A06_GETT25763_Benner_House_Drawings_Revised_20DEC2022.pdf
PDF 6 MB Posted
- Attached to
- REHABILITATION THE JOSIAH BENNER HOUSE
- Solicitation number
- 140P4223R0002
About this file
This solicitation is for a firm-fixed price contract to rehabilitate the Josiah Benner House, spring house and summer kitchen located in Gettysburg National Military Park in Gettysburg, Pennsylvania. The work includes all construction, labor, supplies, materials, tools and equipment necessary to rehabilitate the exterior and interior of the structures.
The acquisition is set aside for competitive offers from women-owned small businesses. The NAICS code is 236118 with a small business size standard of $39.5 million. The project magnitude is estimated between $500,000 to $1 million. The contract performance period is 240 calendar days from notice to proceed. An organized site visit is scheduled for May 31 at 1:00 PM at the project location.
Vendors must have an active SAM registration and DUNS number to conduct business with the National Park Service, which is the contracting agency. Questions must be sent to the specified contracting officer by the stated deadline.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_140P4223R0002_Amd_0002.pdf | ||
| RFI_Responses_0001.pdf | ||
| Benner_House_Images_0001.pdf | ||
| WD_PA20230117_0001.pdf | ||
| Sol_140P4223R0002_Amd_0001.pdf | ||
| A04_GETT_257363_Benner_House_Specifications_revised.pdf | ||
| B03_Wage_Determination.pdf | ||
| Experience_Questionnaire.docx | DOCX document | |
| Roadwork_Experience_Questionnaire.docx | DOCX document | |
| Sol_140P4223R0002.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A/E FIRM - XXXXXX Mark Sheet REVISION Date Initial QUALITY DESIGN CERTIFICATION Prepared in Accordance with Design
Development (Title I)
OR
Variance from Design Development (Title I)
Approved by Superintendent on
OR
Construction Drawing Not Preceded by Design Development (Title I)
Drawing No.
Date
Project Manager Date
UNITED STATES
TITLE OF DRAWING
DEPARTMENT OF THE INTERIOR
LOCATION WITHIN PARK
NAME OF PARK
REGION COUNTY STATE
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
NAME
CITY, STATE
CIVIL:
NAME
CITY, STATE
STRUCTURAL:
NAME
CITY, STATE
MECHANICAL:
NAME
CITY, STATE
ELECTRICAL:
NAME
CITY, STATE
PLUMBING:
NAME
CITY, STATE
FIRE PROTECTION:
NAME
CITY, STATE
CS DAVIDSON
GETTYSBURG, PA
HENRY ADAMS
TOWSON, MD
HENRY ADAMS
TOWSON, MD
HENRY ADAMS
TOWSON, MD
HENRY ADAMS
TOWSON, MD
CS DAVIDSON
GETTYSBURG, PA
SGH
WASHINGTON, DC
P15PC00037
:1 :0
P M
C A u to d e s k L o c a l F il e s B e n n e r H o u s e C D s c o tt m o ir .r v t
ISSUED FOR BID
NPS Office Responsible
REHABILITATE THE JOSIAH BENNER HOUSE, SPRINHOUSE
AND SUMMER KITCHEN
GETTYSBURG, PA
GETTYSBURG NATIONAL MILITARY PARK
1 ADAMS PENNSYLVANIA
178321
257363
1 95
BASIC DATA: 305/41,029A 2/90; 305/40,003C; PARK
MINI FOLDER 1990; REVISED & REDRAWN 2/94. UPDATED
11/98.SGS.
500 0 500 1000
JOSIAH BENNER HOUSE
PROJECT SITE MAP
PROJECT SITE
GETTYSBURG NATIONAL MILITARY PARK
REHABILITATE THE JOSIAH BENNER HOUSE, SPRINGHOUSE AND SUMMER KITCHEN
PROJECT SITE
PROJECT AREA
INDEX OF DRAWINGS
Fire Protection
Sheet Sub Sheet Title of Sheet
54 FP0.0 Fire Protection Cover Sheet
55 F1.1 Cellar New Work Fire Protection
56 F1.2 First Floor New Work Fire Protection
57 F1.3 Second Floor New Work Fire Protection
58 F1.4 Attic New Work Fire Protection
59 FA0.1 Fire Alarm Cover Sheet
60 FA1.0 Cellar Fire Alarm New Work
61 FA1.1 First Floor Fire Alarm New Work
62 FA1.2 Second Floor Fire Alarm New Work
63 FA1.3 Attic Fire Alarm New Work
General
Sheet Sub Sheet Title of Sheet
1 CS 1 Cover Sheet
2 CS 2 Index of Drawings
3 CS 3 Abbreviations, Symbols and Materials
4 CS 4 Code Sheet and Egress Plan
CML
5 C1 Existing Conditions Demolition Plan
6 C2 Site Grading / Utility Improvements Plan
7 C3 EAS Control Notes and Details
8 C4 Construction Details
9 C5 Construction Details
10 AS1 Architectural Site Plan
Mechanical
11 M0.0 Mechanical Cover Sheet
12 M01.1 Cellar Demolition Mechanical
13 M01.2 First Floor Demolition Mechanical
14 M01.3 Second Floor Demolition Mechanical
15 M1.1 Cellar New Work Mechanical
16 M1.2 First Floor New Work Ductwork
17 M1.3 Second Floor New Work Ductwork
18 M1.4 Attic New Work Mechanical
19 M5.1 Details
20 M6.1 Automatic Temperature Controls
21 M7.1 Mechanical Schedules
Plumbing
22 P0.0 Plumbing Cover Sheet
23 P01.1 Cellar Demolition Plumbing
24 P01.2 First Floor Demolition Plumbing
25 P01.3 Second Floor Demolition Plumbing
26 P0.1 Foundation New Work Plumbing
27 P1.1 Cellar New Work Plumbing
28 P1.2 First Floor New Work Plumbing
29 P1.3 Second Floor New Work Plumbing
30 P1.4 Attic New Work Plumbing
31 P1.5 Roof New Work Plumbing
32 P5.1 Plumbing Details and Schedule
33 P6.0 Plumbing Riser Diagrams
Electrical
34 E0.1 Electrical Cover Sheet
35 E0.2 Electrical General Notes
36 ED1.0 Cellar Electrical Demolition
37 ED1.1 First Floor Electrical Demolition
38 ED1.2 Second Floor Electrical Demolition
39 ED1.3 Roof Electrical Demolition
40 E1.0 Cellar Power New Work
41 E1.1 First Floor Power New Work
42 E1.2 Second Floor Power New Work
43 E1.3 Attic and Roof Power New Work
44 E2.0 Cellar Lighting New Work
45 E2.1 First Floor Lighting New Work
46 E2.2 Second Floor Lighting New Work
47 E2.3 Attic Lighting Plan
48 E5.1 Electrical Details
49 E5.2 Electrical Details
50 E6.1 Electrical One-Line Diagram
51 E8.1 Luminaire Schedule
52 E8.2 Electrical Equipment Schedules
53 E8.3 Panelboard Schedules
CMU
PLASTER/ GWB
SURFACES
STEEL (LARGE SCALE)
STEEL (SMALL SCALE)
CONCRETE
GRAVEL / DRAIN ROCK
PLYWOOD
BLOCKING
(INTERMITTENT/ AS REQ)
END GRAIN LUMBER
(CONTINUOUS)
BATT/ ACOUSTICAL INSULATION
RIGID INSULATION
COMPACTED EARTH
BRICK
FLASHING
GLASS (ELEVATION)
KEY TO MATERIALS
SEE MECHANICAL, ELECTRICAL, AND PLUMBING
DRAWINGS FOR SYMBOLS RELATING TO M.E.P. WORK
(ARCHITECTURAL
DRAWINGS ONLY)
BRICK ELEVATION
SAND, GROUT OR MORTAR
AGGREGATE
BACKFILL
ROCK SURFACE
FINISH WOOD
WALL TYPE
WINDOW TYPE
DOOR NUMBER
ROOM IDENTIFICATION
DEMOLITION NOTE
CONSTRUCTION NOTE
REFERENCE POINT
ACCESSORY
DETAIL/ PARTIAL
SECTION
REFERENCE
ELEVATION
REFERENCE
SECTION
REFERENCE
NEW WORK
KEY TO SYMBOLS
SEE MECHANICAL, ELECTRICAL, AND
PLUMBING
DRAWINGS FOR SYMBOLS RELATING
TO M.E.P. WORK
(ARCHITECTURAL DRAWINGS ONLY)
EXISTING
WORK
X.X
X.X
X
X
X
NAME
XXX
X
A A1
A A1
SIM
A1
SIM
X
A/E ARCHITECTURE/ENGINEERING
ABA ARCHITECTURAL BARRIERS ACT
ABAAS ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
ADA AMERICANS WITH DISABILITIES ACT
ADD ADDITION
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
APPROX APPROXIMATELY
AW AWNING
BLDG BUILDING
BLTS BOLTS
BO BOTTOM OF
CL CENTERLINE
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
DH DOUBLE-HUNG
DIA/ø DIAMETER
DWGS DRAWINGS
EL/ELEV ELEVATION
EQ EQUAL
ETR EXISTING TO REMAIN
EX/EXT EXISTING
FCU FAN COIL UNIT
F FIXED
FF FINISHED FLOOR
FP.X FIRE PLACE
GL GLASS, GLAZING
GWB GYPSUM WALL BOARD
HABS HISTORIC AMERICAN BUILDING SURVEY
HM HOLLOW METAL
HSR HISTORIC STRUCTURE REPORT
IBC INTERNATIONAL BUILDING CODE
IEBC INTERNATIONAL EXISTING BUILDING CODE
INT INTERIOR
LARPM LIQUID-APPLIED REINFORCED POLYMER MEMBRANE
LG LARGE
MAL MATERIAL
MIN MINIMUM
MAX MAXIMUM
MEP MECHANICAL/ELECTRICAL/PLUMBING
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NPS NATIONAL PARK SERVICE
OC ON CENTER
OH OPPOSITE HAND
OZ OUNCE
PART PARTIAL
PT PRESSURE-TREATED
REF REFRIGERATOR
REQ'D REQUIRED
RM ROOM
SF SQUARE FEET
SH SINGLE-HUNG
SI SQUARE INCH
SIM SIMILAR
SM SMALL
SS STAINLESS STEEL
TECH TECHNICAL
TYP TYPICAL
USPP UNITED STATES PARK POLICE
VENT VENTILATION
VIF VERIFY IN FIELD
W/ WITH
WD WOOD
W/D WASHER AND DRYER
KEY TO ABBREVIATIONS
ARCHITECTURAL DRAWINGS ONLY
1. THE INFORMATION INCLUDED IN THESE DRAWINGS WITH REGARDS TO THE EXISTING BUILDING IS BASED ON PREVIOUS DOCUMENTATION PROVIDED TO THE ARCHITECT AS WELL AS WHAT IS READILY OBSERVABLE AT THE PROJECT SITE. DESTRUCTIVE INVESTIGATION TECHNIQUES HAVE NOT BEEN USED TO VERIFY
INFORMATION THAT IS NOT READILY OBSERVABLE.
2. ITEMS AND MATERIALS ARE NEW UNLESS NOTED AS EXISTING.
3. THERE IS NO CONTRACTOR STAGING OR STORAGE PERMITTED WITHIN THE BUILDING.
4. CONTRACTOR IS TO MEET THE REQUIREMENTS OF ALL CODES, RULES, AND REGULATIONS GOVERNING THIS PROJECT AS SET BY FEDERAL, STATE, AND LOCAL CODES, BUILDING DEPARTMENT AGENCIES, AND THE
OWNER.
5. CONTRACTOR IS TO MEET THE REQUIREMENTS OF THE APPLICABLE ACCESSIBILITY GUIDELINES FOR ALL
ASPECTS OF THIS PROJECT.
6. PROVIDE BLOCKING AS INDICATED ON THE DRAWINGS OR AT ALL WALL OR CEILING MOUNTED ACCESSORIES AS NECESSARY TO SUPPORT THE WORK. VERIFY MOUNTING HEIGHTS WITH ARCHITECTURAL
DRAWINGS AND MANUFACTURERS RECOMMENDATIONS FOR EACH ITEM.
GENERAL NOTES
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET
NO.
DESIGNED:
CADD:
TECH. REVIEW:
DATE:
ISSUED FOR BID
:1 :0
P M
C A u to d e s k L o c a l F il e s B e n n e r H o u s e C D s c o tt m o ir .r v t
ABBREVIATIONS,
SYMBOLS, AND
MATERIALS
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
3 95
CS.3
LMG
LMG
SDM
02/28/2022
NOTE:
SEE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR MATERIALS, ABBREVIATIONS AND SYMBOLS
RELATING TO M.E.P. WORK
SEE CIVIL AND STRUCTURAL DRAWINGS FOR MATERIALS, ABBREVIATIONS AND SYMBOLS RELATING TO
STRUCTURAL, CIVIL, AND LANDSCAPE WORK
CODE ANALYSIS
NOTE: IF A CONFLICT BETWEEN
APPLICABLE CODES OCCURS THE MORE
RESTRICTIVE REQUIREMENT SHALL
GOVERN, UNLESS NOTED OTHERWISE.
USE AND OCCUPANCY CLASSIFICATION
BUILDING USE GROUP
RESIDENTIAL GROUP R-2 310.4 6.1.8.1.2
IBC NFPA 101
GENERAL INFORMATION
PROJECT NAME: REHABILITATE THE HISTORIC JOSIAH BENNER HOUSR, SPRINGHOUSE AND SUMMER KITCHEN
PROJECT LOCATION: GETTYSBURG, PENNSYLVANIA
APPLICABLE CODES
2018 INTERNATIONAL BUILDING CODE (IBC)
2018 INTERNATIONAL RESIDENTIAL CODE
2018 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
2018 NATIONAL STANDARD PLUMBING CODE
2012 INTERNATIONAL ENERGY CODE
2018 NFPA 1
2018 NFPA 101, LIFE SAFETY CODE
2018 NFPA 10 PORTABLE FIRE EXTINGUISHERS
2019 NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS
2020 NFPA 70 NATIONAL ELECTRICAL CODE
2019 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
GENERAL BUILDING HEIGHTS AND AREAS
ALLOWABLE HEIGHT, NUMBER OF STORIES, AND BUILDING AREA
CONSTRUCTION TYPE
R-2 OCCUPANCY
V-B
HEIGHT: 30'
STORIES: 2
AREA FACTOR: 1000
SF/STORY
V (000)
STORIES: 2
ACTUAL
FULLY SPRINKLERED
HEIGHT: 32-0"
STORIES: 2, PLUS ATTIC
AND BASEMENT
BASEMENT: 907 SF
FIRST FLOOR: 1,129 SF
SECOND FLOOR: 886 SF
TOTAL: 2,922 SF
HEIGHT - TABLE 504.3
STORIES - TABLE 504.4
AREA FACTOR - TABLE 506.2
STORIES - TABLE
6.1.8.1.2
IBC NFPA
ACTUAL OCCUPANT LOAD, EGRESS CAPACITY, AND NUMBER OF EXITS
THE FOLLOWING TABLE INDICATES THE ACTUAL OCCUPANT LOAD BY STORY, PROVIDED EGRESS CAPACITY BY STORY BASED ON THE ABOVE TABLE, REQUIRED NUMBER OF EXITS BY STORY BASED ON IBC TABLE 1006.3.1
AND NFPA 7.4.1.2 AND 6.1.8.1.2, AND PROVIDED NUMBER OF EXITS BY STORY.
OCCUPANT LOAD, EGRESS CAPACITY, AND NUMBER OF EXITS
STORY ACTUAL
OCCUPANT LOAD
EGRESS CAPACITY PROVIDED
(INCLUDES DOORS AND STAIRS)
NUMBER OF EXITS
REQUIRED PROVIDED
1*
* INDICATES LEVEL OF EXIT DISCHARGE.
4 OCCUPANTS 439 OCCUPANTS 2 4
4 OCCUPANTS 56 OCCUPANTS 1 1
MEANS OF EGRESS
0 3 OCCUPANTS 65 OCCUPANTS 1 1
829 SF
ATTIC
4 OCC
4 STAIR 3
# OF EXITING OCCUPANTS: 4
REQUIRED EGRESS WIDTH: 1.2"
PROVIDED EGRESS WIDTH: 34"
482 SF
CELLAR
2 OCC
432 SF
CELLAR
2 OCC
EXIT1
# OF EXITING OCCUPANTS: 4
REQUIRED EGRESS WIDTH: 0.8"
PROVIDED EGRESS WIDTH: 34"
STAIR 1
# OF EXITING OCCUPANTS: 4
REQUIRED EGRESS WIDTH: 1.2"
PROVIDED EGRESS WIDTH: 28"
192 SF
LIVING ROOM
1 OCC
221 SF
DINING ROOM
2 OCC
192 SF
OUT KITCHEN
1 OCC
240 SF
KITCHEN
2 OCC
2 4
LAUNDRY & TOILET
ROOM
EXIT3
# OF EXITING OCCUPANTS: 4
REQUIRED EGRESS WIDTH: 0.8"
PROVIDED EGRESS WIDTH: 34"
EXIT2
# OF EXITING OCCUPANTS: 2
REQUIRED EGRESS WIDTH: 0.4"
PROVIDED EGRESS WIDTH: 34"
EXIT5
# OF EXITING OCCUPANTS: 1
REQUIRED EGRESS WIDTH: 0.2"
PROVIDED EGRESS WIDTH: 34"
EXIT4
# OF EXITING OCCUPANTS: 2
REQUIRED EGRESS WIDTH: 0.4"
PROVIDED EGRESS WIDTH: 34"
HALL
HALL
STAIR 2
# OF EXITING OCCUPANTS: 3
REQUIRED EGRESS WIDTH: 0.9"
PROVIDED EGRESS WIDTH: 30"
STAIR 1
# OF EXITING OCCUPANTS: 4
REQUIRED EGRESS WIDTH: 1.2"
PROVIDED EGRESS WIDTH: 28"
NOT AN EXIT
185 SF
BEDROOM 1
1 OCC
180 SF
BEDROOM 2
1 OCC
180 SF
BEDROOM 3
1 OCC
BATHROOM
BATHROOM
HALLSTAIR
STAIR 2
# OF EXITING OCCUPANTS: 3
REQUIRED EGRESS WIDTH: 0.9"
PROVIDED EGRESS WIDTH: 30"
STAIR 3
# OF EXITING OCCUPANTS: 4
REQUIRED EGRESS WIDTH: 1.2"
PROVIDED EGRESS WIDTH: 28"
8 0 8 16
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET
NO.
DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE A
ISSUED FOR BID
:1 :0
P M
C A u to d e s k L o c a l F il e s B e n n e r H o u s e C D s c o tt m o ir .r v t
CODE SHEET & EGRESS
PLAN
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
4 95
CS.4
LMG
LMG
SDM
02/28/2022
SCALE ACS.4
4 ATTIC - EGRESS PLAN
SCALE ACS.4
1 CELLAR - EGRESS PLAN
SCALE ACS.4
2 FIRST FLOOR - EGRESS PLAN
SCALE ACS.4
3 SECOND FLOOR - EGRESS PLAN
GETTYSBURG NATIONAL MILITARY PARK
A/E FIRM -
K d w g G E T T C B E N N E R
H O U S E .d w g
:3 :0
P M
K d w g G E T T C B E N N E R
H O U S E .d w g
:3 :0
A/E FIRM -
K d w g G E T T C B E N N E R
H O U S E .d w g
:3 :1
K d w g G E T T C B E N N E R
H O U S E .d w g
:3 :1
K d w g G E T T C B E N N E R
H O U S E .d w g
:3 :2
CONCRETE PORCH. REFER TO
CIVIL DRAWINGS
EXISTING
OUT
KITCHEN
EXISTING
JOSIAH BENNER HOUSE
EXISTING
SPRING
HOUSE
EXISTING PORCH
PARKING AND SITE IMPROVEMENTS
SEE CIVIL DRAWINGS
EXISTING BRICK
SIDEWALK. REFER TO
CIVIL DRAWINGS
10 20
SCALE OF FEET
0 10
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET
NO.
DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE A
ISSUED FOR BID
:1 :0
P M
C A u to d e s k L o c a l F il e s B e n n e r H o u s e C D s c o tt m o ir .r v t
ARCHITECTURAL SITE
PLAN
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
10 95
AS.1
LMG
LMG
SDM
02/28/2022
SCALE AAS.1
1 ARCHITECTURAL SITE PLAN
GENERAL MECHANICAL NOTES
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
1. COORDINATE ALL MECHANICAL WORK WITH PLUMBING WORK, ELECTRICAL WORK, AND WORK OF OTHER TRADES SHOWN ON OTHER
DRAWINGS.
2. INFORMATION SHOWN ON THE MECHANICAL DRAWINGS PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION.
EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMOLITION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE
WORK.
3. REMOVE ALL EXISTING PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE COR, OR ARE INDICATED TO REMAIN THE PROPERTY OF COR SHALL BE DELIVERED BY THE COR'S CONTRACTOR WHERE DIRECTED BY THE COR'S CONSTRUCTION MANAGER. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND
SHALL BE REMOVED BY THE CONTRACTOR FROM THE PREMISES.
4. DISCONNECT EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR OTHERWISE) AND REMOVE PIPING BACK TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR NOTED ON PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. CAP, PLUG, OR SEAL EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE. NO EXISTING PIPING SHALL BE LEFT
UNSEALED.
5. EXISTING MECHANICAL PIPING, DUCTWORK, EQUIPMENT, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS.
ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE COR'S CONSTRUCTION MANAGER AND AT NO ADDITIONAL CONTRACT
COST.
6. REMOVE ALL ACCESSORIES, CONTROLS, ENCLOSURES, SUPPORTS, HANGERS, PADS, ETC. ASSOCIATED WITH ALL EQUIPMENT SHOWN TO BE REMOVED. REPAIR AND PAINT DAMAGED SURFACES AND ALL SURFACES BEHIND ALL EQUIPMENT SHOWN TO BE REMOVED TO MATCH
EXISTING ADJACENT SURFACES.
7. THE LOCATION OF EXISTING UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. DETERMINE THE EXACT LOCATION OF ALL EXISTING U TILITIES BEFORE COMMENCING WORK. REPAIR ALL DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY
AND ALL UTILITIES.
8. INSTALL PIPING AND DUCTWORK SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE.
9. UNLESS OTHERWISE NOTED, ROUTE ALL PIPING AND DUCTWORK OVERHEAD, TIGHT TO UNDERSIDE OF SLAB, WITH SPACE FOR INSULATION
IF REQUIRED.
10. MAINTAIN CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES.
11. CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN DUCTWORK AND PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THESE ITEMS AS REQUIRED ELSEWHERE IN THE
CONTRACT DOCUMENTS.
12. WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES REQUIRES CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., CHECK FOR THE PRESENCE OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION. EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO PERSONNEL DUE TO CONTACT WITH SAME. TEMPORARILY DISCONNECT SERVICES DURING THE CUTTING OPERATION. SCHEDULE SERVICE
OUTAGES IN ADVANCE WITH THE COR.
13. FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT.
VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. PROVIDE ADDITIONAL VALVES, PRESSURE GAUGES, ETC. AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS AND DETAILS FOR PIPE SIZES NOT INDICATED ON FLOW SCHEDULES AND RISER
DIAGRAMS.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR RESEARCHING ALL SYSTEMS THAT A PARTICULAR OUTAGE WILL AFFECT AS WELL AS LOCATING ALL SHUTOFF POINTS. INCLUDE THIS INFORMATION IN THE OUTAGE PLAN AND SUBMIT TO COR FOR APPROVAL.
15. EXCEPT AS OTHERWISE NOTED, LOCATE ALL ROOM THERMOSTATS ON SAME HORIZONTAL CENTERLINE AS LIGHT SWITCH. WHERE LIGHT SWITCH AND THERMOSTAT ARE ADJACENT TO EACH OTHER, LIGHT SWITCH SHALL BE CLOSEST TO THE DOOR. COORDINATE WITH ELECTRICAL CONTRACTOR. NOTIFY THE COR OF ROOMS WHERE THE ABOVE LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A
QUESTION ON LOCATION.
16. RUN ALL DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED.
17. RECYCLE ALL MERCURY SWITCH THERMOSTATS THAT ARE REMOVED. RECYCLED THERMOSTATS SHALL BE DELIVERED TO PARTICIPATING
WHOLESALERS
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
ISSUED FOR BID
:1 :1
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
MECHANICAL COVER
SHEET
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
43 95
M0.0
GPZ
GPZ
SRH
02/28/2022
(APPLICABLE TO ALL MECHANICAL DRAWINGS)
MECHANICAL LEGEND
DESCRIPTIONSYMBOL
DIFFUSER TAG:
TOP- NECK SIZE
CENTER- SPECIFICATION TYPE
BOTTOM- AIRFLOW IN CFM
8x8 D-1
FLEXIBLE CONNECTION
VOLUME DAMPER
MOTOR OPERATED DAMPER
GRAVITY BACKDRAFT DAMPER
THERMOSTAT/TEMPERATURE SENSORT
HUMIDISTAT/HUMIDITY SENSORH
RETURN AIR DUCT
OUTDOOR AIR OR SUPPLY AIR DUCT
EXHAUST AIR DUCT
PLAN/ SECTION DESIGNATION
TOP - PLAN/ SECTION REFERENCE,
BOTTOM - REFERENCED DRAWING
M.1
REFRIGERANT SUCTIONRS
REFRIGERANT LIQUIDRL
CONDENSATE DRAIND
MECHANICAL ABBREVIATIONS
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
APD AIR PRESSURE DROP
APPROX APPROXIMATE/APPROXIMATELY
BOT BOTTOM
BDD BACKDRAFT DAMPER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CFM CUBIC FEET PER MINUTE
COR CONTRACT OFFICER REPRESENTATIVE
D DEPTH/DIFFUSER/DAMPER/DROP/DRAIN/
DIAMETER
DB DRY BULB
DN DOWN
DWG DRAWING
EA EXHAUST AIR/EACH
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
ELEC ELECTRIC/ELECTRICAL
ELEV ELEVATION
ESP EXTERNAL STATIC PRESSURE
EX EXISTING
F FAHRENHEIT
FC FLEXIBLE CONNECTION
FP FIRE PROTECTION
FS FUEL OIL SUPPLY
FT FEET/FOOT
G GRILLE
H HEIGHT/HIGH/HUMIDISTAT
HP HORSEPOWER
IN INCH/INCHES
INS INSULATION
KW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
M MECHANICAL
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MD MECHANICAL DEMOLITION
MECH MECHANICAL
MIN MINIMUM
MOD MOTOR OPERATED DAMPER
N NORTH
NC NORMALLY CLOSED
NO NORMALLY OPEN/NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTDOOR AIR
OED OPEN END DUCT
OS OCCUPANCY SENSOR
PD PRESSURE DROP
PSI PRESSURE-POUNDS PER SQUARE INCH
PSIG PRESSURE-POUNDS PER SQUARE INCH, GAGE
R RADIUS/REGISTER/RISE
RA RETURN AIR
RL REFRIGERANT LIQUID
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCITON
RX REMOVE EXISTING
S SECONDS/SWITCH
SA SUPPLY AIR
SENS SENSIBLE
SF SQUARE FEET/SQUARE FOOT
SP STATIC PRESSURE
T THERMOSTAT
TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UH UNIT HEATER
V VENT
VD VOLUME DAMPER
WB WET BULB
WG WATER GAUGE
RX FUEL OIL TANK
CELLAR
CELLAR
RX FS
RX VENT
RX
AHU
R X x8
R X x8
RX 26x12 RA UP
RX 14x12 SA UP
RX 12x4 SA UP
RX 6"Ø SA, TYP
RX 12x8 SA RX 12x14
SA UP
RX 10x4
SA UP
RX FLUE
RX 11x11
SA UP
RX 30x12
RA UP
RX 12x24 RA UP
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
CELLAR - DEMOLITION
- MECHANICAL
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
44 95
MD1.1
GPZ
GPZ
SRH
02/28/2022
SCALE BMD1.1
1 CELLAR - MECHANICAL - DEMOLITION
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY WEIGHT, DASHED LINE,
3. CONTRACTOR SHALL IDENTIFY REMOVAL OF ALL MECHANICAL DUCTWORK AND
EQUIPMENT AND REVIEW WITH COR BEFORE REMOVING. WORK REMOVED
WITHOUT PRIOR CONFIMATION THAT WAS NOT INTENDED TO BE REMOVED
SHALL BE REPLACED IN SAME OR BETTER CONDITION AT CONTRACTOR'S COST.
4. PATCH AND SEAL ALL EXISTING OPENINGS IN WALLS AND FLOORS WHERE
DUCTWORK, PIPING, CONDUIT, ETC IS REMOVED.
DINING ROOM
HALLWAY
LIVING ROOM
STAIR
STAIR
PANTRY
108HALL
OUT KITCHEN
RX 4x12 SA DN
IN WALL
RX 12x4 SA
RX 10x4
SA UP/DN
RX 14x12 REGISTER
RX 14x12 REGISTER
RX 24x12 GRILLE
RX 30x12
GRILLE
RX 12x14
REGISTER
RX 11x11
REGISTER
RX 26x12 GRILLE
RX SA UP
RX SA UP
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
FIRST FLOOR -
DEMOLITION -
MECHANICAL
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
45 95
MD1.2
GPZ
GPZ
SRH
02/28/2022
SCALE BMD1.2
1 FIRST FLOOR - MECHANICAL - DEMOLITION
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY WEIGHT, DASHED LINE,
3. CONTRACTOR SHALL IDENTIFY REMOVAL OF ALL MECHANICAL DUCTWORK AND
EQUIPMENT AND REVIEW WITH COR BEFORE REMOVING. WORK REMOVED
WITHOUT PRIOR CONFIMATION THAT WAS NOT INTENDED TO BE REMOVED
SHALL BE REPLACED IN SAME OR BETTER CONDITION AT CONTRACTOR'S COST.
BEDROOM 3
HALL
BEDROOM 2
CLOSET
CLOSET
BEDROOM 1
STAIR
STAIR
CLOSET
RX 10x12 REGISTER
RX 10x4 SA DN
RX 12x12
REGISTER
RX 12x12
REGISTER
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
SECOND FLOOR -
DEMOLITION -
MECHANICAL
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
46 95
MD1.3
GPZ
GPZ
SRH
02/28/2022
SCALE BMD1.3
1 SECOND FLOOR - MECHANICAL - DEMOLITION
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY WEIGHT, DASHED LINE,
3. CONTRACTOR SHALL IDENTIFY REMOVAL OF ALL MECHANICAL DUCTWORK AND
EQUIPMENT AND REVIEW WITH COR BEFORE REMOVING. WORK REMOVED
WITHOUT PRIOR CONFIMATION THAT WAS NOT INTENDED TO BE REMOVED
SHALL BE REPLACED IN SAME OR BETTER CONDITION AT CONTRACTOR'S COST.
12" DEEP INSULATED OA
PLENUM. WIDTH AND HEIGHT
SHALL MATCH LOUVER.
CELLAR
CELLAR
12" DEEP
INSULATED EA
PLENUM. WIDTH
AND HEIGHT
SHALL MATCH
LOUVER.
EF-1 8x8
6x6
8x6
8x8
6x6
12x30 UP
12x14 UP
12x14 UP 12x14 UP
24x12 UP
12x12 UP
12x12 UP
6x12 UP
H T
BDD
AHU-1
6x6
12x14 DN
6x6
8x6
2 PAIRS RS/RL
STACKED IN
VERTICAL
RS/L UP
M1.1
8x6 x1 010x8
10x8 x1
12x12
8x6
12x12 x8
6x4 UP
EF-5
FC
FC
R-1
6x6
M1.1
M1.1
BELOW
6x6
12x12
8x8 x8
OED WITH BIRDSCREEN
BDD
EX SUMP PIT
FIRST FLOOR
0' - 0"
CELLAR
-7' - 3"
AHU-1
x1
12x12
12x12
FC FC
HOUSEKEEPING PAD
12x12
12x12
FIRST FLOOR
0' - 0"
CELLAR
-7' - 3"
8x8
FLOOR DIFFUSER
PLENUM WIDTH AND
LENGTH SHALL MATCH
DIFFUSER SIZE
FIRST FLOOR
0' - 0"
CELLAR
-7' - 3"
EF-1
FC
12x12 8x8
BDD
6x6
12" DEEP INSULATED EA
PLENUM. WIDTH AND HEIGHT
SHALL MATCH LOUVER.
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :1
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
CELLAR - NEW WORK
- MECHANICAL
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
47 95
M1.1
GPZ
GPZ
SRH
02/28/2022
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL AIR DEVICES SHALL BE PROVIDED WITHOUT INTEGRAL DAMPERS. ALL AIR DEVICES SHALL BE PROVIDED
WITH A DUCT MOUNTED DAMPER AT DUCT TAKE-OFF.
5. IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR DEVICE NECK SIZE.
6. REFRIGERANT PIPING SHALL BE SIZED BY ASSOCIATED EQUIPMENT MANUFACTURER.
SCALE BM1.1
1 CELLAR - MECHANICAL - NEW WORK
12x14 UP
2 CONNECT TO LOUVER PROVIDED UNDER ANOTHER DIVISION
3 MOUNT ON 4" HOUSEKEEPING PAD
SCALE BM1.1
2 AHU-1 - NEW WORK - SECTION
4 ROUTE DUCT THROUGH NEW WALL PENETRATION
SCALE BM1.1
3 TYPICAL DUCT CONNECTION TO FLOOR DIFFUSER - NEW WORK - SECTION
SCALE BM1.1
4 BASEMENT EXHAUST - NEW WORK - SECTION
5 SUPPORT FROM ABOVE
EF-1
HALLWAY
LIVING ROOM
STAIR
STAIR
OUT KITCHEN
KITCHEN
PANTRY
30x12 R-1
14x12 R-1
14x12 R-2
14x12 R-2
14x12 R-1
24x12 R-1
14x12 R-2
14x12 R-2
12x12 R-2
12x12 R-1
12x6 R-1
T
HALL
LAUNDRY & TOILET
ROOM
ACCU-2
ACCU-1
RS/L UP/DN
RS/L DN, TYP OF 2 PAIRS
4x6 EA DN
PROVIDE VENT
CAP FOR 6"
DRYER EXHAUST
AHU-1
6x6 R-2
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
FIRST FLOOR - NEW
WORK - DUCTWORK
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
48 95
M1.2
GPZ
GPZ
SRH
02/28/2022
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
SCALE BM1.2
1 FIRST FLOOR - MECHANICAL - NEW WORK
MOUNT ON 4" HOUSKEEPING PAD
2 MOUNT BOTTOM OF REGISTER 7'-0" AFF
3 INSTALL REGISTER IN EXISTING FLOOR HOLE. VERIFY SIZE
IN FIELD AND SUBMIT TO COR FOR APPROVAL.
4 CREATE NEW HOLE IN FLOOR TO INSTALL REGISTER
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL AIR DEVICES SHALL BE PROVIDED WITHOUT INTEGRAL DAMPERS. ALL AIR DEVICES SHALL BE PROVIDED
WITH A DUCT MOUNTED DAMPER AT DUCT TAKE-OFF.
5. IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR DEVICE NECK SIZE.
6. REFRIGERANT PIPING SHALL BE SIZED BY ASSOCIATED EQUIPMENT MANUFACTURER.
HALL
201 BEDROOM 2
BEDROOM 1
STAIR
STAIR
BATHROOM
BATHROOM
T
EF-3
EF-4
RS/RL
UP/DN
8x8 R-1
8x8 R-1
10x10 R-2
8x8 R-1
8x8 R-1
10x10 R-2
10x10 R-1
8x8 R-1
8x8 R-1
8x8 R-1
8x8 R-1
10x10 R-2
10x10 R-1
AHU-2
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
SECOND FLOOR - NEW
WORK - DUCTWORK
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
49 95
M1.3
GPZ
GPZ
SRH
02/28/2022
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
SCALE BM1.3
1 SECOND FLOOR - MECHANICAL - NEW WORK
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL AIR DEVICES SHALL BE PROVIDED WITHOUT INTEGRAL DAMPERS. ALL AIR DEVICES SHALL BE PROVIDED
WITH A DUCT MOUNTED DAMPER AT DUCT TAKE-OFF.
5. IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR DEVICE NECK SIZE.
6. REFRIGERANT PIPING SHALL BE SIZED BY ASSOCIATED EQUIPMENT MANUFACTURER.
x1
12x12 14x14 x1
12x10 12x12
EF-2
T H
EF-3
EF-4
6ø 6ø
AHU-2
ATTIC
x1
RS/RL DN
8x12
RS/RL ALONG FLOOR
x8 x1 x8
6x6 6x6
8x8 8x8
10x8
10x8
28x
8x8
DN
10x10 DN
10x10 DN
10x10 DN
8x8 DN
8x8 DN
8x88x8
8x8 DN
8x8 DN 10x10 DN 8x8 DN
10x8
10x10 DN
8ø
FC
FC
x1
14x16
FC
FC
EF-2
RS/RL
RS/RL
1 1
BDD
16x10 OED 4
TERMINATE 16x10
OED IN CHIMNEY
6TERMINATE 10x10
OED IN CHIMNEY
10x10
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
ATTIC - NEW WORK -
MECHANICAL
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
50 95
M1.4
GPZ
GPZ
SRH
02/28/2022
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
SCALE BM1.4
1 ATTIC - MECHANICAL - NEW WORK
INSTALL DUCTWORK HIGH AT ROOF PEAK
SLOPE DUCTWORK DOWN PARALLEL TO AND CLOSE TO
THE ROOF
PROVIDE SECONDARY DRAIN PAN WITH LIQUID LEVEL
SENSOR
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. NEW WORK SHOWN WITH HEAVY WEIGHT LINE,
3. ALL ITEMS THAT REQUIRE ACCESS FOR OPERATING, CLEANING, SERVICING, MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS, STRAINERS, TRANSMITTERS, AND CONTROL DEVICES. PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS REQUIREMENT AND CONTRACT DOCUMENTS TO THE
COR FOR RESOLUTION.
4. ALL AIR DEVICES SHALL BE PROVIDED WITHOUT INTEGRAL DAMPERS. ALL AIR DEVICES SHALL BE PROVIDED
WITH A DUCT MOUNTED DAMPER AT DUCT TAKE-OFF.
5. IF DIFFUSER RUNOUT IS NOT INDICATED THEN RUNOUT SIZE IS SAME AS THE AIR DEVICE NECK SIZE.
6. REFRIGERANT PIPING SHALL BE SIZED BY ASSOCIATED EQUIPMENT MANUFACTURER.
4 PROVIDE BIRD SCREEN OVER DUCT OPENING
5 SEAL DUCT PENETRATION AND CHIMNEY BELOW
PENETRATION TO MAKE AIR AND WATER TIGHT
6 SUPPORT FROM ABOVE
CUT HOLE IN RECTANGULAR DUCT LARGE ENOUGH SO THAT
ROUGH METAL EDGE DOES NOT PROJECT INTO AIR STREAM.
NOTES:
1. DO NOT USE 45° TAP FITTINGS EXCEPT WHERE TIGHT
CONDITION PREVENTS USE OF OTHER FITTINGS INDICATED.
SPECIAL NOTES:
AIR FLOW
ROUND DUCT
DO NOT USE
BACKWARD BENDING
MITRE OR RADIUS
IMMEDIATELY AFTER TAP
R=D
CONICAL TEE
FITTING WITH
FLANGEROUND DUCT
AIR FLOW
45° TAP FITTING
WITH FLANGE
MITRED 45° TAP
FITTING WITH FLANGE.
TAPOFF FROM RECTANGULAR DUCT TO ROUND DUCT
RECTANGULAR DUCT
RECTANGULAR DUCT
AIR FLOW
CUSHION HEAD
(SUPPLY ONLY) D/2
(MINIMUM 6")
AIR OUTLET
CEILINGD
NOTES:
1. AIR FLOW IS REVERSE FOR RETURN AND EXHAUST.
OUTLET LOCATED AT END OF RUN
AIR FLOW
6" MINIMUM
NOTES:
1. SAME FOR RETURN AND EXHAUST DUCTS
EXCEPT AIR FLOW IS REVERSED.
REGISTER OR DIFFUSER
DIFFUSER OR REGISTER TAPOFF AND TRANSITION
15° MAXIMUM
TAKEOFFS FROM TOP OF RECTANGULAR DUCTS
TOP VIEWTOP VIEW
RADIUS A X B
AIR FLOW
TRANSITION AFTER
TAKEOFF (IF REQUIRED)
SECTION
AIR FLOW
SECTION
D
B
A
R=D
NOTES:
1. BOTTOM TAKEOFFS SIMILAR.
2. SAME FOR RETURN AND EXHAUST DUCTS EXCEPT AIR FLOW IS REVERSED.
SPECIAL NOTES:
15° MAXIMUM
45°
45° TAP PERMITTED FOR DUCTWORK RATED 2" W.G. OR LESS.1
TAPOFF AND TRANSITION FROM SIDE OF DUCT
AIR FLOW
D
R=D (6" MINIMUM)
NOTES:
1. SEE SMACNA MANUAL FOR METHODS OF SECURING TAP-OFF CONNECTION TO MAIN.
2. SAME FOR RETURN AND EXHAUST DUCTS EXCEPT AIR FLOW IS REVERSED.
SPECIAL NOTES:
45° TAP PERMITTED FOR DUCTWORK RATED 2" W.G. OR LESS.
15° MAXIMUM
AIR FLOW
ROUND DUCT
NOTES:
1. FOR AIR FLOW IN OPPOSITE DIRECTION, TRANSITION
COLLAR SHALL OVERLAP EXTERIOR OR ROUND DUCT.
15°
MAXIMUM
RECTANGULAR TO ROUND DUCT TRANSITION
STRUCTURE ABOVE
ROD
DUCT WITH INSULATION
ATTACH
PER
SMACNA
ANGLE
PROTECT DUCT INSULATION
FROM BEING CRUSHED BY
DUCT SUPPORTS
DUCT WITH INSULATION
DUCT STRAP
MAINTAIN VAPOR BARRIER
AT PENETRATION
ATTACH DUCT STRAP
PER SMACNA
NOTES:
1. REFER TO SMACNA FOR ADDITIONAL HANGERS AND SUPPORTS
DUCT INSULATION SUPPORT
DOUBLE RADIUS
TURNING VANES
DOUBLE
RADIUS
TURNING VANES
SECTION A-A A
A
DUCT SPLITS
FAN COIL UNIT PIPING AND DRIP PAN
PROVIDE GALVANIZED
STEEL DRIP PAN UNDER
ALL FLOOR MOUNTED
HEAT PUMP UNITS.
EXTEND DRIP PAN MIN
6" ALL AROUND UNIT,
TYPICAL
3/4" HOSE
BIBB WITH CAP
RESILIENT MOUNTING
PADS, TYP
CONDENSATE
FLOOR
MIN 3"
FAN COIL
R S R L
D
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
MECHANICAL DETAILS
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
51 95
M5.1
GPZ
GPZ
SRH
02/28/2022
ACCU INSTALLATION
ACCU (OUTDOOR UNIT)
PROVIDE KINDORF REFRIGERANT
LINE AND ELECTRICAL DISCONNECT
SUPPORT STAND. SUPPORT STAND
FROM BASE
REFRIGERANT PIPING,
CONTROL WIRING AND
ELECTRIC CONDUIT TO
ASSOCIATED INDOOR
UNIT
SECURE UNIT TO SUPPORT BEAMS IN
ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS / REQUIREMENTS
ELECTRICAL DISCONNECT
SUPPORT BEAMS
4" HOUSEKEEPING
PAD
FANS-1
OCCUPANCY SENSOR OS
SWITCH
1. EF IS OPERATED MANUALLY BY S-1 OR AUTOMATICALLY BY
OCCUPANCY SENSOR.
2. WHEN FAN IS STARTED, DAMPER D-1 OPENS. WHEN FAN STOPS,
D-1 CLOSES AFTER 2 MINUTE DELAY (ADJUSTABLE).
3. OCCUPANCY SENSOR SHALL STOP FAN 10 MINUTES
(ADJUSTABLE) AFTER NO OCCUPANCY IS SENSED.
EXHAUST FAN (EF-3, 4, 5)
FAN
1. EF IS OPERATED MANUALLY BY S-1 OR AUTOMATICALLY BY
TEMPERATURE OR HUMIDITY SENSOR T-1 OR H-1,
RESPECTIVELY.
2. WHEN EF IS ON, D-1 AND D-2 SHALL BE OPEN.
3. WHEN TERMPARATURE AT T-1 IS ABOVE 80 DEGREES F OR RH
IS ABOVE 60 PERCENT, EF SHALL BE ON.
4. WHEN SPACE TEMPERATURE FROPS BELOW 75 DEGREES F OR
HUMIDITY DROPS BELOW 55 PERCENT, FAN SHALL STOP AND
DAMPERS CLOSE AFTER 2 MINUTE DELAY (ADJUSTABLE).
EXHAUST FAN (EF-1, 2)
D-1
S-1 LINE VOLTAGE SWITCH
LINE VOLTAGE SPACE
TEMPERATURE SENSOR
T-1
LINE VOLTAGE HUMIDISTATH-1
D-2
MOUNT IN DUCT
BDD
VARIABLE REFRIGERANT SYSTEM
1. WALL MOUNTED PROGRAMMABLE THERMOSTAT, T-1 MAINTAINS SPACE
TEMPERATURE AT 75 DEGREES F FOR THE COOLING CYCLE AND 70 DEGREES F
FOR THE HEATING CYCLE THROUGH MANUFACTURER'S SUPPLIED CONTROLS.
2. DURING OCCUPIED HOURS, SYSTEM IS STARTED AUTOMATICALLY BY
PROGRAMMABLE THERMOSTAT AND FAN OPERATES CONTINUOUSLY.
3. DURING UNOCCUPIED HOURS, SYSTEM CYCLES ON WHEN SPACE TEMPERATURE
AT T-1 FALLS BELOW 62 DEGREES F. WHEN SPACE TEMPERATURE AT T-1 RISES
TO 65 DEGREES F, SYSTEM CYCLES OFF. WHEN SPACE TEMPERATURE AT T-1
RISES ABOVE 85 DEGREES F, SYSTEM CYCLES ON. WHEN SPACE TEMPERATURE
AT T-1 FALLS TO 82 DEGREES F, SYSTEM CYCLES OFF.
4. WHEN LLS-1 DETECTS WATER, AHU-1 SHALL CYCLE OFF. AN ALARM IS SENT
THROUGH FIRE ALARM.
5. WHEN LLS-2 DETECTS WATER, AHU-2 SHALL CYCLE OFF. AN ALARM IS SENT
THROUGH FIRE ALARM.
6. WHEN T-1 DETECTS HIGH OR LOW TEMPERATURE, AN ALARM IS SENT THROUGH
FIRE ALARM.
7. COORDINATE CONTROLS WITH VRF MANUFACTURER.
T-1 SPACE TEMPERATURE
AHU-1RS
RL
RS
RL
ACCU RS
RL
TO/FROM MULTIPLE
INDOOR UNITS AHU-2
LLS-1
LLS-2
PLENUM CONNECTION TO LOUVER
E X
TE
R
IO
R
W A
LL
E X
TE
R
IO
R
W A
LL
INSULATED
PLENUM
SLOPE
ARCHITECTURAL
LOUVER. SEE
ARCHITECTURAL
DRAWINGS
SEAL AIR AND WATER
TIGHT AROUND PERIMETER
OF PLENUM
CONNECT
BOTTOM OF
PLENUM TO
TOP OF RAIN
STOP
OPENING
FOR
DRAINAGE
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
AUTOMATIC
TEMPERATURE
CONTROLS AND DETAILS
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
52 95
M6.1
GPZ
GPZ
SRH
02/28/2022
GENERAL NOTES:
1. UNIT NUMBERS ARE INDICATED WHERE ALL UNITS ARE LISTED AND NUMBERED
INDIVIDUALLY.
2. UNIT TYPES ARE DESCRIBED IN THE SPECIFICATIONS.
3. TEMPERATURE VALUES ARE LISTED IN DEGREES FAHRENHEIT.
4. AIR PRESSURE VALUES ARE LISTED IN INCHES OF WATER COLUMN.
(APPLICABLE TO ALL SCHEDULES)
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
MECHANICAL
SCHEDULES
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
53 95
M7.1
GPZ
GPZ
SRH
02/28/2022
FANS
UNIT
SYMBOL TYPE LOCATION SERVICE CFM CLASS TSP MOTOR HP NOTES
EF-1 P 001 CELLAR EXHAUST 500 I 0.5 1/4
EF-2 P ATTIC EXHAUST 500 I 0.5 1/4
EF-3 L ATTIC EXHAUST 90 I 0.7 80 WATTS
EF-4 L ATTIC EXHAUST 90 I 0.7 80 WATTS
EF-5 P 001 CELLAR EXHAUST 75 I 0.6 1/4
SPLIT SYSTEM HEAT PUMPS
UNIT NO
ASSOCIATED
ACCU LOCATION
FAN
OA CFM
COOLING CAPACITY HEATING CAPACITY
NOTESCFM HP ESP
TOTAL
MBH
SENS
MBH EAT DB EAT WB EER CONDENSER EAT
REVERSE CYCLE
MBH SUPPLEMENTAL KW CONDENSER EAT
AHU-1 ACCU-1 001 CELLAR 975 0.75 0.9 140 28.0 22.3 78.2 65.4 11.6 95 24.8 0 0
AHU-2 ACCU-2 301 ATTIC 1,325 0.75 0.9 0 29.8 29.1 75.0 62.5 9.5 95 17.5 0 0
GENERAL PLUMBING NOTES
(APPLICABLE TO ALL PLUMBING DRAWINGS)
1. INFORMATION SHOWN ON THE PLUMBING DRAWINGS PERTAINING TO EXISTING CONDITIONS HAS BEEN OBTAINED FROM AVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTING CONDITIONS IN DETAIL OR DIMENSION. EXISTING CONDITIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE ACTUAL EXISTING CONDITIONS PRIOR TO DEMILITION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BE DISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, OR THERE IS A QUESTION REGARDING SCOPE OF WORK OR LIMITS OF DISTURBANCE, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE COR IN WRITING AND AWAIT WRITTEN DIRECTION BEFORE PROCEEDING WITH THE WORK.
2. REMOVE ALL EXISTING PIPING, EQUIPMENT, AND MATERIALS NOT REQUIRED FOR RE-USE OR RE-INSTALLATION (SHOWN OR OTHERWISE). ALL EXISTING MATERIALS AND EQUIPMENT WHICH ARE REMOVED AND ARE DESIRED BY THE COR, OR ARE INDICATED TO REMAIN THE PROPERTY OF THE COR SHALL BE DELIVERED BY THE COR'S CONTRACTOR WHERE DIRECTED BY THE COR'S CONSTRUCTION MANAGER. ALL OTHER MATERIALS AND EQUIPMENT WHICH ARE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED BY THE
CONTRACTOR FROM THE PREMISES.
3. DISCONNECT EXISTING PIPING NO LONGER REQUIRED TO REMAIN IN SERVICE (SHOWN OR OTHERWISE) AND REMOVE PIPING BACK TO SERVICE MAINS UNLESS OTHERWISE INDICATED OR NOTED ON PLANS. REMOVE EXISTING PIPE HANGERS, SUPPORTS, VALVES, ETC. CAP, PLUG, OR SEAL EXISTING PIPING INDICATED OR REQUIRED TO REMAIN IN SERVICE OR IN PLACE. NO EXISTING PIPING SHALL BE LEFT
UNSEALED.
4. EXISTING MECHANICAL PIPING, EQUIPMENT, AND MATERIALS AFFECTED BY DEMOLITION OR NEW WORK INSTALLATION AND REQUIRED TO REMAIN IN SERVICE SHALL BE RE-INSTALLED OR SUPPORTED AS REQUIRED IN ACCORDANCE WITH THE SPECIFICATIONS. ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE COR'S CONSTRUCTION MANAGER AND AT NO ADDITIONAL CONTRACT COST.
5. REMOVE ALL ACCESSORIES, CONTROLS, ENCLOSURES, SUPPORTS, HANGERS, PADS, ETC. ASSOCIATED WITH ALL EQUIPMENT SHOWN TO BE DEMOLISHED. REPAIR AND PAINT DAMAGED SURFACES AND ALL SURFACES BEHIND ALL EQUIPMENT SHOWN TO BE DEMOLISHED TO MATCH
EXISTING ADJACENT SURFACES.
6. COORDINATE ALL PLUMBING WORK WITH MECHANICAL WORK, ELECTRICAL WORK, AND WORK OF OTHER TRADES.
7. THE LOCATION OF EXISTING UNDERGROUND UTILITIES IS SHOWN IN AN APPROXIMATE WAY ONLY. DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. REPAIR ALL DAMAGES OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY
AND ALL UNDERGROUND UTILITIES.
8. RUN ALL SOIL, WASTE AND DRAIN PIPING WITH 2 PERCENT MINIMUM GRADE UNLESS OTHERWISE NOTED. HORIZONTAL VENT PIPING SHALL BE
GRADED TO DRIP BACK TO THE SOIL OR WASTE PIPE BY GRAVITY.
9. ELEVATIONS NOTED ARE TO CENTERLINES OF PIPES FOR ALL PRESSURE LINES AND TO INVERT FOR ALL GRAVITY FLOW LINES.
10. INSTALL PIPING SO THAT ALL VALVES AND DAMPERS ARE ACCESSIBLE.
11. UNLESS OTHERWISE NOTED, ROUTE ALL PIPING OVERHEAD, TIGHT TO UNDERSIDE OF SLAB, WITH SPACE FOR INSULATION IF REQUIRED.
12. MAINTAIN MINIMUM 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN
MECHANICAL AND ELECTRICAL ROOMS.
13. CERTAIN ITEMS SUCH AS ACCESS DOORS, CLEANOUTS, RISE AND DROPS IN PIPING, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY OR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THESE ITEMS AS REQUIRED ELSEWHERE IN THE CONTRACT DOCUMENTS.
14. WHERE THE INSTALLATION OF NEW SERVICES OR THE EXTENSION OF EXISTING SERVICES REQUIRES CUTTING OF EXISTING FLOORS, WALLS, PARTITIONS, ETC., CHECK FOR THE PRESENCE OF EXISTING MECHANICAL, PLUMBING AND ELECTRICAL SERVICES WITHIN OR IMMEDIATELY BENEATH CONSTRUCTION. EXERCISE NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE SERVICES OR INJURY TO PERSONNEL DUE TO CONTACT WITH SAME. TEMPORARILY DISCONNECT SERVICES DURING THE CUTTING OPERATION. SCHEDULE SERVICE OUTAGES IN ADVANCE
WITH THE OWNER.
15. FLOW SCHEMATIC AND RISER DIAGRAMS INDICATE FLOW AND OPERATION CONCEPTS AS WELL AS GENERAL ARRANGEMENT OF EQUIPMENT.
VALVES, PRESSURE GAUGES, ETC. ARE INDICATED FOR THIS PURPOSE. PROVIDE ADDITIONAL VALVES, PRESSURE GAUGES, ETC. AS SHOWN ON VARIOUS EQUIPMENT DETAILS. SEE PLANS AND DETAILS FOR PIPE SIZES NOT INDICATED ON FLOW SCHEDULES AND RISER DIAGRAMS.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR RESEARCHING ALL SYSTEMS THAT A PARTICULAR OUTAGE WILL AFFECT AS WELL AS LOCATING ALL SHUTOFF POINTS. INCLUDE THIS INFORMATION IN THE OUTAGE PLAN AND SUBMIT TO THE COR FOR APPROVAL.
17. PROVIDE SHUTOFF VALVES IN DOMESTIC WATER SYSTEMS IN BRANCH LINES SERVING TWO OR MORE FIXTURES.
18. PROVIDE WATER HAMMER ARRESTORS AT ALL FAST-CLOSING VALVES. ARRESTORS SHALL CONFORM TO ASSE 1010 AND BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
19. UNLESS OTHERWISE NOTED, WHERE HOT AND COLD WATER PIPING DROPS INTO PIPE CHASE, THE SIZE SHOWN FOR THE PIPE DROPS SHALL
BE USED TO THE LAST FIXTURE.
20. THE MINIMUM SIZE OF WATER SUPPLY MAINS, RISERS, OR BRANCH PIPES SERVING TWO OR MORE PLUMBING FIXTURES, APPLIANCES, OR
OUTLET CONNECTIONS SHALL BE 3/4".
21. USE OF COMBINATION WYE OR CROSS-TEE FITTINGS IN THE PLUMBING SANITARY SYSTEM IS NOT PERMITTED.
22. REFER TO SPECIFICATION SECTION 232000 FOR PLUMBING SYSTEM PIPING REQUIREMENTS. PVC PIPE IS NOT PERMITTED IN CEILING RETURN
AIR PLENUM APPLICATIONS.
23. ADJUST SEWER INVERTS TO KEEP TOPS OF PIPE IN LINE WHERE PIPE SIZE CHANGES.
24. MAINTAIN MINIMUM OF 3'-0" COVER OVER UNDERGROUND WATER MAIN AND MINIMUM OF 2'-6" COVER OVER UNDERGROUND SEWERS AND
DRAINS.
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
ISSUED FOR BID
:1 :2
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
PLUMBING COVER
SHEET
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
54 95
P0.0
GPZ
GPZ
SRH
02/28/2022
(APPLICABLE TO ALL PLUMBING DRAWINGS)
PLUMBING LEGEND
DOMESTIC WATER SERVICE REDUCED PRESSURE ZONE BACKFLOW PREVENTER
DESCRIPTIONSYMBOL
SHUTOFF VALVE
CHECK VALVE
UNION
CAP (PIPE OR DUCT)
ANCHOR
PLAN/ SECTION DESIGNATION
TOP - PLAN/ SECTION REFERENCE,
BOTTOM - REFERENCED DRAWING
M1.1
CONDENSATE DRAIND
WATER METERM
WALL HYDRANT
DRAIN (ALL TYPES)D-(-)
VENT
SANITARYSAN
HOT WATER RETURN- - -
HOT WATER - -
COLD WATER-
PLUMBING ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
APPROX APPROXIMATE
BFP BACKFLOW PREVENTER
BLDG BUILDING
CO CLEANOUT/CONTRACT OFFICER
COND CONDENSATE
CP CONDENSATE PUMP
CW COLD WATER
CX CONNECT TO EXISTING
D DEEP/DEPTH/DIAMETER/DRAIN/DROP
DEG DEGREES
DIA DIAMETER
DN DOWN
DWG DRAWING
DWH DOMESTIC WATER HEATER
EFT ENTERING FLUID TEMPERATURE
EF EXHAUST FAN
EL ELEVATION
ELEV ELEVATION/ELEVATOR
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
FD FLOOR DRAIN
FPD FLUID PRESSURE DROP
FT FEET/FOOT
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H HEIGHT/HIGH
HP HORSEPOWER
HW HOT WATER
HWR HOT WATER RETURN
HZ HERTZ
IN INCH/INCHES
INV INVERT
KW KILOWATT
L LENGTH
LAV LAVATORY
LB POUNDS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MIN MINIMUM
N NORTH
NO NORMALLY OPEN/NUMBER
NTS NOT TO SCALE
P PLUMBING/PLUMBING FIXTURE TYPE
PD PRESSURE DROP/PUMP DISCHARGE/PLUMBING DEMOLITION
PRV PRESSURE REDUCING VALVE
PSI PRESSURE - POUNDS PER SQUARE INCH
PSIG PRESSURE - POUNDS PER SQUARE INCH, GAGE
R RADIUS
RECIRC RECIRCULATION
RPM REVOLUTIONS PER MINUTE
RV RELIEF VALVE
RX REMOVE EXISTING
S SANITARY
SAN SANITARY
SH SHOWER
T TEMPERATURE SENSOR
TEMP TEMPERATURE
TYP TYPICAL
UR URINAL
V VALVE/VENT/VOLTS
VTR VENT THROUGH ROOF
W WIDTH
W/ WITH
WC WATER CLOSET
RX SUMP PUMP
RX PUMP DISCHARGE
RX PUMPRX PRESSURE TANK 1
1RX DWH
RX INCOMING WATER
RX CW
RX CW
RX SINK
RX S
RX S DN
RX S UP
CELLAR
CELLAR
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :4
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
CELLAR - DEMOLITION
- PLUMBING
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
55 95
PD1.1
GPZ
GPZ
SRH
02/28/2022
SCALE BPD1.1
1 CELLAR - PLUMBING - DEMOLITION
REMOVE ALL ASSOCIATED PIPING, WIRING, CONTROLS, ETC.
BACK TO INSIDE OF CELLAR EXTERIOR WALL AND CAP.
3 REMOVE SANITARY PIPE DOWN TO FLOOR AND CAP
REMOVE ASSOCIATED CW, HW, SAN, AND VENT PIPES
BACK TO INSIDE OF CELLAR EXTERIOR WALL AND CAP.
VALVE ALL PRESSURE PIPING.
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)
DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY WEIGHT, DASHED LINE,
3. CONTRACTOR SHALL IDENTIFY REMOVAL OF ALL PLUMBING PIPING AND
EQUIPMENT AND REVIEW WITH COR BEFORE REMOVING. WORK REMOVED
WITHOUT PRIOR CONFIMATION THAT WAS NOT INTENDED TO BE REMOVED
SHALL BE REPLACED IN SAME OR BETTER CONDITION AT CONTRACTOR'S COST.
104 HALLWAY
LIVING ROOM
STAIR
STAIR
PANTRY
HALL
OUT KITCHEN
RX SINK
RX
DISHWASHER
RX WC
RX LAV
RX S
RX S DNRX S DN
4 0 4 8
SCALE OF FEET
A/E FIRM - P15PC00037
TITLE OF SHEET DRAWING NO.
PMIS/PKG NO.
SHEET
OF
PRIME/ARCH:
GWWO, INC.
BALTIMORE, MD
LANDSCAPE:
CS DAVIDSON
GETTYSBURG, PA
CIVIL:
CS DAVIDSON
GETTYSBURG, PA
STRUCTURAL:
SGH
WASHINGTON, DC
MECHANICAL:
HENRY ADAMS
TOWSON, MD
ELECTRICAL:
HENRY ADAMS
TOWSON, MD
PLUMBING:
HENRY ADAMS
TOWSON, MD
FIRE PROTECTION:
HENRY ADAMS
TOWSON, MD
SUB SHEET NO.DESIGNED:
CADD:
TECH. REVIEW:
DATE:
SCALE B
ISSUED FOR BID
:1 :4
A M
C R e vi t P ro je c ts
N Z I M e c h
C e n tr a l (2 za w o d n ia kA Y P F .r vt
FIRST FLOOR -
DEMOLITION -
PLUMBING
GETTYSBURG NATIONAL MILITARY PARK
178321
257363
56 95
PD1.2
GPZ
GPZ
SRH
02/28/2022
SCALE BPD1.2
1 FIRST FLOOR - PLUMBING - DEMOLITION
REMOVE ASSOCIATED CW, HW, SAN, AND VENT PIPES
BACK TO INSIDE OF CELLAR EXTERIOR WALL AND CAP.
VALVE ALL PRESSURE PIPING.
SPECIAL NOTES: (APPLICABLE TO THIS DRAWING ONLY)DRAWING NOTES: (APPLICABLE TO THIS DRAWING ONLY)
1. EXISTING SHOWN WITH LIGHT WEIGHT LINE,
2. DEMOLITION SHOWN WITH HEAVY WEIGHT, DASHED LINE,
3. CONTRACTOR SHALL IDENTIFY REMOVAL OF ALL PLUMBING PIPING AND
EQUIPMENT AND REVIEW WITH COR BEFORE REMOVING. WORK REMOVED
WITHOUT PRIOR CONFIMATION THAT WAS NOT…