SATPC0043055 Tab 04 4 SOW.pdf

PDF 110 KB Posted

Attached to
UPS for Microfabrication Laboratory
Solicitation number
80NSSC27947369Q
Issued by

About this file

This is a Statement of Work (SOW) for the procurement of two replacement Uninterruptible Power Supply (UPS) systems for the Microfabrication Laboratory at NASA Glenn Research Center's Smart Sensing and Electronics System branch. The facility, an ISO 5 cleanroom, conducts silicon carbide integrated circuit and sensor fabrication for aerospace applications, with existing UPS systems providing backup power to strobic exhaust fans for furnace and etcher equipment.

System 1 must be rated at 10 kVA/kW with 208V-208V 4-wire plus ground input/output voltage, while System 2 must be rated at 40 kVA/kW with 480V-480V 3-wire plus ground input/output voltage. Both systems must not exceed 85 inches in height by 36 inches in width by 60 inches in depth and include redundant N+1 power module architecture, transformer-free modular and scalable design, front-to-top airflow with top cable entry, and factory-installed network cards supporting SNMP, Modbus, and BACnet interfacing. Additional requirements include UL Standard 1778 5th Edition listing, IP 20 rated enclosure, 65kA interrupting rating, unity power factor rating, support for loads between 0.5 leading and lagging to unity without de-rating, hot-swappable modules, operation up to 50°C, continuous duty static bypass switch, automatic retransfer functionality, DSP-based controls, waveform capture capability, temperature-compensated charging with battery load test, local and remote emergency power off, front-only service access, and display monitoring of power conversion and UPS operation. The contractor must provide one half-day of customer training, on-site equipment startup service, at least 12 months labor warranty, documentation of similar installations in government/academic/semiconductor R&D facilities, and removal and recycling of two existing Liebert NX 3-Phase UPS cabinets and one bypass cabinet.

View the file

Other files

File Type Posted
SATPC0043055 Tab 10 RFQ Open Market.pdf PDF
SATPC0043055 Tab 06 BNJ REV.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOW for UPS for MicroFabrication Laboratory

The Smart Sensing and Electronics System branch (LCS) at NASA Glenn Research Center

(GRC) at Lewis Field focuses on developing silicon carbide (SiC) integrated circuits (ICs) and sensors for aerospace applications. These circuits and sensors are fabricated in the Microfabrication Laboratory, an

ISO 5 facility. Operational equipment in this facility includes horizontal tube furnaces including an

LPCVD tube for TEOS-based silicon dioxide and RIE equipment for silicon dioxide/silicon nitride/metal etching/sputtering. The exhaust from the processing is vented through two (2) strobic fans for the furnace

460 V, 3-phase 3-wire, 3.8 A and one (1) strobic fan for the etchers 230 V, 3-phase, 4-wire, 1.6 A respectively. One UPS system provides backup to the strobic fans for the furnace and the other provides backup to the strobic fan for the etcher. The quote being solicited is to replace these two UPS systems appropriately.

The following are the requirements for the replacement UPS systems:

System 1:

1. System Input/Output Voltage and Wiring: 208V-208V 4W + G

2. Configured Capacity Rating kVA, kW: 10 kVA/kW

3. Redundant N+1 Power Module: Included

4. UPS Native Voltage/Wiring: 208V 4W + G

5. Not to exceed 85in (H) by 36 in (W) by 60 in (D)

System 2:

6. System Input/Output Voltage and Wiring: 480V-480V 3W + G

7. Configured Capacity Rating kVA/kW: 40 kVA/kW

8. UPS Native Voltage/Wiring: 480V 3W + G

9. Not to exceed 85in (H) by 36 in (W) by 60 in (D)

For both System 1 and 2:

10. Input type: Single Input

11. Airflow: Front to Top Airflow- includes top fan exhaust.

12. Cable Entry: Top

13. Network card factory installed for SNMP, Modbus, BACnet interfacing to Building Management

Systems and environmental sensor support.

14. Transformer-Free Modular and Scalable Architecture

15. Listed to UL Standard 1778 5th Edition

16. IP 20 rated enclosure

17. 65kAIC Rating - Provide interrupting rating and labeling of 65kA

18. Unity Power Factor Rating

19. Load Power Factor Support - Support loads 0.5 leading and lagging to unity without de-rating

20. Hot swappable HMI, bypass, power, and internal lead-acid battery modules to allow service while under operation to protect critical load from bypass.

21. Operation up to 50C°

22. Continuous Duty Static Bypass Switch

23. Automatic retransfer - Provides return to inverter power after an overload.

24. DSP based controls - Provides digital control of power conversion and system operation.

25. Display to monitor power conversion, UPS operation and utility conditions including maintenance bypass when provided.

26. Waveform capture on UPS input power for troubleshooting and analysis.

27. Temperature-Compensated Charging/Battery Load Test.

28. Front only service access

29. Local and Remote Emergency Power Off (EPO)

30. 1 Half-Day of Customer Training

31. On-site equipment Startup Service

32. Labor Warranty – At least 12 Months

33. Documentation of installation of similar equipment in Govt./academic/semiconductor R&D facilities

34. Removal and recycling of two (2) Liebert NX 3-Phase UPS cabinets and one (1) bypass cabinet.

File details come from the government source that posted it. Updated .