A06_Big_Stone_Knight_Fire_Tube_Boiler_Specifications.pdf

PDF 2 MB Posted

Attached to
MN BIG STONE WMD BOILER REPLACEMENT
Solicitation number
140FC226Q0023
Issued by

About this file

This is a product submittal sheet for Lochinvar Knight Fire Tube Boilers, available in both floor and wall-mounted configurations. The document serves as a specification and ordering guide for commercial heating equipment.

The Knight Fire Tube Boiler series features 95% DOE AFUE efficiency across models ranging from 55 MBH to 399 MBH input capacity. Standard features include modulating burners with up to 10:1 turndown, direct spark ignition, low NOx operation, ASME stainless steel heat exchangers, and vertical or horizontal direct vent capabilities using PVC, CPVC, polypropylene, or stainless steel venting up to 100 feet. The advanced Smart System Digital Operating Control provides multi-color graphic LCD display with navigation dial, three boiler setpoint temperature inputs, built-in cascading sequencer for up to eight boilers, outdoor reset control with programmable reset curves, and four pump control options including variable speed boiler pump and DHW recirculation. Additional Smart System capabilities include building management system integration via 0-10 VDC inputs/outputs and Modbus contacts, data logging (runtime hours, ignition attempts, lockout history), maintenance reminders with contractor contact information, low-water flow safety control, and customizable freeze protection. Optional equipment includes Con-x-us Remote Connectivity Modbus communication, BACnet MSTP, flow switch, low-water cutoff with manual reset, alarm bell, condensate neutralization kit, BMS gateway integration, sidewall vent termination, wireless outdoor sensor, LP gas conversion kit, and firing code options (M9 Standard Construction or M7 California Code). Six floor-mount models (KHB055N through KHB285N) and seven wall-mount models (WHB055N through WHB399N) are specified with detailed dimensional data, connection sizes, and shipping weights provided.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KNIGHT

FIRE TUBE BOILER

Submittal Sheet KHBWHB-Sub-02

Job Name: Location:

Engineer: Agent/Wholesaler:

Contractor: Type Gas:

Model #: Equipment Tag(s):

JOB NOTES:

KNIGHT FIRE TUBE BOILERS - FLOOR AND WALL MOUNT MODELS

Smart System Features > Smart System Digital Operating Control

Multi-Color Graphic LCD Display w/Navigation Dial, Soft Keys and Loch-N-Link USB programming

> Three Boiler Setpoint Temperature Inputs Plus Domestic Hot Water Prioritization

> Built-in Cascading Sequencer for up to 8 Boilers, with Cascade Redundancy Multiple Size Boiler Cascade Lead Lag Efficiency Optimization Front End Loading Capability

> Outdoor Reset Control with Outdoor Air Sensor Programmable for Three Reset Temperature Inputs

> Programmable System Efficiency Optimizers SH Night Setback DHW Night Setback Anti-Cycling Outdoor Air Reset Curve Ramp Delay Modulation Factor Control Boost Temperature & Time

> Four Pump Control System Pump with Parameter for Continuous Operation Boiler Pump with Variable Speed Control Domestic Hot Water Pump Domestic Hot Water Recirculation

> Domestic Hot Water Prioritization DHW tank piped with priority in the boiler loop DHW tank piped as a zone in the system with the pumps controlled by the SMART SYSTEM DHW Modulation Limiting Separately Adjustable Space Heat/DHW Switching Times

> Building Management System Integration 0-10 VDC Input to Control Modulation or Setpoint 0-10 VDC Modulation Rate Output 0-10 VDC Input to Enable/Disable Call for Heat

> Access to BMS Settings through Graphic LCD Display

> High-Voltage Terminal Strip 120 VAC / 60 Hertz / 1 Phase Power Supply Three Sets of Pump Contacts

> Low-Voltage Terminal Strip DHW Recirculation Pump Start/Stop 24 VAC Device Relay Configurable Proving Contacts Flow Switch Contacts Alarm on Any Failure Contacts Runtime Contacts DHW Thermostat Contacts 3 Space Heat Thermostat Contacts System Sensor Contacts DHW Tank Sensor Contacts Outdoor Air Sensor Contacts Cascade Contacts

0-10 VDC BMS External Control Contact 0-10 VDC Boiler Rate Output Contacts 0-10 VDC Variable Speed System Pump Signal Input 0-10 VDC Signal to Control Variable Speed Boiler Pump Modbus Contacts

>Time Clock
>Data Logging

Hours Running, Space Heating Hours Running, Domestic Hot Water Ignition Attempts Last 10 Lockouts

> Maintenance Reminder Custom Maintenance Reminder with Contractor Contact Information Installer Ability to De-activate Service Reminder

>Low-Water Flow Safety Control & Indication
>Password Security
>Customizable Freeze Protection Parameters

Standard Features

>95% DOE AFUE Efficiency (55-285)
>Modulating Burner with up to 10:1 Turndown

Direct Spark Ignition Low NOx Operation

> ASME Stainless Steel Heat Exchanger 30 PSI ASME Relief Valve

> Top and bottom water connections (MNPT, WHB 55-285 Only)

> Vertical & Horizontal Direct Vent PVC, CPVC, Polypropylene or SS Venting up to 100 ft.

> Universal Vent Adapter Built-in Combustion Analyzer Port

Optional Equipment

> Firing Codes M9 Standard Construction M7 California Code

Model Number

Input MBH Heating Capacity

MBH

Net

AHRI

Rating

MBH AFUE%

Gas Conn.

Water Conn.

Air Inlet

Vent Size

Shipping Weight (lbs.)Min Max A B C D E F G H I J K

KHB055N 8.3 55 51 44 95 3-1/2" 13-1/4" 6" 2-3/4" 37-2/3" 13-1/2" 8-1/3" 10-1/2" 15" 32-1/2” 8-1/3” 1/2" 1" 2" 2" 160

KHB085N 8.5 85 79 69 95 3-1/2" 13-1/4" 6" 2-3/4" 37-2/3" 13-1/2" 8-1/3" 10-1/2” 15” 32-1/2” 8-1/3” 1/2" 1" 2" 2" 165

KHB110N 11 110 102 89 95 2-3/4" 14-3/4" 7-1/2" 2-3/4" 38" 14-1/3" 9-3/4" 10-1/2” 15” 33" 8-1/3” 1/2" 1" 3" 3" 170

KHB155N 15.5 155 143 124 95 2-3/4" 14-3/4" 7-1/2" 2-1/2" 38" 14-1/3" 9-3/4" 10-1/2” 15” 33” 8-1/3” 1/2" 1" 3" 3" 175

KHB199N 19.9 199 184 160 95 3" 15-1/2" 7-1/2" 2-1/2" 38-1/3" 14-1/3” 10-1/2" 11-1/2” 15” 33” 8-1/3” 1/2" 1-1/4" 3" 3" 195

KHB285N 28.5 285 264 230 95 3" 15-1/2" 7-1/2" 2-1/2" 38-1/3" 14-1/3” 10-1/2" 11-1/2” 15” 33” 8-1/3” 1/2" 1-1/4" 3" 3" 205

2/22—Printed in U.S.A.

Lochinvar, LLC 300 Maddox Simpson Parkway Lebanon, Tennessee 37090 P: 615.889.8900 / F: 615.547.1000

Lochinvar.com

• Information subject to change without notice. • Dimensions shown are approximate and should not be used for construction purposes. •”Output” is “Heating Capacity” for units with inputs <300 MBH and ”Gross Output” for units ≥300 MBH. • Change “N” to “L” for LP gas models. • The Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. • Lochinvar should be consulted before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc. • The ratings have been determined under the provisions governing forced draft burners.

FLOOR MOUNT

TOP RIGHT SIDEBOTTOM

TOP

FRONT LEFT SIDE

J

43-3/8”

16”

19”

A

D

C

B

K

H I

F

E

G

H Flue Vent

Air Intake Water Inlet

Gas Inlet

Water Outlet

Condensate Drain

High Voltage Electrical Connection Low Voltage

Electrical Connection

AC Outlet

F

E

G

I J

K

L M

N

D A

C

Flue Vent Water Inlet

Water Outlet

Air Intake

Gas Inlet

High Voltage Electrical

Connection

Low Voltage Electrical

Connection

Condensate Drain

AC

Outlet

WHB055N8.355514495.0--40" 18-3/4"16" 31-1/8"8-1/2"3-3/4"4-1/2"6-1/2"7-1/4"8-7/8"3-1/2"1-1/2"1-1/2"6" 1/2"1"2"2"139
WHB085N8.585796995.0--39-3/4"18-3/4"16" 31-1/8"8-1/2"3-3/4"4-1/2"6-1/2"7-1/4"8-7/8"3-1/2"1-1/2"1-1/2"6" 1/2"1"2"2"142
WHB110N111101028995.0--41-1/4"18-3/4"19" 31-1/8"10" 2-3/4"5" 5-1/4"11-1/2"8-1/2"5" 1" 1" 4-1/2"1/2"1" 3"3"159
WHB155N15.515514412595.0--41-1/4"18-3/4"19-1/8"31-1/8"10" 2-3/4"5" 5-1/4"11-1/2"8-1/2"5" 1" 1"4-1/2"1/2"1" 3"3"166
WHB199N19.919918416095.0--41-1/4"18-3/4"19-1/8"31-1/8"10-1/2"3" 5-1/4"6" 11"9-1/2"6-1/4"1-1/2"1-1/2"4-1/2"1/2"1-1/4"3" 3"175
WHB285N28.528526423095.0--41-3/4"18-3/4"21-1/8"31-1/8"15" 3" 3-3/4"5-1/4"12-1/4"11" 6-1/4"1-1/2"1-1/2"6-1/2"1/2"1-1/4"3" 3"184
WHB399N39.9399377328- 96.094.4 43-5/8"25-1/4"21-7/8"34-3/8"3-1/8"4-1/4"23" 3-7/8"8-3/4"12-1/2"9-1/4"2" 2" 23" 3/4"1-1/2"4"4"213

WALL MOUNT

Model Number

Input MBH

*Output

MBH

Net AHRI Rating, Water, MBH AFUE,% Co mb us tio n

Eff ici en cy

Th er ma l

Eff ici en cy

Min Max A B C D E F G H I J K L M N Gas

Conn.

Water Conn.

Air Inlet

Vent Size

Ship Wt.

(lbs.)

B

For technical information call 800-722-2101. Lochinvar, LLC reserves the right to make product changes or improvements without prior notice.

khb285text:
knb199text:
khb155text:
khb110text:
khb085Text:
khb055Text:
KHb055:
whb055:
KHb085:
KHb110:
KHb155:
KHb199:
KHb285:
khb055CK:
whb055CK:
khb085CK:
KHB110ck:
KHb155CK:
KHb199CK:
KHb285CK:
WHB055txt:
WHB085txt:
WHB110txt:
WHB155txt:
WHB199txt:
WHB399txt:
WHB285txt:
whb085:
whb085CK 2:
whb110:
whb110CK:
whb155:
whb155CK:
whb199:
whb199CK:
whb285:
whb285CK:
whb399:
whb399CK:
kbwbname:
kbwblocation:
kbwbengr:
kbwbwholesaler:
kbwbcontractor:
kbwbfuel:
kbwbmodel:
kbwbeqtags:
kbwbnotes:
kbwb-cb1: Off
kbwb-cb2: Off
kbwb-cb3: Off
kbwb-cb4: Off
kbwb-cb5: Off
kbwb-cb6: Off
kbwb-cb7: Off
kbwb-cb8: Off
kbwb-cb9: Off
kbwb-cb10: Off
kbwb-cb11: Off
kbwb-cb12: Off
kbwb-cb13: Off
kbwb-cb14: Off

File details come from the government source that posted it. Updated .