Amendment 04 signed.pdf
PDF 2 MB Posted
- Solicitation number
- 80KSC021R0028
About this file
This solicitation requests proposals for the replacement of switchgear at the Booster Fabrication Facility at Kennedy Space Center in Florida. The scope of work includes removing existing electrical equipment that is approximately 25 years old at three locations and installing new substations, medium voltage switches, transformers, secondary switchboards, and PLC controls. Abatement will be required for construction activities involving coatings with asbestos, heavy metals, and PCBs. Coordination of outages and phasing of work will be critical to keep the facility operational during launch vehicle processing and testing. The proposal due date has been extended to August 17, 2021. Offerors must be screened by the Defense Logistics Agency Joint Certification Program prior to receiving controlled drawings and specifications.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
ID Document Sheet / Detail / Comment Text Govt Response
1 79K40973 Note F
Drawing 79K40973 note F calls out for installation of 500’ Of FOC. Is there existing pathways for this cable to be installed of will new pathway need to be provided? Will the FOC need to be installed in inner duct. Does the existing IT rack have existing provision for terminating the new fiber into?
The 500 feet is an estimated run length.
The existing conduit can be reused and no innerduct will be required. The IT rack does have existing provisions for terminating the new fiber.
2 Can a Hazmat report be provided?
See attached Hazmat Lab Analysis Information, 45 pages.
Will floor coatings need to be removed prior to core drilling being performed?
Existing coating systems (not just the epoxy floor) can remain as long as the contractor selects construction methodologies that reduce airborne particle production to the greatest extent feasible, using best management practices in accordance with OSHA requirements and project specifications.
4 79K40974
Drawing 79K40973 (presumed typo, should read 79K40974) note E call for installing CAT 6 cable from the Unmanaged Ethernet Switch to existing switchboard control junction box.
Can the distance between these two locations be provided?
Assume 500 feet with existing pathway.
80KSC021R0028 ‐ Replace Switchgear at the Booster Fabrication Facility (BFF) Amendment 04 ‐ Bidder RFIs
Would it be acceptable to power panel TDP‐1115, with a generator and temp cables in liu of powering from new TX‐ 1115? If yes will KSC assume all re‐fueling operations during generator use?
No. Approach was investigated during design and determined to be infeasible due to redundancy and reliability concerns.
Would it be acceptable to power panel TDP‐1114, with a generator and temp cables in liu of powering from new TX‐ 1114? If yes will KSC assume all re‐fueling operations during generator use?
No. Approach was investigated during design and determined to be infeasible due to redundancy and reliability concerns.
Technical Experience Sub‐Factor (ii) calls for at least one (1) project listed in the Technical Experience Summary to be valued at over $5,000,000. This requirement would effectively eliminate some bidders from consideration who are otherwise qualified to perform the work. We request that the amount be reduced to $1,500,000.
Amount is reduced to $1,500,000.
8 79K40974 Note 1 Drawing 79K40974, note 1, can we get a copy of the environmental report?
See attached Hazmat Lab Analysis Information, 45 pages.
9 02 83 00 1.6.7.2 Is there any load data available to size the generators sufficiently the loads for facility L7‐0251?
No load data. An outage window will be coordinated with the successful contractor to replace the SS‐1116 at the Aft Skirt Test Facility (L7‐0251).
10 02 83 00 1.6.7.2 Will the deluge system at facility L7‐0251 need to be backed up on the temporary generator?
Yes, including the F/A System.
11 79K40973 sheet E‐
Termination detail shows 600amp elbows being used but is calling them 200amp. What is the amp rating for the elbows?
All elbows for 79K40973 will be 200A Load Break Elbows.
12 26 05 19.10 10.3.2 The medium voltage cable that is to be reused will they require VLF testing prior to being re‐energized?
Yes.
Can both facilities L7‐0251 and L6‐0247 be worked simultaneously?
No.
14 RFP Will the proposal date be extended?
Yes. Proposal will be extended to August 17, 2021 at 2:00:00 PM EDT.
15 79K40974 S‐101, S‐
It was noticed on the site visit that 200 lbs. per square foot is the maximum second floor loading. If an alternate engineer sealed method, to the temporary steel plate and temporary beams can be used to keep us below the max rating can it be used?
Yes, reference specification 05 12 00, Part 1.4.2 for requirements regarding alternative designs. Ensure to reference historical asbuilts 79K28970 for original structural drawings.
16 79K40974 E‐102 Has the paint on SS1116 been tested for any hazards, if not will it be the contractors responsibility to do so?
See attached Hazmat Lab Analysis Information, 45 pages.
E‐106
What will be the run times for the temporary generators that are required for the service building and the MPSF building, first shift, first and second or 24/7?
Generators will only be run during outages, whether planned or unplanned. Planned outages will be determined by the contractor based on Sequence of Construction on Sheets E‐ 002 and E‐003.
18 79K40974 E‐003, E004 Because the total footage of 15kv cable needed to connect from the new LBS's to the new TX's is so short will the government consider providing this cable?
No.
Can the Superintendent also serve as the SSHO ( Site Safety and Health Officer)? We can't determine from the specs.
No. See Contract Attachment J‐B‐17, Superintendent Assignment ‐ Full Time.
20 What is to be done with the old gear?
It will become property of the Contractor.
Attn:
Address: 280 North Burnett Road Order #: 397821 Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/15/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-001 1 SS-1114 Ext Metals Analysis
Arsenic PPM KM12/15/206.37<6.37EPA 6010D
Barium PPM KM12/15/206.3773.5EPA 6010D
Cadmium PPM KM12/15/206.37<6.37EPA 6010D
Chromium PPM KM12/15/2015.9<16.0EPA 6010D
Lead PPM KM12/15/206.3712.5EPA 6010D
Selenium PPM KM12/15/206.37<6.37EPA 6010D
Silver PPM KM12/15/206.37<6.37EPA 6010D The matrix spike failed for Ag, As, Cr, Pb & Se due to interference. The results are unaffected.
397821-002 2 SS-1115 Ext Metals Analysis
Arsenic PPM KM12/15/206.21<6.22EPA 6010D
Barium PPM KM12/15/206.21104EPA 6010D
Cadmium PPM KM12/15/206.21<6.22EPA 6010D
Chromium PPM KM12/15/2015.530.2EPA 6010D
Lead PPM KM12/15/206.219.21EPA 6010D
Selenium PPM KM12/15/206.21<6.22EPA 6010D
Silver PPM KM12/15/206.21<6.22EPA 6010D
397821-003 3 SS-1113 A/B Ext Metals Analysis
Arsenic PPM KM12/15/206.37<6.37EPA 6010D
Barium PPM KM12/15/206.37110EPA 6010D
Cadmium PPM KM12/15/206.3715.0EPA 6010D
Chromium PPM KM12/15/2015.926.5EPA 6010D
Lead PPM KM12/15/206.3727.5EPA 6010D
Selenium PPM KM12/15/206.37<6.37EPA 6010D
Silver PPM KM12/15/206.37<6.37EPA 6010D
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate only to the samples submitted.
Hazmat Lab Analysis Information per Question 2
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/15/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-004 4 Rm 110 L7-0251 Metals Analysis
Arsenic PPM KM12/15/205.78<5.78EPA 6010D
Barium PPM KM12/15/205.7872.9EPA 6010D
Cadmium PPM KM12/15/205.78<5.78EPA 6010D
Chromium PPM KM12/15/2014.5<14.5EPA 6010D
Lead PPM KM12/15/205.78<5.78EPA 6010D
Selenium PPM KM12/15/205.78<5.78EPA 6010D
Silver PPM KM12/15/205.78<5.78EPA 6010D
397821-005 5 Rm 103 L7-0251 Metals Analysis
Arsenic PPM KM12/15/206.04<6.05EPA 6010D
Barium PPM KM12/15/206.0472.1EPA 6010D
Cadmium PPM KM12/15/206.04<6.05EPA 6010D
Chromium PPM KM12/15/2015.1<15.1EPA 6010D
Lead PPM KM12/15/206.04<6.05EPA 6010D
Selenium PPM KM12/15/206.04<6.05EPA 6010D
Silver PPM KM12/15/206.04<6.05EPA 6010D
397821-006 6 Rm 1129 Floor L6-247 Metals Analysis
Arsenic PPM KM12/15/205.93<5.94EPA 6010D
Barium PPM KM12/15/205.9375.4EPA 6010D
Cadmium PPM KM12/15/205.93<5.94EPA 6010D
Chromium PPM KM12/15/2014.8<14.9EPA 6010D
Lead PPM KM12/15/205.9317.6EPA 6010D
Selenium PPM KM12/15/205.93<5.94EPA 6010D
Silver PPM KM12/15/205.93<5.94EPA 6010D
397821-007 7 Rm 1129 Wall Metals Analysis
Arsenic PPM KM12/15/206.17<6.18EPA 6010D
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate only to the samples submitted.
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/15/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-007 7 Rm 1129 Wall Barium PPM KM12/15/206.1786.0EPA 6010D
Cadmium PPM KM12/15/206.17<6.18EPA 6010D
Chromium PPM KM12/15/2015.4<15.5EPA 6010D
Lead PPM KM12/15/206.17<6.18EPA 6010D
Selenium PPM KM12/15/206.17<6.18EPA 6010D
Silver PPM KM12/15/206.17<6.18EPA 6010D
397821-008 8 Rm M 124 Floor Metals Analysis
Arsenic PPM KM12/15/205.85<5.85EPA 6010D
Barium PPM KM12/15/205.8576.9EPA 6010D
Cadmium PPM KM12/15/205.8577.0EPA 6010D
Chromium PPM KM12/15/2014.619.5EPA 6010D
Lead PPM KM12/15/205.8516.1EPA 6010D
Selenium PPM KM12/15/205.85<5.85EPA 6010D
Silver PPM KM12/15/205.8568.5EPA 6010D The LCS for Ag fell outside of acceptable range; possibilty of biased low results for Ag.
397821-009 9 M124 Floor Metals Analysis
Arsenic PPM KM12/15/206.60<6.60EPA 6010D
Barium PPM KM12/15/206.6065.3EPA 6010D
Cadmium PPM KM12/15/206.60<6.60EPA 6010D
Chromium PPM KM12/15/2016.5<16.5EPA 6010D
Lead PPM KM12/15/206.60<6.60EPA 6010D
Selenium PPM KM12/15/206.60<6.60EPA 6010D
Silver PPM KM12/15/206.60<6.60EPA 6010D
397821-010 10 Rm 2331 Floor Metals Analysis
Arsenic PPM KM12/15/206.43<6.43EPA 6010D
Barium PPM KM12/15/206.43109EPA 6010D
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/15/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-010 10 Rm 2331 Floor Cadmium PPM KM12/15/206.4326.7EPA 6010D
Chromium PPM KM12/15/2016.119.3EPA 6010D
Lead PPM KM12/15/206.4339.0EPA 6010D
Selenium PPM KM12/15/206.43<6.43EPA 6010D
Silver PPM KM12/15/206.43<6.43EPA 6010D
397821-011 11 Rm 2331 Floor Metals Analysis
Arsenic PPM KM12/15/205.80<5.80EPA 6010D
Barium PPM KM12/15/205.8063.5EPA 6010D
Cadmium PPM KM12/15/205.80<5.80EPA 6010D
Chromium PPM KM12/15/2014.539.4EPA 6010D
Lead PPM KM12/15/205.80195EPA 6010D
Selenium PPM KM12/15/205.80<5.80EPA 6010D
Silver PPM KM12/15/205.80<5.80EPA 6010D
397821-12/15/20 04:43 PM
Analyst Reviewed By: Ben Wood
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/15/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
Method Parameter Florida Virginia
State Certifications
Arsenic ELAP Certified VELAP CertifiedEPA 6010D
Barium ELAP Certified VELAP CertifiedEPA 6010D
Cadmium ELAP Certified VELAP CertifiedEPA 6010D
Chromium ELAP Certified VELAP CertifiedEPA 6010D
Lead ELAP Certified VELAP CertifiedEPA 6010D
Selenium ELAP Certified VELAP CertifiedEPA 6010D
Silver ELAP Certified VELAP CertifiedEPA 6010D
State Certificate Number
Florida ELAP E87828
Virginia VELAP 11110
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/17/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-001 1 SS-1114 Ext Metals Analysis
Mercury PPM JL12/15/200.111<0.111EPA 7471B
Arsenic PPM KM12/15/206.37<6.37EPA 6010D
Barium PPM KM12/15/206.3773.5EPA 6010D
Cadmium PPM KM12/15/206.37<6.37EPA 6010D
Chromium PPM KM12/15/2015.9<16.0EPA 6010D
Lead PPM KM12/15/206.3712.5EPA 6010D
Selenium PPM KM12/15/206.37<6.37EPA 6010D
Silver PPM KM12/15/206.37<6.37EPA 6010D The matrix spike failed for Ag, As, Cr, Pb & Se due to interference. The results are unaffected.
397821-002 2 SS-1115 Ext Metals Analysis
Mercury PPM JL12/15/200.111<0.111EPA 7471B
Arsenic PPM KM12/15/206.21<6.22EPA 6010D
Barium PPM KM12/15/206.21104EPA 6010D
Cadmium PPM KM12/15/206.21<6.22EPA 6010D
Chromium PPM KM12/15/2015.530.2EPA 6010D
Lead PPM KM12/15/206.219.21EPA 6010D
Selenium PPM KM12/15/206.21<6.22EPA 6010D
Silver PPM KM12/15/206.21<6.22EPA 6010D
397821-003 3 SS-1113 A/B Ext Metals Analysis
Mercury PPM JL12/15/200.118<0.118EPA 7471B
Arsenic PPM KM12/15/206.37<6.37EPA 6010D
Barium PPM KM12/15/206.37110EPA 6010D
Cadmium PPM KM12/15/206.3715.0EPA 6010D
Chromium PPM KM12/15/2015.926.5EPA 6010D
Lead PPM KM12/15/206.3727.5EPA 6010D
Selenium PPM KM12/15/206.37<6.37EPA 6010D
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/17/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-003 3 SS-1113 A/B Ext Silver PPM KM12/15/206.37<6.37EPA 6010D
397821-004 4 Rm 110 L7-0251 Metals Analysis
Mercury PPM JL12/15/200.105<0.105EPA 7471B
Arsenic PPM KM12/15/205.78<5.78EPA 6010D
Barium PPM KM12/15/205.7872.9EPA 6010D
Cadmium PPM KM12/15/205.78<5.78EPA 6010D
Chromium PPM KM12/15/2014.5<14.5EPA 6010D
Lead PPM KM12/15/205.78<5.78EPA 6010D
Selenium PPM KM12/15/205.78<5.78EPA 6010D
Silver PPM KM12/15/205.78<5.78EPA 6010D
397821-005 5 Rm 103 L7-0251 Metals Analysis
Mercury PPM JL12/15/200.108<0.108EPA 7471B
Arsenic PPM KM12/15/206.04<6.05EPA 6010D
Barium PPM KM12/15/206.0472.1EPA 6010D
Cadmium PPM KM12/15/206.04<6.05EPA 6010D
Chromium PPM KM12/15/2015.1<15.1EPA 6010D
Lead PPM KM12/15/206.04<6.05EPA 6010D
Selenium PPM KM12/15/206.04<6.05EPA 6010D
Silver PPM KM12/15/206.04<6.05EPA 6010D
397821-006 6 Rm 1129 Floor L6-247 Metals Analysis
Mercury PPM JL12/15/200.100<0.100EPA 7471B
Arsenic PPM KM12/15/205.93<5.94EPA 6010D
Barium PPM KM12/15/205.9375.4EPA 6010D
Cadmium PPM KM12/15/205.93<5.94EPA 6010D
Chromium PPM KM12/15/2014.8<14.9EPA 6010D
Lead PPM KM12/15/205.9317.6EPA 6010D
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/17/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-006 6 Rm 1129 Floor L6-247 Selenium PPM KM12/15/205.93<5.94EPA 6010D
Silver PPM KM12/15/205.93<5.94EPA 6010D
397821-007 7 Rm 1129 Wall Metals Analysis
Mercury PPM JL12/15/200.0992<0.0992EPA 7471B
Arsenic PPM KM12/15/206.17<6.18EPA 6010D
Barium PPM KM12/15/206.1786.0EPA 6010D
Cadmium PPM KM12/15/206.17<6.18EPA 6010D
Chromium PPM KM12/15/2015.4<15.5EPA 6010D
Lead PPM KM12/15/206.17<6.18EPA 6010D
Selenium PPM KM12/15/206.17<6.18EPA 6010D
Silver PPM KM12/15/206.17<6.18EPA 6010D
397821-008 8 Rm M 124 Floor Metals Analysis
Mercury PPM JL12/15/200.0977<0.0977EPA 7471B
Arsenic PPM KM12/15/205.85<5.85EPA 6010D
Barium PPM KM12/15/205.8576.9EPA 6010D
Cadmium PPM KM12/15/205.8577.0EPA 6010D
Chromium PPM KM12/15/2014.619.5EPA 6010D
Lead PPM KM12/15/205.8516.1EPA 6010D
Selenium PPM KM12/15/205.85<5.85EPA 6010D
Silver PPM KM12/15/205.8568.5EPA 6010D The LCS for Ag fell outside of acceptable range; possibilty of biased low results for Ag.
397821-009 9 M124 Floor Metals Analysis
Mercury PPM JL12/15/200.0926<0.0926EPA 7471B
Arsenic PPM KM12/15/206.60<6.60EPA 6010D
Barium PPM KM12/15/206.6065.3EPA 6010D
Cadmium PPM KM12/15/206.60<6.60EPA 6010D
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/17/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
397821-009 9 M124 Floor Chromium PPM KM12/15/2016.5<16.5EPA 6010D
Lead PPM KM12/15/206.60<6.60EPA 6010D
Selenium PPM KM12/15/206.60<6.60EPA 6010D
Silver PPM KM12/15/206.60<6.60EPA 6010D
397821-010 10 Rm 2331 Floor Metals Analysis
Mercury PPM JL12/15/200.109<0.109EPA 7471B
Arsenic PPM KM12/15/206.43<6.43EPA 6010D
Barium PPM KM12/15/206.43109EPA 6010D
Cadmium PPM KM12/15/206.4326.7EPA 6010D
Chromium PPM KM12/15/2016.119.3EPA 6010D
Lead PPM KM12/15/206.4339.0EPA 6010D
Selenium PPM KM12/15/206.43<6.43EPA 6010D
Silver PPM KM12/15/206.43<6.43EPA 6010D
397821-011 11 Rm 2331 Floor Metals Analysis
Mercury PPM JL12/15/200.115<0.115EPA 7471B
Arsenic PPM KM12/15/205.80<5.80EPA 6010D
Barium PPM KM12/15/205.8063.5EPA 6010D
Cadmium PPM KM12/15/205.80<5.80EPA 6010D
Chromium PPM KM12/15/2014.539.4EPA 6010D
Lead PPM KM12/15/205.80195EPA 6010D
Selenium PPM KM12/15/205.80<5.80EPA 6010D
Silver PPM KM12/15/205.80<5.80EPA 6010D
397821-12/17/20 03:53 PM
Analyst Reviewed By: Sultan Al-Johani
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
Cocoa, FL 32924-3188
Project: BFF Facility
20079
Sunrise Systems of Brevard, Inc (4020)Customer:
20079bcNumber: PO Number:
Received 12/14/20 Matrix Paint
Schneider Laboratories Global, Inc 2512 W. Cary Street • Richmond, Virginia • 23220-5117 804-353-6778 • 800-785-LABS (5227) • Fax 804-359-1475
Location: Kennedy Space Center FL
12/17/20Reported
Analysis Report
Cust. Sample ID
Parameter
Sample ID Location
UnitsRL* AnalystAnalysis DateResultMethod
Method Parameter Florida Virginia
State Certifications
Arsenic ELAP Certified VELAP CertifiedEPA 6010D
Barium ELAP Certified VELAP CertifiedEPA 6010D
Cadmium ELAP Certified VELAP CertifiedEPA 6010D
Chromium ELAP Certified VELAP CertifiedEPA 6010D
Lead ELAP Certified VELAP CertifiedEPA 6010D
Selenium ELAP Certified VELAP CertifiedEPA 6010D
Silver ELAP Certified VELAP CertifiedEPA 6010D
Mercury ELAP Certified VELAP CertifiedEPA 7471B
State Certificate Number
Florida ELAP E87828
Virginia VELAP 11110
All internal QC parameters were met. Unusual sample conditions, if any, are described. Surrogate Spike results designated with "D" indicate that the analyte was diluted out. "MI" indicates matrix interference. Concentration and *Reporting Limit (RL) based on areas provided by client. Values are reported to three significant figures. Solid PPM = mg/kg | PPB = µg/kg and Water PPM = mg/L | PPB = µg/L. The test results reported relate
10775 Central Port Drive
Orlando FL, 32824
407.826.5314 407.850.6945Phone: FAX:
[TOC_1]ENCO Laboratories, Inc.[TOC]
ENCO Workorder(s): AD03176
Kennedy Space Center, FL 32899
Unless otherwise noted in an attached project narrative, all samples were received in acceptable condition and processed in accordance with the referenced methods/procedures.
Results for these procedures apply only to the samples as submitted.
The analytical results contained in this report are in compliance with NELAC standards, except as noted in the project narrative if applicable. This report shall not be reproduced except in full, without the written approval of the Laboratory.
This report contains only those analyses performed by Environmental Conservation
Laboratories. Unless otherwise noted, all analyses were performed at ENCO Orlando. Data from outside organizations will be reported under separate cover.
If you have any questions or require further information, please do not hesitate to contact me.
Sincerely, Enclosure(s)
Project Number: T202005-23411-1556, Project Name/Desc: Waste Sampling L6-0147 Paint and Caulk
Attn: Sarah Hausman
Integrated Mission Support Services, LLC (IN029)
Logistics Building K6-1547, Room 2504
Carlene S Pasipanki
Project Manager
Thursday, May 21, 2020
RE: Laboratory Results for
Dear Sarah Hausman, Enclosed is a copy of your laboratory report for test samples received by our laboratory on
Thursday, May 14, 2020.
Enclosure(s)
Page 1 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL www.encolabs.com
PROJECT NARRATIVE
[TOC_1]Project Narrative[TOC]
Client: Integrated Mission Support Services, LLC (IN029)
Project: Waste Sampling L6-0147 Paint and Caulk
ENCO Project ID: AD03176
Overview
All samples submitted were analyzed by Environmental Conservation Laboratories, Inc. in accordance with the methods referenced in the laboratory report. Any particular difficulties encountered during sample handling and processing will be discussed in the Remarks section below.
Remarks
Analysis: EPA 1311
Affected Samples: L6-147-Doors-Blue [AD03176-01], L6-147-Siding-Blue [AD03176-02], L6-147-Beams-Blue
[AD03176-03], L6-147-Roll-Doors-White [AD03176-04]
Nonconformance: Sample submitted for TCLP analysis was less than the method required 100 grams.
Additional Information: Although, there was not 100 grams of material, there was enough to produce a sufficient amount of leachate for analysis.
Carlene S Pasipanki
Project Manager
Page 2 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
SAMPLE SUMMARY/LABORATORY CHRONICLE
[TOC_1]Sample Chronical[TOC]
L6-147-Doors-Blue AD03176-01 Sampled: 05/14/20 09:25 Received: 05/14/20 15:45Client ID: Lab ID:
Prep Date/Time(s)Hold Date/Time(s)Parameter Analysis Date/Time(s)Preparation
EPA 6020B 11/10/20 05/19/20 10:47 05/20/20 14:4911/15/20EPA 3010A
EPA 7470A 06/11/20 05/19/20 13:04 05/20/20 11:0806/16/20EPA 7470A
L6-147-Siding-Blue AD03176-02 Sampled: 05/14/20 08:50 Received: 05/14/20 15:45Client ID: Lab ID:
Prep Date/Time(s)Hold Date/Time(s)Parameter Analysis Date/Time(s)Preparation
EPA 6020B 11/10/20 05/19/20 10:47 05/20/20 14:5511/15/20EPA 3010A
EPA 7470A 06/11/20 05/19/20 13:04 05/20/20 11:1106/16/20EPA 7470A
L6-147-Beams-Blue AD03176-03 Sampled: 05/14/20 09:20 Received: 05/14/20 15:45Client ID: Lab ID:
Prep Date/Time(s)Hold Date/Time(s)Parameter Analysis Date/Time(s)Preparation
EPA 6020B 11/10/20 05/19/20 10:47 05/20/20 14:5711/15/20EPA 3010A
EPA 7470A 06/11/20 05/19/20 13:04 05/20/20 11:1406/16/20EPA 7470A
L6-147-Roll-Doors-White AD03176-04 Sampled: 05/14/20 09:45 Received: 05/14/20 15:45Client ID: Lab ID:
Prep Date/Time(s)Hold Date/Time(s)Parameter Analysis Date/Time(s)Preparation
EPA 6020B 11/10/20 05/19/20 10:47 05/20/20 15:0011/15/20EPA 3010A
EPA 7470A 06/11/20 05/19/20 13:04 05/20/20 11:2606/16/20EPA 7470A
Page 3 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
SAMPLE DETECTION SUMMARY
[TOC_1]Detection Summary[TOC]
Lab ID:Client ID: L6-147-Doors-Blue AD03176-01
Analyte MethodUnitsPQLResults Flag NotesMDL
3.53 5.00 mg/L EPA 6020BI Barium - TCLP 2.50
Lab ID:Client ID: L6-147-Siding-Blue AD03176-02
Analyte MethodUnitsPQLResults Flag NotesMDL
12.2 0.500 mg/L EPA 6020B Chromium - TCLP 0.250
Page 4 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
ANALYTICAL RESULTS
[TOC_1]Analytical Results[TOC]
L6-147-Doors-BlueDescription: Lab Sample ID:AD03176-01 05/14/20 15:45Received:
AD03176Work Order:05/14/20 09:25Sampled:SolidMatrix:
% Solids:John Leslie WilliamsSampled By:Project: Waste Sampling L6-0147 Paint and Caulk
[TOC_2]L6-147-Doors-Blue[TOC]
TCLP Metals by 6000/7000 Series Methods
^ - ENCO Orlando certified analyte [NELAC E83182]
NotesFlag PQL Batch ByAnalyzedMethodMDLResults Units DFAnalyte [CAS Number] mg/L EPA 6020B 05/20/20 14:49Antimony [7440-36-0] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 6020B 05/20/20 14:49Arsenic [7440-38-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:49Barium [7440-39-3] 2.50 SSE0E190115.003.53 I 10 mg/L EPA 6020B 05/20/20 14:49Beryllium [7440-41-7] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:49Cadmium [7440-43-9] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:49Chromium [7440-47-3] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:49Lead [7439-92-1] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 7470A 05/20/20 11:08Mercury [7439-97-6]^ 0.000230 JSS0E190250.002000.000230 U 1 mg/L EPA 6020B 05/20/20 14:49Nickel [7440-02-0] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:49Selenium [7782-49-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:49Silver [7440-22-4] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:49Thallium [7440-28-0] 0.0250 SSE0E190110.05000.0250 U 10
L6-147-Siding-BlueDescription: Lab Sample ID:AD03176-02 05/14/20 15:45Received:
AD03176Work Order:05/14/20 08:50Sampled:SolidMatrix:
% Solids:John Leslie WilliamsSampled By:Project: Waste Sampling L6-0147 Paint and Caulk
[TOC_2]L6-147-Siding-Blue[TOC]
TCLP Metals by 6000/7000 Series Methods
^ - ENCO Orlando certified analyte [NELAC E83182]
NotesFlag PQL Batch ByAnalyzedMethodMDLResults Units DFAnalyte [CAS Number] mg/L EPA 6020B 05/20/20 14:55Antimony [7440-36-0] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 6020B 05/20/20 14:55Arsenic [7440-38-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:55Barium [7440-39-3] 2.50 SSE0E190115.002.50 U 10 mg/L EPA 6020B 05/20/20 14:55Beryllium [7440-41-7] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:55Cadmium [7440-43-9] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:55Chromium [7440-47-3] 0.250 SSE0E190110.50012.2 10 mg/L EPA 6020B 05/20/20 14:55Lead [7439-92-1] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 7470A 05/20/20 11:11Mercury [7439-97-6]^ 0.000230 JSS0E190250.002000.000230 U 1 mg/L EPA 6020B 05/20/20 14:55Nickel [7440-02-0] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:55Selenium [7782-49-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:55Silver [7440-22-4] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:55Thallium [7440-28-0] 0.0250 SSE0E190110.05000.0250 U 10
Page 5 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
L6-147-Beams-BlueDescription: Lab Sample ID:AD03176-03 05/14/20 15:45Received:
AD03176Work Order:05/14/20 09:20Sampled:SolidMatrix:
% Solids:John Leslie WilliamsSampled By:Project: Waste Sampling L6-0147 Paint and Caulk
[TOC_2]L6-147-Beams-Blue[TOC]
TCLP Metals by 6000/7000 Series Methods
^ - ENCO Orlando certified analyte [NELAC E83182]
NotesFlag PQL Batch ByAnalyzedMethodMDLResults Units DFAnalyte [CAS Number] mg/L EPA 6020B 05/20/20 14:57Antimony [7440-36-0] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 6020B 05/20/20 14:57Arsenic [7440-38-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:57Barium [7440-39-3] 2.50 SSE0E190115.002.50 U 10 mg/L EPA 6020B 05/20/20 14:57Beryllium [7440-41-7] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:57Cadmium [7440-43-9] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:57Chromium [7440-47-3] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:57Lead [7439-92-1] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 7470A 05/20/20 11:14Mercury [7439-97-6]^ 0.000230 JSS0E190250.002000.000230 U 1 mg/L EPA 6020B 05/20/20 14:57Nickel [7440-02-0] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:57Selenium [7782-49-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 14:57Silver [7440-22-4] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 14:57Thallium [7440-28-0] 0.0250 SSE0E190110.05000.0250 U 10
L6-147-Roll-Doors-WhiteDescription: Lab Sample ID:AD03176-04 05/14/20 15:45Received:
AD03176Work Order:05/14/20 09:45Sampled:SolidMatrix:
% Solids:John Leslie WilliamsSampled By:Project: Waste Sampling L6-0147 Paint and Caulk
[TOC_2]L6-147-Roll-Doors-White[TOC]
TCLP Metals by 6000/7000 Series Methods
^ - ENCO Orlando certified analyte [NELAC E83182]
NotesFlag PQL Batch ByAnalyzedMethodMDLResults Units DFAnalyte [CAS Number] mg/L EPA 6020B 05/20/20 15:00Antimony [7440-36-0] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 6020B 05/20/20 15:00Arsenic [7440-38-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 15:00Barium [7440-39-3] 2.50 SSE0E190115.002.50 U 10 mg/L EPA 6020B 05/20/20 15:00Beryllium [7440-41-7] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 15:00Cadmium [7440-43-9] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 15:00Chromium [7440-47-3] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 15:00Lead [7439-92-1] 0.125 SSE0E190110.2500.125 U 10 mg/L EPA 7470A 05/20/20 11:26Mercury [7439-97-6]^ 0.000230 JSS0E190250.002000.000230 U 1 mg/L EPA 6020B 05/20/20 15:00Nickel [7440-02-0] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 15:00Selenium [7782-49-2] 0.250 SSE0E190110.5000.250 U 10 mg/L EPA 6020B 05/20/20 15:00Silver [7440-22-4] 0.0250 SSE0E190110.05000.0250 U 10 mg/L EPA 6020B 05/20/20 15:00Thallium [7440-28-0] 0.0250 SSE0E190110.05000.0250 U 10
Page 6 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
QUALITY CONTROL DATA
[TOC_1]QC Data[TOC]
TCLP Metals by 6000/7000 Series Methods - Quality Control
Batch 0E19011 - EPA 3010A
Prepared: 05/19/2020 10:47 Analyzed: 05/20/2020 13:23Blank (0E19011-BLK1)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.2500.125 U Antimony mg/L0.5000.250 U Arsenic mg/L5.002.50 U Barium mg/L0.05000.0250 U Beryllium mg/L0.05000.0250 U Cadmium mg/L0.5000.250 U Chromium mg/L0.2500.125 U Lead mg/L0.5000.250 U Nickel mg/L0.5000.250 U Selenium mg/L0.05000.0250 U Silver mg/L0.05000.0250 U Thallium
Prepared: 05/19/2020 10:47 Analyzed: 05/20/2020 13:25Blank (0E19011-BLK2)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.2500.125 U Antimony mg/L0.5000.250 U Arsenic mg/L5.002.50 U Barium mg/L0.05000.0250 U Beryllium mg/L0.05000.0250 U Cadmium mg/L0.5000.250 U Chromium mg/L0.2500.125 U Lead mg/L0.5000.250 U Nickel mg/L0.5000.250 U Selenium mg/L0.05000.0250 U Silver mg/L0.05000.0250 U Thallium
Prepared: 05/19/2020 10:47 Analyzed: 05/20/2020 13:28LCS (0E19011-BS1)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.250 2.50 80-120962.40 Antimony mg/L0.500 25.0 80-1209724.2 Arsenic mg/L5.00 25.0 80-1209323.2 Barium mg/L0.0500 2.50 80-120982.45 Beryllium mg/L0.0500 2.50 80-120962.39 Cadmium mg/L0.500 25.0 80-1209222.9 Chromium mg/L0.250 25.0 80-1209423.5 Lead mg/L0.500 25.0 80-1209523.7 Nickel mg/L0.500 25.0 80-1209724.2 Selenium mg/L0.0500 2.50 80-120962.39 Silver mg/L0.0500 2.50 80-120922.31 Thallium
Prepared: 05/19/2020 10:47 Analyzed: 05/20/2020 13:36Matrix Spike (0E19011-MS1)
Source: AD03204-01
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.250 2.50 75-125950.125 U2.36 Antimony mg/L0.500 25.0 75-125940.250 U23.6 Arsenic mg/L5.00 25.0 75-125932.50 U23.3 Barium
Page 7 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
TCLP Metals by 6000/7000 Series Methods - Quality Control
Batch 0E19011 - EPA 3010A - Continued
Prepared: 05/19/2020 10:47 Analyzed: 05/20/2020 13:36Matrix Spike (0E19011-MS1) Continued
Source: AD03204-01
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.0500 2.50 75-125930.0250 U2.33 Beryllium mg/L0.0500 2.50 75-125940.0250 U2.36 Cadmium mg/L0.500 25.0 75-125900.250 U22.5 Chromium mg/L0.250 25.0 75-125930.13923.4 Lead mg/L0.500 25.0 75-125920.250 U23.1 Nickel mg/L0.500 25.0 75-125950.250 U23.7 Selenium mg/L0.0500 2.50 75-125940.0250 U2.35 Silver mg/L0.0500 2.50 75-125910.0250 U2.27 Thallium
Prepared: 05/19/2020 10:47 Analyzed: 05/20/2020 13:38Matrix Spike Dup (0E19011-MSD1)
Source: AD03204-01
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.250 2.50 2075-12596 20.125 U2.40 Antimony mg/L0.500 25.0 2075-12597 30.250 U24.2 Arsenic mg/L5.00 25.0 2075-12596 22.50 U23.9 Barium mg/L0.0500 2.50 2075-12598 50.0250 U2.44 Beryllium mg/L0.0500 2.50 2075-12596 20.0250 U2.40 Cadmium mg/L0.500 25.0 2075-12593 30.250 U23.2 Chromium mg/L0.250 25.0 2075-12596 30.13924.1 Lead mg/L0.500 25.0 2075-12596 40.250 U23.9 Nickel mg/L0.500 25.0 2075-12596 20.250 U24.1 Selenium mg/L0.0500 2.50 2075-12594 0.20.0250 U2.35 Silver mg/L0.0500 2.50 2075-12594 30.0250 U2.34 Thallium
Batch 0E19025 - EPA 7470A
Prepared: 05/19/2020 13:04 Analyzed: 05/20/2020 09:36Blank (0E19025-BLK1)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.0002002.30E-5 U Mercury
Prepared: 05/19/2020 13:04 Analyzed: 05/20/2020 09:39Blank (0E19025-BLK2)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.002000.000230 U Mercury
Prepared: 05/19/2020 13:04 Analyzed: 05/20/2020 09:42LCS (0E19025-BS1)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.000200 0.00500 80-1201030.00515 Mercury
Prepared: 05/19/2020 13:04 Analyzed: 05/20/2020 09:49Matrix Spike (0E19025-MS1)
Source: AD03163-01
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.00200 0.0500 75-1251030.000230 U0.0517 Mercury
Page 8 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
Batch 0E19025 - EPA 7470A - Continued
Prepared: 05/19/2020 13:04 Analyzed: 05/20/2020 09:52Matrix Spike Dup (0E19025-MSD1)
Source: AD03163-01
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.00200 0.0500 2075-125103 0.30.000230 U0.0516 Mercury
Page 9 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
FLAGS/NOTES AND DEFINITIONS
[TOC_1]Flags/Notes[TOC]
PQL: Practical Quantitation Limit. The PQL presented is the laboratory MRL.PQL
B Results are based upon membrane filter colony counts that are outside the method indicated ideal range.
I The reported value is between the laboratory method detection limit (MDL) and the practical quantitation limit (PQL).
J Estimated value.
K Off-scale low; Actual value is known to be less than the value given.
L Off-scale high; Actual value is known to be greater than value given.
M Presence of analyte is verified but not quantified; the actual value is less than the MRL but greater than the MDL.
N Presumptive evidence of presence of material.
O Sampled, but analysis lost or not performed.
Q Sample exceeded the accepted holding time.
T Value reported is less than the laboratory method detection limit. The value is reported for informational purposes only and shall not be used in statistical analysis.
U Indicates that the compound was analyzed for but not detected.
V Indicates that the analyte was detected in both the sample and the associated method blank.
Y The laboratory analysis was from an improperly preserved sample. The data may not be accurate.
Z Too many colonies were present (TNTC); the numeric value represents the filtration volume.
? Data are rejected and should not be used. Some or all of the quality control data for the analyte were outside criteria, and the presence or absence of the analyte cannot be determined from the data.
* Not reported due to interference.
Calculated analyte - MDL/MRL reported to the highest reporting limit of the component analyses.[CALC]
Page 10 of 11This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
10775 Central Port Drive
Orlando FL, 32824
407.826.5314 407.850.6945Phone: FAX:
[TOC_1]ENCO Laboratories, Inc.[TOC]
ENCO Workorder(s): AD03575
Kennedy Space Center, FL 32899
Unless otherwise noted in an attached project narrative, all samples were received in acceptable condition and processed in accordance with the referenced methods/procedures.
Results for these procedures apply only to the samples as submitted.
The analytical results contained in this report are in compliance with NELAC standards, except as noted in the project narrative if applicable. This report shall not be reproduced except in full, without the written approval of the Laboratory.
This report contains only those analyses performed by Environmental Conservation
Laboratories. Unless otherwise noted, all analyses were performed at ENCO Orlando. Data from outside organizations will be reported under separate cover.
If you have any questions or require further information, please do not hesitate to contact me.
Sincerely, Enclosure(s)
Project Number: T202005-23411-1578, Project Name/Desc: Waste Sampling L6-0147 Paint and Caulk
Attn: Sarah Hausman
Integrated Mission Support Services, LLC (IN029)
Logistics Building K6-1547, Room 2504
Carlene S Pasipanki
Project Manager
Tuesday, June 9, 2020
RE: Laboratory Results for
Dear Sarah Hausman, Enclosed is a copy of your laboratory report for test samples received by our laboratory on
Tuesday, June 2, 2020.
Enclosure(s)
Page 1 of 10This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
PROJECT NARRATIVE
[TOC_1]Project Narrative[TOC]
Client: Integrated Mission Support Services, LLC (IN029)
Project: Waste Sampling L6-0147 Paint and Caulk
ENCO Project ID: AD03575
Overview
All samples submitted were analyzed by Environmental Conservation Laboratories, Inc. in accordance with the methods referenced in the laboratory report. Any particular difficulties encountered during sample handling and processing will be discussed in the Remarks section below.
Remarks
Analysis: EPA 1311
Affected Samples: L6-0147-J14870 [AD03575-01]
Nonconformance: Sample submitted for TCLP analysis was less than the method required 100 grams.
Additional Information: Although, there was not 100 grams of material, there was enough to produce a sufficient amount of leachate for analysis.
Carlene S Pasipanki
Project Manager
Page 2 of 10This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
SAMPLE SUMMARY/LABORATORY CHRONICLE
[TOC_1]Sample Chronical[TOC]
L6-0147-J14870 AD03575-01 Sampled: 05/29/20 12:00 Received: 06/02/20 15:00Client ID: Lab ID:
Prep Date/Time(s)Hold Date/Time(s)Parameter Analysis Date/Time(s)Preparation
EPA 6020B 11/25/20 06/05/20 09:51 06/08/20 11:0812/02/20EPA 3010A
EPA 7470A 06/26/20 06/05/20 12:21 06/08/20 10:5207/03/20EPA 7470A
Page 3 of 10This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
SAMPLE DETECTION SUMMARY
[TOC_1]Detection Summary[TOC]
Lab ID:Client ID: L6-0147-J14870 AD03575-01
Analyte MethodUnitsPQLResults Flag NotesMDL
0.000595 0.00200 mg/L EPA 7470AI Mercury - TCLP 0.000230
Page 4 of 10This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
[TOC_1]Analytical Results[TOC]
L6-0147-J14870Description: Lab Sample ID:AD03575-01 06/02/20 15:00Received:
AD03575Work Order:05/29/20 12:00Sampled:SolidMatrix:
% Solids:John Leslie WilliamsSampled By:Project: Waste Sampling L6-0147 Paint and Caulk
[TOC_2]L6-0147-J14870[TOC]
TCLP Metals by 6000/7000 Series Methods
^ - ENCO Orlando certified analyte [NELAC E83182]
NotesFlag PQL Batch ByAnalyzedMethodMDLResults Units DFAnalyte [CAS Number] mg/L EPA 6020B 06/08/20 11:08Antimony [7440-36-0] 0.125 SSE0F050140.2500.125 U 10 mg/L EPA 6020B 06/08/20 11:08Arsenic [7440-38-2] 0.250 SSE0F050140.5000.250 U 10 mg/L EPA 6020B 06/08/20 11:08Barium [7440-39-3] 2.50 SSE0F050145.002.50 U 10 mg/L EPA 6020B 06/08/20 11:08Beryllium [7440-41-7] 0.0250 SSE0F050140.05000.0250 U 10 mg/L EPA 6020B 06/08/20 11:08Cadmium [7440-43-9] 0.0250 SSE0F050140.05000.0250 U 10 mg/L EPA 6020B 06/08/20 11:08Chromium [7440-47-3] 0.250 SSE0F050140.5000.250 U 10 mg/L EPA 6020B 06/08/20 11:08Lead [7439-92-1] 0.125 SSE0F050140.2500.125 U 10 mg/L EPA 7470A 06/08/20 10:52Mercury [7439-97-6]^ 0.000230 JSS0F050180.002000.000595 I 1 mg/L EPA 6020B 06/08/20 11:08Nickel [7440-02-0] 0.250 SSE0F050140.5000.250 U 10 mg/L EPA 6020B 06/08/20 11:08Selenium [7782-49-2] 0.250 SSE0F050140.5000.250 U 10 mg/L EPA 6020B 06/08/20 11:08Silver [7440-22-4] 0.0250 SSE0F050140.05000.0250 U 10 mg/L EPA 6020B 06/08/20 11:08Thallium [7440-28-0] 0.0250 SSE0F050140.05000.0250 U 10
Page 5 of 10This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
[TOC_1]QC Data[TOC]
TCLP Metals by 6000/7000 Series Methods - Quality Control
Batch 0F05014 - EPA 3010A
Prepared: 06/05/2020 09:51 Analyzed: 06/08/2020 09:50Blank (0F05014-BLK1)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.2500.125 U Antimony mg/L0.5000.250 U Arsenic mg/L5.002.50 U Barium mg/L0.05000.0250 U Beryllium mg/L0.05000.0250 U Cadmium mg/L0.5000.250 U Chromium mg/L0.2500.125 U Lead mg/L0.5000.250 U Nickel mg/L0.5000.250 U Selenium mg/L0.05000.0250 U Silver mg/L0.05000.0250 U Thallium
Prepared: 06/05/2020 09:51 Analyzed: 06/08/2020 09:53Blank (0F05014-BLK2)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.2500.125 U Antimony mg/L0.5000.250 U Arsenic mg/L5.002.50 U Barium mg/L0.05000.0250 U Beryllium mg/L0.05000.0250 U Cadmium mg/L0.5000.250 U Chromium mg/L0.2500.125 U Lead mg/L0.5000.250 U Nickel mg/L0.5000.250 U Selenium mg/L0.05000.0250 U Silver mg/L0.05000.0250 U Thallium
Prepared: 06/05/2020 09:51 Analyzed: 06/08/2020 09:55Blank (0F05014-BLK3)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.2500.125 U Antimony mg/L0.5000.250 U Arsenic mg/L5.002.50 U Barium mg/L0.05000.0250 U Beryllium mg/L0.05000.0250 U Cadmium mg/L0.5000.250 U Chromium mg/L0.2500.125 U Lead mg/L0.5000.250 U Nickel mg/L0.5000.250 U Selenium mg/L0.05000.0250 U Silver mg/L0.05000.0250 U Thallium
Prepared: 06/05/2020 09:51 Analyzed: 06/08/2020 09:58LCS (0F05014-BS1)
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.250 2.50 80-120932.32 Antimony mg/L0.500 25.0 80-1209323.2 Arsenic mg/L5.00 25.0 80-1209223.0 Barium
Page 6 of 10This report relates only to the sample as received by the laboratory, and may only be reproduced in full.FINAL
Batch 0F05014 - EPA 3010A - Continued
Prepared: 06/05/2020 09:51 Analyzed: 06/08/2020 09:58LCS (0F05014-BS1) Continued
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.0500 2.50 80-120922.29 Beryllium mg/L0.0500 2.50 80-120932.32 Cadmium mg/L0.500 25.0 80-1208822.1 Chromium mg/L0.250 25.0 80-1209323.2 Lead mg/L0.500 25.0 80-1209022.6 Nickel mg/L0.500 25.0 80-1209323.3 Selenium mg/L0.0500 2.50 80-120922.29 Silver mg/L0.0500 2.50 80-120922.30 Thallium
Prepared: 06/05/2020 09:51 Analyzed: 06/08/2020 10:05Matrix Spike (0F05014-MS1)
Source: AD03569-02
FlagResult Units Level Result %REC Limits RPD Limit Notes Analyte PQL
Spike Source %REC RPD mg/L0.250 2.50 75-125950.125 U2.38 Antimony mg/L0.500 25.0…