrosion-resistant materials suitable for outdoor installation and potable-water service.

Components in contact with potable water shall meet applicable safe-drinking-water material requirements.

File details come from the government source that posted it. Updated .