A06_Appendix_A-Fog_Signal_Pages_from_Asbestos_and_Lead_Based_Paint_Assessment_Survey_2023.pdf

PDF 3 MB Posted

Attached to
WI-HORICON NWR-SIGNAL BUILDING PROJECT
Solicitation number
140FC225Q0051
Issued by

About this file

This document is an asbestos and lead-based paint inspection report for the US Fish and Wildlife Service Fog Signal building on Plum Island, Wisconsin. On May 17, 2023, TriMedia Environmental & Engineering conducted a comprehensive hazardous materials survey of the approximately 1,000 square foot two-story brick building. The asbestos survey identified several materials containing asbestos, including brown and red floor tiles (3-9% Chrysotile), transite siding (10% Chrysotile), and white caulk (4% Chrysotile) surrounding windows and doors. Additionally, the lead inspection using X-ray fluorescence (XRF) detected lead-containing paint on multiple exterior and interior components, including trim, soffits, door frames, and sign posts.

The report recommends managing asbestos-containing materials according to OSHA and EPA regulations, and notes that all paint on the building is in damaged condition with significant peeling and chipping. TriMedia suggests repairing lead-containing painted surfaces through enclosure, encapsulation, or abatement before the building is accessible to the public. The inspection also identified potential health hazards such as animal feces and mold, recommending proper clean-up protocols and addressing water infiltration. The building's poor condition and the presence of hazardous materials necessitate careful remediation before any future use or public access.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

830 W. Washington Street Marquette, MI 49855

906.228.5125

906.228.5126 Fax

www.trimediaee.com

US Fish and Wildlife – Plum Island, WI Fog Signal

TriMedia was on-site on May 17, 2023 to conduct sampling to identify the presence of asbestos-containing materials (ACM), lead-containing paint and other hazardous materials within the identified building. The property was in poor condition; however, safe entry was possible to all desired areas.

The site is approximately 1,000 sq. ft. two-story property. The property is constructed of brick with wood framing and metal supports. The shingled roof appears to be less than 10 years of age;

however, remnants of the former roof remain. The assessment is intended to identify building contaminants that, if mismanaged during demolition or alteration activities, could pose an environmental or health and safety concern.

ASBESTOS SURVEY

TriMedia collected a total of 25 samples (consisting of 37 sample layers) of suspect asbestos-containing materials to be submitted for laboratory analysis. Sample Locations for Asbestos can be found in Figure 1: Asbestos Sample Locations.

ASBESTOS RESULTS

Asbestos was detected in the following materials;

• Samples 001a through 001c brown floor tile and mastic are between 3% and 8% Chrysotile and is found within the watch room.

• Samples 002a through 002c red floor tile and mastic range from 5% and 9% Chrysotile and is found within the watch room.

• Samples 005a through 005c transite siding are 10% Chrysotile and is found surrounding the watch room.

• Samples 008a through 008c white caulk are 4% Chrysotile and is found surrounding all exterior windows and doors.

The shingled roof and other roofing materials were not sampled as part of the assessment and should be treated as presumed asbestos containing materials and must be sampled prior to replacement or disturbance.

Complete analytical laboratory results have been enclosed for your records. Sampled materials, locations, and analytical results have been summarized in Table 1: Materials Sampled and Found to Not Contain Asbestos and Table 2: Materials Sampled and Found to Contain Asbestos.

LEAD INSPECTION

▪ TriMedia utilized an XRF to perform a lead inspection collecting 26 unique readings of different building components as required per EPA/HUD inspection protocols. The inspection was limited to the exterior of the building and one interior reading to confirm it being of high lead content. Sample Locations for Lead can be found in Figure 2: Lead Sample Locations.

Inspection Report

LEAD CONTAINING PAINT RESULTS

XRF readings detected the presence of lead equal to or above EPA/HUD regulation of 1 mg/cm2 in 18 readings. A full summary of building component readings and estimated quantities can be found in Table 3: Lead Inspection

OTHER HAZARDOUS MATERIALS

Animal feces can be a serious indoor air quality concern based on the presence of fungus and yeast capable of infecting humans through inhalation and can also contain Escherichia Coli SP. (E. Coli).

While there are no current regulatory guidelines for feces disposal or remediation, it is recommended that personnel receive training on proper clean up methods, personal protection, and potential health hazards prior to clean up.

The building has the potential for elevated levels of mold. It is important to note that all individuals respond differently to their environments, and some individuals may be sensitive to airborne mold spores even at lower spore counts. There is no regulatory limit for disposal or established threshold levels at which adverse health effects are documented. TriMedia recommends stopping water infiltration into the building and cleaning the building with a bleach based cleaner to remediate any historical mold growth.

SUMMARY OF FINDINGS AND RECOMMENDATIONS

▪ Asbestos containing material must be managed in accordance with provisions stipulated in States Occupational Safety and Health Administration (US OSHA) Safety and Health Regulations for Construction, Part 29 Code of Federal Regulations 1926.1101 and in accordance with applicable provisions in Environmental Protection Agency (EPA) National Emissions Standards for Hazardous Air Pollutants (NESHAP) 40 CFR Part 61, Subpart M.

▪ It is TriMedia’s opinion that all paint on the Fog Signal building is in damaged or significantly damaged condition with peeling and chipping occurring on all lead containing paints. The window and components, door and components, soffit and fascia, sign and signposts, sump pit doors, and all interior surfaces should be treated as lead containing paint. It is TriMedia’s opinion that lead-containing painted surfaces be repaired by enclosure, encapsulation, or abatement prior to the building being open to the general public. In addition, TriMedia recommends that items currently stored within the building be covered to prevent chipping paint from falling on them.

▪ Information regarding painted surfaces must be provided to contractors who may be performing paint-disturbing activities and to scrap metal dealers or other entities who may take possession of the materials. Applicable state, federal and local regulations for worker and environmental protection must be met when impacting lead-containing paint during paint-disturbing activities. Additional requirements may be enforced based on owning agency policies and procedures, up to Housing and Urban Development (HUD) requirements.

TriMedia made every reasonable attempt to access all areas of the building. However, as with all hazardous material assessments, there exists the potential for discovering additional suspect materials not addressed by this report during demolition activities. In the event suspect materials are identified during on-site activities, they must be sampled before being disturbed.

Inspection Report

Enclosures: Table 1: Materials Sampled and Found to Not Contain Asbestos Table 2: Materials Sampled and Found to Contain Asbestos Table 3: Lead Inspection Figure 1: Asbestos Sample Locations Figure 2: Lead Sample Locations Photo Log Asbestos Photo Log Lead EMSL Analytical Reports

Sincerely, TriMedia Environmental & Engineering Services, LLC

Tim Sorensen, ASP Project Industrial Hygienist State of Wisconsin Inspector AII-188677 Lead Inspector License LRA-188677

Table 1 Materials Sampled and Found to Not Contain Asbestos

USFWS

Fog Signal - Plum Island TriMedia 2023-0280

Sample # (Layers)* Material/Description

FS-A-003a Watch room Walls below 4 ft Drywall

FS-A-003b Watch room Walls below 4 ft Drywall

FS-A-003c Watch room Walls below 4 ft Drywall

FS-A-004a Watch room Walls above 4 ft Cellulose Acoustical tile

FS-A-004b Watch room Walls above 4 ft Cellulose Acoustical tile

FS-A-004c Watch room Walls above 4 ft Cellulose Acoustical tile

FS-A-005a (1 of 2) Surrounding whole building On exterior walls tar paper (exterior)

FS-A-005b (1 of 2) Surrounding whole building On exterior walls tar paper (exterior)

FS-A-005c (1 of 2) Surrounding whole building On exterior walls tar paper (exterior)

FS-A-006a (2) Watch room Perimeter of floor Cove base molding and adhesive

FS-A-006b (2) Watch room Perimeter of floor Cove base molding and adhesive

FS-A-006c (2) Watch room Perimeter of floor Cove base molding and adhesive/glue

FS-A-007a Cupola On ground within attic Cellulose blown in pile

FS-A-007b Cupola On ground within attic Cellulose blown in pile

FS-A-007c Cupola On ground within attic Cellulose blown in pile

FS-A-009 Exterior West Taken from ground pile Shingles

*Material layers separated in lab

Location Details

Table 2 Materials Sampled and Found to Contain Asbestos

USFWS

Fog Signal - Plum Island TriMedia 2023-0280

Sample # (Layers)* Material/Description Material Condition Asbestos Concentration Estimated

Quantity**

Estimated Abatement

Cost**

FS-A-001a (1 of 2) Brown Floor Tile Significantly Damaged 8% Chrysotile

FS-A-001a (2 of 2) Brown Floor Tile Mastic Significantly Damaged 3% Chrysotile

FS-A-001b (1 of 2) Brown Floor Tile Significantly Damaged Stop Positive

FS-A-001b (2 of 2) Brown Floor Tile Mastic Significantly Damaged Stop Positive

FS-A-001c (1 of 2) Brown Floor Tile Significantly Damaged Stop Positive

FS-A-001c (2 of 2) Brown Floor Tile Mastic Significantly Damaged Stop Positive

FS-A-002a (1 of 2) Red Floor tile Significantly Damaged 9% Chrysotile

FS-A-002a (2 of 2) Red Floor tile Mastic Significantly Damaged 5% Chrysotile

FS-A-002b (1 of 2) Red Floor tile Significantly Damaged Stop Positive

FS-A-002b (2 of 2) Red Floor tile Mastic Significantly Damaged Stop Positive

FS-A-002c (1 of 2) Red Floor tile Significantly Damaged Stop Positive

FS-A-002c (2 of 2) Red Floor tile Mastic Significantly Damaged Stop Positive

FS-A-005a (1 of 2) Surrounding whole building On exterior walls Transite Siding (exterior) Damaged 10% Chrysotile

FS-A-005b (1 of 2) Surrounding whole building On exterior walls Transite Siding (exterior) Damaged Stop Positive

FS-A-005c (1 of 2) Surrounding whole building On exterior walls Transite Siding (exterior) Damaged Stop Positive

FS-A-008a All exterior walls door/window borders Caulk (exterior) Significantly Damaged 4% Chrysotile

FS-A-008b All exterior walls door/window borders Caulk (exterior) Significantly Damaged Stop Positive

FS-A-008c All exterior walls door/window borders Caulk (exterior) Significantly Damaged Stop Positive

Material Condition

Good = No damage at all

Damaged = evenly distributed damage over <10% of a functional space/material or localized over <25% of a functional space/material

Significantly Damaged = evenly distributed damage over 10% or more of the functional space/material or localized over 25% of a functional space/material

*Material layers separated in laboratory

$900 to $6,675

Watch room Floor

$825 to $2,451

$82.50 to $245

$700 to $2,352

**The provided quantities and estimated costs are for engineering and budgeting purposes only and should not be used for contractor bid development. Bidding contractors should produce internal quantifications based on their work plan.

Location Details

150 sqft

15 sq ft

147 sq ft

150 ln ft

Watch room Floor

Watch room Floor

Watch room Floor

Watch room Floor

Watch room Floor

Table 3 - Lead Inspection USFWS - Plum Island

Fog Signal TriMedia 2023-0280

Sample

ID #

Sample Side

Room Equivalent Component Substrate Color XRF Reading HUD/EPA

Classification Lead

Containing Material

Condition Estimated Quantity** Estimated Abatement Cost**

FS-Pb-1 A Exterior Wall Brick White 0.005 Negative Yes Damaged NA NA

FS-Pb-2 A Exterior Wall Brick Gray 0.032 Negative Yes Damaged NA NA

FS-Pb-3 A Exterior Trim Wood Gray 3.409 Positive Yes Damaged 31.25 sq ft $781.25 - $937.50 FS-Pb-4 A Exterior Soffit Metal Gray 3.634 Positive Yes Damaged 125 sq ft $3125 - $3750 FS-Pb-5 A Exterior Trim Wood Red 0.134 Negative Yes Damaged NA NA

FS-Pb-6 A Exterior Door Trim Wood White 2.147 Positive Yes Damaged 8 sq ft $200 - $240 FS-Pb-7 A Exterior Door Header Wood White 2.992 Positive Yes Damaged 4 sq ft $100 - $120 FS-Pb-8 B Exterior Wall Brick White 0.273 Negative Yes Damaged NA NA

FS-Pb-9 B Exterior Wall Brick Gray 0.032 Negative Yes Damaged NA NA

FS-Pb-10 B Exterior Window Sill Wood White/Gray 3.164 Positive Yes Damaged 8 sq ft $200 - $240 FS-Pb-11 B Exterior Window Header Wood White 1.441 Positive Yes Damaged 4 sq ft $100 - $120 FS-Pb-12 B Exterior Door Trim Wood White 4.333 Positive Yes Damaged 8 sq ft $200 - $240 FS-Pb-13 B Exterior Door Header Wood White 3.942 Positive Yes Damaged 4 sq ft $100 - $120 FS-Pb-14 B Exterior Trim Wood White 3.802 Positive Yes Damaged 31.25 sq ft $781.25 - $937.50 FS-Pb-15 B Exterior Wall Transite White 0.011 Negative Yes Damaged NA NA

FS-Pb-16 B Exterior Window Trim Wood White 2.023 Positive Yes Damaged 4 sq ft $100 - $120 FS-Pb-17 B Exterior Soffit Wood White 2.243 Positive Yes Damaged 125 sq ft $3125 - $3750 FS-Pb-18 B Exterior Fascia Wood White 3.929 Positive Yes Damaged 62.5 sq ft $1562.5 - $1875 Fs-Pb-19 B Exterior Wall Trim Wood White 3.005 Positive Yes Damaged 31.25 sq ft $781.25 - $937.50 FS-Pb-20 B Exterior Sump Door Metal Yellow 1.61 Positive Yes Damaged 18 sq ft $450 - $540 FS-Pb-21 C Exterior Foundation Concrete Gray 0.021 Negative Yes Damaged NA NA

FS-Pb-22 D Exterior Sign Posts Metal Gray 1.846 Positive Yes Damaged 230 sq ft $5750 - $6900 FS-Pb-23 D Interior Walls Brick White 9.125 Positive Yes Damaged NA (all interior) NA

FS-Pb-24 D Interior Door Jamb Wood White 2.363 Positive Yes Damaged 80 sq ft $2000 - $2400 FS-Pb-25 D Exterior Door Wood Green 2.363 Positive Yes Damaged Included with Jamb Included with Jamb

FS-Pb-26 D Exterior Door Floor Concrete Yellow 0.063 Negative Yes Damaged NA NA

Material Condition Good = No damage at all Damaged = evenly distributed damage over <10% of a functional space/material or localized over <25% of a functional space/material Significantly Damaged = evenly distributed damage over 10% or more of the functional space/material or localized over 25% of a functional space/material

Table 3 - Lead Inspection USFWS - Plum Island

Fog Signal TriMedia 2023-0280

Calibration Check

Fog Signal

Test Type Device XRF Serial No. Contractor Inspector NIST SRM Used

Calibration Check Tolerance Used First Reading Second

Reading Third Reading Average

Initial SciAps X- 550 00342 TriMedia TRS 1.04 0.8-1.2 1.105 1.057 1.051 1.071

20 Sample SciAps X- 550 00342 TriMedia TRS 1.04 0.8-1.2 1.11 1.072 1.066 1.082666667

Post

SciAps X-

550 00342 TriMedia TRS

1.04 0.8-1.2 1.13 1.07 1.041 1.080333333

**The provided quantities and cost estimates are for engineering and budgeting purposes only and should not be used for contractor bid development. Bidding contractors should produce internal quantifications based on their work plan.

US FISH & WILDLIFE – PLUM ISLAND

FOG SIGNAL - ASBESTOS

Photo Log Page 1 of 6 Fog Signal - Asbestos TriMedia Project #2023-0280

Description: FS-A-001a – brown floor tile – 8% Chrysotile Date: 5/17/23 Taken By: AJV

Description: FS-A-001b – brown floor tile – 8% Chrysotile

Description: FS-A-001c – brown floor tile – 3%-8% Chrysotile Date: 5/17/23 Taken By: AJV

Description: FS-A-002a – red floor tile – 5%-9% Chrysotile

Photo Log Page 2 of 6

Description: FS-A-002b – red floor tile – 5%-9% Chrysotile

Description: FS-A-002c – red floor tile – 5%-9% Chrysotile

Description: FS-A-003a - drywall

Description: FS-A-003b - drywall

Photo Log Page 3 of 6

Description: FS-A-003c - drywall

Description: FS-A-004a – cellulose acoustical tile

Description: FS-A-004b – cellulose acoustical tile

Description: FS-A-004c – cellulose acoustical tile

Photo Log Page 4 of 6

Description: FS-A-005a – transite siding – 10% Chrysotile

Description: FS-A-005b – transite siding – 10% Chrysotile

Description: FS-A-005c – transite siding – 10% Chrysotile

Description: FS-A-006a – cove base

Photo Log Page 5 of 6

Description: FS-A-006b – cove base

Description: FS-A-006c – cove base

Description: FS-A-007abc - Cellulose

Description: FS-A-008a – Caulk – 4% Chrysotile

Photo Log Page 6 of 6

Description: FS-A-008b – Caulk – 4% Chrysotile

Description: FS-A-008c – Caulk – 4% Chrysotile

Description: FS-A-009 - shingles

FOG SIGNAL - PAINT

Photo Log Page 1 of 5 Fog Signal - Paint

Description: FS-Pb-3 – gray trim – 3.409

Description: FS-Pb-4 – gray soffit – 3.634

Description: FS-Pb-6 – white door trim – 2.147

Description: FS-Pb-7 – white door header – 2.992

Photo Log Page 2 of 5

Description: FS-Pb-10 – white/gray windowsill – 3.164

Description: FS-Pb-11 – white window header – 1.441

Description: FS-Pb-12 – white door trim – 4.333

Description: FS-Pb-13 – white door header – 3.942

Photo Log Page 3 of 5

Description: FS-Pb-14 – white trim – 3.802

Description: FS-Pb-16 – white window trim – 2.023

Description: FS-Pb-17 – white wood soffit – 2.243

Description: FS-Pb-18 – white wood fascia – 3.929

Photo Log Page 4 of 5

Description: FS-Pb-19 – white wall trim – 3.005

Description: FS-Pb-20 – yellow sump door – 1.610

Description: FS-Pb-22 – gray sign posts – 1.846

Description: FS-Pb-23 – white interior wall – 9.125

Photo Log Page 5 of 5

Description: FS-Pb-24 – white door jamb – 2.363

Description: FS-Pb-25 – green door – 2.363

EMSL Analytical, Inc.

15111 Northville Rd Plymouth, MI 48170

Tel/Fax: (734) 668-6810 / (734) 668-8532 http://www.EMSL.com / annarborlab@emsl.com

082301060EMSL Order:

Customer ID: TRIC50

Customer PO: 2023-0280

Project ID:

Attention: Phone:Tim Sorensen (906) 228-5125

Fax:TriMedia Environmental & Engineering Svs (906) 228-5126

Received Date:830 W. Washington St 05/23/2023 12:45 PM

Analysis Date:Marquette, MI 49855 05/24/2023 - 05/25/2023

Collected Date:

Project: 2023-0280-Plum Island Fog Signal

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

FS-A-001a

082301060-0001

8% ChrysotileNon-fibrous (Other)92%Tan

Non-Fibrous

Heterogeneous

Floor Tile

FS-A-001a

082301060-0001A

3% ChrysotileNon-fibrous (Other)97%Black

Non-Fibrous

Heterogeneous

Mastic

FS-A-001b

082301060-0002

Positive Stop (Not Analyzed)Floor Tile

FS-A-001b

082301060-0002A

Positive Stop (Not Analyzed)Mastic

FS-A-001c

082301060-0003

Positive Stop (Not Analyzed)Floor Tile

FS-A-001c

082301060-0003A

Positive Stop (Not Analyzed)Mastic

FS-A-002a

082301060-0004

9% ChrysotileNon-fibrous (Other)91%Red

Non-Fibrous

Heterogeneous

Floor Tile

FS-A-002a

082301060-0004A

5% ChrysotileNon-fibrous (Other)95%Black

Non-Fibrous

Heterogeneous

Mastic

FS-A-002b

082301060-0005

Positive Stop (Not Analyzed)Floor Tile

FS-A-002b

082301060-0005A

Positive Stop (Not Analyzed)Mastic

FS-A-002c

082301060-0006

Positive Stop (Not Analyzed)Floor Tile

FS-A-002c

082301060-0006A

Positive Stop (Not Analyzed)Mastic

FS-A-003a

082301060-0007

None DetectedNon-fibrous (Other)80%Cellulose20%White

Fibrous

Heterogeneous

Drywall

FS-A-003b

082301060-0008

None DetectedNon-fibrous (Other)85%Cellulose15%White

Fibrous

Heterogeneous

Drywall

FS-A-003c

082301060-0009

None DetectedNon-fibrous (Other)93%Cellulose7%Brown/Gray

Fibrous

Heterogeneous

Drywall

FS-A-004a

082301060-0010

None DetectedNon-fibrous (Other)10%Cellulose90%Tan

Fibrous

Homogeneous

Ceiling Tile

Initial report from: 05/30/2023 16:33:25

Page 1 of 3ASB_PLM_0008_0001 - 1.78 Printed: 5/30/2023 4:33 PM

Tel/Fax: (734) 668-6810 / (734) 668-8532 http://www.EMSL.com / annarborlab@emsl.com

082301060EMSL Order:

Customer ID: TRIC50

Customer PO: 2023-0280

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

FS-A-004b

082301060-0011

None DetectedNon-fibrous (Other)10%Cellulose90%Tan

Fibrous

Homogeneous

Ceiling Tile

FS-A-004c

082301060-0012

None DetectedNon-fibrous (Other)5%Cellulose95%Brown/White

Fibrous

Heterogeneous

Ceiling Tile

FS-A-005a

082301060-0013

10% ChrysotileNon-fibrous (Other)90%Gray

Fibrous

Heterogeneous

Transite

FS-A-005a

082301060-0013A

None DetectedNon-fibrous (Other)10%Cellulose90%Black

Fibrous

Heterogeneous

Tar Paper

FS-A-005b

082301060-0014

Positive Stop (Not Analyzed)Transite

FS-A-005b

082301060-0014A

None DetectedNon-fibrous (Other)10%Cellulose90%Black

Fibrous

Heterogeneous

Tar Paper

FS-A-005c

082301060-0015

Positive Stop (Not Analyzed)Transite

FS-A-005c

082301060-0015A

None DetectedNon-fibrous (Other)20%Cellulose80%Black

Fibrous

Homogeneous

Tar Paper

FS-A-006a

082301060-0016

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Cove Base

FS-A-006a

082301060-0016A

None DetectedNon-fibrous (Other)100%Yellow

Non-Fibrous

Homogeneous

Adhesive

FS-A-006b

082301060-0017

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Cove Base

FS-A-006b

082301060-0017A

None DetectedNon-fibrous (Other)100%Brown

Non-Fibrous

Homogeneous

Adhesive

FS-A-006c

082301060-0018

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Cove Base

FS-A-006c

082301060-0018A

None DetectedNon-fibrous (Other)100%Cellulose<1%Brown/Yellow

Non-Fibrous

Heterogeneous

Adhesive/Glue

Inseperable Layers

FS-A-007a

082301060-0019

None DetectedNon-fibrous (Other)6%Min. Wool94%White

Fibrous

Homogeneous

Insulation

FS-A-007b

082301060-0020

None DetectedNon-fibrous (Other)4%Min. Wool96%White

Fibrous

Homogeneous

Insulation

FS-A-007c

082301060-0021

None DetectedNon-fibrous (Other)2%Cellulose

Min. Wool

8%

90%

Gray

Fibrous

Homogeneous

Insulation

FS-A-008a

082301060-0022

4% ChrysotileNon-fibrous (Other)96%Gray

Non-Fibrous

Heterogeneous

Caulk

FS-A-008b

082301060-0023

Positive Stop (Not Analyzed)Caulk

Page 2 of 3ASB_PLM_0008_0001 - 1.78 Printed: 5/30/2023 4:33 PM

Tel/Fax: (734) 668-6810 / (734) 668-8532 http://www.EMSL.com / annarborlab@emsl.com

082301060EMSL Order:

Customer ID: TRIC50

Customer PO: 2023-0280

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

FS-A-008c

082301060-0024

Positive Stop (Not Analyzed)Caulk

FS-A-009

082301060-0025

None DetectedQuartz

Non-fibrous (Other)

8%

37%

Cellulose55%Black

Fibrous

Heterogeneous

Shingles

Analyst(s)

Eric Budai (6)

Kassandra Maraz (19)

Eric Budai, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Plymouth, MI NVLAP Lab Code 101048-4

Page 3 of 3ASB_PLM_0008_0001 - 1.78 Printed: 5/30/2023 4:33 PM

OrderID: 082301060

OrderID: 082301060