A06-Mechanical_Drawings_-_Hagerman_NWR_HVAC_Replacement.pdf
PDF 2 MB Posted
- Attached to
- TX-HAGERMAN NWR-HVAC REPLACEMENT Federal contract opportunity
- Solicitation number
- 140FC124R0036
About this file
This solicitation requests proposals for an HVAC replacement project at the Hagerman National Wildlife Refuge Headquarters and Visitor Center. The project requires removing and replacing the existing Daikin VRF system with a new Variable Refrigerant Flow heat recovery system. The magnitude of the project is between $200,000 and $250,000. This is a 100% total small business set-aside with a NAICS code of 238220. Proposals are due by March 22, 2022 and the acceptance period is 60 days. The award will be made to the lowest price technically acceptable proposal. Firms must be registered in SAM and direct all inquiries to the contracting point of contact by the specified date to receive a response.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140FC124R0036_Amd_0001.pdf | ||
| A04-SOW_-_Hagerman_NWR_HVAC_Replacement_0001.pdf | ||
| Sol_140FC124R0036.pdf | ||
| B08_Construction_Over_SAT_FFP_2_14_24.pdf | ||
| A06-Specifications_Package_-_Hagerman_NWR_HVAC_Replacement.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
M0.1M0.1M0.1M0.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
MECHANICAL LEGEND AND NOTESMECHANICAL LEGEND AND NOTESMECHANICAL LEGEND AND NOTESMECHANICAL LEGEND AND NOTES
MRMRMRMRMRMRMRMR
1281281281281001001001002R-TX-404-46-100.02R-TX-404-46-100.02R-TX-404-46-100.02R-TX-404-46-100.0
M
G
M
T
S
F
MECHANICAL LEGEND
T
D
RD
OD
STORM DRAIN ABOVE GRADESD
SD
F
G
CHS
CHR
CWS
CWR
HWS
HWR
S
RL
RS
F
FS
18/12
RPBP
T
GATE VALVE
OVERFLOW DRAIN
BALL VALVE
BUTTERFLY VALVE
MOTORIZED VALVE OPERATOR
CHECK VALVE (SWING OR LIFT AS REQ'D)
SOLENOID VALVE
AUTOMATIC CONTROL VALVE (2-WAY)
AUTOMATIC CONTROL VALVE (3-WAY)
PRESSURE REDUCING VALVE
P & T RELIEF VALVE
AIR VENT (AUTOMATIC)
STRAINER
CALIBRATED BALANCING VALVE
VENTURI FLOW METER
REDUCER VALVE
PET COCK OR GAUGE COCK
PRESSURE GAUGE W/GAUGE COCK
THERMOMETER
TEMPERATURE & PRESSURE TEST PLUG
PUMP
FLOW SWITCH
TEMPERATURE SENSOR
HOSE BIB OR SILLCOCK
YARD HYDRANT
FLOOR DRAIN
FLOOR SINK
WALL CLEANOUT
FLOOR OR GRADE CLEANOUT
EXPANSION JOINT
FLEXIBLE PIPE CONNECTION
REDUCED PRESSURE BACKFLOW PREVENTER
DOUBLE CHECK BACKFLOW PREVENTER
WATER HAMMER ARRESTOR
ELBOW DOWN
ELBOW UP
PIPE CAP
TEE DOWN
UNION
DOMESTIC COLD WATER (DCW)
DOMESTIC HOT WATER (DHW)
DOMESTIC HOT WATER RECIRC.
DOMESTIC TEMPERED WATER
SANITARY VENT
SANITARY SEWER ABOVE GRADE (SS)
SANITARY SEWER BELOW GRADE (SS)
DRAIN
ROOF DRAIN
SECTION CUT LINE
STORM DRAIN BELOW GRADE
FIRE SERVICE
NATURAL GAS
HEAT TRACING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSOR WATER SUPPLY
CONDENSOR WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
STEAM
REFRIGERANT LIQUID
REFRIGERANT SUCTION
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST GRILLE
RETURN AIR DUCT SECTION
RETURN AIR DUCT TURNED UP
RETURN AIR DUCT DOWN
SUPPLY AIR DUCT SECTION
SUPPLY AIR DUCT TURNED UP
SUPPLY AIR DUCT DOWN
EXHAUST AIR DUCT SECTION
EXHAUST AIR DUCT TURNED UP
EXHAUST AIR DUCT DOWN
ACCESS PANEL
MANUAL VOLUME DAMPER
GRAVITY BACKDRAFT DAMPER
MOTORIZED DAMPER
FIRE DAMPER
COMBINATION FIRE/SMOKE DAMPER
DUCT SIZE (FIRST FIGURE IS SIZE SHOWN)
BURIED OR UNDERFLOOR DUCT
DUCT W/ ACOUSTICAL LINING
FLEXIBLE DUCT (HELICAL)
FLEXIBLE DUCT CONNECTION
DUCT TRANSITION
ELBOW W/ TURNING VANES
TEE W/45 DEGREE ENTRY
WYE W/ 45 DEGREE ENTRY
THERMOSTAT OR TEMP SENSOR
ZONE SENSOR
POINT OF REMOVAL FROM EXISTING
POINT OF CONNECTION TO EXISTING
DETAIL TAG
KEYED NOTE
STANDARD MECHANICAL ABBREVIATIONS
DIA OR Ø DIAMETER
ABOVE FINISHED FLOORAFF
ALTERNATEALT
AIR PRESSURE DROPAPD
BOTTOM OF DUCTBOD
BOTTOM OF PIPEBOP
BRITISH THERMAL UNITS PER HOURBTU/H
CAPACITYCAP.
CUBIC FEET PER MINUTECFM
CONSTANT VOLUMECV
DRY BULBDB
EXISTING(E)
EXHAUST AIREA
ENTERING AIR TEMPERATUREEAT
EFFICIENCYEFF
ELEVATIONELEV
EXTERNAL STATIC PRESSUREESP
ENTERING WATER TEMPERATUREEWT
FREE AREAFA
FEET PER MINUTEFPM
FEETFT
FACE VELOCITYFV
GAUGEGA
GALLONGAL
GALLONS PER MINUTEGPM
HORSEPOWERHP
HOURHR
HEIGHTHT
INCHIN.
INCHES OF WATER COLUMNINWC
INCHES OF WATER GAUGEINWG
LEAVING AIR TEMPERATURELAT
POUNDSLBS
LEAVING WATER TEMPERATURELWT
MAXIMUMMAX
THOUSAND BRITISH THERMAL UNITS/HOURMBH
MECHANICALMECH
MINIMUMMIN
NOISE CRITERIANC
NOT IN CONTRACTNIC
NUMBERNO.
NOMINALNOM
NOT TO SCALENTS
OPPOSED BLADE DAMPEROBD
OUTSIDE AIROSA
PRESSURE DROPPD
POUNDS PER SQUARE INCHPSI
POUNDS PER SQUARE INCH GAUGEPSIG
RETURN AIRRA
SUPPLY AIRSA
SENSIBLESEN
SEA LEVELSL
STATIC PRESSURESP
SQUARE FEETSQ FT
SERVICE SINK OR STAINLESS STEELSS
TOP OF DUCTTOD
TOTAL STATIC PRESSURETSP
VARIABLE AIR VOLUMEVAV
VARIABLE FREQUENCY DRIVEVFD
VOLUMEVOL
WITHW/
WITHOUTW/O
WET BULBWB
MANUAL VOLUME DAMPERMVD
WATER PRESSURE DROPWPD
WEIGHTWT
ANALOG INPUTAI
ANALOG OUTPUTA0
DIGITAL INPUTDI
DIGITAL OUTPUTDO
FRESH WATERFW
INDOOR AIR QUALITYIAQ
SHEET NO. SHEET TITLE REVISION
#1 #2
SHEET INDEX
M0.1 MECHANICAL LEGEND AND NOTES
MZ1.1 MECHANCIAL ZONE PLAN
M1.1 MECHANICAL FLOOR PLAN
M2.1 MECHANCIAL SCHEMATICS
M3.1 MECHANICAL SECTIONS
M4.1 ENLARGED MECHANICAL FLOOR PLAN
M5.1 MECHANICAL DETAILS
M6.1 MECHANICAL SCHEDULES
MECHANICAL
U. ALL ITEMS LOCATED IN A RETURN AIR PLENUM TO HAVE A FLAME SPREAD
INDEX OF 25 AND SMOKE DEVELOPMENT INDEX OF 50. DUCT COVERINGS
AND LININGS TO HAVE A FLAME SPREAD INDEX NOT MORE THAN 25 AND A
SMOKE-DEVELOPED INDEX OF 50 IN ACCORDANCE WITH ASTM84. DUCT
COVERINGS AND LININGS SHALL NOT FLAME, GLOW, SMOLDER, OR SMOKE
WHEN TESTED IN ACCORDANCE WITH ASTMC411.
V. LINE ALL RECTANGULAR SUPPLY AND RETURN DUCT. LINE ALL RETURN AIR
TRANSFERS AND GRILLE PLENUM BOXES. DUCT LINER TO BE MINIMUM
R-5. TRIM AND SEAL JOINTS.
W. INSULATE ALL CONCEALED UNLINED DUCT WITH MINIMUM R-5 (INSTALLED)
FIBERGLASS DUCT WRAP. INSULATE ALL OUTSIDE AIR DUCT WITH MINIMUM
R-5 (INSTALLED) FIBERGLASS DUCT WRAP. INSULATION TO BE UL LISTED
AND MEET NFPA 220. ALL DUCT LOCATED IN COLD ATTIC TO BE INSULATED
WITH MINIMUM R-8 (INSTALLED).
X. INSULATE REFRIGERANT PIPING WITH 1" INSULATION. PROVIDE ALUMINUM
JACKET ON ALL INSULATION LOCATED OUTDOORS. INSULATION TO BE 0.27
BTU*IN/HR*FT²*°F.
Y. ROUND FLEXIBLE DUCT TO BE 1" THICK INSULATED AND MEET NFPA 90A
STANDARDS. FLEXIBLE DUCT RUNS TO BE MAXIMUM 8 FEET IN LENGTH
AND FREE OF KINKS. FLEXIBLE DUCTS TO BE TESTED ACCORDING TO
UL181. FLEXIBLE DUCT FASTENERS TO COMPLY WITH UL181B. UNLISTED
DUCT TAPE IS PROHIBITED.
Z. ALL ROUND EXPOSED DUCT TO BE SPIRAL DUCT.
AA. CONSTRUCT ALL DUCT TEES, BENDS, AND ELBOWS WITH RADIUS NOT LESS
THAN 1.5 TIMES THE WIDTH OF THE DUCT. WHERE PHYSICAL CONSTRAINTS
PROHIBIT RADIUSED ELBOWS, PROVIDE RECTANGULAR ELBOW WITH
TURNING VANES. ALL BRANCH TAKEOFFS TO BE CONSTRUCTED OF 90°
WYE WITH 45° ENTRY.
AB. DUCT DIMENSIONS SHOWN ARE CLEAR INSIDE DIMENSIONS.
AC. PAINT DUCT INTERIORS VISIBLE THROUGH REGISTERS, GRILLES,
DIFFUSERS, AND LOUVERS FLAT BLACK.
AD. MECHANICAL EQUIPMENT INSTALLED OUTDOORS TO BE LISTED AND
LABELED FOR OUTDOOR INSTALLATION.
AE. ALL DUCTS ABOVE RATED CEILINGS TO BE MINIMUM 24-GAUGE SHEET
METAL.
AF. PROVIDE FIRE AND FIRE/SMOKE DAMPERS WHERE REQUIRED. INSTALL
DAMPERS PER UL555, UL555S, AND UL555C AND MANUFACTURER'S
RECOMMENDATIONS. PROVIDE FIRE SAFING ON ALL PENETRATIONS
THROUGH FIRE RATED SEPARATIONS WITH UL RATED FIRE SAFING
MATERIAL.
AG. CONCEALED VENTS, DUCTS, AND ALL PIPING INSTALLED THROUGH
FRAMING MEMBERS MUST BE PROTECTED FROM FASTENER PENETRATION
BY A STEEL SHIELD PLATE (MINIMUM THICKNESS OF 1/16") UNLESS THE
DISTANCE FROM THE FACE EDGE OF THE FRAMING IS NOT LESS THAN 1.5".
AH. PROVIDE WATER LEVEL DETECTOR FOR ALL DOWNFLOW UNITS WITHOUT
SECONDARY DRAIN PANS. DISABLE EQUIPMENT UPON DETECTION OF
WATER.
AI. PROVIDE NEW FILTERS ON ALL FORCED AIR SYSTEMS AND NEW BELTS FOR
ALL BELT DRIVEN EQUIPMENT WITHIN ONE WEEK PRIOR TO SUBSTANTIAL
COMPLETION.
AJ. ALL REFRIGERATION TO BE NON CFC TYPE REFRIGERANT TO COMPLY WITH
LEED 3.0, EA PREREQUISITE 3.
AK. PROVIDE FILTERS (MERV 8) AT EACH RETURN GRILLE IF AIR HANDLERS ARE
OPERATED DURING THE CONSTRUCTION PHASE AND REPLACE ALL
FILTRATION MEDIA TO HVAC EQUIPMENT PRIOR TO OCCUPANCY OF
BUILDING TO COMPLY WITH LEED 3.0, IEQ CREDIT 3.1.
AL. DURING CONSTRUCTION, MEET OR EXCEED THE RECOMMENDED CONTROL
MEASURES OF THE SMACNA IAQ GUIDELINES FOR OCCUPIED BUILDINGS
UNDER CONSTRUCTION, 2ND EDITION 2007, ANSI/SMACNA 008-2008
(CHAPTER 3) TO COMPLY WITH LEED 3.0, IEQ CREDIT 3.1.
AM. AT COMPLETION OF CONSTRUCTION AND PRIOR TO OCCUPANCY, WITH ALL
INTERIOR FINISHES INSTALLED, INSTALL NEW FILTRATION MEDIA TO ALL
HVAC EQUIPMENT AND PERFORM A BUILDING FLUSH-OUT BY SUPPLYING A
TOTAL AIR VOLUME OF 14,000 CUBIC FEET OF OUTDOOR AIR PER SQUARE
FOOT OF FLOOR AREA WHILE MAINTAINING AN INTERNAL TEMPERATURE OF
AT LEAST 60 DEGREES AND RELATIVE HUMIDITY NO HIGHER THAN 60% TO
COMPLY WITH LEED 3.0, IEQ CREDIT 3.2.
AN. ALL ADHESIVES, SEALANTS, AND SEALANT PRIMERS USED IN HVAC
CONSTRUCTION TO BE WITHIN THE VOC LIMITS OF SCAQMD RULE #1168 TO
COMPLY WITH LEED 3.0, IEQ CREDIT 4.1.
MECHANICAL
A. INSTALL ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH 2006
INTERNATIONAL BUILDING CODE, 2006 INTERNATIONAL MECHANICAL
CODE, AND 2006 INTERNATIONAL PLUMBING CODE, 2006 INTERNATIONAL
ENERGY CONSERVATION CODE, AND 2006 INTERNATIONAL FUEL GAS CODE.
B. CLOSELY COORDINATE ALL MECHANICAL WITH ELECTRICAL,
ARCHITECTURAL, AND STRUCTURAL. DUCTWORK AND PIPING IS
APPROXIMATE AND DIAGRAMMATIC AND IS NOT TO BE SCALED. PROVIDE
ALTERNATE ROUTING, OFFSETS, AND TRANSITIONS AS REQUIRED FOR
COORDINATION OF ALL WORK WITHOUT ADDITIONAL COST TO THE OWNER.
C. FIELD VERIFY ALL MECHANICAL PRIOR TO COMMENCING NEW WORK. DO
NOT FABRICATE OR INSTALL ANY MECHANICAL BEFORE VERIFYING
DIMENSIONS AND ROUTING WITH BUILDING CONDITIONS AND ALL OTHER
TRADES.
D. COORDINATE ALL ELECTRICAL AND CONTROL REQUIREMENTS WITH
ELECTRICIAN.
E. INSTALL ALL EQUIPMENT AND DEVICES PER MANUFACTURER'S
RECOMMENDATIONS.
F. CONTRACTOR IS RESPONSIBLE FOR ALL APPLICABLE PERMITS AND FEES.
G. PROVIDE SUBMITTALS ON ITEMS LISTED IN SCHEDULES TO ENGINEER FOR
REVIEW PRIOR TO ORDER, PURCHASE, OR INSTALLATION. ALL REQUIRED
SUBMITTALS TO BE SUBMITTED IN A SINGLE TABBED BINDER. PROVIDE ALL
HVAC CONSTRUCTION COSTS FOR ENGINEER DATA BASE AS PART OF
SUBMITTALS.
H. ALL MANUFACTURER SUBSTITUTIONS MUST BE SUBMITTED TO ENGINEER
AND APPROVED THROUGH AN ADDENDUM. PRIOR APPROVALS MUST BE
SUBMITTED 10 DAYS PRIOR TO BID DATE.
I. PROVIDE OPERATIONS AND MAINTENANCE MANUAL INCLUDING ALL HVAC
EQUIPMENT.
J. CLOSE ENDS OF DUCTWORK AND PIPING AND COVER FLOOR DRAINS
DURING CONSTRUCTION. CLEAN ALL EQUIPMENT, PIPING, AND DUCTWORK
AT COMPLETION OF PROJECT.
K. COORDINATE ALL DIFFUSER AND GRILLE LOCATIONS WITH REFLECTED
CEILING PLAN AND ELECTRICAL DRAWINGS.
L. COORDINATE ALL STRUCTURAL PENETRATIONS FOR DUCT WORK WITH
GENERAL CONTRACTOR. DUCT PENETRATIONS THROUGH ROOF ARE TO BE
COORDINATED WITH JOIST LAYOUT.
M. COORDINATE EXACT LOCATION OF THERMOSTATS WITH ARCHITECT PRIOR
TO INSTALLATION.
N. PROVIDE BALANCE VALVES AND DAMPERS TO ALLOW COMPLETE BALANCE
OF HVAC SYSTEMS.
O. PROVIDE ACCESS PANELS FOR ALL EQUIPMENT, DAMPERS, ACTUATORS,
AND FILTERS. ENSURE ADEQUATE ACCESS TO ALL SYSTEM COMPONENTS
FOR MAINTAINABILITY.
P. PROVIDE FLUSH CUP CONCEALED OPERATORS ON ALL HAND DAMPERS
LOCATED ABOVE HARD OR INACCESSIBLE CEILINGS.
Q. PROVIDE STARTERS AND CONTACTORS NECESSARY TO OPERATE ALL
MECHANICAL EQUIPMENT. COORDINATE ALL REQUIREMENTS WITH
ELECTRICAL.
R. PROVIDE VIBRATION ISOLATION FOR ALL FAN OR COMPRESSOR DRIVEN
EQUIPMENT. PROVIDE FLEXIBLE CONNECTIONS TO EQUIPMENT.
S. PROVIDE TRAPPED CONDENSATE DRAINS PIPED FULL SIZE TO ROOF DRAIN
FOR ALL AIR CONDITIONING EQUIPMENT. PIPING TO BE TYPE L COPPER.
T. PROVIDE SEISMIC RESTRAINTS FOR HVAC EQUIPMENT, DUCTWORK, AND
PIPING IN ACCORDANCE WITH INTERNATIONAL BUILDING CODE WITH
SEISMIC DESIGN CATEGORY D, SITE CLASS D, OCCUPANCY CATEGORY II,
SHORT PERIOD DESIGN SPECTRAL RESPONSE ACCELERATION COEFFICIENT
SDS=0.742, ONE SECOND PERIOD DESIGN SPECTRAL RESPONSE
ACCELERATION COEFFICIENT SD1=0.401, AND IMPORTANCE FACTOR 1.0.
PIPING SUPPORTED WITHIN 12" OF STRUCTURE DOES NOT REQUIRE
SEISMIC BRACING. DUCTS SUPPORTED WITHIN 12" OF STRUCTURE OR
DUCTS LESS THAN 6 SQ. FT. CROSS-SECTIONAL AREA DO NOT REQUIRE
SEISMIC BRACING.
HEAT PUMP - INDOORHPI
HEAT PUMP - OUTDOORHPO
ENERGY RECOVERY VENTILATORERV
DWG#
DET#
DWG#
SEC#
NOTE #
DWG#
DWG#
FD FD
FD
1111 4444 5555
EEEE
FFFF
JJJJ
2222 3333
8.18.18.18.1
10101010
DDDD
CCCC
AAAA
BBBB
11111111
11111111
8.58.58.58.5
GGGG
HHHH
E.5E.5E.5E.5
7.17.17.17.1
7.17.17.17.1
4.94.94.94.9
A.5A.5A.5A.5
VESTIBULEVESTIBULEVESTIBULEVESTIBULE
101101101101
CORRIDORCORRIDORCORRIDORCORRIDOR
103103103103
ELECELECELECELEC
102102102102
OFFICEOFFICEOFFICEOFFICE
104104104104
OFFICEOFFICEOFFICEOFFICE
105105105105
RESOURCERESOURCERESOURCERESOURCE
106106106106
ASST MGRASST MGRASST MGRASST MGR
OFFICEOFFICEOFFICEOFFICE
108108108108
BREAKBREAKBREAKBREAK
ROOMROOMROOMROOM109109109109
OFFICEOFFICEOFFICEOFFICE
110110110110
TOILETTOILETTOILETTOILET
112112112112
COPYCOPYCOPYCOPY
ROOMROOMROOMROOM114114114114
ADMINISTRATIONADMINISTRATIONADMINISTRATIONADMINISTRATION
116116116116
MGRMGRMGRMGR
OFFICEOFFICEOFFICEOFFICE117117117117
MULTI PURPOSEMULTI PURPOSEMULTI PURPOSEMULTI PURPOSE
ROOMROOMROOMROOM
125125125125
CLOSETCLOSETCLOSETCLOSET
126126126126
VESTIBULEVESTIBULEVESTIBULEVESTIBULE
127127127127
TOILETTOILETTOILETTOILET
130130130130
TOILETTOILETTOILETTOILET
128128128128
JANITORJANITORJANITORJANITOR
123123123123
CONFERENCECONFERENCECONFERENCECONFERENCE
107107107107
VESTIBULEVESTIBULEVESTIBULEVESTIBULE
118118118118CLOSETCLOSETCLOSETCLOSET
129129129129
EXHIBITEXHIBITEXHIBITEXHIBIT
120120120120
LOBBYLOBBYLOBBYLOBBY
119119119119
CORRIDORCORRIDORCORRIDORCORRIDOR
124124124124
OFFICEOFFICEOFFICEOFFICE
122122122122
BOOKSTOREBOOKSTOREBOOKSTOREBOOKSTORE
121121121121
CLOSETCLOSETCLOSETCLOSET
111111111111
ITITITIT
115115115115
TOILETTOILETTOILETTOILET
113113113113
CLOSETCLOSETCLOSETCLOSET
122A122A122A122A
RECYCLERECYCLERECYCLERECYCLE
105A105A105A105A
RECYCLERECYCLERECYCLERECYCLE
124A124A124A124A
CLOSETCLOSETCLOSETCLOSET
131131131131
ZONE 1A (HPI-1)
ZONE 2 (HPI-3)
ZONE 3 (HPI 4 & 5)
ZONE 4 (HPI-6)
ZONE 5 (HPI-7)
ZONE 7 (HPI-10)
ZONE 9 (HPI-11)
ZONE 8 (HPI-9)
ZONE 10 (HPI-12)
ZONE 6 (HPI-8)
ZONE 1B (HPI-2)
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
MZ1.1MZ1.1MZ1.1MZ1.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
MECHANCIAL ZONE PLANMECHANCIAL ZONE PLANMECHANCIAL ZONE PLANMECHANCIAL ZONE PLAN
MRMRMRMRMRMRMRMR
1281281281281011011011012R-TX-404-46-101.02R-TX-404-46-101.02R-TX-404-46-101.02R-TX-404-46-101.0
SCALE: NONE1 MECHANICAL ZONE PLAN
1111 4444 5555
EEEE
FFFF
JJJJ
2222 3333
8.18.18.18.1
10101010
DDDD
CCCC
AAAA
BBBB
11111111
11111111
8.58.58.58.5
GGGG
HHHH
E.5E.5E.5E.5
7.17.17.17.1
7.17.17.17.1
4.94.94.94.9
A.5A.5A.5A.5
VESTIBULEVESTIBULEVESTIBULEVESTIBULE
101101101101
CORRIDORCORRIDORCORRIDORCORRIDOR
ELECELECELECELEC
102102102102
OFFICEOFFICEOFFICEOFFICE
104104104104
105105105105
RESOURCERESOURCERESOURCERESOURCE
106106106106
ASST MGRASST MGRASST MGRASST MGR
OFFICEOFFICEOFFICEOFFICE
108108108108
BREAKBREAKBREAKBREAK
ROOMROOMROOMROOM109109109109
OFFICEOFFICEOFFICEOFFICE
110110110110
TOILETTOILETTOILETTOILET
COPYCOPYCOPYCOPY
ROOMROOMROOMROOM114114114114
ADMINISTRATIONADMINISTRATIONADMINISTRATIONADMINISTRATION
116116116116
MGRMGRMGRMGR
OFFICEOFFICEOFFICEOFFICE117117117117
MULTI PURPOSEMULTI PURPOSEMULTI PURPOSEMULTI PURPOSE
ROOMROOMROOMROOM
125125125125
CLOSETCLOSETCLOSETCLOSET
126126126126
VESTIBULEVESTIBULEVESTIBULEVESTIBULE
127127127127
128128128128
CONFERENCECONFERENCECONFERENCECONFERENCE
107107107107
VESTIBULEVESTIBULEVESTIBULEVESTIBULE
118118118118CLOSETCLOSETCLOSETCLOSET
129129129129
EXHIBITEXHIBITEXHIBITEXHIBIT
120120120120
LOBBYLOBBYLOBBYLOBBY
119119119119
CORRIDORCORRIDORCORRIDORCORRIDOR
OFFICEOFFICEOFFICEOFFICE
122122122122
BOOKSTOREBOOKSTOREBOOKSTOREBOOKSTORE
121121121121
ITITITIT
115115115115
TOILETTOILETTOILETTOILET
CLOSETCLOSETCLOSETCLOSET
122A122A122A122A
RECYCLERECYCLERECYCLERECYCLE
124A124A124A124A
S S
S
S
S
S
S
S
S
S
S
S
F F
S
S
S S
S
S
S
HPO-A
HPO-B
ERV-1
HPI-1 HPI-2
14"/12"
12"/10"
18"/10"
14"/8"
14"/8"
16"/16"
18"/14"
16"/14"
14"/8"
18"/10"
5 5
102 105
102 105
102 105
102 106
14"/12"
14"/12"
ERV-2
10"ø
10"ø
12"ø
102 106
102 104
102 104
RL/RS
RL/RS
RL/RS/HG
RL/RS/HG
RL/RS/HG UP
14"/14"
MD-2
MD-1
MD-3
MD-4
1 LOCATE OUTDOOR EQUIPMENT UP ON STEEL MOUNTING FRAME 12” ABOVE GRADE ON CONCRETE PAD. COORDINATE PAD DIMENSIONS AND CONCRETE STRIP FOR PIPING UNISTRUT SUPPORT WITH
GENERAL CONTRACTOR.
2 PROVIDE UNISTRUT SUPPORT EVERY 5 FEET FOR ALL REFRIGERANT PIPING ROUTED ABOVE
GROUND OUTDOORS. PROVIDE SHEET METAL COVER FOR REFRIGERANT PIPING ABOVE GROUND.
3 ALL DUCT LOCATED OUTDOORS TO BE DOUBLE WALL INSULATED DUCT WITH R-11 ANNULAR
INSULATION. PITCH TOP OF DUCT TO AVOID MOISTURE COLLECTION. PROVIDE UNISTRUT SUPPORT
STANDS AT MAXIMUM 24” O.C. AND ELEVATE DUCT MINIMUM 12” ABOVE GRADE.
4 APPROXIMATE LOCATION OF BS BOX.
5 DUCT INTENDED TO BE ROUTED UP WITHIN STRUCTURE. COORDINATE ROUTING THROUGH
STRUCTURAL WITH GENERAL CONTRACTOR AND OTHER TRADES.
6 APPROXIMATE LOCATION OF ZONE SENSOR. PROVIDE VANDAL RESISTANT LOCKABLE COVER FOR
SENSOR LOCATED WITH IN PUBLIC ACCESS. COORDINATE FINAL LOCATION WITH ARCHITECT.
7 PROVIDE CURB FOR ERV TO ELEVATE BOTTOM OF ERV MINIMUM 10” ABOVE GRADE. COORDINATE
CONCRETE HOUSEKEEPING PAD AND FINAL LOCATION FOR EQUIPMENT WITH GENERAL
CONTRACTOR/ARCHITECT. MAINTAIN MINIMUM MANUFACTURER RECOMMENDED CLEARANCES
FOR ACCESS TO EQUIPMENT.
8 LOCATE DUCT AS LOW AS POSSIBLE AS IT ENTERS BUILDING (APPROX 12” ABOVE GRADE TO
BOTTOM OF DUCT). COORDINATE FINAL HEIGHT WITH ARCHITECTURAL.
9 COORDINATE DUCT PENETRATION THROUGH SHEAR WALL WITH GENERAL CONTRACTOR.
10 PROVIDE PARAGON CONTROLS OUTDOOR AIRFLOW MEASUREMENT STATION MODEL OAFE-1500
(OR APPROVED EQUAL) IN SUPPLY/VENTILATION AIR DUCT FROM ERV TO BUILDING. AIRFLOW
MONITOR TO SEND DI/DO BOARD BINARY OUTPUT TO ALARM I-TOUCH CONTROLLER WHEN
OUTSIDE AIRFLOW DECREASES 15% BELOW SCHEDULED SUPPLY CFM VALUE TO COMPLY WITH
LEED IEQ CREDIT 1.
11 PROVIDE C02 SENSOR IN SPACE TO COMPLY WITH LEED IEQ CREDIT 1. SENSOR TO BE KELE CD-AW-R-LCD (OR APPROVED EQUAL) WITH HIGH LIMIT ALARM RELAY AND LCD DISPLAY. SENSOR TO BE MOUNTED ON WALL 3’ TO 6’ AFF. PROVIDE BRIGHT RED FLASHING LED LIGHT LINKED TO HIGH LIMIT ALARM. LOCATE LED LIGHT IN VISIBLE LOCATION WITHIN SPACE. COORDINATE LIGHT AND SENSOR LOCATION WITH ARCHITECT PRIOR TO INSTALLATION. LED LIGHT TO BE PROVIDED
WITH FACE PLATE AND INSTALLED FOR CLEAN APPEARANCE.
KEYNOTES
A. REFER TO 1, 2, 3, 4/M5.1 AND SPECIFICATIONS FOR DUCT CONSTRUCTION AND INSTALLATION
REQUIREMENTS.
B. REFRIGERANT PIPING RL/RS/HG SHOWN AS SINGLE LINE FOR CLARITY. ALL REFRIGERANT PIPING TO
BE COPPER, TYPE L, DRAWN-TEMPER TUBING AND WROUGHT COPPER FITTINGS WITH SOLDERED
JOINTS. INSTALL ALL REFRIGERANT PIPING PARALLEL TO OR AT RIGHT ANGLES WITH BUILDING ELEMENTS AND WITH NEAT/CLEAN APPEARANCE. ALL PIPING TO BE SUPPORTED WITH UNISTRUT
SUPPORT AND ALL THREAD RODS SECURELY FASTENED TO STRUCTURAL ELEMENTS. PIPING
ANCHORED TO SHEETROCK OR OTHER NON-STRUCTURAL ELEMENTS IS NOT ACCEPTABLE.
C. REFER TO M2.1 FOR REFRIGERANT SCHEMATIC AND VRF CONTROL SCHEMATIC.
D. DUCT RUNOUTS TO MATCH NECK SIZE UNLESS NOTED OTHERWISE.
GENERAL NOTES
SCALE: 1/8" = 1'-0"1 MECHANICAL FLOOR PLAN
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
M1.1M1.1M1.1M1.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
MECHANICAL FLOOR PLANMECHANICAL FLOOR PLANMECHANICAL FLOOR PLANMECHANICAL FLOOR PLAN
MRMRMRMRMRMRMRMR
1281281281281021021021022R-TX-404-46-102.02R-TX-404-46-102.02R-TX-404-46-102.02R-TX-404-46-102.0
16840
Scale in Feet
1235 4
Scale in meters
HPO-A
BS BOX HPI-5
HPI-4
HPI-3
HPI-1
HPI-2
BS BOX
BS BOX
HPO-B
BS BOX HPI-11
HPI-10
HPI-12
HPI-9
HPI-7
HPI-8
HPI-6
BS BOX
BS BOX
BS BOX
BRC1E71
INTELLIGENT
TOUCH
CONTROLLER
ERV-2
CONTROLLER
HPO-A
HPI-5 HPI-4
HPI-3 HPI-1 HPI-2
HPI-11 HPI-10 HPI-12 HPI-9 HPI-8 HPI-6HPI-7
HPO-B
ERV-1
CONTROLLER
BRC1E71 BRC1E71 BRC1E71
BRC1E71BRC1E71BRC1E71BRC1E71BRC1E71BRC1E71BRC1E71
DI/DO
BOARD(S)
OUTDOOR AIRFLOW STATION
OUTDOOR AIRFLOW STATION
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
M2.1M2.1M2.1M2.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
MECHANCIAL SCHEMATICSMECHANCIAL SCHEMATICSMECHANCIAL SCHEMATICSMECHANCIAL SCHEMATICS
MRMRMRMRMRMRMRMR
1281281281281031031031032R-TX-404-46-103.02R-TX-404-46-103.02R-TX-404-46-103.02R-TX-404-46-103.0
SCALE: NONE2 VRF CONTROL SCHEMATIC
VRF SYSTEM
EACH INDIVIDUAL INDOOR HEAT PUMP TO BE EQUIPPED WITH ZONE CONTROLLER
(BRC1E71) LOCATED IN THE CONDITIONED SPACE. INDOOR HEAT PUMP AND
BRANCH SELECTOR UNIT TO OPERATE TO MAINTAIN SPACE HEATING AND COOLING
TEMPERATURE SET POINTS.
EACH INDOOR HEAT PUMP TO BE EQUIPPED WITH PACKAGED CONDENSATE PUMP
WITH CONTROLS AND A SECONDARY CONDENSATE SENSOR FOR UNIT SHUTDOWN
UPON MOISTURE DETECTION.
OUTDOOR UNIT TO OPERATE TO SATISFY HEATING AND COOLING DEMAND OF EACH
INDOOR UNIT.
PROVIDE CENTRAL CONTROLLER (INTELLIGENT TOUCH CONTROLLER) TO PERFORM
THE FOLLOWING FUNCTIONS:
1. ALL INDOOR UNIT CONTROLLERS TO INTEGRATE WITH CENTRAL
CONTROLLER.
2. CONTROLLER TO HOUSE OPERATING SCHEDULE FOR OCCUPIED AND
UNOCCUPIED SCHEDULED AS WELL AS TEMPERATURE SET POINTS FOR EACH
STATUS.
3. CENTRAL CONTROLLER TO BE EQUIPPED WITH HEATING OPTIMIZATION MODE
THAT WILL CYCLE INDOOR UNIT FANS WHEN IN HEATING MODE.
4. ENABLE AND DISABLE EACH ERV DURING PROGRAMMED OCCUPIED
SCHEDULE. MONITOR ALARM FROM ERV CONTROLLER.
BASIS OF DESIGN FOR VRF SYSTEM IS DAIKIN. DAIKIN, MITSUBISHI, LG
AND SANYO (OR APPROVED EQUAL) ARE APPROVED MANUFACTURER'S.
ALL MANUFACTURERS MUST PROVIDE ALL COMPONENTS OF EQUAL
QUALITY AND FUNCTIONALITY AS THAT OF THE BASIS OF DESIGN. ALL
MANUFACTURERS MUST SUBMIT THE FOLLOWING FOR APPROVAL:
WIRING DIAGRAMS, REFRIGERATION SCHEMATICS AND REQUIREMENTS,
CONTROL SCHEMATICS, SEQUENCE OF OPERATION AND EQUIPMENT
PERFORMANCE DATA. THE SCHEDULED EQUIPMENT PERFORMANCES
ARE MINIMUM VALUES AS INSTALLED IN SYSTEM. ALL VRF SYSTEMS AND
CONTROLS TO BE COMMISSIONED BY FACTORY TRAINED AND
AUTHORIZED PERSONNEL. CONTRACTOR IS RESPONSIBLE TO VERIFY ALL
REFRIGERANT LINE LENGTHS, ROUTING, AND PIPE DIAMETERS WITH
FIELD CONDITIONS PRIOR TO PURCHASE AND INSTALLATION. PROVIDE
TRAINING ON EQUIPMENT OPERATION AND CONTROLLABILITY FOR
OWNER AND STAFF.
SEQUENCE OF OPERATIONSEQUENCE OF OPERATIONSEQUENCE OF OPERATIONSEQUENCE OF OPERATION
SCALE: NONE1 REFRIGERANT PIPING SCHEMATIC
ERV-1
ERV UNIT TO BE EQUIPPED WITH STAND ALONE CONTROLLER TO PERFORM ALL CONTROL
AND MONITORING FUNCTIONS. ERV TO MAINTAIN 75 °F DB/62 °F WB DAT DURING
COOLING OPERATION. DURING HEATING OPERATION ERV TO MAINTAIN 72 °F DAT.
DAIKIN CENTRAL CONTROLLER TO ENABLE AND DISABLE ERV OPERATION ( DIGITAL
INPUT). EXHAUST AND SUPPLY FANS OPERATES CONTINUOUSLY WHEN ENABLED. OPEN
INTAKE AND DISCHARGE MOTORIZED DAMPERS WHEN UNIT IS ENABLED. SEND ALARM
TO DAIKIN CENTRAL CONTROLLER (DIGITAL OUTPUT).
ERV-2
ERV UNIT TO BE EQUIPPED WITH STAND ALONE CONTROLLER TO PERFORM ALL CONTROL
AND MONITORING FUNCTIONS. DURING HEATING OPERATION ERV TO MAINTAIN 65°F
DAT. DAIKIN CENTRAL CONTROLLER TO ENABLE AND DISABLE ERV OPERATION (DIGITAL
INPUT). EXHAUST AND SUPPLY FANS OPERATES CONTINUOUSLY WHEN ENABLED. OPEN
INTAKE AND DISCHARGE MOTORIZED DAMPERS WHEN UNIT IS ENABLED. SEND ALARM
TO DAIKIN CENTRAL CONTROLLER (DIGITAL OUTPUTS).
OUTDOOR AIRFLOW MEASUREMENT STATION
AIR FLOW MONITOR TO SEND DI/DO BOARD A BINARY OUTPUT TO ALARM I-TOUCH
CONTROLLER WHEN OUTSIDE AIRFLOW DECREASES 15% BELOW SCHEDULED OUTDOOR
AIR SUPPLY CFM OF ERV UNITS IN COMPLIANCE WITH LEED IEQ CREDIT 1..
SEQUENCE OF OPERATION CONT.SEQUENCE OF OPERATION CONT.SEQUENCE OF OPERATION CONT.SEQUENCE OF OPERATION CONT.
DDDD AAAABBBB
DDDD AAAABBBB
HPI-10
170-
12"/12"10"/10"
8"/8"
12"/12"12"/18"12"/12"
HPI-6
10"/12"
6"/8" 12"/10" 8"ø
38"ø
12"/18"
14"/16"
12"/12"
12"/10"
8"/6"
8"ø
12"ø 1
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
M3.1M3.1M3.1M3.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
MECHANICAL SECTIONSMECHANICAL SECTIONSMECHANICAL SECTIONSMECHANICAL SECTIONS
MRMRMRMRMRMRMRMR
1281281281281041041041042R-TX-404-46-104.02R-TX-404-46-104.02R-TX-404-46-104.02R-TX-404-46-104.0
SCALE: 1/4" = 1'-0"1 MECHANICAL SECTION - ADMINISTRATION
SCALE: 1/4" = 1'-0"2 MECHANICAL SECTION - CONFERENCE
16840
Scale in Feet
1235 4
Scale in meters
16840
Scale in Feet
1235 4
Scale in meters
1 APPROXIMATE LOCATION OF BS BOX.
2 DUCT INTENDED TO BE ROUTED UP WITHIN STRUCTURE. COORDINATE ROUTING THROUGH
STRUCTURAL WITH GENERAL CONTRACTOR AND OTHER TRADES.
3 INDOOR HEAT PUMP LOCATED ABOVE CEILING. COORDINATE FINAL LOCATION WITH GENERAL
CONTRACTOR AND OTHER TRADES.
4 OFFSET DUCT UP TO ABOVE CORRIDOR CEILING.
KEYNOTES
A. REFER TO 1, 2, 3, 4/M5.1 AND SPECIFICATIONS FOR DUCT CONSTRUCTION AND INSTALLATION
REQUIREMENTS.
B. REFRIGERANT PIPING RL/RS/HG SHOWN AS SINGLE LINE FOR CLARITY. ALL REFRIGERANT PIPING TO
BE COPPER, TYPE L, DRAWN-TEMPER TUBING AND WROUGHT COPPER FITTINGS WITH SOLDERED
JOINTS. INSTALL ALL REFRIGERANT PIPING PARALLEL TO OR AT RIGHT ANGLES WITH BUILDING ELEMENTS AND WITH NEAT/CLEAN APPEARANCE. ALL PIPING TO BE SUPPORTED WITH UNISTRUT
SUPPORT AND ALL THREAD RODS SECURELY FASTENED TO STRUCTURAL ELEMENTS. PIPING
ANCHORED TO SHEETROCK OR OTHER NON-STRUCTURAL ELEMENTS IS NOT ACCEPTABLE.
C. REFER TO M2.1 FOR REFREGERANT SCHEMATIC AND VRF CONTROL SCHEMATIC.
D. DUCT RUNOUTS TO MATCH NECK SIZE UNLESS NOTED OTHERWISE.
GENERAL NOTES
FD FD
128128128128
CLOSETCLOSETCLOSETCLOSET
129129129129
CORRIDORCORRIDORCORRIDORCORRIDOR
OFFICEOFFICEOFFICEOFFICE
122122122122
CLOSETCLOSETCLOSETCLOSET
122A122A122A122A
S S
S
F F
S
S
S
S
S
S
S
VESTIBULEVESTIBULEVESTIBULEVESTIBULE
101101101101
CORRIDORCORRIDORCORRIDORCORRIDOR
OFFICEOFFICEOFFICEOFFICE
104104104104
105105105105
RESOURCERESOURCERESOURCERESOURCE
106106106106
S
S
HPI-4
HPI-5
EWH-1
7 12"ø
10"/10"
8"/6"
14"/14"
18"/10"
18"/10"
18"/10"
18"/10"
HPI-3
10"/10"
14"/14"
16"/16"
12"ø
12"ø
16"/16"
14"/12"
10"/10" 11
1 1
14"/12" 14"/12"
12"ø 10"/10"
R L/
R S
/H G
RL/RS/HG
RL/RS/HG
R
L/ R
S
RL/RS
R L/
R S
/H G
12"ø
18"/14"
18"/10"18"/14"
16"/14"
10"/10"
1 1
12"/12"
18"/12"
18"/12"
HPI-6
HPI-7
HPI-8
HPI-10
HPI-9
16"/16"
8"/8"
8"/10"
12"/10"
10"/10"
8"/6"
8"/6"
14"/14"
12"ø
12"ø
6"/6"
6"/6"
8"/8"
10"/10"
78"ø
12"/12"
12"/12"
12"/10"
8"/6" -
8"/6"
8"/8"
12"/10"
12"/12"
RL/RS/HG
RL/R
S/H
G
RL/R
S/H
G
RL/RS
RL/RS
RL/RS
RL/RS
RL/RS/HG
RL/RS
RL/RS
RL/R
S
RL/RS
RL/RS
RL/R
S
8"ø
8"ø
8"ø
102 104
RL/RS
12"/10"
18"/12"
16"/14"
14"/12"
8"/6"
12"/10"
14"/12"
8"ø
12"/12"
HPI-11
10"/10"
12"/10"
12"/10" 8"/6"
HPI-12
12"/10"
8"/6"
8"/6"
4"ø
RL/RS
RL/R
S
RL/RS
RL/R
S
102 104
4"ø
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
M4.1M4.1M4.1M4.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
ENLARGED MECHANICAL FLOOR PLANENLARGED MECHANICAL FLOOR PLANENLARGED MECHANICAL FLOOR PLANENLARGED MECHANICAL FLOOR PLAN
MRMRMRMRMRMRMRMR
1281281281281051051051052R-TX-404-46-105.02R-TX-404-46-105.02R-TX-404-46-105.02R-TX-404-46-105.0
SCALE: 1/4" = 1'-0"2 ENLARGED MECHANICAL FLOOR PLAN - B
1 DUCT INTENDED TO BE ROUTED UP WITHIN STRUCTURE. COORDINATE ROUTING THROUGH
STRUCTURAL WITH GENERAL CONTRACTOR AND OTHER TRADES.
2 LOCATION OF 24 V I-TOUCH CONTROLLER.
3 LOCATION OF (208/1) DI/DO BOARD.
4 COORDINATE DUCT ROUTING ABOVE CEILING WITH LIGHTING LAYOUT.
5 INDOOR HEAT PUMP LOCATED ABOVE CEILING. COORDINATE FINAL LOCATION WITH GENERAL
CONTRACTOR AND OTHER TRADES.
6 LOCATE HEAT PUMP IN OPEN CEILING SPACE OF JANITOR’S CLOSET.
7 APPROXIMATE LOCATION OF ZONE SENSOR. PROVIDE VANDAL RESISTANT LOCKABLE COVER FOR
SENSOR LOCATED WITH IN PUBLIC ACCESS. COORDINATE FINAL LOCATION WITH ARCHITECT.
8 OFFSET DUCT UP TO ABOVE CORRIDOR CEILING.
9 APPROXIMATE LOCATION OF BS BOX.
10 BALANCE DAMPER TO PROVIDE SCHEDULED OSA CFM.
11 12/10 RA DUCT FROM HP-11 IS ROUTED BELOW 10/10 RA DUCT FROM HP-11. OFFSET 10/10 RA DUCT UP AFTER BRANCH TAKEOFF TO OFFICE 104 SO 10/10 RA DUCT IS ROUTED ABOVE HP-11 AS IT HEADS TOWARDS OFFICE 106. 10/10 RA DUCT IS INTENDED TO ROUTE WITHIN STRUCTURE.
12 LOCATE DUCT AS LOW AS POSSIBLE AS IT ENTERS BUILDING (APPROX 12” ABOVE GRADE TO
BOTTOM OF DUCT). COORDINATE FINAL HEIGHT WITH ARCHITECTURAL.
13 COORDINATE FINAL LOCATION OF FIRE DAMPER IN RATED ASSEMBLY AND ACCESS PANEL WITH
ARCHITECTURAL.
14 COORDINATE DUCT PENETRATION THROUGH SHEAR WALL WITH GENERAL CONTRACTOR.
15 PROVIDE C02 SENSOR IN SPACE TO COMPLY WITH LEED IEQ CREDIT 1. SENSOR TO BE KELE CD-AW-R-LCD (OR APPROVED EQUAL) WITH HIGH LIMIT ALARM RELAY AND LCD DISPLAY. SENSOR TO BE MOUNTED ON WALL 3’ TO 6’ AFF. PROVIDE BRIGHT RED FLASHING LED LIGHT LINKED TO HIGH LIMIT ALARM. LOCATE LED LIGHT IN VISIBLE LOCATION WITHIN SPACE. COORDINATE LIGHT AND SENSOR LOCATION WITH ARCHITECT PRIOR TO INSTALLATION. LED LIGHT TO BE PROVIDED
WITH FACE PLATE AND INSTALLED FOR CLEAN APPEARANCE.
KEYNOTES
A. REFER TO 1, 2, 3, 4/M5.1 AND SPECIFICATIONS FOR DUCT CONSTRUCTION AND INSTALLATION
REQUIREMENTS.
B. REFRIGERANT PIPING RL/RS/HG SHOWN AS SINGLE LINE FOR CLARITY. ALL REFRIGERANT PIPING TO
BE COPPER, TYPE L, DRAWN-TEMPER TUBING AND WROUGHT COPPER FITTINGS WITH SOLDERED
JOINTS. INSTALL ALL REFRIGERANT PIPING PARALLEL TO OR AT RIGHT ANGLES WITH BUILDING ELEMENTS AND WITH NEAT/CLEAN APPEARANCE. ALL PIPING TO BE SUPPORTED WITH UNISTRUT
SUPPORT AND ALL THREAD RODS SECURELY FASTENED TO STRUCTURAL ELEMENTS. PIPING
ANCHORED TO SHEETROCK OR OTHER NON-STRUCTURAL ELEMENTS IS NOT ACCEPTABLE.
C. REFER TO M2.1 FOR REFRIGERANT SCHEMATIC AND VRF CONTROL SCHEMATIC.
D. DUCT RUNOUTS TO MATCH NECK SIZE UNLESS NOTED OTHERWISE.
GENERAL NOTES
SCALE: 1/4" = 1'-0"1 ENLARGED MECHANICAL FLOOR PLAN - A
SCALE: 1/4" = 1'-0"3 ENLARGED MECHANICAL FLOOR PLAN - C
Scale in Feet
1000 02000
Scale in mm
Scale in Feet
1000 02000
Scale in mm
Scale in Feet
1000 02000
Scale in mm
1.
KEYNOTES:
45° TAP AND DAMPER
L
W
ASSEMBLY IS PRE
MANUFACTURED. DO NOT
FABRICATE IN SHOP OR FIELD
2. RIGID ROUND DUCT SEE
PLANS FOR LENGTH. WRAP
WITH EXTERNAL INSULATION
3. SEE SECTION A
4. INSULATED FLEX DUCT MAX
LENGTH 8'-0"
5. CEILING DIFFUSER
6. LOCKING QUADRANT HANDLE
OR REMOTE CEILING OPERATOR
WHERE DAMPER INACCESSIBLE
7. 24 GA.
8. AIR FLOW
11.
KEYNOTES CONT:
INSULATION
B. AREA OF LxW SHALL BE EQUAL TO 1.5 x AREA
BRANCH DUCT
9. NYLON CLAMP OVER
INSULATION
10. NYLON CLAMP OVER FLEX
DUCT
12. FLEX DUCT
13. RIGID ROUND DUCT OR
DIFFUSER COLLAR
A.
NOTES:
TAKE-OFFS SHOULD NOT BE
INSTALLED CLOSER THAN TWO
DUCT WIDTHS TO ELBOWS OR
INTERSECTIONS
SECTION A
WHERE REQUIRED
(OPERATE EXTENSION WHERE
INSULATED)
TRANSVERSE REINFORCING (1)
DIMENSION OF LONGEST
SIDE (IN)
SHEET METAL GAGE
(ALL FOUR SIDES)
MIN. REINFORCING ANGLE
SIZE AND MAX. LONGITUDINAL
SPACING BETWEEN TRANSVERSE
AT JOINTS
SLIP
PLAIN
S SLIP
DRIVE
HEMMED
S SLIP
ALTER'NT
BAR SLIP
H
REIN-
FORCED
BAR SLIP
H
MIN.
H.
IN.
UP THRU 12 26 NONE REQUIRED 26
RECOMMENDED
GAGE
JOINTS AND OR INTERMEDIATE
REINFORCING
RECOMMENDED
GAGE
RECOMMENDED
GAGE
RECOMMENDED
GAGE
1 26 24 24
13 THRU 18 24 NONE REQUIRED 241 24 24 24
19 THRU 30 24 1"x1"x1/8" AT 60" -1 24 24 24
31 THRU 36 22 1"x1"x1/8" AT 60" -1 - 22 22
(1) TRANSVERSE REINFORCING SIZE IS DETERMINED BY DIMENSION OF SIDE TO WHICH ANGLE IS APPLIED
(2) LONGITUDINAL JOINTS TO BE PITTSBURGH OR SNAP LOCK TYPE
1.
KEYNOTES:
DUCT LINER
2. 5/8" GYPSUM BOARD
3. BOTTOM CHORD OF TRUSSED
RAFTER OR I JOIST
4. 1-1/4" MIN PENETRATION
5. #10x3/4" SELF TAPPING
GALVANIZED SHEET METAL
SCREWS TO ANCHOR STRAPS
TO DUCT. ALL STRAPS TO BE
TIGHT AGAINST DUCT AND
SUPPORT MEMBERS (TYPICAL)
NO POP RIVETS ALLOWED
6. 1"x18 GAGE STRAP HANGERS
AT 8'-0" MAX. SPACING
7. (1) #10x2" WOOD SCREWS
AT EACH TRUSS CHORD (TYP)
2"
8. DOUBLE SHEET METAL STRAP
BACK OVER
6 6
1.
KEYNOTES:
2'-0" MAX
2. FOR UPPER ATTACHMENT SEE
DUCT STRAP HANGER DETAIL
3. 1"x18" GAGE BAND CLAMP
4. MAX. SAG 1/2"/FT. OF
SUPPORT SPACING
V A R
IE
S
1. ANGLE IRON UNISTRUT P1026
TYPICAL OF 4
2. 18 GAUGE GALVANIZED SHEET
METAL PROTECTIVE COVER.
RUN FROM COND. UNIT TO
BUILDING
3. 1 5/8"x1 5/8" UNISTRUT
CHANNEL GALVANIZED (TYP)
4. CONCRETE
5. SECURE REFRIGERANT PIPING
TO SUPPORTS WITH
"HYDRA-ZORB" "CUSH-A-
CLAMP" OR EQUAL (TYP)
6. BUTT INSULATION OF SUCTION
LINE AGAINST CLAMP ASSEMBLY
7. UNISTRUT PIPE CLAMP (TYP)
KEYNOTES:
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
M5.1M5.1M5.1M5.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
MECHANICAL DETAILSMECHANICAL DETAILSMECHANICAL DETAILSMECHANICAL DETAILS
MRMRMRMRMRMRMRMR
1281281281281061061061062R-TX-404-46-106.02R-TX-404-46-106.02R-TX-404-46-106.02R-TX-404-46-106.0
NO SCALE
BRANCH DUCT AND GRILLE1
NO SCALE
DUCT CONSTRUCTION2
NO SCALE
DUCT STRAP HANGER3
NO SCALE
FLEXIBLE DUCT SUPPORT4
NO SCALE
EXTERIOR REFRIGERANT PIPE SUPPORT5
DESIGN:DESIGN:DESIGN:DESIGN: DRAWN:DRAWN:DRAWN:DRAWN: CHECK:CHECK:CHECK:CHECK:
DRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBERDRAWING FILENAME AND NUMBER
HAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGEHAGERMAN NATIONAL WILDLIFE REFUGE
HEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDINGHEADQUARTERS/VISITOR BUILDING
GRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTYGRAYSON COUNTY TEXASTEXASTEXASTEXAS
UNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIORUNITED STATES DEPARTMENT OF THE INTERIOR
U.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICEU.S. FISH AND WILDLIFE SERVICE DIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERINGDIVISION OF ENGINEERING
DATE:DATE:DATE:DATE:
HAGERMAN NWRHAGERMAN NWRHAGERMAN NWRHAGERMAN NWR SHT NO:SHT NO:SHT NO:SHT NO: SEQ NO:SEQ NO:SEQ NO:SEQ NO:
OFOFOFOF
PRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTIONPRELIMINARY, NOT FOR CONSTRUCTION
MECHANICALMECHANICALMECHANICALMECHANICAL
M6.1M6.1M6.1M6.1
03/23/1003/23/1003/23/1003/23/10
JJJJJJJJ
MECHANICAL SCHEDULESMECHANICAL SCHEDULESMECHANICAL SCHEDULESMECHANICAL SCHEDULES
MRMRMRMRMRMRMRMR
1281281281281071071071072R-TX-404-46-107.02R-TX-404-46-107.02R-TX-404-46-107.02R-TX-404-46-107.0
MARK
HEAT PUMP - INDOOR UNIT (HPI)
MANUFACTURER
& MODEL NO.
DIMENSIONS
L (IN)
ELECTRICAL
VOLT/PH MCA
REMARKS
W (IN) H (IN)
HPI-1 990 N/A N/A 8.1 17.9 24.8 208/1 1.2 15 33 33 12 75 DAIKIN FXFQ *,**,****
HPI-2 990 N/A N/A 8.1 17.9 24.8 208/1 1.2 15 33 33 12 75 DAIKIN FXFQ *,**,****
HPI-3 340 N/A 0.37 6.4 7.0 7.1 208/1 0.7 15 32 22 12 69 DAIKIN FXSQ *,**,***
HPI-4 990 N/A 0.57 11.4 20.5 24.2 208/1 1.8 15 32 56 12 119 DAIKIN FXSQ *,**,***
HPI-5 950 N/A 0.57 11.4 20.5 24.2 208/1 1.8 15 32 56 12 119 DAIKIN FXSQ *,**,***
HPI-6 1300 515 0.34 21.6 23.0 36.4 208/1 2.4 15 32 56 12 119 DAIKIN FXSQ *,**,***
HPI-7 530 60 0.38 4.2 8.2 10.6 208/1 1.0 15 32 28 12 66 DAIKIN FXSQ *,**,***
HPI-8 260 N/A N/A 0.5 4.2 4.2 208/1 0.3 15 32 9 12 31 DAIKIN FXAQ **,****,*****
HPI-9 950 145 0.57 8.4 13.6 19.6 208/1 1.8 15 32 56 12 119 DAIKIN FXSQ *,**,***
HPI-10 950 95 0.57 8.6 15.1 18.6 208/1 1.8 15 32 56 12 96 DAIKIN FXSQ *,**,***
HPI-11 530 50 0.38 5.1 8.8 10.4 208/1 1.0 15 32 28 12 66 DAIKIN FXSQ *,**,***
HPI-12 320 20 N/A 2.4 3.2 3.9 208/1 0.8 15 28 28 12 48 DAIKIN FXZQ **,****
CFM ESP
MFS
MARK
HEAT PUMP - OUTDOOR (HPO)
MAX. DIMENSIONSELECTRICAL
MCA
REMARKS*
(MBH)
NOM COOLING
(°F)
OSA TEMP.
VOLT/PHASE H (IN)MFS D (IN) W (IN) WT (LBS)
HPO-A 144 100 208/3 72.2 80 67 31 52 600 DAIKIN REYQ144
HPO-B 120 100 208/3 44.2 50 67 31 52 800 DAIKIN REYQ120
*SUMMER OUTDOOR AMBIENT (DB/WB °F): 100/76, WINTER OUTDOOR AMBIENT (DB°F): 15
MIN SEN
CAPACITY
(MBH)**
MIN
HEATING
(MBH)** WT (LBS)
TOT. SEN
CAPACITY
(MBH)**
MARK
ENERGY RECOVERY VENTILATOR (ERV)
WINTER**
EAT
KW
UNIT ELECTRICAL*
MOP
VOLT/
PH
MCA
MANUFACTURER
MODEL ***
ERV-1 500 885 0.65 0.65 15/14 46/40 99/76 86/69 9 65 N/A N/A N/A 1/4 1/4 1.98 15 208/3 25 40 208/3 41 91 50 1,400 COOK ERV
ERV-2 1,000 1,770 0.65 0.65 15/14 43/40 99/76 86/70 18 72 86/70 55/54 75/62 1.0 1.5 33.8 40 208/3 62.5 70 208/3 53 135 53 2,500 VENMAR VHC
EXHAUST
CFM
SUPPLY
CFM
SUPPLY EXHAUST
ESP
(DB/WB)
LAT
(DB/WB)
SUMMER**
EAT
(DB/WB)
LAT
(DB/WB)
HEAT WHEEL
HEATING
(DB)
EAT
(DB/WB)
LAT
(DB/WB)
DX COOLING
EXHAUST
FAN (HP)
SUPPLY
FAN (HP)LAT
(DB/WB)
1 SUPPLY 24"x12" 22"x10" N/A 685 0.03 15 TITUS 272RS 22.5° DEFLECTION
2 RETURN 18"x18" 16"x16" N/A 970 0.07 24 TITUS 300R O° DEFLECTION
3 ADJUSTABLE
LOUVERED
24"x24" 8"Ø GRID 300 0.13 26 TITUS TDCA 18"x18" CORE
4 ADJUSTABLE
LOUVERED
24"x24" 10"Ø GRID 400 0.12 27 TITUS TDCA 18"x18" CORE
5 PERFORATED
RETURN
22"x10" 24"x12" GRID 600 0.06 10 TITUS PXP -
6 ADJUSTABLE
LOUVERED
24"x24" 12"Ø GRID 550 0 .11 26 TITUS TDCA 18"x18" CORE
7 PERFORATED
RETURN
24"x24" 22"x22" GRID 1200 0.05 17 TITUS PXP -
8 LOUVERED
SUPPLY
12"x12" 6"Ø SURFACE 120 0.06 15 TITUS TDC 9"x9" CORE
9 PERFORATED
EXHAUST
10"x10" 8"x8" SURFACE 190 0.12 10 TITUS 8F -
10 PERFORATED
EXHAUST
12"x12 14"x14" SURFACE 440 0.12 11 TITUS 8F -
11 LOUVERED
SUPPLY
12"x12" 8"Ø SURFACE 175 0.07 16 TITUS TDC 9"x9" CORE
12 RETURN 22"x22" 20"x20" N/A 1300 0.08 24 TITUS 300R -
13 LOUVERED
SUPPLY
18"x18" 12"Ø SURFACE 390 0.09 20 TITUS TDC 12"x12" CORE
14 ADJUSTABLE
LOUVERED
24"X24" 10"Ø GRID 400 0.12 27 TITUS TDCA 18"x18" CORE
15 RETURN 12"x12" 10"x10" N/A 280 0.06 25 TITUS 300R -
MARK
AIR DEVICE
MAX. T.P.
(IN WC)
N.C. LEVEL
MAX.
MANUFACTURER
& MODEL NO. REMARKS**TYPE &
DUTY
FACE
SIZE
NECK
SIZE
CEILING*
TYPE
MAX.
CFM
CFM
AIR DEVICE #
* VERIFY FRAME TYPE OF ALL AIR DEVICES WITH ARCHITECTURAL REFLECTED CEILING PLAN BEFORE ORDERING ** TITUS, PRICE, AND METAL AIRE (OR APPROVED EQUAL) ARE APPROVED MANUFACTURER'S. COLOR BY ARCHITECT
REFER TO M2.1 FOR REFRIGERATION AND CONTROL SCHEMATIC AND APPROVED MANUFACTURER'S.
*UNIT TO BE EQUIPPED WITH CONDENSATE PUMP AND HIGH WATER KIT.
**RATINGS ARE BASED ON SPACE TEMPERATURE OF 75°F/50%RH FOR COOLING AND 72°F FOR HEATING.
***PROVIDE FACTORY FILTER KIT WITH LONG LIFE WASHABLE FILTER.
****PROVIDE LONG LIFE WASHABLE FILTER.
*****PROVIDE WITH CONDENSATE PUMP (MINI AQUA (OR APPROVED EQUAL), 240/1, 16 W).
*UNIT REQUIRES TWO SEPARATE ELECTRICAL CONNECTIONS
**INDOOR RETURN TEMPERATURES: SUMMER (DB/WB) 75/62; WINTER (DB) 72, 35% RH.
***COOK, VENMAR, AND GREENHECK (OR APPROVED EQUAL) ARE APPROVED MANUFACTURERS. UNIT TO BE FOR OUTDOOR INSTALLATION. PROVIDE WITH HAIL GUARD.
OSA
CFM
ELECTRIC
LAT
POST HEAT ELECTRICAL*
MOP
VOLT/
PH
MCA
REHEAT
ELECTRIC MAX DIMENSIONS
L(IN)H(IN) W(IN) WT(LBS)
MARK
MOTORIZED DAMPER SCHEDULE (MD)
MANUFACTURER
& MODEL NO.**
DIMENSIONS* (IN)
HEIGHTWIDTH
VOLTAGE WATTS REMARKS
MD-1 14 12 120 6 RUSKIN CD60 BELIMO ACTUATOR, POWER CLOSE/SPRING OPEN,
AIRFOIL BLADE
MD-2 12 10 120 6 RUSKIN CD60 BELIMO ACTUATOR, POWER CLOSE/SPRING OPEN,
AIRFOIL BLADE
MD-3 14 14 120 6 RUSKIN CD60 BELIMO ACTUATOR, POWER CLOSE/SPRING OPEN,
AIRFOIL BLADE
MD-4 16 16 120 6 RUSKIN CD60 BELIMO ACTUATOR, POWER CLOSE/SPRING OPEN,
AIRFOIL BLADE
*FINAL DIMENSIONS TO BE COORDINATED WITH DUCT DIMENSIONS AFTER COORDINATION WITH ALL TRADES AND FIELD CONDITIONS.
**RUSKIN, POTTORFF, & HONEYWELL (OR APPROVED EQUAL) ARE APPROVED MANUFACTURER'S.
3/23/2010
File details come from the government source that posted it. Updated .