This document is a Brand Name or Equal Specification for a motor-operated plug valve assembly required for delivery to 7794 Folsom Dam Road, Folsom, CA 95630, Attn: Janell Vincent, on an F.O.B. Destination basis.
The specification calls for a ten-inch Nordstrum Dynamic Plug Valve Assembly (or equivalent) consisting of three integrated components: a 10" Nordstrum 1949 Plug Valve, a Limitorque MXB Series Electric Actuator, and a Limitorque WG35 Gear Box. The valve body must be ASME B16.34 Class 150 iron in Figure 1949 Short Pattern with a 10-inch nominal pipe size and a 13.00-inch face-to-face flanged dimension. The valve plug shall be a quarter-turn metal tapered design with a coated, low-friction surface and self-protecting metal seating. It must include an integral sealant system with a replaceable drop-tight sealant injection fitting and internal configuration that maintains pressure equalization while protecting the balancing system from foreign material. The gear box shall have a 52:1 ratio (or as appropriate for the connected actuator), adjustable quarter-turn travel, self-locking bronze worm gear with steel worm shaft, FA16 iron housing, and position indication on the housing cover. The electric actuator must be multi-turn, 3-phase, 60 Hertz, 480 VAC. The assembly shall be fully assembled and cycle tested at the factory. The contractor is responsible for protecting all parts from corrosion, deformation, and damage during storage, handling, and delivery, with any transit damage to be replaced at the contractor's expense.
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BRAND NAME OR EQUAL SPECIFICATIONS:
Furnish a ten (10) inch motor operated Nordstrum Dynamic Plug Valve Assembly (or equivalent) with the following specifications:
Assembly includes:
10” Nordstrum 1949 Plug Valve (or equivalent)
Limitorque MXB Series Electric Actuator (or equivalent), and
Limitorque WG35 Gear Box (or equivalent)
A. Valve body:
1. Figure 1949 Short Pattern.
2. ASME B16.34 Class 150 iron.
3. Nominal Pipe Size: 10”.
4. Flanged ends face-to-face dimension of 13.00 inch.
5. Top mounted worm gear operator.
6. Metal embossed nameplate with valve information.
7. Valve markings that comply with MSS SP-25.
B. Flanged ends:
1. ASME B16.47 Series A raised face.
2. Two (2) threaded UNC ¾”-10 bolt holes.
C. Valve plug:
1. Quarter-turn metal tapered plug.
2. Coated for low-friction operation.
3. Self-protecting and self-cleaning metal seating surface with no enlarged pockets or recesses.
4. Integral sealant system with replaceable drop-tight sealant injection fitting that allows jacking of valve from seat and seat restoration with high-pressure lubricant gun.
5. Internal configuration that:
a. Maintains pressure equalization between the plug port and the bottom of the plug,
b. Ensures that pressure above the plug is equal or greater than the plug port, and
c. Protects balancing system from foreign material exposure in line fluid.
6. Spring loaded to prevent jamming of plug into taper.
D. Valve Stem:
1. Coated for low-friction operation.
E. Gear box
1. 52:1 ratio or as appropriate for the connected electric actuator.
2. Adjustable travel for quarter-turn applications.
3. Self-locking bronze worm gear with steel worm shaft.
4. Constructed for manual operation with handwheel in accordance with AWWA C504 or motorized operation in accordance with AWWA C542.
5. FA16 iron housing.
6. Position indication on housing cover with pointer on top cap.
F. Manual handwheel
G. Electric Actuator
1. Multi-turn
2. 3 phase, 60 Hertz, 480 VAC
H. Factory testing and assembly:
1. Fully assembled and cycle tested in the factory.
I. DELIVERY TERMS: The contractor shall protect all parts from corrosion, deformation, and other types of damage during storage, handling, and delivery. Damage to the product or its components during transit shall be replaced at the contractor’s expense.
Delivery Address: 7794 Folsom Dam Road, Folsom, CA. 95630, Attn: Janell Vincent
F.O.B. Destination