The document provided is an Excel spreadsheet listing the elevators located at the Grand Coulee Dam and related facilities, as well as a related federal contract opportunity.
The spreadsheet contains detailed information about each elevator, including the rated payload, car speed, machine type, controller type, roping hitch, and installation and modernization dates. It also includes a schedule for the required 5-year and annual elevator inspections and tests.
The related federal contract opportunity is for "Annual & 5-Year Elevator Inspections" at the Grand Coulee Dam, with a Solicitation Number of 140R1724Q0042. The opportunity is being issued by the Department of the Interior Bureau of Reclamation. The contract will involve performing the required elevator inspections and tests as detailed in the spreadsheet.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140R1724Q0042.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 List of Elevators
Grand Coulee Elevators Main Dam Right Power House Left Power House Pump/Generation Plant Wing Dam tc={2C514140-C2ED-4E0B-B9BF-BBC874035DF8}: [Threaded comment]
Your version of Excel allows you to read this threaded comment; however, any edits to it will get removed if the file is opened in a newer version of Excel. Learn more: https://go.microsoft.com/fwlink/?linkid=870924
Comment:
| Forebay Dam | Third Power Plant | Industrial Area | Fire Station | |||||||||||||||||
| B11 | B31 | B64 | B84 | RP1 | RP2 | LP1 | LP2 | P1 | P11 | P13 | B119 | TPN | TPS | TP Inclined | ADMIN | VAC | FS (as specified) | |||
| Parameter | ||||||||||||||||||||
| Rated Payload-Lbs | 10,000 | 10,000 & 44,000 | 10,000 | 10,000 | 12,000 | 12,000 | 12,000 | 4,000 | 8,500 | 5,000 | 8,000 | 3,500 | 10,000 | 10,000 | 10,000 | 3,500 | 3,500 | 2,100 |
Car Speed-FPM 500 500 & 25 500 500 500 500 500 500 500 200 500 350 200 200 200 150 50 75 - 80
Machine Type Gearless Gearless Gearless Gearless Gearless Gearless Gearless Gearless Gearless Geared Gearless Geared Geared Geared Geared Hydraulic Hydraulic Hydraulic
Machine-AC/DC DC DC-Two in tandem DC DC DC DC DC DC DC AC DC AC DC DC DC n/a n/a n/a
| Controller Type | Thyssen | Otis | MCE | MCE | MCE | MCE | MCE | MCE | MCE | MCE | MCE | MCE | Westinghouse | Westinghouse | MCE | ThyssenKrupp | MCE | |
| Counterweight-% | 45 | 45 | 40 | 40 | 45 | 45 | 45 | 45 | 40 | 40 | 40 | 40 | 40 | 40 | n/a | n/a | n/a | |
| Roping Hitch | 2:1 | 2:1 | 2:1 | 2:1 | 2:1 | 2:1 | 2:1 | 2:1 | 2:1 | 1:1 | 2:1 | 1:1 | 2:1 | 2:1 | n/a | n/a | n/a | |
| Wrap | Double | Double | Double | Double | Double | Double | Double | Double | Double | Double | Underslung | Underslung | Double | n/a | n/a | n/a | ||
| Number of Landings | 10 | 12 | 12 | 9 | 9 | 6 | 11 | 11 | 5 | 5 | 12 | 9 | 5 | 5 | 3 | 2 | 3 | 2 |
| Installed Date | 1942 | 1942 | 1947 | 1947 | 1949 | 1949 | 1942 | 1942 | 1950-53 | 1950-53 | 1950-53 | 1972 | 1972 | 1972 | 1990 | 2005 | 20XX | |
| Contract Modernized Award Date | 1996 | 2006 | 2006 | 1999 | 1999 | 1999 | 1999 | 2006 | 2006 | 2006 | 2006 | 2013 | 2013 | N/A | ||||
| Original Manufacturer | Otis | Otis | Otis | Otis | Otis | Otis | Otis | Otis | Westinghouse | Westinghouse | Westinghouse | Westinghouse | Westinghouse | Westinghouse | Western Gear | Amtech | ThyssenKrupp | ThyssenKrupp or equal |
Inspect and Test to ASME Code Edition 1996 As applicable 2004 2004 1996 1996 1996 1996 2004 2004 2004 2004 2010 2010 As applicable 2004 As applicable
Test Schedule
| Elevator | B11 | B31 | B64 | B84 | RP1 | RP2 | LP1 | LP2 | P1 | P11 | P13 | B119 | TPN | TPS | TP Inclined | ADMIN | VAC | Fire Station | |
| Test Type | Year | ||||||||||||||||||
| 5-year Test Required | FY25 | Yes | TBD | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Out of Service | Yes | Yes | No |
| Annual Test Required | FY26 | Yes | TBD | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Out of Service | Yes | Yes | No |
| Annual Test Required | FY27 | Yes | TBD | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Out of Service | Yes | Yes | No |
| Annual Test Required | FY28 | Yes | TBD | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Out of Service | Yes | Yes | No |
| Annual Test Required | FY29 | Yes | TBD | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Out of Service | Yes | Yes | No |
| Block 31 modernization completion and elevator Return To Service date TBD - possibly the end of calendar year 2024. |
| TPP Inclined Elevator is Out of Service with no RTS date. |
| Fire Station with elevator construction estimated to be complete by 2025. Elevator maintenance and inspections to be performed by others. |