141 N. REAMSTOWN RD.
STEVENS, PA 17578
PHONE 717.951.7466
SCHILLARCS@GMAIL.COM
ALTERATIONS TO AN
EXISTING BUILDING FOR:
HEIDELBERG
TOWNSHIP
111 MILL ROAD
SCHAEFFERSTOWN PA 17088
CONTACT LIST
GENERAL NOTES CODE ANALYSIS
SITE LOCATION MAP
DRAWING INDEX
CS Cover Sheet A100 Alteration Floor Plan A101 Electrical Plan A102 Schedules & Details
E0.1 Electrical Notes & Schedules E1.0 Electrical Power Plan
P1.0 Plumbing Notes & Plan
SITE IMAGE
1. Mount all ADA approved graphic / tactile signs w/ center line of sign at 60" A.F.F. to the bottom of the lowest character (on latch side of door where applicable.
2. All door hardware to be approved ADA hardware.
3. Provide proper blocking in all walls to allow secure fastening of all toilet accessories and grab bars.
4. All approved exit doors to have tactile "EXIT" sign mounted on wall (latch side of door) at 48" A.F.F. to lowest character.
5. All work surfaces shall comply with ADA clear space forward approach requirements as well as knee / toe clearances. Tops of work surfaces to be a min. 28" A.F.F. to max. 34" A.F.F.
6. All controls, outlets, and light switches to be mounted at ADA / ANSI 117.1 compliant heights.
7. Fire walls, fire barriers, smoke partitions are to be permanently identified with signs and or stenciling. Such ID is to be in concealed spaces of the walls at intervals no exceeding 30"
8. Any penetrations of a fire / smoke wall or partition shall comply with sections 713.3.1 thru 713.3.3.
9. Fire Extinguisher Cabinets to be mounted at 48" A.F.F. max. to top of cabinet.
10. Fixed or built in storage cabinets, coat hooks, shelves, closets, and drawers in accessible spaces are required to have 5% (not less than 1) accessible.
11. All new windows and doors shall comply with Table C402.4 of 2018 IECC.
12. Flame Spread Index (Must comply with IBC Table 803.1.1) Interior Exits / Stairways / Exit Access Stairs minimum Class A All other rooms (finishes) to be Class C
Interior wall and ceiling finish materials shall be classified in accordance with ASTM E84 or UL 723. Such interior finish materials shall be grouped in the following classes in accordance with their flame spread and smoke developed indexes.
Class A = Flame spread index 0-25; smoke-developed index 0-450.
Class B = Flame spread index 26-75; smoke developed index 0-450.
Class C = Flame spread index 76-200: smoke developed index 0-450.
13. Parking space identification signs shall include the International Symbol of Accessibility complying with 703.7.2.1. Signs identifying van parking spaces shall contain designation "Van Accessible". Signs shall be 60" (1525MM) minimum above the finish floor or ground surface measured to the bottom of the sign.
INTERNATIONAL EXISTING BUILDING CODE 2018
HEIDELBERG TOWNSHIP
ALTERATION LEVEL: LEVEL 2
OCCUPANCY: B
CONSTRUCTION TYPE: IIIB
SQUARE FOOTAGE OF WORK AREA: 2,339 SQ.FT.
OCCUPANT LOAD: 35 MAXIMUM
3 NORMAL BUSINESS HOURS
Governing Codes
- 2018 IBC/ International Building Code
- 2018 IEBC / International Existing Building Code
- 2018 IMC/ International Mechanical Code
- 2018 IPC/ International Plumbing Code
- 2017 NEC / National Electrical Code
- 2018 IECC/ International Energy Conservation Code
- 2009 ICC/ANSI 117.1
- 2018 IFC/ International Fire Code
ARCHITECT
Schillaci Architects Ltd.
141 N. Reamstown Road Stevens, PA 17578 717.951.7466 Mark Schillaci Schillarcs@gmail.com
DRAWING KEY
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW WALL
EXISTING DOOR
NEW DOOR
SCALE: 14"=1'-0"
ALTERATION FLOOR PLAN2SCALE: 14"=1'-0"
REFLECTED CEILING PLAN3
SECURE
VESTIBULE
OFFICE
OFFICE
OFFICE
OFFICE
WORK
ROOM
STORAGE
CORRIDOR
LOBBY
MEETING
ROOM
STAFF
FILE
ROOM
EXISTING
WOMEN'S
EXISTING
MEN'S
EXISTING
LOCKER
101 102
105106
110 111
U P
PASS-THRU WINDOW.
SILL HEIGHT MAX. 34"
A.F.F. PROVIDE
SOLID SURFACE SILL
/ COUNTER
W1
A102
A102
PASS-THRU WINDOW.
SILL HEIGHT MAX. 34"
A.F.F. PROVIDE SOLID
SURFACE SILL /
COUNTER
W1
EXISTING
RECESSED FIRE
EXTINGUISHER
FE
TOP OF COUNTER OR
SINK RIM (WHICHEVER
IS HIGHER) SHALL BE
34" MAX. A.F.F., PROVIDE
36" x 48" CLEAR FLOOR
SPACE FOR PARALLEL
APPROACH CENTERED
ON SINK.
1 1 1 11
9' -0
5'
-1
9' -6
15'-111 2" 16'-11"
5'-0"
13'-6" 6'-0" 13'-0"
6'-8"
5' -1
6'
-1
1' -0
45°
6'-7"2'-31 2" 24'-4"
U P
0"
EQ
U A
L
EQ
U A
L
REMOVE EXISTING MIRROR AND
REPLACE WITH NEW. BOTTOM
OF REFLECTIVE SURFACE
SHALL BE 40" MAX. A.F.F.
PROVIDE ADA
COMPLIANT
GRAPHIC
MOUNTED WITH
BOTTOM OF
LOWEST
CHARACTER @
60" A.F.F.
PROVIDE ADA
COMPLIANT
GRAPHIC
MOUNTED WITH
BOTTOM OF
LOWEST
CHARACTER @
60" A.F.F.
SCALE: 18"=1'-0"
EXISTING / DEMO FLOOR PLAN1
REMOVE EXISTING
WALLS AND DOORS
AS REQUIRED TO
ACCOMMODATE
NEW LAYOUT.
REMOVE EXISTING
WALLS AND DOORS
AS REQUIRED TO
ACCOMMODATE
NEW LAYOUT.
THIS DRAWING AS AN INSTRUMENT OF SERVICE, IS THE
PROPERTY OF THE ARCHITECTS, AND MAY NOT BE
REPRODUCED WITHOUT THEIR PERMISSON AND UNLESS
THE REPRODUCTION CARRIES THEIR NAME AS
ARCHITECTS
DUE TO DISTORTION FROM REPRODUCTION
PROCEDURES, DIMENSIONS SHALL NOT BE SCALED FROM
THE DRAWING. ONLY DIMENSIONS AS SHOWN SHALL BE
VALID
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
CONDITIONS AT THE SITE BEFORE PROCEEDING WITH THE
WORK
ISSUED:
REVISIONS:
M A
R K
S C
H
IL
L A
C I
7.
1.
SC
H
IL
LA
R C
S@ G
M
AI
L.
C
O M
WWW.SCHILLACIARCHITECTS.COM
141 N. Reamstown Rd.
Stevens, PA 17578
SC
H
IL
LA
C I
A R
C H
IT
EC
TS
L
TD
K Y
L E
S C
H
IL
L A
C I
7.
5.
K
SC
H
IL
LA
C
I1 3@
G M
AI
L.
C O
M
02/26/2024
H ei de lb er g
To w ns hi p
Al te ra tio ns to a n
Ex is tin g
B ui ld in g
# DATE DESCRIPTION
M ill
R oa d Sc ha ef fe rt ow n
P A
A101
First Floor Alterations
SYMBOL LEGEND
EMERGENCY LIGHT BATTERY PACK
EMERGENCY LIGHT BATTERY PACK
W/ ILLUMINATED EXIT SIGN
EMERGENCY LIGHT REMOTE HEAD
NEW 15 AMP DUPLEX OUTLET
LIGHTING SWITCH
LIGHTING WIRING
NEW 15 AMP GFCI DUPLEX OUTLET
GFCI
6" LED WAFER LIGHT
INSTALL WATER
RESISTANT FIXTURE IN
ALL WET AREAS
24" x 24" LED LIGHT
FIXTURE
GFCI
SCALE: 14"=1'-0"
ELECTRICAL FLOOR PLAN1
EXISTING
TO REMAIN
EXISTING
TO REMAIN
EXISTING
TO REMAIN
EXISTING ILLUMINATED
EXIT SIGNAGE AND
EMERGENCY LIGHTING
TO REMAIN TO REMAIN
THIS DRAWING AS AN INSTRUMENT OF SERVICE, IS THE
PROPERTY OF THE ARCHITECTS, AND MAY NOT BE
REPRODUCED WITHOUT THEIR PERMISSON AND UNLESS
THE REPRODUCTION CARRIES THEIR NAME AS
ARCHITECTS
DUE TO DISTORTION FROM REPRODUCTION
PROCEDURES, DIMENSIONS SHALL NOT BE SCALED FROM
THE DRAWING. ONLY DIMENSIONS AS SHOWN SHALL BE
VALID
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
CONDITIONS AT THE SITE BEFORE PROCEEDING WITH THE
WORK
ISSUED:
REVISIONS:
M A
R K
S C
H
IL
L A
C I
7.
1.
SC
H
IL
LA
R C
S@ G
M
AI
L.
C
O M
WWW.SCHILLACIARCHITECTS.COM
141 N. Reamstown Rd.
Stevens, PA 17578
SC
H
IL
LA
C I
A R
C H
IT
EC
TS
L
TD
K Y
L E
S C
H
IL
L A
C I
7.
5.
K
SC
H
IL
LA
C
I1 3@
G M
AI
L.
C O
M
02/26/2024
H ei de lb er g
To w ns hi p
Al te ra tio ns to a n
Ex is tin g
B ui ld in g
# DATE DESCRIPTION
M ill
R oa d Sc ha ef fe rt ow n
P A
A102
First Floor Alterations
DOOR SCHEDULE NOTES:
1. ALL NEW DOORS SHALL BE EQUIPPED WITH LEVER HARDWARE. NEW DOOR LEVER HARDWARE SHALL BE MOUNTED AT ADA HEIGHT RANGE. (TYPICAL)
2. ALL NEW DOOR SHALL MATCH EXISTING.
3. VERIFY DOOR SIZE WITH EXISTING OPENING IN FIELD FOR ALL EXISTING DOOR OPENINGS.
FRAMEDOOR
SIZE (WxH)DOOR
TYPENO
DOOR SCHEDULE
MATERIAL FRAME
TYPE RATING HARDWARE WEATHER-
STRIPPING REMARKS
DOOR TYPES FRAME TYPES
A B
SEE
SCHEDULE
SE
E
SC
H
ED
U
LE
SEE
SCHEDULE
SE
E
SC
H
ED
U
LE
SEE
SCHEDULE
SE
E
SC
H
ED
U
LE
3' -7
SEE
SCHEDULE
SE
E
SC
H
ED
U
LE
1'-6" 4'-0"
4' -0
2'
-8
6' -8
WINDOW TYPES
W1
1. VINYL PASS THRU WINDOW
2. 6'-8" HEAD HEIGHT
B
A A A
A A A
A
B B
B B
B
H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 1 H.M.3'-0" x 6'-8" H.M. 2 H.M.3'-0" x 6'-8" H.M. 1
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
- - -PRIVACY LEVER /CLOSER
WALL TYPE SCHEDULE:
A
TYPICAL INTERIOR WALL:
· WOOD STUDS AND DRYWALL SHALL EXTEND TO UNDERSIDE
OF DROPPED CEILING ABOVE.
· USE MOISTURE RESISTANT GYP.BD. IN ALL WET LOCATIONS.
B
CONTINUOUS
BOTTOM PLATE
CONTINUOUS
BOTTOM PLATE
2" DRYWALL BOTH SIDES.
EXTEND TO UNDERSIDE OF
STRUCTURE ABOVE. INSTALL
MOISTURE RESISTANCE DRYWALL
IN ALL WET LOCATIONS.
2x4 WOOD STUDS @ 16" O.C. MAX.
EXTEND TO UNDERSIDE OF
STRUCTURE ABOVE. INSTALL 2x6
WOOD STUDS WHERE REQUIRED
FOR MEP APPURTENANCES.
INCLUDING, BUT NOT LIMITED TO
BEHIND TOILETS.
SOUND ATTENUATING
BATT. INSULATION.
INSTALL IN BATH
ROOM WALLS ONLY.
TYPICAL INTERIOR WALL:
· WOOD STUDS AND DRYWALL SHALL EXTEND TO UNDERSIDE
OF DROPPED CEILING ABOVE.
· USE MOISTURE RESISTANT GYP.BD. IN ALL WET LOCATIONS.
CONTINUOUS
BOTTOM PLATE
CONTINUOUS
BOTTOM PLATE
2" DRYWALL BOTH SIDES.
EXTEND TO UNDERSIDE OF
STRUCTURE ABOVE. INSTALL
MOISTURE RESISTANCE DRYWALL
IN ALL WET LOCATIONS.
2x4 WOOD STUDS @ 16" O.C. MAX.
EXTEND TO UNDERSIDE OF
STRUCTURE ABOVE. INSTALL 2x6
WOOD STUDS WHERE REQUIRED
FOR MEP APPURTENANCES.
INCLUDING, BUT NOT LIMITED TO
BEHIND TOILETS.
SCALE: 12"=1'-0"
KITCHENETTE ELEVATION1
2'-0" 2'-0"
2'-0"2'-0"
2'-0"
2' -1
0" M
A X.
TO
P
O F
C O
U N
TE
R
1' -8
2'
-6
7' -0
2'-0"
REFRIG.
(NOT IN
CONTRACT)
5' -6
1'
-6
SCALE: 12"=1'-0"
WORK ROOM ELEVATION2
2'-0" 2'-0"
2'-0"2'-0"
2'-0"
2' -1
0" M
A X.
TO
P
O F
C O
U N
TE
R
1' -8
2'
-6
7' -0
2'-0"
5' -6
1'
-6
THIS DRAWING AS AN INSTRUMENT OF SERVICE, IS THE
PROPERTY OF THE ARCHITECTS, AND MAY NOT BE
REPRODUCED WITHOUT THEIR PERMISSON AND UNLESS
THE REPRODUCTION CARRIES THEIR NAME AS
ARCHITECTS
DUE TO DISTORTION FROM REPRODUCTION
PROCEDURES, DIMENSIONS SHALL NOT BE SCALED FROM
THE DRAWING. ONLY DIMENSIONS AS SHOWN SHALL BE
VALID
CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
CONDITIONS AT THE SITE BEFORE PROCEEDING WITH THE
WORK
ISSUED:
REVISIONS:
M A
R K
S C
H
IL
L A
C I
7.
1.
SC
H
IL
LA
R C
S@ G
M
AI
L.
C
O M
WWW.SCHILLACIARCHITECTS.COM
141 N. Reamstown Rd.
Stevens, PA 17578
SC
H
IL
LA
C I
A R
C H
IT
EC
TS
L
TD
K Y
L E
S C
H
IL
L A
C I
7.
5.
K
SC
H
IL
LA
C
I1 3@
G M
AI
L.
C O
M
02/26/2024
H ei de lb er g
To w ns hi p
Al te ra tio ns to a n
Ex is tin g
B ui ld in g
# DATE DESCRIPTION
M ill
R oa d Sc ha ef fe rt ow n
P A
A103
First Floor Plan
LIGHTING FIXTURE SCHEDULE
LAMPINGMODEL NO.MANUFACTURERDESCRIPTIONTYPESYMBOL COMMENTS
EM1
EM2
EM3
E-XCL2RCW 3.4W
EMERGENCY EXIT SIGN
LIGHT COMBO
DUAL REMOTE HEAD
LIGHT
E-XHL2WG (DBL) 5.4W
1.8WE-XML2WE-CONOLIGHTEMERGENCY LIGHT
BATTERY UNIT
E-CONOLIGHT
E-CONOLIGHT OR EQUAL
OR EQUAL
OR EQUAL
2X2 LED PANEL TBD TBD 31.5W F1 OR EQUAL
F1
VERIFY AND REVIEW ALL LIGHTING FIXTURE WITH OWNER.
USE FIRE RATED FIXTURE WHERE PENETRATING RATED ASSEMBLIES.
EXIT SIGNS AND EM LIGHTS TO BE TIE IN TO THE LOCAL LIGHTING CIRCUIT FEEDING THAT AREA
NOTES:
MS = FIXTURE CONTROL MOTION SENSOR.
FIXTURES LISTED ARE A BASIS OF DESIGN. SUBSTITUTIONS MUST BE OF EQUAL QUALITY AND APPROVED BY THE ELECTRICAL DESIGNER AND CUSTOMER.
OS = OCCUPANCY SENSOR SENSOR.
6" LED WAFER TBD TBD 14WF2 OR EQUAL
EXIT SIGN (HIGH LOCATION)
4" TELECOM CONDUITS
UP THE POLE
RECEPTACLES IN
ELECTRICAL/MECHANICAL SPACES
SWITCHES
SWITCHES
TELE/DATA OUTLETS
RECEPTACLES1'-6"
0" F.F.
3'-6"
4'-6"
8'-6"
NOTES:
1. DEVICES SHALL BE INSTALLED ON A COMMON VERTICAL CENTERLINE WHEREVER POSSIBLE.
2. ELECTRICAL RECEPTACLES SHALL BE MOUNTED A MINIMUM OF 15" TO THE BOTTOM OF THE RECEPTACLE.
3. ELECTRICAL SWITCHES SHALL BE MOUNTED A MAXIMUM OF 48" TO THE TOP OF THE SWITCH.
4. COUNTERTOP ELECTRICAL RECEPTACLES SHALL BE MOUNTED A MAXIMUM OF 44" TO THE TOP OF THE RECEPTACLE.
5. CIRCUIT BREAKERS, DISCONNECT SWITCHES, ETC. SHALL BE INSTALLED SO THAT THE CENTER OF THE GRIP OF THE OPERATING HANDLE IN
IT'S HIGHEST POSITION IS NOT MORE THAN 6'-7" A.F.F.
6. MOUNT EXIT SIGNS ABOVE DOORS WITH 2" BETWEEN BOTTOM OF THE EXIT SIGN AND THE TOP OF THE DOOR.
7. THE MOUNTING HEIGHTS SHOWN ARE GENERALLY DIMENSIONED TO THE MID-LINE OF A GIVEN DEVICE. EXACT DEVICE MOUNTING
HEIGHTS SHALL BE WITHIN THE SPECIFIC REACH LIMITS SPECIFIED IN THE LATEST REVISION OF THE ADA GUIDELINES AND THE LATEST REVISION OF ICC/ANSI A117.1, SPECIFICALLY FIRE ALARM DEVICES, CONTROLS, OPERATING MECHANISMS AND HARDWARE, INCLUDING
RECEPTACLES AND SWITCHES THAT CONTROL LIGHTING, VENTILATION, ETC.
8. THIS DETAIL IS MEANT AS A GENERAL GUIDE. ALL FINAL MOUNTING HEIGHTS SHALL BE INSTALLED PER ARCHITECTURAL DRAWINGS AND
ADOPTED CODES.
SCALE: N.T.S.
TYPICAL DEVICE MOUNTING HEIGHTS
6'-6"
PANEL BOARD
5'-0"
DISCONNECT SWITCHES
8"
ELECTRICAL GENERAL NOTES:
1. THE ENTIRE INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE ENFORCED REVISIONS OF IBC 2018, NEC 2017 EDITION, NFPA 70, NEMA, UL LISTINGS, MANUFACTURERS' RECOMMENDATIONS, THE NATIONAL BOARD OF UNDERWRITERS, STATE CODES, LOCAL CODES, AND ALL AUTHORITIES HAVING JURISDICTION.
2. ALL MATERIAL AND EQUIPMENT SHALL BE LISTED AND LABELED FOR THE APPLICATION BY UNDERWRITERS LABORATORIES
AND INSTALLED ACCORDING TO ITS LISTING.
3. ALL DEVICES SHOWN ON DRAWINGS ARE DIAGRAMMATIC IN LOCATION AND SHOWN TO INDICATE THE EXTENT, GENERAL
CHARACTER, AND GENERAL WIRING REQUIREMENTS ONLY.
4. THE TERM "FURNISH" SHALL MEAN TO OBTAIN AND SUPPLY TO THE JOB SITE. THE TERM "INSTALL" SHALL MEAN TO FIX IN POSITION AND CONNECT FOR USE. THE TERM "PROVIDE" SHALL MEAN TO FURNISH AND INSTALL. THE TERM "WORK" SHALL MEAN ALL LABOR, MATERIAL, EQUIPMENT, SCAFFOLDING, RIGGING, TOOLS, SUPERVISION, SERVICES, SETUP, PROGRAMMING, AND OTHER INCIDENTALS NECESSARY FOR COMPLETE AND OPERABLE INSTALLATION.
5. THE CONTRACTOR SHALL PROVIDE ALL WORK REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION OF THE
ELECTRICAL SYSTEMS AS INDICATED OR IMPLIED BY THE DESIGN DOCUMENTS.
6. THE CONTRACTOR SHALL REVIEW ALL CONTRACT DOCUMENTS (DRAWINGS, SPECIFICATIONS, EQUIPMENT CUT SHEETS, ETC.)
FOR ALL TRADES AND PROVIDE ALL ELECTRICAL WORK REQUIRED FOR COMPLETE AND OPERABLE INSTALLATION.
7. THE CONTRACTOR SHALL COORDINATE ALL WORK, ELECTRICAL REQUIREMENTS, AND THE ACTUAL LOCATIONS OF ALL EQUIPMENT, CASEWORK, DEVICES, FIXTURES, SWITCHES, SENSORS, ETC., WITH ALL CONTRACTORS PRIOR TO PROVIDING
PRICING AND PERFORMING ANY ROUGH-IN WORK.
8. THE CONTRACTOR IS HEREBY CAUTIONED THAT THE ELECTRICAL POWER CHARACTERISTICS (VOLTAGE, PHASE, HORSEPOWER, AMPERAGE, ETC.) OF EQUIPMENT ARE BASED ON INFORMATION AVAILABLE AT THE TIME OF PROJECT DESIGN.
CONTRACTOR SHALL VERIFY ACTUAL CHARACTERISTICS FOR EACH PIECE OF EQUIPMENT TO BE INSTALLED PRIOR TO
ORDERING EQUIPMENT OR PERFORMING ANY ROUGH-IN WORK.
9. DEVICES INDICATED TO BE INSTALLED IN THE SAME LOCATIONS WITH DIFFERENT ELEVATIONS SHALL BE ALIGNED VERTICALLY AND HORIZONTALLY. FOR ALL MOUNTING HEIGHTS AND LOCATIONS (SWITCHES, OUTLETS, FIRE ALARM AUDIBLE AND VISUAL DEVICES, FIRE ALARM PULL STATIONS, SECURITY DEVICES, CARD READERS, SENSORS, ETC.), REFER TO THE
ARCHITECTURAL DRAWINGS
10. ADJUSTMENTS TO WIRING DEVICES TO AVOID STRUCTURAL OR OTHER INTERFERENCES AS WELL AS WORK INDICATED WITH
MINOR DETAILS OMITTED SHALL BE PROVIDED WITHOUT EXTRA COST.
11. ANY CHANGES AND/OR MODIFICATIONS MUST BE REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL AND/OR
OWNER'S REPRESENTATIVE PRIOR TO CONSTRUCTION.
12. REMOVE ALL TRASH, DEBRIS, AND DEMOLITION MATERIAL FROM THE PREMISES AT THE END OF EACH WORK DAY.
13. ELECTRICAL PANELS SHALL BE LABELED WITH ENGRAVED PLASTIC TAGS MOUNTED ON THE OUTSIDE OF THE EQUIPMENT
AND BEARING THE VOLTAGE AND DESIGNATION OF THE EQUIPMENT.
14. PROVIDE ALL PANELBOARD SCHEDULES IN AN EDITABLE ELECTRONIC FORMAT (MS WORD OR EXCEL). LABELS SHALL BE SPECIFIC TO THE AREA. USE BUILDING COLUMNS, ROOM NAMES, ETC. FOR A MORE ACCURATE LOCATION.
15. IN THE EVENT THAT LOCAL EQUIPMENT DISCONNECTS CANNOT BE LOCATED SUCH THAT WORKING CLEARANCES ARE MAINTAINED, THE NEXT UPSTREAM OVERCURRENT DEVICE SHALL BE INDIVIDUALLY CAPABLE OF BEING LOCKED IN THE OPEN
POSITION IN ACCORDANCE WITH NEC 440.14 AND 430.102.
16. ALL FIRE/SMOKE RATINGS SHALL BE MAINTAINED. APPLY FIRESTOPPING AND SEALANT AS REQUIRED.
17. PROVIDE ALL WORK REQUIRED FOR A COMPLETE AND OPERABLE INSTALLATION OF THE FIRE ALARM, SECURITY, AND ANY
OTHER SPECIAL SYSTEMS. COORDINATE EXACT REQUIREMENTS WITH OWNER'S VENDORS.
18. WHERE NO CIRCUIT IS DESIGNATED FOR A DEVICE (INCLUDING EQUIPMENT NOT SHOWN ON DRAWINGS), THE E.C. SHALL CIRCUIT TO THE NEAREST AVAILABLE PANEL WITH CONDUCTOR, RACEWAY, AND BREAKER SIZED PER THE LATEST ADOPTED
REVISION OF THE NEC.
19. ALL WIRE AND CONDUIT SHALL BE CONCEALED IN WALLS, CEILING PLENUMS, BULKHEADS AND IN ROOF STRUCTURAL AREAS, U.O.N. THE E.C. SHALL COORDINATE FULLY WITH ALL OTHER TRADES TO INSTALL ALL CONDUIT AND WIRING IN THESE ASSOCIATED STRUCTURES. ANY OTHER MEANS OF PATHWAY SUGGESTED MUST FIRST BE APPROVED FROM THE DESIGN PROFESSIONAL BEFORE INSTALLATION CAN PROCEED. MC CABLE MAY BE EXPOSED IN ELECTRICAL ROOM
20. NOTHING IN THESE DRAWINGS AND SPECIFICATIONS SHALL BE CONSTRUED TO CONSTRUCT WORK NOT CONFORMING TO GOVERNING CODES. THIS SHALL NOT BE CONSTRUED AS TO RELIEVE THE CONTRACTOR FROM COMPLYING WITH ANY REQUIREMENTS OF THE PLANS OR SPECIFICATIONS WHICH MAY BE IN EXCESS OF REQUIREMENTS HEREIN BEFORE
MENTIONED GOVERNING CODES AND RULES AND NOT CONTRARY TO THE SAME.
21. THE ELECTRICAL DESIGN IS BASED UPON TYPICAL COMMERCIALLY MANUFACTURED ITEM(S) AND/OR COMPONENT(S). THE CONTRACTOR SHALL COORDINATE THE FINAL EQUIPMENT INSTALLATION WITH ACTUAL EQUIPMENT FURNISHED.
22. WIRING METHOD: UTILIZE MC IN INTERIOR SPACES WHERE CONCEALED, EMT WHERE EXPOSED, AND PVC UNDERGROUND.
MC CABLE MAY BE EXPOSED IN ELECTRICAL ROOM.
23. CONDUCTORS: COPPER CONDUCTORS SHALL BE TYPE THHN/THWN; ALUMINUM CONDUCTORS SHALL BE XHHW.
CONDUCTORS SHALL BE SIZED PER NEC 310-15A AND 310-16.
24. STARTERS, CONTROLS AND REMOTE SWITCHES SHOW FOR EQUIPMENT FURNISHED BY OTHER CONTRACTORS WILL BE PROVIDED WITH THE RESPECTIVE EQUIPMENT, BUT SHALL BE CONNECTED BY THE ELECTRICAL CONTRACTOR.
25. FIXTURES SHALL GENERALLY BE INSTALLED IN THE CENTER OF THE CEILING PANEL OR INTERSECTIONS OF JOINTS IN A
MANNER THAT IS APPROVED BY THE ARCHITECT.
26. THE ELECTRICAL CONTRACTOR SHALL CHECK ARCHITECTURAL DRAWINGS FOR DOOR SWINGS TO VERIFY THE LOCATION OF
DOOR SWITCHES 0N THE STRIKE SIDE OF THE DOOR
27. THE ELECTRICAL CONTRACTOR SHALL INSTALL A COMPLETE GROUNDING AND BONDING SYSTEM AS REQUIRED BY THE NEC AND THE UTILITY COMPANY INCLUDING EQUIPMENT GROUNDS. THIS SHALL INCLUDE GROUNDING THE WATER METER, FUEL
GAS PIPING AND SPRINKLER PIPING (AS APPLICABLE).
28. GROUNDING ELECTRODES: COPPER-CLAD STEEL GROUND RODS; 3/4 INCH BY 10 FEET AND UL LISTED CLAMPS.
29. THE ELECTRICAL DESIGN SHALL COMPLY WITH THE AIC REQUIREMENTS OF THE POWER COMPANY.
30. PROVIDE PROPER CLEARANCES FOR ELECTRICAL PANELS AS PER NEC110.26(F)
31. ALL ELECTRICAL EQUIPMENT AMPERAGE TO BE CHECKED AND DETERMINED BY ELECTRICAL CONTRACTOR.
32. ALL FIXTURE TYPES AND LOCATIONS TO BE VERIFIED BY ELECTRICAL CONTRACTOR.
33. EMERGENCY LIGHTING TO BE CONNECTED TO LOCAL LIGHTING CIRCUIT.
34. ALL EQUIPMENT AND ELECTRICAL MATERIALS USED TO CONNECT THE EQUIPMENT, WHERE POSSIBLE, TO BE LISTED BY A
RECOGNIZED TESTING AGENCY SUCH AS UL.
35. PVC CONDUIT SHALL BE RIGID NON-METALLIC SCHEDULE 40 ELECTRICAL CONDUIT. UNDERGROUND PVC : ELECTRICAL GRADE SCHEDULE
40 HEAVY WALL TYPE .
36. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS FOR THE ACTUAL EQUIPMENT AND DEVICES BEING INSTALLED AND SHALL MAKE ANY CHANGES IN THE WIRE SIZES, BREAKERS, ETC. TO BE ALL NEC REQUIRED STANDARDS AND SAFETIES REQUIREMENTS.
37. REUSE EXISTING TO REMAIN RECEPTACLES ON EXISTING WALLS. REUSE THE EXISTING EXTERIOR LIGHTING. RECONNECT CIRCUITS INTO
NEW OFFICE PANEL.
PANELBOARD, RECESSED-MOUNTED
DUPLEX RECEPTACLE, NEMA 5-20R
SINGLE POLE WALL SWITCH, 120vAC
GROUND FAULT CIRCUIT INTERRUPTER
THREE-WAY SWITCH, 120vAC
SYMBOLS
SAME CIRCUIT, SWITCHED SEPARATELY
HOMERUN TO PANEL
THREE CONDUCTOR
MANUAL MOTOR STARTERMS
FOUR-WAY SWITCH, 120vAC
JUNCTION BOXJ
MOTORM
OCCUPANCY MOTION SENSOR SWITCH, 120vAC
DIMMER SWITCH, 120vAC
QUAD RECEPTACLE
220 RECEPTACLE
RECEPTACLE - IN FLOOR RECEPT.
PANELBOARD, SURFACE-MOUNTED
SINGLE RECEPTACLE, NEMA 5-20R
DISCONNECT SWITCH
TIMER SWITCH, 120vAC
COMMUNICATION LEGEND
TELEPHONE OUTLET
COMBINATION TELEPHONE/ DATA OUTLET
DATA OUTLET
DUPLEX RECEPTACLE, COUNTER HEIGHT
CEILING-MOUNTED OCCUPANCY SENSOR
SWITCH BY E.C. VERIFY CAPACITY.
TV OUTLET
WEATHER PROOF
CARD READER
MOTOR SWITCH
CTR
RECEPTACLE - SPECIAL PURPOSE (EC TO VERIFY REQ.)
WP
RECEPTACLE - HIGH VOLTAGE
S
SMS
S 3
S 4
S
DM
SW
SM
OS
TV
CR
S SMOKE DETECTOR
W
M MICROPHONE JACK RECEPTACLE - OVERHEAD DOOR RECEPT.
OHD
HIGH CEILING-MOUNTED OCCUPANCY SENSOR
SWITCH BY E.C. VERIFY CAPACITY.OS
HC
GFI
RECEPTACLE - CORD DROP
CD
RECEPTACLE - CEILING RECEPT.
CEILING DATA OUTLET
TAMPER RESISTANT IN APARTMENTS
CONDUIT COAX
EXISTING
PANEL
PB1
225A MB
120/240V
1 PH 3W
CONDUIT/ WIRE SCHEDULE:
A. (1) SET 1-1/2" EMT W/ (3) #2/0 XHHW AL, (1) #4 XHHW AL GRND.
NEW PANEL
P1
150A MLO
120/240V
1PH 3W
A
SE
AL
NUMBER:
SCALE:
DATE:
SHEET NAME
CHECKED BY:
DRAWN BY:
SHEET NUMBER
03-07-25
DE
SI
GN
P
RO
FE
SS
IO
N
AL
RE
VI
SI
O
N S
DA
TE
A B C D E F G H I J K L M
2025-038
AL
TE
RA
TI
O N
S
TO
A N
E
XI
ST
IN
G
BU
IL
DI
N G
FO
R:
H E
ID
E
LB
E
R G
T O
W N
SH
IP
M
IL
L
RO
AD
SC
HA
EF
FE
RS
TO
W
N , P
A.
PO
B
O X
LA
N
C
AS
TE
R
, P A
7-
3-to dd m ep de si gn co m ca st .n et
EV
OL
UT
IO
N
BU
IL
DI
N G
SE
RV
IC
ES
, L
LC
DTP AS NOTED
ELECTRICAL NOTES & SCHEDULES
E0.1
DTP
ELECTRICAL SINGLE LINE DIAGRAM
SCALE: N.T.S.
DIAGRAM GENERAL NOTE:
1. THE ENTIRE INSTALLATION SHALL BE IN STRICT COMPLIANCE WITH THE ENFORCED REVISIONS OF NFPA 70, THE BUILDING CODE, THE UTILITY PROVIDER, AND ALL OTHER NATIONAL, STATE, AND LOCAL CODES AND AUTHORITIES HAVING JURISDICTION.
2. AT THE TIME OF DESIGN, THE FINAL UTILITY LAYOUT WAS NOT AVAILABLE. AS SUCH, THE CONTRACTOR SHALL INCLUDE IN HIS BID TIME TO FILL OUT FINAL
SERVICE APPLICATION AND MEET UTILITY PROVIDER REPRESENTATIVES ON SITE.
3. FULLY COORDINATE ALL OUTAGES AND SERVICE TRANSFERS WITH OWNER.
4. PROVIDE OVER CURRENT PROTECTIVE DEVICE SHORT-CIRCUIT, COORDINATION, AND FULLY IN COMPLIANCE WITH IEEE 399, 551, 242, AND 1584.
5. A.I.C. RATING OF SWITCHBOARDS AND PANELBOARDS ARE PRELIMINARY "MINIMUM" RATINGS AND SHALL BE FINALIZED WITH UTILITY CO"
6. THE GROUND-FAULT PROTECTION SYSTEM SHALL BE PERFORMANCE TESTED WHEN FIRST INSTALLED ON SITE. THIS TESTING SHALL BE CONDUCTED BY A
QUALIFIED PERSON(S) USING A TEST PROCESS OF PRIMARY CURRENT INJECTION, IN ACCORDANCE WITH INSTRUCTIONS THAT SHALL BE PROVIDED WITH THE EQUIPMENT. A WRITTEN RECORD OF THIS TESTING SHALL BE MADE AND SHALL BE AVAILABLE TO THE AUTHORITY HAVING JURISDICTION.
7. PER NEC 2017 110.24(A) FIELD MARKING SERVICE EQUIPMENT AT OTHER THAN DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL INCLUDE THE DATE THE FAULT CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE CALCULATION SHALL BE DOCUMENTED AND MADE AVAILABLE TO THOSE AUTHORIZED TO DESIGN, INSTALL, INSPECT, MAINTAIN, OR OPERATE THE SYSTEM. THE LABELS OUTSIDE, NEED TO BE ENGRAVED PHENOLIC PLATES AND
NEED TO BE IN PLACE BEFORE WE APPROVE THE SERVICE TO PPL.
SECURE
VESTIBULE
OFFICE
OFFICE
OFFICE
OFFICE
WORK
ROOM
STORAGE
CORRIDOR
LOBBY
MEETING
ROOM
STAFF
FILE
ROOM
EXISTING
WOMEN'S
EXISTING
MEN'S
U P
7" U
P 7"
GFCI
EXISTING
PANEL PB1
120/240V 3W
225 AMP
MS MS
MSMS
MS MS
MS
MS
MS
OS OS
4 4 4
4 4 4
F1
F1 F1
F1
F1 F1
F1 F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1 F1
F1
F1F1F1F1F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F2
F2
F2
EM2
EM3
EM2
EM2
EM2
EM3
GFCI
CTR
P1
NEW 150 AMP
120/240V 1 PH
SUB PANEL
(E)(E) (E) (E)
(E)
(E)
(E)
(E)
(E)(E)(E)
(E)
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6 P1-7
(E)
GFCI
(E)
GFCI
(E)
GFCI
P1-8
P1-9
P1-9
P1-9
P1-10 P1-10
P1-11
P1-12
P1-12 P1-12P1-12
P1-12
SE
AL
NUMBER:
SCALE:
DATE:
SHEET NAME
CHECKED BY:
DRAWN BY:
SHEET NUMBER
03-07-25
DE
SI
GN
P
RO
FE
SS
IO
N
AL
RE
VI
SI
O
N S
DA
TE
A B C D E F G H I J K L M
2025-038
AL
TE
RA
TI
O N
S
TO
A N
E
XI
ST
IN
G
BU
IL
DI
N G
FO
R:
H E
ID
E
LB
E
R G
T O
W N
SH
IP
M
IL
L
RO
AD
SC
HA
EF
FE
RS
TO
W
N , P
A.
PO
B
O X
LA
N
C
AS
TE
R
, P A
7-
3-to dd m ep de si gn co m ca st .n et
EV
OL
UT
IO
N
BU
IL
DI
N G
SE
RV
IC
ES
, L
LC
DTP AS NOTED
ALTERATION POWER PLAN
E1.0
DTP
ALTERATION - ELECTRICAL PLAN
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
LOCKER
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
EXISTING TO REMAIN
FLOOR CLEAN OUT
WALL CLEAN OUT
FIXTURE STOP
BALL VALVE
FLOOR DRAIN
VENT THRU WALL
COLD WATER PIPING
HOT WATER PIPING
GAS PIPINGG
CW
HW
VTW
ELECTRICAL CONTRACTOR
WASTE OR SANITARY PIPING
BELOW FLOOR
VENT PIPING
ABOVE FINISHED FLOOR
HVAC CONTRACTOR
GENERAL CONTRACTOR
PLUMBING CONTRACTOR
W OR S
V
A.F.F.
B.F.
P.C.
E.C.
H.C.
G.C.
CO
CO
VTR VENT THRU ROOF
WV WET VENT
CDV COMB. DRAIN & VENT
M
M
WATER METER
GAS METER
HB HOSE BIB
SYMBOLS & ABBREVIATIONS
POINT OF CONTACT
FD
GAS VALVE
HWCWSAN.MANUF.TAG DESCRIPTION MODEL
PLUMBING FIXTURE SCHEDULE
NOTESVENTQNTY
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT MOUNTING HEIGHT OF ALL FIXUTES AND LOCATIONS OF ADA FIXTURES.
2. AN APPROVED EQUAL MAY BE USED FOR ALL FIXTURES SPECIFIED IF QUALIFIED IN BID.
3. LAVATORY & KITCHEN SINKS ARE TO BE PROVIDED WITH ASSE 1070 RATED MIXING VALVES TO LIMIT WATER TEMP TO 110 DEGREES
4. PLUMBING CONTRACTOR SHALL REVIEW AND COORDINATE PLUMBING FIXTURES AND CONNECTION SIZES AND MAKE ANY NECESSARY CHANGES.
PLUMBING CONTRACTOR IS RESPONSIBLE FOR COORDINATING ARE FIXTURES AND THEIR CONNECTION SIZES.
5. SUBMIT PLUMBING FIXTURE CUTS TO THE OWNER FOR REVIEW AND APPROVAL BEFORE ORDERING ANY FIXTURES. FIXTURES LISTED ARE PLACE
HOLDERS AND NOT FINAL SELECTIONS.
S1 COUNTER SINK (ADA COMPLIANT) TBD TBD VERIFY SINK AND TYPE WITH OWNER1 1 1
2" 1 1
2" 2" 1
2"
SECURE
VESTIBULE
OFFICE
OFFICE
OFFICE
OFFICE
WORK
ROOM
STORAGE
CORRIDOR
LOBBY
MEETING
ROOM
STAFF
FILE
ROOM
EXISTING
WOMEN'S
EXISTING
MEN'S
U P
7" U
P 7"
1-1/2" TIE INTO
EXISTING SANITARY
1-1/2" VENT TIE INTO EXISTING
TIE NEW 12"CW/HW
INTO EXISTING CW/HW
EXISTING
PLUMBING
TO REMAIN
EXISTING
PLUMBING
TO REMAIN
EXISTING
PLUMBING
TO REMAIN
S1
SE
AL
NUMBER:
SCALE:
DATE:
SHEET NAME
CHECKED BY:
DRAWN BY:
SHEET NUMBER
03-07-25
DE
SI
GN
P
RO
FE
SS
IO
N
AL
RE
VI
SI
O
N S
DA
TE
A B C D E F G H I J K L M
2025-038
AL
TE
RA
TI
O N
S
TO
A N
E
XI
ST
IN
G
BU
IL
DI
N G
FO
R:
H E
ID
E
LB
E
R G
T O
W N
SH
IP
M
IL
L
RO
AD
SC
HA
EF
FE
RS
TO
W
N , P
A.
PO
B
O X
LA
N
C
AS
TE
R
, P A
7-
3-to dd m ep de si gn co m ca st .n et
EV
OL
UT
IO
N
BU
IL
DI
N G
SE
RV
IC
ES
, L
LC
DTP AS NOTED
PLUMBING NOTES & PLANS
P1.0
DTP
PLUMBING NOTES:
1. IT IS THE INTENTION OF THE DRAWINGS TO CALL FOR FINISHED WORK, TESTED AND READY FOR OPERATION.
ANY APPARATUS, APPLIANCE, MATERIAL OR WORK NOT INDICATED ON THE DRAWINGS OR ANY INCIDENTAL ACCESSORIES REQUIRED TO MAKE THE WORK COMPLETE TO ALL RESPECTS AND READY FOR OPERATION SHALL BE FURNISHED, DELIVERED AND INSTALLED WITHOUT ADDITIONAL EXPENSE OR TIME TO THE PROJECT.
2. EACH CONTRACTOR SHALL PROVIDE OPENINGS THROUGH THE CONSTRUCTION AND SLEEVES AS REQUIRED FOR CONTRACTOR'S WORK. ANY PIPING OR CONDUIT PASSING THROUGH MASONRY OR CONCRETE WALLS OR FLOORS SHALL BE PROVIDED WITH SLEEVES AS PER SPECIFICATIONS, FILL THE ANNULAR VOIDS AS PER THE
SPECIFICATIONS.
3. TAKE PRECAUTION AGAINST DAMAGE TO ANY EXISTING UTILITIES, AND CONSTRUCTION NOT INCLUDED
WITHIN THE SCOPE OF WORK.
4. THE DRAWINGS ARE DIAGRAMATIC AND INDICATE THE GENERAL ARRANGEMENT OF THE VARIOUS SYSTEMS AND WORK INDICATED IN THE CONTRACT. THE RIGHT IS RESERVED TO MAKE MINOR CHANGES IN LOCATIONS UP TO THE POINT OF ROUGH-IN WITHOUT ADDITIONAL CHARGE TO THE OWNER OR SCHEDULE EXTENSION.
5. ALL WORK DESCRIBED IN THESE DOCUMENTS SHALL COMPLY WITH ALL RELEVANT CODES.
6. MAINTAIN THE INTEGRITY OF ALL EXISTING PIPING SYSTEMS. PRIOR TO CONNECTING NEW WORK TO ANY EXISTING SYSTEM, CONFIRM SYSTEM IDENTIFICATION AND DIRECTION OF FLOW. VERIFY THAT EXISTING PIPING IDENTIFICATION LABELS ARE CORRECT, AND PROVIDE ALL INSTALLATION REQUIREMENTS FOR PROPER
CONNECTION TO THE EXISTING SYSTEM.
7. PROVIDE ALL NECESSARY TEMPORARY OR PERMANENT CAPS OR PLUGS FOR PIPING. DO NOT LEAVE PIPING
OPEN ENDED.
8. PRIOR TO STARTING CONSTRUCTION, DETERMINE EXACT INVERT ELEVATIONS, SIZE, DEPTH AND LOCATION OF ALL EXISTING UTILITIES WHERE CONNECTIONS ARE TO BE MADE OR INTERSECTIONS OCCUR. WORK BACK
TOWARD FIXTURE FROM UTILITY CONNECTION FOR ALL PIPING SYSTEMS.
9. PROVIDE THREE (3) ELBOW SWING JOINTS FOR ALL HOT WATER BRANCH CONNECTIONS TO THE MAIN.
10. INSTALL ALL SHOCK ABSORBERS IN ACCORDANCE WITH THE LATEST "PLUMBING AND DRAINAGE INSTITUTE"
STANDARDS FOR WATER HAMMER ARRESTORS.
11. LOCATE ACCESS PANELS IN NON ACCESSIBLE CEILINGS AND WALLS FOR ALL VALVES, SHOCK ABSORBERS, CLEANOUTS AND ALL OTHER ITEMS THAT REQUIRE ACCESS TO PROPERLY MAINTAIN OR SERVICE THE BUILDING.
COORDINATE ALL FINAL LOCATIONS WITH ENGINEER PRIOR TO INSTALLATION. FAILURE TO DO SO MAY CAUSE A RELOCATION OF FIXTURE AND ACCESS PANELS WITHOUT ADDITIONAL EXPENSE OR TIME TO THE PROJECT.
12. ALL SUPPLY PIPING GREATER THEN 3/4" SHALL BE CPVC TYPE. ALL SUPPLY PIPING 3/4" AND SMALLER SHALL BE
CPVC OR PEX TYPE.
13. COORDINATE ALL SANITARY AND VENT PIPING WITH MECHANICAL DUCTWORK AND ELECTRICAL LIGHTING.
14. ALL SANITARY PIPING SHALL BE PVC, 3" OR LARGER TO SLOPE AT 1/8" PER FOOT MINIMUM, PIPING SMALLER
TO SLOPE AT 1/4" PER FOOT MINIMUM UNLESS OTHERWISE NOTED.
15. ALL SANITARY PIPING TO RUN BELOW FLOOR, ALL VENT PIPING TO RUN ABOVE CEILING UNLESS OTHERWISE
NOTED.
16. ALL PIPE PENETRATIONS TO HAVE FIRE RATED SLEEVE AND PACKAGING.
17. MINIMUM INVERT FOR SANITARY STACKS BELOW FIRST FLOOR TO BE 1'-6" UNLESS OTHERWISE NOTED.
18. FOR TRAP PRIMING OF ALL FLOOR DRAINS, PROVIDE PROSET SYSTEMS INC, TRAP GUARD, AS AN ADDED ALTERNATE, TO PROSET, ZURN TRAP PRIMER Z-1022, OR SIMILAR PRODUCT MAY BE SPECIFIED.
19. PROVIDE ACCESSIBLE CLEANOUTS AT THE BASE OF ALL SANITARY STACKS.
20. PLUMBING CONTRACTOR SHALL COORDINATE HIS WORK WITH WORK OF ALL OTHER CONTRACTORS PRIOR TO
START OF PLUMBING SYSTEM INSTALLATION.
21. FOR MOUNTNG HEIGHTS OF ALL PLUMBING FIXTURES, SEE ARCHITECTURAL DRAWINGS.
22. INSULATE CPVC COLD WATER MAINS AND RISERS WITH 12" FIBERGLASS INSULATION. INSULATE CPVC HOT
WATER MAINS AND RISERS WITH 1" FIBERGLASS INSULATION.
23. ALL SHUT-OFFS VALVES TO BE OPEN PORT VALVES PER IPC 601.1.
24. WATER TEMPERATURE AT PUBLIC HAND WASHING FACILITIES SHALL BE CONTROLLED BY AN ASSE 1070 MIXING
VALVE.
25. SEE PLUMBING SCHEDULES FOR CONNECTION SIZES AND LOADS.
ALTERATION PLUMBING PLAN
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
LOCKER
| Sheets and Views |
| Heidelberg EP Plans 3-2-25-E0.1 |
| Heidelberg EP Plans 3-2-25-E1.0 |
| Heidelberg EP Plans 3-2-25-P0.1 |
File details come from the government source that posted it. Updated .