A06_Pages_from_SAHO_Construction_Drawings.pdf

PDF 3 MB Posted

Attached to
GATE-TROUBLESHOOT & REPAIR HVAC-BLDG 65
Solicitation number
140P4525Q0047
Issued by

About this file

These mechanical drawings detail the HVAC renovation for Building 65 at Gateway National Recreation Area's Sandy Hook Unit. The comprehensive set includes mechanical plans, demolition plans, equipment schedules, and system details for a complete mechanical systems upgrade. Key elements include installing multiple Mitsubishi air conditioning units (AC-1 through AC-18), a heat pump (HP-2), an energy recovery ventilator (ERV-3), electric baseboard heaters (EBB-3, EBB-4), and an electric unit heater (EUH-1).

The drawings specify a variable refrigerant flow (VRF) system with precise installation requirements, including routing refrigerant lines, mounting units at specific heights, and implementing 7-day programmable thermostats with occupancy override. The control sequence details setpoints for occupied and unoccupied hours (cooling at 75°F/80°F, heating at 70°F/65°F), and includes provisions for simultaneous heating and cooling across multiple zones. The project involves careful coordination of ductwork, electrical connections, and integration with existing building structures, with a focus on energy efficiency and precise environmental control for different spaces within Building 65.

View the file

Other files

File Type Posted
Sol_140P4525Q0047_Amd_0001.pdf PDF
B03_NJ20250037.pdf PDF
B08_References_Worksheet_(1)_(1).pdf PDF
A04_2025-03_SOW_Heat_pump_TS_and_Repair.docx DOCX document
A06_Photos_of_HVAC_systems_at_B65.docx DOCX document
B08_Price_Schedule_GATE_Troubleshoot_B65.docx DOCX document
Sol_140P4525Q0047.pdf PDF
A04_Spec_Sheets.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F/S

S

F

A

NOTE

NECESSARILY USED.

ALL SYMBOLS AND ABBREVIATIONS SHOWN ARE NOT

VENTILATION AND AIR CONDITIONING SYMBOLSABBREVIATIONS

12x20

SECOND FIGURE, SIDE NOT SHOWN)

ALL DUCTS DIMENSIONS SHALL BE

SUPPLY DUCT UP

RETURN DUCT UP

SUPPLY DUCT DOWN

RETURN DUCT DOWN

AIR FLOW

AIR FLOW

R

D

TRANSITIONS

MANUAL VOLUME DAMPER

FLEXIBLE CONNECTION

SUPPLY OR RETURN

RECTANGULAR DUCT ELBOW WITH

TURNING VANES

SHOWN IN INCHES.

DUCT (FIRST FIGURE, SIDE SHOWN AND

RECTANGULAR TO ROUND TRANSITION

STANDARD RECTANGULAR BRANCH FOR

INCLINED DROP (D), ARROW IN DIRECTION OF

INCLINED RISE (R), ARROW IN DIRECTION OF

T

H

D

THERMOSTAT

HUMIDISTAT

DUCT MOUNTED SMOKE DETECTOR

ACCESS PANEL

FIRE DAMPER

SMOKE DAMPER

COMBINATION FIRE/SMOKE DAMPER

EXHAUST DUCT DOWN

EXHAUST DUCT UP

M MOTORIZED DAMPER

RL REFRIGERANT LIQUID LINE

RS REFRIGERANT SUCTION LINE

TEMPERATURE AND PRESSURE

TYPICAL

URINAL

VENT, VOLTS

T&P

TYP.

U

V

SS SINK

SL SEA LEVEL

MSB MOP SERVICE BASIN

FT FEET

FPM FEET PER MINUTE

FAHRENHEITF

EWT ENTERING WATER TEMP

AVG AVERAGE

WET BULBWB

NORMALLY OPENNO

NORMALLY CLOSEDNC

DRY BULBDB

LEAVING AIR TEMPERATURELAT

ENTERING AIR TEMPERATUREEAT

W WATT, WASTE

REVOLUTIONS PER MINUTERPM

KILOWATTKW

GALLONS PER MINUTEGPM

CFM

BTUH

VOLUME DAMPERVD

(E)

EA

EXISTING

EXHAUST AIR

CUBIC FEET PER MINUTE

FULL LOAD AMPSFLA

NOT IN CONTRACTNIC

DRAIND

VENT THROUGH ROOF

PRV PRESSURE REDUCING VALVE

INSIDE DIAMETERID

AAV AUTOMATIC AIR VENT

AIR SEPARATORAS

SINKS

DRINKING FOUNTAINDF

WATER HAMMER ARRESTORWHA

WCO

WC

W/O W/

VTR

SA

WALL CLEANOUT

WATER CLOSET, WATER COLUMN

WITHOUT

WITH

SUPPLY AIR

OAT

OA

M

L

IN

HW

HB

GCO

FD

FCO

OUTSIDE AIR TEMPERATURE

OUTSIDE AIR

MOTORIZED DAMPER

LAVATORY

INCHES

DOMESTIC HOT WATER

HOSE BIBB

GRADE CLEANOUT

FLOOR DRAIN, FIRE DAMPER

FLOOR CLEANOUT

DN

CW

CO

C.I.

BDD

AUX.

AP

AFF

AD

DOWN

COLD WATER

CLEANOUT

CAST IRON

BACKDRAFT DAMPER

AUXILIARY

ACCESS PANEL

ABOVE FINISHED FLOOR

ACCESS DOOR

SHEET WHERE SHOWN

DETAIL IDENTIFIER

SHEET WHERE SHOWN

SECTION LETTER

NOT APPLICABLENA

DOMESTIC HOT WATER RECIRCHWC

F/S FIRE SMOKE DAMPER

SP STATIC PRESSURE

HEAT EXCHANGERHX

RPBP REDUCED PRESSURE BACKFLOW PREVENTER

FS FLOW SWITCH

DOUBLE CHECK BACKFLOW PREVENTERDCBP

ELECTRICAL CONTRACTORE.C.

G.C. GENERAL CONTRACTOR

M.C. MECHANICAL CONTRACTOR

UNINTERRUPTIBLE POWER SUPPLYUPS

BRITISH THERMAL UNIT PER HOUR

M1

EXTERNAL STATIC PRESSUREESP

REFRIGERANT LIQUIDRL

REFRIGERANT SUCTIONRS

EFFICIENCYEFF

ENERGY EFFICIENCY RATIOEER

SEASONAL ENERGY EFFICIENCY RATIOSEER

HEATING SEASONAL PERFORMANCE FACTORHSPF

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:3

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

MECHANICAL COVER

SHEET

06.30.2017 225

M0.00

MECHANICAL NOTES

I. GENERAL

A. ALL WORK SHALL BE IN ACCORDANCE WITH SMACNA STANDARDS AND SPECIFICATIONS, AND LOCAL AUTHORITY HAVING JURISDICTION.

B. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS

DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.

C. COORDINATE SPACE REQUIREMENTS, SUPPORTS, AND INSTALLATION OF MECHANICAL WORK, WHICH ARE INDICATED DIAGRAMMATICALLY ON THE DRAWINGS. FOLLOW ROUTING SHOWN FOR PIPES AND DUCTS AS CLOSELY AS PRACTICABLE; PLACE RUNS PARALLEL WITH LINES OF BUILDING. UTILIZE SPACES EFFICIENTLY TO MAXIMIZE

ACCESSIBILITY FOR OTHER INSTALLATIONS, FOR MAINTENANCE, AND FOR REPAIRS.

D. COMPLY WITH MANUFACTURER’S INSTRUCTIONS INCLUDING EACH STEP IN SEQUENCE. SHOULD MANUFACTURERS’ INSTRUCTIONS CONFLICT WITH THE DRAWINGS

REQUEST CLARIFICATION FROM THE ENGINEER BEFORE PROCEEDING.

E. DUCT SIZES ARE INSIDE DIMENSION.

F. CONTRACTOR SHALL REVIEW THESE DOCUMENTS CAREFULLY. CONTRACTOR SHALL CONTACT CONTRACTING OFFICER, FOR RESOLUTION OF ANY DISCREPANCIES, OMISSIONS, OR CLARIFICATIONS, BEFORE BID DATE. IN THE EVENT THAT AN INTERPRETATION OF BID DOCUMENTS IS NECESSARY AFTER THE BID DATE, THE DECISION

OF CONTRACTING OFFICER SHALL BE FINAL AND BINDING.

G. PRODUCT DELIVERY, STORAGE, AND HANDLING: PROVIDE EQUIPMENT AND PERSONNEL TO HANDLE PRODUCTS BY METHODS TO PREVENT DAMAGE. PROMPTLY INSPECT SHIPMENTS TO ENSURE THAT PRODUCTS ARE UNDAMAGED. STORE AND PROTECT PRODUCTS IN ACCORDANCE WITH MANUFACTURERS’ INSTRUCTIONS.

H. THE CONTRACTOR IS RESPONSIBLE FOR THE COSTS OF ALL CHANGE ORDERS, WHICH THE OWNER AND ENGINEER HAVE NOT APPROVED IN WRITING PRIOR TO THE

EXECUTION OF THE ASSOCIATED WORK.

I. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES AND NOTIFY CONTRACTING OFFICER IF ANY CONFLICTS OCCUR.

J. THERMOSTAT LOCATIONS AND HEIGHTS TO BE COORDINATED WITH BUILDING MANAGEMENT, VERIFIED BY THE ENGINEER. HEATING THERMOSTATS MUST REMAIN OPERATIONAL AT ALL TIMES. IF REQUIRED FOR BETTER PROTECTION, THERMOSTATS MAY BE TEMPORARILY MOUNTED IN THE CEILING PLENUM.

K. PROVIDE ALL THERMOSTATS ON EXTERIOR WALLS WITH INSULATED BASES.

L. PROVIDE VOLUME DAMPERS AT ALL DIFFUSER TAKEOFFS.

M. ALL TAKEOFFS, RUNOUTS, AND FLEX DUCTWORK TO DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER INLET UNLESS OTHERWISE NOTED.

N. THERMOSTAT CONTROL LINES SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED 4’ 0".

O. PROVIDE EXTERNAL INSULATION ON ALL NEW CONCEALED RIGID ROUND DUCTWORK.

P. PROVIDE INTERNAL INSULATION ON ALL NEW EXPOSED RIGID ROUND DUCT WORK.

Q. PROVIDE ACCESS DOORS IN DUCTWORK AS REQUIRED FOR ACCESS TO FIRE DAMPERS, FIRE/SMOKE DAMPERS, OR ANY OTHER MECHANICAL EQUIPMENT REQUIRING

MAINTENANCE OF SERVICE.

3.1

3.3 3.4

3.5 3.6

3.7

3.9

3.A

3.B

3.C

3.D

3.2

3.8

3.1 3.3 3.4

3.5 3.6

3.7

3.9

3.A

3.B

3.C

3.D

3.2

3.8

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:3

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 MECHANICAL

DEMO PLANS

06.30.2017 229

M3.11

SCALE A

M3.11

BUILDING #65 FIRST FLOOR MECHANICAL DEMO PLAN1

SCALE A

4’ 0’ 4’

SCALE OF FEET

8’ 16’

KEY NOTES:

EXISTING BOILER AND ASSOCIATED PIPING AND CONTROLS WITHIN LEAN−TO SHALL BE REMOVED. RE: HAZMAT

REPORT.

EXISTING STEAM RADIANT HEATER TO BE DECOMMISSIONED. HEATER TO BE CLEANED AND PAINTED WITH VERTICAL PIPING STILL ATTACHED. VERTICAL PIPING TO BE CLEANED, PAINTED, AND CAPPED AT ENDS.

RELOCATE HEATER AS REQUIRED. RE: ARCHITECTURAL PLANS FOR NEW HEATER LOCATIONS.

DEMOLISH ALL HORIZONTAL RUNS OF STEAM PIPING SERVING EXISTING STEAM RADIATORS IN FIRST FLOOR

SPACE AND CRAWL SPACE. PROPERLY DISPOSE OF ALL MATERIALS OFF SITE.

DEMOLISH EXISTING EXHAUST DUCT AND PROPERLY DISPOSE OF ALL MATERIALS OFF SITE.

NO DEMO WORK ON THIS FLOOR.

SCALE A

M3.11

BUILDING #65 SECOND FLOOR MECHANICAL DEMO PLAN2

GENERAL NOTES:

REMOVE ALL EXISTING MECHANICAL EQUIPMENT SERVING BUILDING AND

DISPOSE OF PROPERLY OFF SITE (UNLESS OTHERWISE NOTED).

8"x8"8"x8"

3.1

3.3 3.4

3.5 3.6

3.7

3.9

3.A

3.B

3.C

3.D

3.2

3.8

8"x8"

UNISEX

OFFICE

SERVER

OFFICE

SHED

WORK ROOM

UNISEX

MECH/JANITOR

FILE STORAGE

OPEN

OFFICE/RECEPTION

CONFERENCE

ROOM

AC−1

AC−3

AC−4

AC−2

AC−17

AC−5

EBB−3

EBB−4

EUH−1

AC−6

AC−7

AC−18

AC−8

HP−2

BC−1

BC−2

8"x8"

8" Ø

140 CFM

C

8" x 8"

100 CFM

C

8" x 8"

100 CFM

C

8" x 8"

100 CFM

C

3.1 3.3 3.4

3.5 3.6

3.7

3.9

3.A

3.B

3.C

3.D

3.2

3.8

OFFICE

STORAGE

STORAGE

OFFICE

CLOSET

324A

CLOSET

321A

CLOSET

322A

CLOSET

323A

MECHANICAL

OFFICE

OFFICE

OPEN OFFICE

"x

"x

AC−9

AC−10

AC−15

AC−16

AC−11

AC−12

AC−13

AC−14

ERV−3

M7.30

18" x 6"

400 CFM

A

18" x 6"

400 CFM

B

(TYP. OF 4)

(TYP. OF 4)

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:4

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 MECHANICAL

PLANS

06.30.2017 230

M3.21

SCALE A

M3.21

BUILDING #65 FIRST FLOOR MECHANICAL PLAN1

SCALE A

4’ 0’ 4’

SCALE OF FEET

8’ 16’

KEY NOTES:

PROVIDE NEW AIR CONDITIONING UNIT, AC−1. MOUNT HIGH ON WALL.

PROVIDE NEW AIR CONDITIONING UNIT, AC−2. MOUNT HIGH ON WALL.

PROVIDE NEW AIR CONDITIONING UNIT, AC−3. MOUNT HIGH ON WALL.

PROVIDE NEW AIR CONDITIONING UNIT, AC−4. MOUNT HIGH ON WALL.

PROVIDE NEW ELECTRIC UNIT HEATER, EUH−1. PROVIDE WITH REMOTE HEATING ONLY THERMOSTAT.

PROVIDE NEW AIR CONDITIONING UNIT, AC−5. MOUNT HIGH ON WALL.

STACK REFRIGERANT LINES AND DUCT WORK IN THIS ROOM. COORDINATE ROUTING AROUND THE TOP

OF SERVER RACKS..

PROVIDE NEW ELECTRIC BASEBOARD HEATER, EBB−3.

PROVIDE NEW ELECTRIC BASEBOARD HEATER, EBB−4.

PROVIDE NEW AIR CONDITIONING UNIT, AC−6. MOUNT HIGH ON WALL.

PROVIDE NEW AIR CONDITIONING UNIT, AC−17. MOUNT HIGH ON WALL.

PROVIDE NEW AIR CONDITIONING UNIT, AC−7. MOUNT HIGH ON WALL.

SCALE A

M3.21

BUILDING #65 SECOND FLOOR MECHANICAL PLAN2

GENERAL NOTES:

RE: VRF FLOW DIAGRAM ON SHEET M7.40 FOR REFRIGERANT PIPING SIZES.

CONTRACTOR TO INSTALL HARD 90 DEG ELBOWS ON ALL REFRIGERANT PIPING AT FLOOR PENETRATIONS.

ROUTE ALL REFRIGERANT LINES AND DUCT WORK ON FIRST FLOOR RUNNING NORTH TO SOUTH TIGHT TO STRUCTURE. ROUTE ALL REFRIGERANT LINES AND DUCT WORK ON FIRST FLOOR RUNNING EAST TO WEST IN BETWEEN WOOD STRUCTURE.

PROVIDE SCREEN ON ALL OA ENDS AT UNITS.

MOUNT ALL WALL MOUNTED AC UNITS 2" BELOW CEILING.

KEY NOTES:

PROVIDE NEW AIR CONDITIONING UNIT, AC−8. MOUNT HIGH ON WALL. PROVIDE UNIT WITH DIFFERENT OCCUPIED COOLING SETPOINT (72 DEG. F), TO PROVIDE TWO STAGES OF COOLING IN SERVER ROOM.

PROVIDE NEW OUTDOOR HEAT PUMP, HP−2. ROUTE RL AND RS LINES TO BC CONTROLLER IN

MECHANICAL ROOM. ROUTE LINES DOWN UNDER PLATFORM AND INTO BUILDING THROUGH CRAWL

SPACE. COME UP THROUGH FLOOR TO BRANCH CONTROLLER IN MECHANICAL ROOM. RE: DETAIL 7 ON

SHEET M7.20.

PROVIDE NEW BRANCH CIRCUIT CONTROLLER, BC−1, IN MECHANICAL ROOM.

PROVIDE NEW AIR CONDITIONING UNIT, AC−9. RE: DETAIL 5 ON SHEET M7.20 FOR MOUNTING. PROVIDE

WITH REFRIGERANT LIQUID AND SUCTION LINES, AND 4" OA DUCT FROM BELOW.

PROVIDE NEW AIR CONDITIONING UNIT, AC−10. RE: DETAIL 5 ON SHEET M7.20 FOR MOUNTING. PROVIDE

WITH REFRIGERANT LIQUID AND SUCTION LINES, AND 4" OA DUCT FROM BELOW.

PROVIDE NEW AIR CONDITIONING UNIT, AC−15. RE: DETAIL 5 ON SHEET M7.20 FOR MOUNTING. PROVIDE

WITH REFRIGERANT LIQUID AND SUCTION LINES, AND 4" OA DUCT FROM BELOW.

PROVIDE NEW AIR CONDITIONING UNIT, AC−16. RE: DETAIL 5 ON SHEET M7.20 FOR MOUNTING. PROVIDE

WITH REFRIGERANT LIQUID AND SUCTION LINES, AND 4" OA DUCT FROM BELOW.

PROVIDE NEW AIR CONDITIONING UNIT, AC−11. MOUNT ON FLOOR. PROVIDE WITH REFRIGERANT LIQUID

AND SUCTION LINES, AND 3" OA DUCT FROM BELOW.

PROVIDE NEW AIR CONDITIONING UNIT, AC−12. MOUNT ON FLOOR. PROVIDE WITH REFRIGERANT LIQUID

AND SUCTION LINES, AND 3" OA DUCT FROM BELOW.

PROVIDE NEW AIR CONDITIONING UNIT, AC−13. MOUNT ON FLOOR. PROVIDE WITH REFRIGERANT LIQUID

AND SUCTION LINES, AND 3" OA DUCT FROM BELOW.

PROVIDE NEW AIR CONDITIONING UNIT, AC−14. MOUNT ON FLOOR. PROVIDE WITH REFRIGERANT LIQUID

AND SUCTION LINES, AND 3" OA DUCT FROM BELOW.

PROVIDE NEW SUB BRANCH CONTROLLER, BC−2, IN MECHANICAL ROOM.

KEY NOTES:

PROVIDE NEW ENERGY RECOVERY VENTILATOR, ERV−3. RE: DETAIL 2 ON SHEET M7.30 FOR ELEVATION.

ROUTE DUCT IN BETWEEN STRUCTURE TIGHT TO BOTTOM OF ROOF DECK UP TO EXISTING VENT. RE: DETAIL 4 ON SHEET M7.20.

PROVIDE NEW AIR CONDITIONING UNIT, AC−18. MOUNT HIGH ON WALL.

3" OA UP TO AC UNIT ON SECOND FLOOR.

4" OA UP TO AC UNIT ON SECOND FLOOR.

REFRIGERANT LIQUID AND SUCTION LINES UP TO AC UNIT ON SECOND FLOOR.

3.1 3.3 3.4 3.5

3.6 3.7

3.9

3.A

3.B

3.C

3.D

3.2

3.8

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:5

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 ROOF

MECHANICAL PLAN

06.30.2017 231

M3.22

SCALE A

M3.22

BUILDING #65 ROOF MECHANICAL PLAN1

SCALE A

4’ 0’ 4’

SCALE OF FEET

8’ 16’

KEY NOTES:

EXISTING ATTIC VENT TO REMAIN AND BE USED FOR OA

AND EA FOR ERV. RE: DETAIL 4 ON SHEET M7.20 FOR

DUCTING DETAIL.

BUILDING 65 INDOOR AIR CONDITIONING UNIT SCHEDULE

TAG

AC-1

AC-2

AC-3

AC-4

AC-5

AC-6

AC-7

AC-8

AC-9

AC-10

AC-11

AC-12

AC-13

AC-14

AC-15

AC-16

AC-17

AC-18

REMARKS:

1.

2.

NOTES:

1.

2.

3.

SERVING

OFFICE 310

OFFICE307

CONFERENCE 309

CONFERENCE 309

OPEN OFFICE 301

FILE STORAGE 303

WORK ROOM 302

STORAGE 308

OPEN OFFICE 320

OPEN OFFICE 320

OFFICE 323

OFFICE 324

OFFICE 322

OFFICE 321

OPEN OFFICE 320

OPEN OFFICE 320

OPEN OFFICE 301

STORAGE 308

7-DAY PROGRAMMABLE THERMOSTAT.

DIRECTIONAL DISCHARGE AIR GRILLE.

NOMINAL COOLING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 80/67°F (DB/WB), OUTDOOR OF 95°F (DB).

NOMINAL HEATING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 70°F (DB), OUTDOOR OF 43°F (WB).

SEE OUTDOOR UNIT SCHEDULE FOR OUTDOOR AMBIENT CONDITIONS, CONNECTED CAPACITY, AND OTHER FACTORS ASSOCIATED WITH CORRECTED CAPACITIES.

MANUFACTURER

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MITSUBISHI

MODEL

PKFY-P08NHMU-E2

PKFY-P24NKMU-E2.TH

PKFY-P08NHMU-E2

PKFY-P08NHMU-E2

PKFY-P12NHMU-E2

PKFY-P12NHMU-E2

PKFY-P15NHMU-E2

PKFY-P24NKMU-E2.TH

PVFY-P12NAMU-E

PVFY-P12NAMU-E

PFFY-P06NEMU-E

PFFY-P06NEMU-E

PFFY-P08NEMU-E

PFFY-P08NEMU-E

PVFY-P12NAMU-E

PVFY-P12NAMU-E

PKFY-P12NHMU-E2

PKFY-P24NKMU-E2.TH

TYPE

WALL MOUNTED

WALL MOUNTED

WALL MOUNTED

WALL MOUNTED

WALL MOUNTED

WALL MOUNTED

WALL MOUNTED

WALL MOUNTED

VERTICAL TYPE

VERTICAL TYPE

EXPOSED FLOOR STANDING

EXPOSED FLOOR STANDING

EXPOSED FLOOR STANDING

EXPOSED FLOOR STANDING

VERTICAL TYPE

VERTICAL TYPE

WALL MOUNTED

WALL MOUNTED

COOL EAT/DB

COOL EAT/WB

TOTAL BTUH

6,605.7

19,817.2

6,605.7

6,605.7

9,908.6

9,908.6

12,385.7

19,817.2

9,908.6

9,908.6

4,954.3

4,954.3

6,605.7

6,605.7

9,908.6

9,908.6

9,908.6

19,817.2

HEAT EAT/DB

TOTAL BTUH

5,619.5

16,858.4

5,619.5

5,619.5

8,429.2

8,429.2

10,614.6

16,858.4

8,429.2

8,429.2

4,183.4

4,183.4

5,619.5

5,619.5

8,429.2

8,429.2

8,429.2

16,858.4

VOLTAGE

PHASE

MCA

0.38

0.63

0.38

0.38

0.38

0.38

0.38

0.63

0.86

0.86

0.32

0.32

0.32

0.32

0.86

0.86

0.38

0.63

MOCP

REMARKS:

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

BUILDING 65 HEAT PUMP CONDENSING UNIT

TAG

HP-2

REMARKS:

1.

2.

3.

4.

5.

6.

MFG

MITSUBISHI ELECTRIC

PROVIDE WITH HAIL GUARDS.

HP IS (2) UNITS TWINNED TOGETHER. EACH UNIT WILL REQUIRE A SEPARATE ELECTRICAL CONNECTION WITH THE GIVEN ELECTRICAL DATA.

PROVIDE WITH TWINNING KIT.

PROVIDE WITH LOW AMBIENT KIT.

PROVIDE WITH COATING FOR CORROSION PROTECTION FROM SEA COAST CLIMATE.

PROVIDE WITH HEAT RECOVERY FOR SIMULTANEOUS HEATING AND COOLING.

MODEL

PURY-P192TSLMU-A-BS

EER

12.1

COOLING

BTUH

NOM.

192000

HEATING

BTUH

NOM.

215,000

OPERATING TEMP RANGE

COOLING

(DEG F)

23-126

HEATING

(DEG F)

-13-60

ELECTRICAL

MCA

TOTAL

MOP

VOLT

PH

REMARKS

1,2,3,4,5,6

BUILDING 65 ENERGY RECOVERY VENTILATION UNIT SCHEDULE

TAG

ERV-3

REMARKS:

1.

2.

MFG

RENEWAIRE

PROVIDE WITH FACTORY MOUNTED FILTER ALARMS.

PROVIDE WITH BACKDRAFT DAMPERS.

MODEL#

HE1XINV

SA (CFM)

EA (CFM)

SUPPLY FAN / EXHAUST FAN

ESP (IN W.G)

0.4

OA DB

3.

4.

OA WB

MECHANICAL CONTRACTOR TO PROVIDE WITH 7-DAY PRGRAMMABLE TIMECLOCK.

INTERLOCK WITH FIRE ALARM CONTROL PANEL FOR SHUTDOWN IN CASE OF FIRE. RE: ELEC PLANS.

SUMMER

RA DB

RA WB

62.6

SA DB

79.3

SA WB

62.8

OA DB

OA WB

-2

WINTER

RA DB

RA WB

54.4

SA DB

50.1

SA WB

41.0

V/PH

208/3

ELECTRICAL

MCA

5.2

MOCP

REMARKS

1,2,3,4

BUILDING 65 VRF BRANCH CONTROLLER SCHEDULE

TAG

BC-1

BC-2

REMARKS:

SERVICE

MAIN BRANCH CONTROLLER

SUB BRANCH CONTROLLER

MANUFACTURER

MITSUBISHI

MITSUBISHI

MODEL

CMB-P1013NU-GA1

CMB-P108NU-GB1

# OF BRANCHES

WEIGHT (LBS)

MCA

1.08

0.64

VOLTAGE

PHASE

REMARKS:

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:2

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 MECHANICAL

SCHEDULES

06.30.2017 236

M6.30

BUILDING 65 ELECTRIC HEAT SCHEDULE

TAG

EUH-1

EBB-3

EBB-4

REMARKS:

1.

2.

MANUFACTURER

CHROMALOX

BERKO

BERKO

PROVIDE WITH INTEGRAL TAMPERPROOF THERMOSTAT SET AT 70 DEG F.

PROVIDE WITH INTEGRAL ELECTICAL DISCONNECT

MODEL#

LUH-04

BKOC2515W

BKOC2515W

LENGTH

5'-0"

5'-0"

WATTS

VOLTAGE

AMPS

11.2

10.4

10.4

ELEC. PH

REMARKS

1,2

1,2

1,2

GRILLES, REGISTERS & DIFFUSERS

TAG

A

B

C

REMARKS:

1.

2.

MANUFACTURER

PRICE

PRICE

PRICE

PROVIDE WITH GYP BOARD MOUNTING KIT WHERE REQUIRED.

CONFIRM COLOR AND FINISH WITH ARCHITECT PRIOR TO ORDERING.

MODEL NUMBER

SERVICE

SUPPLY

RETURN

EXHAUST

FACE SIZE

18x6

18x6

12x12

MATERIAL

STEEL

STEEL

STEEL

REMARKS:

1,2

1,2

1,2

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:2

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 MECHANICAL

SCHEDULES

06.30.2017 237

M6.40

SCALE: NTS

EXHAUST/TRANSFER FAN DETAIL2

M7.20

SCALE: NTS

DUCT TO ATTIC VENT DETAIL4

M7.20

SCALE: NTS

CONCEALED FLOOR MOUNTED AC UNIT DETAIL5

M7.20

110 VAC SUPPLY CABLE

(PROVIDED)

POWER DISCONNECT

CABLE

(PROVIDED)AIRFLOW

RANGE HOOD

(PROVIDED)

CABINET

SOFFIT

PLENUM READY

SUPPLY CABLE TO

FAN (PROVIDED)

INLINE DUCT

FAN

(PROVIDED)

ROOF CAP

(BY OTHERS)

10" DUCTWORK

7" TO 10"

TRANSITION

SCALE: NTS

RANGE HOOD VENT DETAIL3

M7.20

CONNECT CUSTOM SHEET METAL BOX

TO EXISTING ATTIC VENT. SEAL OUTER

EDGES AS TIGHT AS POSSIBLE. WOOD

STRUCTURE DIRECTLY BELOW

EXISTING VENT TO REMAIN.

PROVIDE BDD

MOUNT FAN FROM

& VIBRATION ISOLATION

WITH METAL STRAPS

STRUCTURE ABOVE

CONNECTION

FLEXIBLE

CONNECTION

FLEXIBLE

SCALE: NTS

AUTO SHOP AHU DETAIL1

M7.20

AHU−1

CUSTOM UNISTRUT

STAND, UNIT SHALL BE

1’−0" ABOVE CRITICAL

EQUIPMENT LEVEL MIN.

FLEXIBLE DUCT

CONNECTION (TYP.)

FLOOR

AC UNIT

CUSTOM UNISTRUT

STAND, UNIT SHALL BE

1’−0" ABOVE FINISHED

FLOOR

FLEXIBLE

DUCT

CONNECTION

(TYP.)

FLOOR

W A L L

WALL

GRILLE LOW

ON WALL

FOR

RETURN AIR

WALL

GRILLE HIGH

ON WALL

FOR SUPPLY

AIR

OA DUCT FROM BELOW STUBBED UP THRU

FLOOR TO FEED INTO UNITS RETURN AIR

ELBOW WITH

TURNING

VANES

SCALE: NTS

BUILDING #49 SPLIT SYSTEM HEAT PUMP PIPING DETAIL6

M7.20

FILTER DRYER

HEAT PUMP

HP−1

CONDENSING UNIT

SOLENOID VALVE SIGHT GLASS

CHARGING VALVE

LIQUID LINE

EXPANSION VALVE

AHU-1F

E X T E R

IO

R

IN

T E R

IO

R ROUTE HIGH INSIDE OF BUILDING

TO MECHANICAL ROOM

SCALE: NTS

BUILDING #65 SPLIT SYSTEM HEAT PUMP PIPING DETAIL7

M7.20

FILTER DRYER

HEAT PUMP

HP−2

CONDENSING UNIT

SOLENOID VALVE

SIGHT GLASS

CHARGING VALVE

LIQUID LINE

EXPANSION VALVE

BC-1

AND 2

F

E X T E R

IO

R

IN

T E R

IO

R

ROUTE HIGH INSIDE OF BUILDING

TO MECHANICAL ROOM

CRAWLSPACE

DUCT TO ERV

CONNECT DUCT FROM

ERV TO CUSTOM SHEET

METAL BOX.

ROUTE DUCT TIGHT TO BOTTOM

OF ROOF DECK IN BETWEEN

WOOD STRUCTURE.

GYP. CEILING

WOOD STRUCTURE

WOOD STRUCTURE

GYP. CEILING

WOOD STRUCTURE

DUCT TO ERV

CONNECT DUCT FROM

ERV TO CUSTOM SHEET

METAL BOX.

EXISTING ATTIC VENT

ROUTE DUCT TIGHT TO

BOTTOM OF ROOF DECK

IN BETWEEN WOOD

STRUCTURE.

CONNECT CUSTOM SHEET METAL BOX TO

EXISTING ATTIC VENT. SEAL OUTER

EDGES AS TIGHT AS POSSIBLE. WOOD

STRUCTURE DIRECTLY BELOW EXISTING

VENT TO REMAIN.

EXISTING ATTIC VENT

ROUTE PIPING INTO MECHANICAL ROOM

UNDER EXTERIOR PLATFORM AND UP

THRU FLOOR IN WALL

EXTERIOR PLATFORM

EXTERIOR PLATFORM

COMPONENT LOCATED

INSIDE HP−1 CABINET

COMPONENT LOCATED

INSIDE HP−2 CABINET

ROUTE PIPING INTO MECHANICAL ROOM

UNDER EXTERIOR PLATFORM AND UP

THRU FLOOR IN WALL

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:2

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

MECHANICAL DETAILS

06.30.2017 243

M7.20

(E.) #49 T.O. RIDGE

120' - 0"

AUTOSHOP ROOF

PEAK

129' - 0"

AUTO SHOP FLOOR

100’ − 0"

CRITICAL SYSTEMS #68

106’ − 5"

12"x24"

12"x24"

12"x24"

12"x24"

ERV−4

VEHICLE/LIFT CLEARANCE

MOUNT ERV ABOVE HOIST

STRUCTURAL BEAMS

BUILDING #65

SECOND FLOOR

110' - 0"

(E) #65 SECOND FLOOR

110’ − 2"

3.3 3.4 3.5 3.6 3.7 3.8

12"ø

12"x8" 12"ø 14"x6"

8"x12"

ERV−3

oa/ea up in between wood structure to existing vent on roof

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:3

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

MECHANICAL DETAILS

06.30.2017 244

M7.30

SCALE A

M7.30

AUTO SHOP ERV ELEVATION1

SCALE A

M7.30

BUILDING #65 ERV ELEVATION2

SCALE A

4’ 0’ 4’

SCALE OF FEET

8’ 16’

P1 P1 P1 P1 P1

SCALE: NTS

BUILDING #65 VRF FLOW DIAGRAM1

M7.40

OPEN OFFICE 320 CONFERENCE 309 OFFICE 324 OFFICE 323 STORAGE 308 CONFERENCE 309 STORAGE 308 OFFICE 307 OFFICE 310 OPEN OFFICE 320 OPEN OFFICE 301 FILE STORAGE 303 OPEN OFFICE 320 OFFICE 322 OFFICE 321 WORK ROOM 302

AC−10 AC−9 AC−3 AC−12 AC−11 AC−18 AC−4 AC−8 AC−2 AC−1 AC−15 AC−17 AC−5 AC−6 AC−16 AC−13 AC−14 AC−7

AE−200A−A

M−NET

TB3 LAN

TB5 TB15

L1L2 G

GP1 TB5TB15

L1L2 G

GP2 TB5 TB15

L1L2 G

GP3 TB5 TB15

L1L2 G

GP4 TB5 TB15

L1L2 G

GP5 TB5 TB15

L1L2 G

GP6 TB5 TB15

L1L2 G

GP7 TB5 TB15

L1L2 G

GP8 TB5 TB15

L1L2 G

GP9 TB5 TB15

L1L2 G

GP10 TB5 TB15

L1L2 G

GP11 TB5 TB15

L1L2 G

GP12 TB5 TB15

L1L2 G

GP13 TB5 TB15

L1L2 G

GP14 TB5 TB15

L1L2 G

GP15 TB5 TB15

L1L2 G

GP16 TB5 TB15

L1L2 G

GP17 TB5 TB15

L1L2 G

GP18

PVFY−

P12E00A

PVFY−

P12E00A

PKFY−

P08NHMU−E2

PVFY−

P12E00A

PVFY−

P12E00A

PFFY−

P06NEMU−E

PKFY−

P08NHMU−E2

PKFY−

P08NHMU−E2

PFFY−

P06NEMU−E

PKFY−

P24NKMU−E2.TH

PKFY−

P24NKMU−E2.TH

PKFY−

P24NKMU−E2.TH

PKFY−

P12NHMU−E2

PKFY−

P12NHMU−E2

PKFY−

P12NHMU−E2

PKFY−

P15NHMU−E2

PFFY−

P08NEMU−E

PFFY−

P08NEMU−E

P1 P1 P1 P1 P1 P1 P1 P1 P1 P1P2 P2 P2

J1 J1 J1 J1 J1 J1 J1 J1 J1 J1 J1 J1 J1 J1 J1

1 2 3 4 5 6 7 8 9 10 11 12 13 1 2 3 4 5 G G

BC CONTROLLER 1

CMB−P1013NU−GA1

SUB CONTROLLER

CMB−P108NU−GB1

P3 TB2 054

TO MAIN BC

P5

TB2 053

P4

TO SUB BC

16−2 AWG(S)

16−2 AWG(S) P6

P6P7

TB3 G

P0

TB3 G

PURY−P96TLMU−A

PURY−P96TLMU−A

TB7TB7 DIP SWITCH 3−8 ON HIGH HEATING

PERFORMANCE MODE

SYSTEM 1

OUTDOOR UNIT 1

PURY−

P192TSLMU−A

16−2 AWG(S)

P1

P2

P3

P4

P5

P6

P7

1/4

3/8

3/8

7/8

3/4

7/8

1/2

5/8

3/4

1−1/8

SYMBOL LIQUID GAS PIPE SIZE

J1 REDUCER

SYMBOL BRANCH PIPE MODEL

NAME

PIPING LIST

REF PIPE

CONTROL WIRE

DISPLAY DESCRIPTION

DIAGRAM SYMBOL LEGEND

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:3

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 VRF FLOW

DIAGRAM

06.30.2017 245

M7.40

DESIGNED:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:3

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

MECHANICAL CONTROLS

06.30.2017 246

M7.50

BUILDING #49 CONTROLS SEQUENCE:

AHU−1: PROVIDE 7−DAY PROGRAMMABLE THERMOSTAT FOR AHU−1 WITH ONE STAGE OF COOLING AND TWO STAGES OF HEATING. FIRST STAGE OF HEAT SHALL BE THE OUTDOOR HEAT PUMP, HP−1. SECOND STAGE OF HEAT SHALL BE THE GAS FIRED SECTION OF AHU−1.

OCCUPIED HOURS: COOLING SETPOINT = 75° F

HEATING SETPOINT = 70° F

UNOCCUPIED HOURS: COOLING SETPOINT = 80° F

HEATING SETPOINT = 65° F

PROVIDE 2−HOUR OVERRIDE BUTTON ON THERMOSTAT TO ALLOW OCCUPANT TO CHANGE UNOCCUPIED MODE TO OCCUPIED MODE FOR A PERIOD OF 2−HOURS.

INTERLOCK AHU−1 TO ERV−2 SUCH THAT ERV−2 RUNS ANYTIME AHU−1 IS RUNNING.

ERV−1: PROVIDE 7−DAY PROGRAMMABLE TIME CLOCK TO TURN ERV ON/OFF. ERV SHALL BE ON DURING ALL OCCUPIED HOURS AND SHALL BE OFF DURING UNOCCUPIED HOURS. PROVIDE OVERRIDE BUTTON/SWITCH TO ALLOW FOR ERV TO BE CHANGED FROM UNOCCUPIED MODE TO OCCUPIED MODE FOR A PERIOD OF TWO HOURS BY THE

OCCUPANT.

WHEN UNIT IS OFF THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL BE CLOSED.

ERV−2: INTERLOCK TO AHU−1 TO OPERATE WHENEVER AHU−1 IS IN OPERATION.

WHEN UNIT IS OFF THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL BE CLOSED.

TF−1: PROVIDE COOLING ONLY THERMOSTAT FOR TRANSFER FAN IN SERVER ROOM #208. SET THERMOSTAT TO 75° F (ADJ.). FAN SHALL TURN ON WHENEVER THE

SPACE TEMPERATURE EXCEEDS 75° F.

EBB−1 AND EBB−2: PROVIDE WALL MOUNTED THERMOSTAT FOR ELECTRIC BASEBOARD HEATERS IN THE RESTROOMS. SET THERMOSTAT TO MAINTAIN 70°F. PROVIDE INSULATED WALL BACKING ON THERMOSTATS IN BOTH RESTROOMS.

EF−1: CONNECT EXHAUST FAN TO 7−DAY PROGRAMMABLE TIMECLOCK ASSOCIATED WITH ERV−1. EXHAUST FAN SHALL OPERATE DURING OCCUPIED TIMES AND BE OFF

DURING UNOCCUPIED TIMES.

EF−2: PROVIDE OCCUPANCY SENSOR TO TURN FAN ON UPON ACTIVATION OF SENSOR. PROVIDE MANUAL OVERRIDE SWITCH NEXT TO OCCUPANCY SENSOR TO ALLOW THE

OCCUPANT TO TURN THE FAN ON WHEN THE ROOM IS NOT OCCUPIED.

GUH−1, 2, 3, 4, 11, & 12: PROVIDE HEATING ONLY THERMOSTAT FOR GAS UNIT HEATERS. LOCATE THERMOSTATS AS SHOWN ON THE PLANS. GUH−3 AND GUH−4 SHALL BE

CONTROLLED VIA THE SAME THERMOSTAT. SET THERMOSTAT TO MAINTAIN 65° F (ADJ.).

BUILDING #65 CONTROLS SEQUENCE:

AC UNITS & HP−2: PROVIDE SYSTEM CONTROLS TO ALLOW INDOOR AIR CONDITIONING UNITS TO PROVIDE HEATING AND COOLING BASED ON SPACE TEMPERATURE.

EACH AC UNIT SHALL BE PROVIDED WITH A SEPARATE 7−DAY PROGRAMMABLE THERMOSTAT WITH A 2−HOUR OCCUPANCY OVERRIDE.

OCCUPIED HOURS: COOLING SETPOINT = 75° F

HEATING SETPOINT = 70° F

UNOCCUPIED HOURS: COOLING SETPOINT = 80° F

HEATING SETPOINT = 65° F

IN LOCATIONS WHERE THERMOSTATS ARE LOCATED ON EXTERIOR WALLS, PROVIDE A INSULATED WALL BACKING ON THE THERMOSTAT.

HP−2 SHALL BE CAPABLE OF PROVIDING SIMULTANEOUS HEATING AND COOLING FOR THE SPACE SUCH THAT MULTIPLE UNITS CAN BE IN COOLING MODE AND

MULTIPLE UNITS CAN BE IN HEATING MODE AT THE SAME TIME.

ERV−3: PROVIDE 7−DAY PROGRAMMABLE TIME CLOCK TO TURN ERV ON/OFF. ERV SHALL BE ON DURING ALL OCCUPIED HOURS AND SHALL BE OFF DURING UNOCCUPIED HOURS. PROVIDE OVERRIDE BUTTON/SWITCH TO ALLOW FOR ERV TO BE CHANGED FROM UNOCCUPIED MODE TO OCCUPIED MODE FOR A PERIOD OF TWO HOURS BY

THE OCCUPANT.

WHEN UNIT IS OFF THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL BE CLOSED.

EBB−3 AND EBB−4: PROVIDE WALL MOUNTED THERMOSTAT FOR ELECTRIC BASEBOARD HEATERS IN THE RESTROOMS. SET THERMOSTAT TO MAINTAIN 70°F. PROVIDE

INSULATED WALL BACKING ON THERMOSTATS IN BOTH RESTROOMS.

EUH−1: PROVIDE HEATING ONLY THERMOSTAT FOR ELECTRIC UNIT HEATERS. LOCATE THERMOSTATS AS SHOWN ON THE PLANS. SET THERMOSTAT TO MAINTAIN

65° F (ADJ.).

AUTO SHOP CONTROLS SEQUENCE:

AHU−2: PROVIDE 7−DAY PROGRAMMABLE THERMOSTAT FOR AHU−2 WITH ONE STAGE OF COOLING AND TWO STAGES OF HEATING. FIRST STAGE OF HEAT SHALL BE THE OUTDOOR HEAT PUMP, HP−3. SECOND STAGE OF HEAT SHALL BE THE GAS FIRED SECTION OF AHU−2.

OCCUPIED HOURS: COOLING SETPOINT = 75° F

HEATING SETPOINT = 70° F

UNOCCUPIED HOURS: COOLING SETPOINT = 80° F

HEATING SETPOINT = 65° F

PROVIDE 2−HOUR OVERRIDE BUTTON ON THERMOSTAT TO ALLOW OCCUPANT TO CHANGE UNOCCUPIED MODE TO OCCUPIED MODE FOR A PERIOD OF 2−HOURS.

ERV−4: PROVIDE 7−DAY PROGRAMMABLE TIME CLOCK TO TURN ERV ON/OFF. ERV SHALL BE ON DURING ALL OCCUPIED HOURS AND SHALL BE OFF DURING UNOCCUPIED HOURS. PROVIDE OVERRIDE BUTTON/SWITCH TO ALLOW FOR ERV TO BE CHANGED FROM UNOCCUPIED MODE TO OCCUPIED MODE FOR A PERIOD OF TWO HOURS BY

THE OCCUPANT.

WHEN UNIT IS OFF THE OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL BE CLOSED.

TF−2: PROVIDE COOLING ONLY THERMOSTAT FOR TRANSFER FAN IN IT CLOSET. SET THERMOSTAT TO 75° F (ADJ.). FAN SHALL TURN ON WHENEVER THE SPACE

TEMPERATURE EXCEEDS 75° F.

EF−3: CONNECT EXHAUST FAN TO 7−DAY PROGRAMMABLE TIMECLOCK ASSOCIATED WITH ERV−4. EXHAUST FAN SHALL OPERATE DURING OCCUPIED TIMES AND BE

OFF DURING UNOCCUPIED TIMES.

EF−4: PROVIDE ON/OFF SWITCH ON WALL TO ALLOW THE OCCUPANT TO CONTROL THE FAN.

EUH−3 AND EUH−4: PROVIDE WALL MOUNTED THERMOSTAT FOR ELECTRIC BASEBOARD HEATERS IN THE RESTROOMS. SET THERMOSTAT TO MAINTAIN 70°F. PROVIDE

INSULATED WALL BACKING ON THERMOSTATS IN BOTH RESTROOMS.

GUH−5, 6, 7, 8, 9 & 10: PROVIDE HEATING ONLY THERMOSTAT FOR GAS UNIT HEATERS. LOCATE THERMOSTATS AS SHOWN ON THE PLANS. SET THERMOSTAT TO

MAINTAIN 65° F (ADJ.).

EUH−2: PROVIDE HEATING ONLY THERMOSTAT FOR ELECTRIC UNIT HEATERS. LOCATE THERMOSTATS AS SHOWN ON THE PLANS. SET THERMOSTAT TO MAINTAIN

65° F (ADJ.).

DVE−1 & 2: PROVIDE SPRING DAMPER AT HOSE REEL OUTLET TO TURN ASSOCIATED EXHAUST FAN ON/OFF WHEN HOSE REEL IS IN USE.

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:3

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 COMCHECK

06.30.2017 250

M8.30

DRAWING NO.

PMIS/PKG NO.

SHEET

TITLE OF SHEET

OF

200607 A

127962

CWC

SUB SHEET NO.

REVIEWED BY:

DMD

GATEWAY NATIONAL RECREATION AREA6

/2

/2

:1

:3

A

M C

U s e rs

\c c ro w \D o c u m e n ts

\2 N

P S

S A

H O

M P c c ro w S

C H

U C

.r v t

RELOCATE MAINTENANCE FACILITIES TO MORE

SUSTAINABLE LOCATIONS - SANDY HOOK UNIT

BUILDING #65 COMCHECK

06.30.2017 251

M8.40