SATPC0037271 Tab 04 4 SOW.pdf

PDF 104 KB Posted

Attached to
277V/480V, 3 PHASE , 4 WIRES, 60 HZ Switchboard
Solicitation number
80NSSC25891642Q
Issued by

About this file

This Statement of Work specification sheet details requirements for a high-capacity electrical switchboard system. The specifications call for a UL 891 listed switchboard operating at 277V/480V, 3-phase, 4-wire, 60Hz with a 2000A copper main bus (tin-plated) and 100% rated neutral. The system requires a 65 KAIC rating, NEMA 1 enclosure, and 240kA surge protective device (SPD) with dry contact and surge counter.

Key technical requirements include a 2000A main breaker with comprehensive protection features (trip unit, long/short time, instantaneous, and ground fault), arc flash reduction maintenance mode switch, and a 3-phase power meter with CTs and display. The enclosure dimensions are specified as 91.5" height, 72" width, and 24" depth, with top entry main feeders. Square D QED-2 is suggested as the manufacturer, and the design includes copper ground bus with plugs for each device. This specification appears to be part of a sole-source procurement for NASA's Shared Services Center.

View the file

Other files

File Type Posted
SATPC0037271 Tab 07 Capability Statement SAM.gov.pdf PDF
SATPC0037271 Tab 06 RDSS..pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of work - Specifica�on Sheet

• UL 891 AND UL LISTED

• SYSTEM VOLTAGE: 277V/480V, 3 PHASE , 4 WIRES, 60 HZ

• NEUTRAL BUS FULLY RATED

• MAIN BUS 2000A, COPPER BUS, TIN, 1005 NEUTRAL

• 65 K.A.I.C. RATING

• ENCLOSURE: NEMA 1

• SPD: 240 kA. INCLUDING SPD DRY CONTACT AND SURGE COUNTER

• MAIN BREAKER 2000 A WITH PROTECTION INCLUDING TRIP UNIT, LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND FAULT

• MAINTENANCE MODE SWITCH: ARC FLASH REDUCTION

• POWER METER WITH 3 CTS AND DISPLAY, 3 PHASE, 4 WIRES

• GROUND PLUG PROVIDE FOR EACH DEVICE

• COPPER GROUND BUS

• MAIN FEEDERS ENTER ON TOP ENCLOSURE

• SUGGESTED MANUFACTURER: SQUARE D QED-2

• Dimensions o Overall Height 91.5” o Overall Width 72” o Overall Depth 24”