A 02 Details LED Luminaire.pdf

PDF 299 KB Posted

Attached to
Concrete and Electrical
Solicitation number
W912LM-22-R-1010
Issued by

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONDUIT STUBBED UP ADJACENT TO

HANDHOLE; NUMBER AND SIZE AS

REQUIRED --------..

SET TOP OF CONCRETE

FOUNDATION 24" ABOVE

GRADE-------.

COPPER EQUIPMENT

GROUNDING CONDUCTOR

- ATTACH TO INTERNAL

LUG WELDED TO INTERIOR OF

POLE. CONDUCTOR

TO BE SAME SIZE AND

TYPE AS SUPPLY PHASE

CONDUCTOR. ____ __,

CIRCUIT CONDUCTORS AND

CONDUIT TO POWER

SOURCE OR NEXT POLE

CONCRETE PER SPECIFICATION

POLE - SEE POLE SKETCH AND

SPECIFICATION

HANDHOLE - SEE POLE SKETCH

AND SPECIFICATION

CHAMFER ALL EDGES OF CONCRETE

BASE 1/2"

FINISHED GRADE

INSULATED COPPER GROUNDING

CONDUCTOR ATTACHED TO INTERNAL

LUG WELDED TO INTERIOR OF

POLE. SIZE PER NFPA 70.

#4 BARS VERTICAL AT 6"

EACH FACE

#3 BARS AT 12" ON

CENTER HORIZONTALLY

3/4" X 10' GROUND ROD ------J

POLE A B HEIGHT

8'-12' 36" 12"

13'-20' 42" 16"

21 '-30' 72" 24"

31 '-40' 78" 30"

ANCHOR BASE POLE FOUNDATION

REVISED: NOVEMBER 2020 LUMINAIRE PLATE: XL-21

1267183372C Rectangle