This document is a bidding schedule item specifying technical requirements for a 115 kV single-phase surge arrester procurement. The surge arrester must comply with ANSI C62.1 and WAPA ES 9.1 equipment standards and include associated support structures. The specified equipment shall be rated for Station class operation with a Maximum Continuous Operating Voltage (MCOV) of not less than 76 kV (rms), a system voltage (L-L) range of 115-121 kV, and a duty cycle voltage of 96 kV. The associated mounting bracket must be a Cooper Power Systems #90054-3001 crossarm mounting bracket or equivalent, with both bracket and surge arrester installed on the support structure as shown in referenced drawings.

The surge arresters and support structures must qualify to operate under service conditions specified elsewhere in the solicitation and meet IEEE 693 seismic qualification requirements at either Low, Moderate, or High performance levels (qualification method to be determined). Wind and seismic loads are specified as nonsimultaneous. Required features include base mounting capability, metal oxide station-type construction, pressure relief diaphragm, gray colored porcelain finish, NEMA CCI terminal pads, ground connector rated for No. 2 AWG to 400-kcmil copper cable, and grading rings if required for the application.

View the file

Other files

File Type Posted
Attach_A_WAPA_SurgeArresterSpecs.pdf PDF
Sol_89503127QWA000433.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .