Question and Answer Solicitation 93095202020
Amendment A0001 CT & PT Testing of Falcon Dam and Amistad Dam Transformers
Question 1.
Q) I am hoping to find out if there is an incumbent contractor currently performing these services, if similar services have been performed in the past, or if this is a new requirement.
If there is an incumbent, could you please provide the contract or task order number?
A) There is no current contractor performing the required services.
No similar services have been performed in the past for both Falcon Power Plant and Amistad Power Plant.
Question 2.
Q) Is this service being done in regard to a maintenance outage?
A) A maintenance outage is not the cause of this project. The project is to comply with
NERC/ERCOT/TRE standards.
Question 3.
Q) The scope includes CT’s / PT’s and (3) 138KV CB’s. Is there any requirement to test the protection relays?
A) There is no requirement to test the protection relays for Falcon Power Plant and Amistad
Power Plant.
Question 4.
Q) Can we receive a single line diagram?
A) A single line diagram for Falcon Power Plant and Amistad Power Plant are attached.
AMISTAD 13.8 KV ONE LINE DIAGRAM
FALCON 138 KV Schematic
Falcon Electrical Diagram
File details come from the government source that posted it.