8-2-DA27003-26290480 Plans.pdf
PDF 38 MB Posted
- Solicitation number
- DA27003
- Issued by
- Utah
About this file
This is a construction permit set and architectural plans prepared by Architectural NEXUS, Inc. for the Utah Division of Facilities Construction and Management (DFCM) and the Utah National Guard. The project involves the construction of a new vehicle wash rack facility at Camp Williams in Bluffdale, Utah, located at 17800 South Redwood Road. The facility will consist of a covered pre-engineered metal building (PEMB) structure measuring approximately 74 feet by 81 feet with two pull-through wash bays designed to accommodate military and support vehicles, along with an associated 15-foot by 37-foot pump house. The facility will include integrated drainage systems connected to settling basins for wash water collection and treatment, mechanical systems to condition the wash bays and mitigate freezing conditions during winter operations, and comprehensive site development including grading, paving, utilities, storm drainage, erosion control, and infrastructure tie-ins to existing systems. The permit set is dated June 18, 2026, and includes detailed specifications for foundations, structural systems, plumbing, mechanical, and electrical installations across civil, architectural, structural, mechanical, plumbing, and electrical disciplines.
The project encompasses site demolition and removal of certain existing utilities, installation of new storm and sanitary sewer infrastructure, grading and drainage improvements with numerous catch basins and cleanout boxes, new concrete pavement and waterways, utility relocations, and erosion control measures. The design adheres to the 2021 International Building Code, 2021 National Electrical Code, ADA accessibility standards, and applicable DFCM Design Criteria and Guidelines. The contract documents specify that all construction must comply with Unified Facilities Criteria (UFC), APWA standards, and ANSI specifications, with the order of precedence established as DFCM, UFC, 2018 IBC, 2020 NEC, ANSI, design engineer requirements, UTNG Construction Guidelines, APWA, and the Manual on Uniform Traffic Control Devices. The estimated construction cost is $2,850,000, and the contract is restricted to prequalified contractors from the DFCM Prequalified Contractors list as of the solicitation date.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTACT: E-MAIL:
PHONE: INTERNET:
OWNER
Utah DFCM 43145 South 2700 West, Fl. 3
Taylorsville, UT 84129
801.960.7647
Randy Mellor rmellor@utah.gov http://www.dfcm.utah.gov
CONTACT: E-MAIL:
PHONE: INTERNET:
AGENCY
Utah National Guard 12953 South Minuteman Drive
Draper, UT 84020
801.471.9696
Jonathan Butler jonathan.d.butler21.nfg@army.mil http://www.guard.utah.gov
CONTACT: E-MAIL:
PHONE: INTERNET:
ARCHITECT
Architectural NEXUS, Inc.
2505 East Parleys Way
Salt Lake City, UT 84109
801.924.5000
Stephen Springer sspringer@archnexus.com http://www.archnexus.com
CONTACT: E-MAIL:
PHONE: INTERNET:
MECHANICAL ENGINEER
Colvin Engineering 505 East South Temple, Suite 100
Salt Lake City, UT 84102
801.505.5417
Mike Dallon mike.dallon@lynkengineers.com http://www.cea-ut.com
CONTACT: E-MAIL:
PHONE: INTERNET:
ELECTRICAL ENGINEER
Colvin Engineering 505 East South Temple, Suite 100
Salt Lake City, UT 84102
801.698.2875
Tyler Squire tyler.squire@lynkengineers.com http://www.cea-ut.com
NEXUS PROJECT #: DFCM PROJECT #: 26290480
VICINITY MAP
PROJECT
LOCATION
PROJECT DESCRIPTION:
DFCM APPROVAL
UTAH NATIONAL GUARD
CAMP WILLIAMS
WASH RACK
17800 S REDWOOD RD
(AT CORNER OF MAINTENANCE AVE. & SUPPLY ST.)
BLUFFDALE, UTAH 84065
PERMIT SET
06.18.2026
25061
The UTNG Camp Williams Wash Rack project includes the construction of a new vehicle wash facility located at Camp Williams in Bluffdale, Utah. The project consists of a covered, open pre-engineered metal building (PEMB) structure housing two pull-through wash bays designed to accommodate military and support vehicles. Each wash bay will be equipped with integrated drainage systems connected to settling basins for the collection and treatment of wash water. The facility will also include mechanical systems to condition the wash bays and mitigate freezing conditions during winter operations.
The scope of work further includes associated site development and infrastructure improvements necessary to support the facility, including grading, paving, utilities, storm drainage, erosion control, and tie-ins to existing systems. Work also encompasses foundations, structural systems, plumbing, mechanical, and electrical installations, along with all appurtenant components required for a complete and operational wash rack facility in accordance with the contract documents.
CONTACT: E-MAIL:
PHONE: INTERNET:
STRUCTURAL ENGINEER
Structural Design Studio 2225 East Murray Hollady Rd., Suite 100
Salt Lake City, UT 84117
801.274.3950
Jake Merkley jake@structuralds.com http://www.structuralds.com
CONTACT: E-MAIL:
PHONE: INTERNET:
CIVIL ENGINEER
Ensign Engineering 45 West 10000 South, Ste 500
Sandy, UT 84070
801.255.0529
Koby Morgan kmorgan@ensignutah.com https://www.ensignutah.com
SEE GI101
DESIGN CRITERIA
APPLICABLE CODES
DEFERRED SUBMITTALS
PRE-ENGINEERED METAL BUILDING (PEMB)
METAL CATWALK AND STAIRS
SEISMIC RESTRAINTS
HIGH PRESSURE WASH AND BLOW DOWN SYSTEM
DUPLEX SUMP PUMP SYSTEM (ABI 2)
BID PACKAGE GENERAL NOTES
A. THIS BID PACKAGE SHALL BE BID IN ITS ENTIRETY. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO REVIEW AND COORDINATE THE WORK OF ALL SUB-CONTRACTORS,
TRADES AND SUPPLIERS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS
BEFORE COMMENCING CONSTRUCTION, AND TO ASSURE THAT ALL PARTIES ARE
AWARE OF ALL REQUIREMENTS, REGARDLESS OF WHERE THE REQUIREMENTS OCCUR
IN THE CONTRACT DOCUMENTS, WHICH MIGHT AFFECT THE WORK OF THAT PARTY.
B. AS PART OF THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE THE WORK OF ALL
SUB-CONTRACTORS, TRADES AND SUPPLIERS, THE CONTRACTOR SHALL ENDEAVOR
TO IDENTIFY AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES OR CONFLICTS
BETWEEN THE WORK OF DIFFERENT PARTIES AT THE EARLIEST POSSIBLE DATE SO AS
TO ALLOW REASONABLE AND ADEQUATE TIME FOR THE CONFLICT TO BE RESOLVED
WITHOUT DELAYING THE WORK. ALL DEVIATIONS FROM THAT WHICH IS REQUIRED BY
THE CONTRACT DOCUMENTS MUST BE APPROVED IN ADVANCE BY THE ARCHITECT.
C. IN CASE OF ANY DISCREPANCY WITHIN THE CONTRACT DOCUMENTS, THE MOST
STRINGENT REQUIREMENT OR MOST COSTLY OPTION SHALL APPLY, UNLESS
CLARIFICATION IS SOUGHT IN WRITING AND RECEIVED FROM THE ARCHITECT PRIOR
TO BIDDING. THE CONTRACTOR SHALL BRING ANY KNOWN DISCREPANCIES TO THE
ATTENTION OF THE ARCHITECT AS SOON AS POSSIBLE, AND IN ANY EVENT, PRIOR TO
COMMENCING AFFECTED WORK.
D. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY CONFLICTS
BETWEEN VENDOR DRAWINGS AND THE CONTRACT DOCUMENTS. THE LATEST
VENDOR DRAWINGS SHALL GOVERN AND BE VERIFIED WITH THE OWNER AND THE
ARCHITECT.
E. THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE IN ESTABLISHING AND
COORDINATING THE FINISHED APPEARANCE AND EXACT LOCATION OF ALL EXPOSED
ELEMENTS OF THE WORK OF ALL TRADES, INCLUDING THAT WORK WHICH IS
ILLUSTRATED PRIMARILY ON DRAWINGS OF OTHER DISCIPLINES. QUANTITIES ARE TO
BE PROVIDED AS SHOWN ON DRAWINGS OF OTHER DISCIPLINES, BUT LOCATIONS
SHOWN ON OTHER DRAWINGS ARE SUBJECT TO COORDINATION WITH THE
ARCHITECTURAL DRAWINGS WHERE SUCH ITEMS ARE SHOWN, UNLESS OTHERWISE
NOTED ON THE ARCHITECTURAL DRAWINGS.
F. EXCEPT WHERE DIRECTED TO PLACE ITEMS OF WORK AT THE APPROXIMATE
LOCATION SHOWN, DO NOT SCALE DRAWINGS FOR DIMENSIONAL INFORMATION. NOT
ALL ELEMENTS OF THE DRAWINGS MAY BE DRAWN TO EXACT SCALE. ALL REQUIRED
DIMENSIONS ARE SHOWN OR MAY BE DERIVED FROM THOSE SHOWN ON THE
DRAWINGS, SCHEDULES AND SPECIFICATIONS. IF DIMENSIONS ARE NOT PRESENT, THE
ARCHITECT IS TO BE NOTIFIED SO THAT A CLARIFICATION CAN BE ISSUED. DIMENSIONS
ARE TO BE COORDINATED WITH ALL DISCIPLINES, VENDORS AND OWNER-FURNISHED
EQUIPMENT, FURNITURE AND DEVICES TO ASSURE PROPER PLACEMENT AND
WARRANTY REQUIREMENTS.
G. ALL CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES, ORDINANCES AND
REGULATIONS. SEE THE GI-SERIES SHEETS FOR PARTIAL REGULATORY INFORMATION,
INCLUDING CODE COMPLIANCE TABLES, RATED ASSEMBLY TYPES AND TYPICAL
ACCESSIBILITY CLEARANCE AND COMPLIANCE REQUIREMENTS.
H. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR
COMPATIBILITY WITH NEW CONSTRUCTION, AND COORDINATE ANY DISCREPANCIES
WITH THE ARCHITECT PRIOR TO PROCEEDING WITH AFFECTED WORK.
APPROVALS
Jonathan D. Butler, CFMO Manager Date
801.274.3950 :: structuralds.com
LANOISSEF
O
R P
ENG I N
E
E R
JACOB L.
MERKLEY
7937030
OETATS
F UTAH
06/18/2026
No.
8182456
TYLER
SQUIRE
L
IC
E N
S E D
PROFESS IONAL
E N G
I N E
E R
STATE OF UTAH
06/18/2026
P R
O
FESS IONA L ENG
IN
E
E R
S
T A T E O F UT A
H
No. 318584-2202
Michael E. Dallon
06/18/2026
MATCH LINE
A1 / Axxx
MATCH LINE TAG
EXISTING WALL TO REMAIN
WALL TO BE DEMOLISHED
NEW WALL
BREAK LINE
CENTER LINE SYMBOL
0' x' y' z'
REVISION DESIGNATION
ELEVATION SYMBOL
REVISION NUMBER
ELEVATION ABOVE DATUM
ELEVATION DESCRIPTION
DRAWING SYMBOL LEGEND
CASEWORK TYPE DESIGNATION
CDS NUMBER (M DENOTES
MODIFICATION - SEE SHEET
A551 FOR MODIFIED MILLWORK
ELEVATIONS AND DETAILS)
AWS STANDARD CDS NUMBERING SYSTEM
WIDTH
HEIGHT DEPTH
NORTH ARROW
PLAN NORTH
GRAPHIC SCALES
ROUND BREAK LINE
REVISION CLOUD
SLOPE INDICATION
##" / 12"
DETAIL REFERENCE
A2 A401
A1
A3
INTERIOR ELEVATIONS
DETAIL NUMBER
SHEET NUMBER
A1 A501
DETAIL REFERENCE
DETAIL NUMBER
SHEET NUMBER
A1 A201
EXTERIOR ELEVATION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1 A302
WALL SECTION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1 A301
BUILDING SECTION REFERENCE
DETAIL NUMBER
SHEET NUMBER
ROOM DESIGNATION (FLOOR PLAN)
ROOM NUMBER
ROOM NAME
A1 A301
DETAIL NUMBER
SHEET NUMBER
ROOM DESIGNATION (REFLECTED
CEILING PLAN)
CEILING HEIGHT ABOVE FINISH FLOOR
ROOM NUMBER
GLASS TYPE DESIGNATION
KEYED NOTE DESIGNATION
ASSEMBLY TYPE DESIGNATION
EQUIPMENT DESIGNATION
WINDOW DESIGNATION
DOOR DESIGNATION
GLASS TYPE
EQUIPMENT NAME
KEY NOTE NUMBER
WINDOW TYPE
DOOR NUMBER
ASSEMBLY TYPE (FLOOR, WALL, CEILING, ROOF)
MATERIAL TYPE DESIGNATION
FINISH TYPE
SEE AI601 FINISH LEGEND
RISE
RUN
TRUE NORTH
CL
DETAIL / SHEET NUMBER
Room Name
EQUIPMENT MARK#####
DESCRIPTION
100'-0"
T.O. WALL
###M #W
#H
#D
MODIFICATION DESCRIPTION
xx" = 1'-0" GRAPHIC SCALE
A1 A301
12"
LIST OF ABBREVIATIONS
THE PRECEDING LIST OF ABBREVIATIONS
IS PRESENTED AS A GENERAL GUIDE AND
DOES NOT NECESSARILY SHOW ALL
ABBREVIATIONS USED. OTHER
GENERALLY ACCEPTED ABBREVIATIONS
MAY BE FOUND AMONG THE DRAWINGS -
SOME ABBREVIATIONS SHOWN ABOVE
MAY NOT BE USED WITHIN THIS DRAWING
SET.
A
A/C AIR CONDITIONING
ACT ACOUSTICAL CEILING TILE
APC ACOUSTICAL PANEL CEILING
AD AREA DRAIN
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALUM ALUMINUM
ANOD ANODIZED
ARCH ARCHITECT
@ AT
B
BD BOARD
BLDG BUILDING
BO BOTTOM OF
C
C CELSIUS
CH COAT HOOK
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CG CORNER GUARD
CI CONTINUOUS INSULATION
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CT CERAMIC TILE
CTJ CONSTRUCTION JOINT
D
D DEEP
DEG DEGREE
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
DWGS DRAWINGS
E
(E) EXISTING
EA EACH
EJ EXPANSION JOINT
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EOS EDGE OF SLAB
ERD EXISTING ROOF DRAIN
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
F
F FAHRENHEIT
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FDC FIRE DEPARTMENT CONNECTION
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FE FIRE EXTINGUISHER
FE FINISHED EDGE
FG FINISH GRADE
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FND FOUNDATION
FO FINISHED OPENING
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FRG FIBER REINFORCED GYPSUM
FSP FIRE STANDPIPE
FT FEET
FV FIELD VERIFY
G
GA GAUGE
GALV GALVANIZED
GFRC GLASS-FIBER-REINFORCED
CONCRETE
GFRG GLASS-FIBER-REINFORCED GYPSUM
GL GLASS
GWB GYPSUM WALL BOARD
GYP GYPSUM
H
H HIGH
HB HOSE BIBB
HDR HEADER
HM HOLLOW METAL
HR HOUR
HT HEIGHT
I
ID INSIDE DIAMETER; INSIDE DIMENSION
IN INCH
INFO INFORMATION
INT INTERIOR
J
JAN JANITOR
K (NOT USED)
L
LAB LABORATORY
LAV LAVATORY
LBS POUNDS
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
M
MACH RM MACHINE ROOM
MAX MAXIMUM
MFR MANUFACTURER
MECH MECHANICAL
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
N
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER;
OUTSIDE DIMENSION
OFD OVERFLOW DRAIN
OH DR OVERHEAD DOOR
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OPH OPPOSITE HAND
OPP OPPOSITE
OFOI OWNER FURNISHED, OWNER INSTALLED
ORIG ORIGINAL
P
P LAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PR PAIR
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
Q
QT QUARRY TILE
R
R RISER
RAD RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIDGERATOR
REQD REQUIRED
REV REVISION
RH RELATIVE HUMIDITY
RM ROOM
RO ROUGH OPENING
RTU ROOF TOP UNIT
RWL RAIN WATER LEADER
S
S SMOKE DETECTOR
SAM SELF ADHESIVE MEMBRANE
SCHED SCHEDULE
SECT SECTION
SIM SIMILAR
SPEC SPECIFICATION
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
T
T TREAD
TEL TELEPHONE
TEMP TEMPORARY
THK THICK
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF SLAB; TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
TO TOP OF
U
UL UNDERWRITER'S LABORATORIES
UNO UNLESS NOTED OTHERWISE
V
VCT VINYL COMPOSITE TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W
W/ WITH
W/O WITHOUT
WD WOOD
WH WALL HYDRANT
WP WORKING POINT
WRB WEATHER RESISTIVE BARRIER
X,Y,Z (NOT USED)
CAST-IN-PLACE CONCRETE
CONCRETE MASONRY UNIT
PRECAST CONCRETE / GLASS FIBER
REINFORCED CONCRETE (GFRC)
BRICK VENEER
RIGID INSULATION
BATT INSULATION
CONTINUOUS MATERIAL
NON CONTINUOUS MATERIAL
(BLOCKING)
GYPSUM BOARD
PLYWOOD
UNDISTURBED EARTH
GRAVEL
HATCH LEGEND
NOTE: HATCHING ANGLES MAY VARY DUE TO ANGLE OF WALL DRAWN, WHILE HATCHING PATTERN REMAINS SIMILAR.
BACKFILL OR FILL
EXTERIOR SHEATHING
RECEPTACLE
OUTLET
UNOBSTRUCTED
THERMOSTAT
UNOBSTRUCTED
SWITCH
RECEPTACLES AND SWITCH MOUNTING HEIGHTS
UNOBSTRUCTED FIRE
ALARM PULL BOX
"M
IN
.36
"M
IN
"M
AX
"M
AX
FIRE EXTINGUISHER
A. DETAILS AND DIAGRAMS ON THIS SHEET ARE
PROVIDED AS A MINIMUM DEMONSTRATION OF
ACCESSIBILITY REQUIREMENTS BASED ON THE 2009
ICC / ANSI A117.1 STANDARDS. SEE THE
AFOREMENTIONED STANDARD FOR A
COMPREHENSIVE COLLECTION OF DETAILS AND
BUILDING BLOCKS. SEE PROJECT SPECIFIC DETAILS
FOR ADDITIONAL INFORMATION. VERIFY WITH
ARCHITECT ANY DIFFERENCES OR DISCREPANCIES
BEFORE PROCEEDING WITH CONSTRUCTION.
B. PROVIDE BACKING / SUPPORT FOR ALL MOUNTED
FIXTURES, AND/OR EQUIPMENT. COORDINATE WITH
FLOOR PLANS, AND INTERIOR ELEVATIONS. REFER TO
MANUFACTURER'S RECOMMENDATIONS WHERE
APPLICABLE.
C. DO NOT SCALE DRAWINGS.
GENERAL NOTES - ACCESSIBILITY
T
CR H IT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
06-18-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:1
:3
P M
A u to d e sk
D o c s:
U T
N G
C W
W a sh R a c k _r
/A R
C H
_2
-U
T N
G C
W W a sh
R a c k
_2
.r v t
GENERAL
INFORMATION
AN
S R
E D
W O
O D
R D
(A T
C O
R N
E R
O F
M A
IN
T
E N
A N
C E
A V
E
S
U P
P L
Y S
T
B L
U F
F D
A L
E U
T A
H
U T
A H
N A
T
IO
N A
L G
U A
R D
25061
06.18.2026
PERMIT SET
GI001
AN
C A
M P
W
IL
L
IA
M S
W A
S H
R A
C K
3/8" = 1'-0"GI001
A6 MISC. MOUNTING HEIGHTS
GENERAL:
GI000 COVER SHEET
GI001 GENERAL INFORMATION
GI101 CODE ANALYSIS
GI102 SPECIAL INSPECTIONS & TESTING
GI501 ASSEMBLY TYPES
CIVIL/SITE:
C001 GENERAL NOTES
C002 GENERAL NOTES
C100 DEMOLITION PLAN
C200 SITE PLAN
C300 GRADING PLAN
C301 DRAINAGE PLAN
C400 UTILITY PLAN
C401 SANITARY SEWER UTILITY PLAN
C500 EROSION CONTROL PLAN
C600 DETAILS
C601 DETAILS
C602 DETAILS
C603 PUMP DETAILS
C604 PUMP DETAILS
AS101 ARCHITECTURAL SITE PLAN
STRUCTURAL:
S001 GENERAL STRUCTURAL NOTES
S002 GENERAL STRUCTURAL NOTES
S101 FOOTING + FOUNDATION PLAN
S121 ROOF FRAMING PLAN
S301 STRUCTURAL SCHEDULES
S302 STRUCTURAL SCHEDULES
S501 STRUCTURAL DETAILS
S521 STRUCTURAL DETAILS
ARCHITECTURAL:
AC101 LEVEL 01 OVERALL SLAB CONTROL PLAN
AE101 LEVEL 01 OVERALL FLOOR PLAN & AXON
AE121 LEVEL 01 OVERAL RCP & ROOF PLAN
AE201 BUILDING ELEVATIONS & SECTIONS
AE501 ARCHITECTURAL PLAN DETAILS
AE601 DOOR SCHEDULE AND DETAILS
MECHANICAL:
M001 MECHANICAL LEGEND, SYMBOLS & ABBREVIATIONS
MH101 LEVEL 1 MECHANICAL PLANS BASE & ABI 2
MH501 MECHANICAL DETAILS
MH601 MECHANICAL SCHEDULES
MP101 LEVEL 1 PIPING PLANS BASE & ABI 1
PLUMBING:
P001 PLUMBING LEGEND, SYMBOLS, ABBREVIATIONS, & SCHEDULES
PL101 UNDERGROUND & LEVEL 1 PLUMBING PLANS BASE & ABI 2
PL501 PLUMBING DETAILS ANS SCHEDULES
ELECTRICAL:
E-001 ELECTRICAL LEGEND, SYMBOLS & ABBREVIATIONS
ED100 ELECTRICAL DEMO SITE
ES100 ELECTRICAL SITE
EP101 LEVEL 1 POWER PLANS BASE & ABI 2
EL101 LEVEL 1 LIGHTING PLANS BASE & ABI 2
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES
E-701 ELECTRICAL ONE-LINES
SHEET INDEX
# Date Revision
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)______
1) One Story: ______
c) Total Allowable Area for:
1_< Allowable Area
Actual Area
b) Sum of the Ratio Calculations for Mixed Occupancies:
a)
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
e) Drinking Fountains: ______ Service Sinks: ______
d) Bath Tubs or Showers: ______
c) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: __________ Exit Width Provided: ____________
Element Hours Assembly
ListingListing Element
Assembly Hours
Smoke Partitions
Fire Partitions
Exterior Bearing Walls
Interior Bearing Walls
Exterior Non-Bearing Walls
Structural Frame
Partitions - Permanent
Fire Barriers
Floors - Ceiling Floors
Roofs - Ceiling Roofs
Exterior Doors and Windows
Shaft Enclosures
Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: __________________________________
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
Tabular Area:I:
per Floor (square feet): ____________________________________Actual AreaH:
Number of Stories: ______ Building Height: ______G:
Required: ______ Provided: ______
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guildelines
ADA Accessibility
Building Conservation
Uniform Code for
National Electrical Code
Conservation Code
International Energy
International Fire Code
International Plumbing Code
International Mechanical Code
International Building Code
A. Occupancy and Group: ________ ________ ________ ________ ________
International Fuel Gas Code
Type of Sprinkler System (IBC 903.3.1)__________________
0.25I =f F P 30W
b) Urinals - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
(table 503): ____________________________________________
CODE ANALYSIS
APPLICABLE CODES
Year Year
528 SF
PUMP HOUSE
5809 SF
WASH RACK
EXIT ACCESS TRAVEL DISTANCE PER
TABLE 1017.2, WITHOUT SPRINKLERS:
OCCUPANCY
MAX. TRAVEL
DISTANCE
UTILITY / MISC. SERVICES (U) 300'
TRAVEL DISTANCE
COMMON PATH OF TRAVEL
COMMON PATH OF TRAVEL DISTANCE PER
TABLE 1006.2.1, WITHOUT SPRINKLERS:
OCCUPANCY
MAX. TRAVEL
DISTANCE
UTILITY / MISC. SERVICES 75'
PATH OF TRAVEL
EGRESS
NUMBER OF OCCUPANTS PER
EXIT/EGRESS PATH
OCCUPANCY TAG
ROOM NAME
Name
000 SF
A-3 000
ROOM AREA
OCCUPANCY TYPE
OCCUPANCY LOAD FACTOR
PER TABLE 1004.5 / 1004.6
OCCUPANT LOAD
FIRE EXTINGUISHERS
COORDINATE TYPE AND LOCATION
WITH LOCAL FIRE MARSHALL
FE
FIRE EXTINGUISHER; CLASS A-B-C
FEC
FIRE EXTINGUISHER CABINET; CLASS A-B-C
(UTNG CW WASH RACK)
ICC/ANSI A117.1-2009
N/A
X X
N/A
D 105
NO
WASH RACK: 13,872 SF | PUMP HOUSE: 11,858 SF
N/A
N/A
NO NO
X
Utah Amendments, Title 15A Current
0 0 0 0
N/A
OTHER CRITERIA
DFCM DESIGN CRITERIA AND GUIDELINES AND GENERAL CONDITIONS
NOTE: THESE DRAWINGS COMPLY WILL ALL THE REQUIREMENTS OF THE DFCM DESIGN CRITERIA AND GUIDELINES
NOTE: THESE DRAWINGS COMPLY WITH THE UTNG CONSTRUCTION GUIDELINES
NO
U
1 25'-0"
N/A N/A
N/A
N/A
N/A N/A N/A
N/A
N/A
WASH RACK: 5,809 SF | PUMP HOUSE: 528 SF
8,500 SF
(table 506.2)
WASH RACK
Aa = 8,500 + (8,500 x .632) Aa = 13,872 SF
WASH RACK
lf = [269 / 305 - 0.25] (30/30) lf = 0.632
Aa = At + (NS x lf)
PUMP HOUSE
lf = [65.3 / 101.3 - 0.25] (30/30) lf = 0.395
PUMP HOUSE
Aa = 8,500 + (8,500 x .395) Aa = 11,858 SF
A. SEE WALL TYPES ON FLOOR PLANS AND RATED WALL
ASSEMBLIES IN GI500s SHEET SERIES FOR SPECIFIC
WALL CONSTRUCTION TO ACHIEVE THE RATINGS
SHOWN ON THIS PLAN.
GENERAL NOTES - REGULATORY PLANS
NONSTRUCTURAL COMPONENT CHECKLIST
ITEM DESCRIPTION
ON CONSTR.
DOCUMENTS
DEFERRED
SUBMITTAL COMMENTS
ARCHITECTURAL COMPONENTS:
NONE
MEP COMPONENTS:
MECHANICAL EQUIPMENT (I.E. HVAC, FANS,
AIR HANDLERS, BOILERS, FURNACES, TANKS,
CHILLERS, WATER HEATERS, HEAT
EXCHANGERS, EVAPORATORS, ENGINES,
TURBINES, PUMPS, COMPRESSORS, MFR
EQUIPMENT, ETC.)
ELECTRICAL EQUIPMENT (I.E. GENERATORS,
BATTERIES, INVERTERS, TRANSFORMERS, MCC,
PANEL BOARDS, SWITCH GEAR, CABINETS,
ETC.)
LIGHTING FIXTURES
PIPING & CONDUIT SYSTEMS
NOTES:
1. Deferred submittals for seismic restraint of nonstructural components must be submitted to the DFCM Building Official a minimum of two weeks prior to the planned installation in order to allow for plan review and forwarding to inspectors. In the event that the submittal is deficient additional time may become necessary.
2. When seismic restraint of non-structural components is installed prior to receiving DFCM approval it shall not be covered or concealed until receiving both plan review and inspection approval. Further, installers are proceeding at their own risk until plan review and inspection approval occurs.
3. The requirements for seismic restraint of nonstructural components cannot be satisfied by a general reference to Design Manuals.
The design professional may utilize these manuals as a basis of their design, but must provide all supporting documentation to ensure that the design conforms to the requirements of ASCE 7-05, Chapter 13.
4. Submittals must include details of the proposed seismic restraint of nonstructural components. These details must show specific information relating to the materials, type, size, and locations of anchorages; materials used for bracing; attachment requirements of bracing to structure and component; and locations of transverse and longitudinal sway bracing and rod stiffeners. Submittals may also require structural calculations, engineering reports, test data, and/or specifications to ensure code compliance.
T
CR H IT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
06-18-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:1
:3
P M
A u to d e sk
D o c s:
U T
N G
C W
W a sh R a c k _r
/A R
C H
_2
-U
T N
G C
W W a sh
R a c k
_2
.r v t
CODE ANALYSIS
CG
S R
E D
W O
O D
R D
(A T
C O
R N
E R
O F
M A
IN
T
E N
A N
C E
A V
E
S
U P
P L
Y S
T
B L
U F
F D
A L
E U
T A
H
U T
A H
N A
T
IO
N A
L G
U A
R D
25061
06.18.2026
PERMIT SET
GI101
SS
C A
M P
W
IL
L
IA
M S
W A
S H
R A
C K
1/8" = 1'-0"GI101
A6 LEVEL 01 - AREA PLAN
EGRESS PATH LENGTHS
PATH #
COMMON PATH
OF TRAVEL
LONGEST PATH
OF TRAVEL
TAG DESCRIPTION #
FE CLASS A-B-C; SURFACE MOUNT 1
T
CR H IT
E
A
IC
E
L
N S E D
C
O UT
HS
TE
TA
F A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
06-18-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:2
:3
P M
A u to d e sk
D o c s:
U T
N G
C W
W a sh R a c k _r
/A R
C H
_2
-U
T N
G C
W W a sh
R a c k
_2
.r v t
SPECIAL
INSPECTIONS &
TESTING
CG
S R
E D
W O
O D
R D
(A T
C O
R N
E R
O F
M A
IN
T
E N
A N
C E
A V
E
S
U P
P L
Y S
T
B L
U F
F D
A L
E U
T A
H
U T
A H
N A
T
IO
N A
L G
U A
R D
25061
06.18.2026
PERMIT SET
GI102
SS
C A
M P
W
IL
L
IA
M S
W A
S H
R A
C K
A. WALL HEIGHT: ALL NEW INTERIOR WALL ASSEMBLIES ARE
CONTINUOUS TO BOTTOM OF DECK UNLESS NOTED OTHERWISE.
REFER TO THE LEGENDS ON THIS SHEET AND COORDINATE WITH
PLANS.
B. BACKING / SUPPORT: WALL TYPES DESCRIBED ON THIS SHEET DO
NOT ACCOUNT FOR REQUIRED BACKING. CONTRACTOR TO
PROVIDE BACKING / SUPPORT FOR ALL MOUNTED FIXTURES,
EQUIPMENT, ETC. REFER TO MANUFACTURER'S
RECOMMENDATIONS WHERE APPLICABLE.
C. STRUCTURAL SHEATHING: REFER TO STRUCTURAL DRAWINGS FOR
STRUCTURAL SHEATHING REQUIREMENTS AND ATTACHMENTS.
D. SEISMIC BRACING: PROVIDE SEISMIC BRACING AT ALL WALL TYPES
THAT DO NOT EXTEND TO DECK.
E. PENETRATIONS: PENETRATIONS SHALL HAVE A FINISHED
APPEARANCE WITH APPROPRIATE TRIMS AND ESCUTCHEONS.
F. LISTED ASSEMBLIES: RATED ASSEMBLIES PROVIDED PER G500s
SHEET SERIES.
G. INFORMATION IN THE LEGENDS BELOW IS FOR REFERENCE ONLY
AND DOES NOT OVERRIDE THE CONTENTS OF THE DETAILS ON THIS
SHEET.
H. DO NOT SCALE DRAWINGS.
GENERAL NOTES -
WALL TYPE ASSEMBLIES
XS#1.1
PREFIX: 'X' FOR EXTERIOR CORE WALL
CONSTRUCTION TYPE (SEE BELOW)
STRUCTURE THICKNESS (TO NEAREST No.)
FIRE RATING (AS NEEDED, SEE BELOW)
EXTERIOR WALL TAG LEGEND
CONSTRUCTION TYPES
CONCRETE C
MASONRY M
STEEL STUDS S
C-H (SHAFTWALL) STUD H
WOOD STUDS W
TOP OF WALL MODIFIERS
(U) = UNDERSIDE / BOTTOM OF CEILING
WALL EXTENDS TO UNDERSIDE OF
CEILING. TERMINATE WITH "J" MOULD AT
GYP. BOARD WALLS.
EXAMPLE
LINE OF STRUCTURE ABV. TYP.
CEILING, TYP.
SUBSTRATE, TYP.
FIRE RATING
1 HOUR 1
2 HOUR 2
3 HOUR 3
4 HOUR 4
NO RATING NOT SHOWN
TYPE (AS NEEDED)
(C) = 6" ABOVE CEILING
WALLS WILL TERMINATE AT 6" ABOVE THE HIGHEST
ADJOINING CEILING (UNLESS OTHERWISE NOTED)
OR 1 FULL COURSE ABOVE FOR MASONRY WALLS.
(H) = PARTIAL HEIGHT
REFER TO DRAWINGS FOR TOP OF
WALL ELEVATION
(S) = ONE SUBSTRATE TO STRUCTURE
SUBSTRATE BOARD WILL TERMINATE TO BOTTOM
OF DECK ON ONE SIDE AND THE OTHER SIDE SHALL
TERMINATE AT 6" ABOVE ADJOINING CEILING
(UNLESS OTHERWISE NOTED). TERMINATE 1 FULL
COURSE ABOVE FOR MASONRY WALLS.
(N) = NO SUBSTRATES TO STRUCTURE
SUBSTRATE BOARDS WILL TERMINATE AT 6" ABOVE
ADJOINING CEILING (UNLESS OTHERWISE NOTED)
OR 1 FULL COURSE ABOVE FOR MASONRY WALLS.
BRACING, TYP.
DETAILS PROVIDED PER A700s SHEET SERIES.
STUDS, TYP.
6" A
BV
6"
A
BV
6" A
BV
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
C# N/A N/A N/A N/A
CAST-IN-PLACE CONCRETE WALL;
COORDINATE WITH STRUCTURAL
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
M8 N/A N/A N/A N/A
CONCRETE MASONRY UNIT. SEE
STRUCTURAL FOR SIZE
C8 = 8" C12 = 12" C24 = 24"
FLOOR TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
N/A
N/A
N/A N/AFG#
CAST-IN-PLACE CONCRETE;
COORDINATE WITH STRUCTURAL
COMPACTED GRAVEL SUB-BASE
VA
R
IE
S
AND/OR CIVL
FG5 = 5"
FG8 = 8"
FG8.5 = 8.5"
ROOF TYPE:
FIRE RATING:
SOUND RATING: TEST:RS3 N/A
N/A N/A
ROOF TYPE:
FIRE RATING:
SOUND RATING: TEST:RS2 N/A
N/A N/A
STANDING SEAM METAL ROOF.
COLOR: COLONIAL RED
PEMB MAIN FRAME
PEMB PERLIN
STANDING SEAM METAL ROOF.
COLOR: COLONIAL RED
SELF ADHERED HIGH-TEMP ICE &
WATER SHIELD
1/2" COVER BOARD
METAL DECK; COORDINATE WITH
STRUCTURAL
STEEL BEAM. COORDINATE WITH
STRUCTURAL
A. REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL DECKING
REQUIREMENTS AND ATTACHMENTS.
B. INFORMATION SUPPLIED ON THIS SHEET IS SUPPLIED AS A BASE
CASE AND IS SUPERCEDED BY LOCATION SPECIFIC DETAIL
DRAWINGS.
C. ALL FIRE RATED ASSEMBLIES TO BE CONTINUOUS; FIRE CAULK
AND/OR FIRE SAFING TO BE PROVIDED AT ALL ASSEMBLY
TERMINATIONS.
D. ALL EXPOSED INTERIOR CONCRETE IS TO BE SEALED UNLESS
NOTED OTHERWISE.
E. INFORMATION IN THE LEGEND BELOW IS FOR REFERENCE ONLY
AND DOES NOT OVERRIDE THE CONTENTS OF THE DETAILS ON
THIS SHEET.
F. DO NOT SCALE DRAWINGS.
GENERAL NOTES -
HORIZONTAL ASSEMBLIES
RC#1.1
PREFIX: 'R' FOR ROOF
CONSTRUCTION TYPE (SEE BELOW)
STRUCTURE THICKNESS (TO NEAREST No.)
FIRE RATING (AS NEEDED, SEE BELOW)
ROOF TAG LEGEND
CONSTRUCTION TYPES
COMPOSITE CONC. C
STEEL DECK S
WOOD JOIST / TRUSS W
POST-TENSIONED CONC. P
CONC. WAFFLE SLAB F
FIRE RATING
TYPE (AS NEEDED)
FC#2.1
PREFIX: 'F' FOR FLOOR
CONSTRUCTION TYPE (SEE BELOW)
STRUCTURE THICKNESS (TO NEAREST No.)
FIRE RATING (AS NEEDED, SEE BELOW)
FLOOR TAG LEGEND
CONSTRUCTION TYPES
CONCRETE C
CONCRETE, S.O.G G
CONCRETE PAD P
STEEL JOIST / TRUSS S
WOOD JOIST / TRUSS W
METAL DECK W/ SUBSTRATE D
FIRE RATING
TYPE (AS NEEDED)
1 HOUR 1
2 HOUR 2
3 HOUR 3
4 HOUR 4
NO RATING NOT SHOWN
1 HOUR 1
2 HOUR 2
3 HOUR 3
4 HOUR 4
NO RATING NOT SHOWN
T
CR H IT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
06-18-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:1
:4
P M
A u to d e sk
D o c s:
U T
N G
C W
W a sh R a c k _r
/A R
C H
_2
-U
T N
G C
W W a sh
R a c k
_2
.r v t
ASSEMBLY
TYPES
CG
S R
E D
W O
O D
R D
(A T
C O
R N
E R
O F
M A
IN
T
E N
A N
C E
A V
E
S
U P
P L
Y S
T
B L
U F
F D
A L
E U
T A
H
U T
A H
N A
T
IO
N A
L G
U A
R D
25061
06.18.2026
PERMIT SET
GI501
SS
C A
M P
W
IL
L
IA
M S
W A
S H
R A
C
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D
FC
M P
R O
JE
C
T N
O . 2
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
BP
25061
06.18.2026
KM
# Date Revision
BENCHMARK
SURVEY MONUMENT IN CAMP WILLIAMS
ENTRANCE ROAD, SECTION 34, TOWNSHIP 4
SOUTH, RANGE 1 WEST,
SALT LAKE BASE AND MERIDIAN
BENCHMARK ELEVATION = 4833.50
WWW.ENSIGNENG.COM
SANDY
45 W 10000 S, Suite 500 Sandy, UT 84070 Phone: 801.255.0529
LAYTON
Phone: 801.547.1100
TOOELE
Phone: 435.843.3590
CEDAR CITY
Phone: 435.865.1453
RICHFIELD
Phone: 435.896.2983
ENSIGN PROJECT #14497
CALL BLUESTAKES
@ 811 AT LEAST 48 HOURS
PRIOR TO THE
COMMENCEMENT OF ANY
CONSTRUCTION.
Know what'sbelow.
before you dig.Call
R
S
R
ED
W O
O D
R D
(A T
C O
R N
ER
O
F M
A
IN
TE
N
A N
C E
A
VE
S
U
PP
LY
S
T.
B
LU
FF
D
A
LE
, U
TA
H
PERMIT SET
U
TA
H N
A
TI
O N
A L
G U
A R
D
C A
M P
W
IL
LI
A
M S
W A
SH
R
A C
K
GENERAL
NOTES
C001
ABBREVIATIONS
NOTE: MAY CONTAIN ABBREVIATIONS THAT ARE NOT USED IN THIS PLAN SET.
1. ALL CONSTRUCTION MUST STRICTLY FOLLOW THE STANDARDS AND SPECIFICATIONS SET FORTH BY: DFCM, UNIFIED FACILITIES CRITERIA (UFC), 2018 IBC, 2020 NEC, ANSI, THE DESIGN ENGINEER, UTNG CONSTRUCTION GUIDELINES, APWA, AND THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (M.U.T.C.D.). THE ORDER LISTED ABOVE IS ARRANGED BY SENIORITY. THE LATEST EDITION OF ALL STANDARDS AND SPECIFICATIONS MUST BE ADHERED TO. IF A CONSTRUCTION PRACTICE IS NOT SPECIFIED BY ANY OF THE
LISTED SOURCES, CONTRACTOR MUST CONTACT DESIGN ENGINEER FOR DIRECTION.
2. CONTRACTOR TO STRICTLY FOLLOW THE MOST CURRENT COPY OF THE SOILS REPORT FOR THIS PROJECT. ALL GRADING INCLUDING BUT NOT LIMITED TO CUT, FILL, COMPACTION, ASPHALT SECTION, SUBBASE, TRENCH EXCAVATION/BACKFILL, SITE
GRUBBING, AND FOOTINGS MUST BE COORDINATED DIRECTLY WITH SOILS REPORT.
3. CONTRACTOR MUST VERIFY ALL EXISTING CONDITIONS BEFORE BIDDING, AND BRING UP ANY QUESTIONS BEFORE SUBMITTING BID.
4. CONTRACTOR SHALL PROVIDE A CONSTRUCTION SCHEDULE IN ACCORDANCE WITH THE CITY, STATE, OR COUNTY REGULATIONS FOR
WORKING IN THE PUBLIC WAY.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR DUST CONTROL ACCORDING TO GOVERNING AGENCY STANDARDS. WET DOWN DRY
MATERIALS AND RUBBISH TO PREVENT BLOWING.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO ADJACENT SURFACE IMPROVEMENTS.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTING ANY SETTLEMENT OF OR DAMAGE TO EXISTING UTILITIES.
8. THE CONTRACTOR IS RESPONSIBLE TO FURNISH ALL MATERIALS TO COMPLETE THE PROJECT.
9. UNLESS OTHERWISE NOTED, ALL ON-GRADE CONCRETE WILL BE PLACED ON A MINIMUM 4" GRAVEL BASE OVER A WELL COMPACTED
(95 % DENSITY PER ASTM D-1557) SUB GRADE.
10. ALL EXPOSED SURFACES WILL HAVE A TEXTURED FINISH, RUBBED, OR BROOMED. ANY "PLASTERING" OF NEW CONCRETE WILL BE
DONE WHILE IT IS STILL "GREEN".
11. PRIOR TO STARTING CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL REQUIRED PERMITS AND APPROVALS HAVE BEEN OBTAINED. NO CONSTRUCTION OR FABRICATION SHALL BEGIN UNTIL THE CONTRACTOR HAS RECEIVED AND THOROUGHLY REVIEWED ALL PLANS AND OTHER DOCUMENTS APPROVED BY ALL OF THE PERMITTING AUTHORITIES.
12. THE LOCATIONS OF UNDERGROUND FACILITIES SHOWN ON THESE PLANS ARE BASED ON FIELD SURVEYS AND LOCAL UTILITY COMPANY RECORDS. IT SHALL BE THE CONTRACTOR'S FULL RESPONSIBILITY TO CONTACT THE VARIOUS UTILITY COMPANIES TO LOCATE THEIR FACILITIES PRIOR TO PROCEEDING WITH CONSTRUCTION. NO ADDITIONAL COMPENSATION SHALL BE PAID TO THE CONTRACTOR FOR DAMAGE AND REPAIR TO THESE FACILITIES CAUSED BY HIS WORK FORCE. CONTRACTOR SHALL START
INSTALLATION AT LOW POINT OF ALL NEW GRAVITY UTILITY LINES.
13. ALL DIMENSIONS, GRADES, AND UTILITY DESIGN SHOWN ON THE PLANS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO CONSTRUCTION. CONTRACTOR SHALL NOTIFY THE ENGINEER IF ANY DISCREPANCIES EXIST, PRIOR TO PROCEEDING WITH CONSTRUCTION FOR NECESSARY PLAN OR GRADE CHANGES. NO EXTRA COMPENSATION SHALL BE PAID TO THE CONTRACTOR FOR WORK HAVING TO BE REDONE DUE TO THE DIMENSIONS OR GRADES SHOWN INCORRECTLY ON THESE PLANS, IF SUCH
NOTIFICATION HAS NOT BEEN GIVEN.
14. NO CHANGE IN DESIGN LOCATION OR GRADE WILL BE MADE BY THE CONTRACTOR WITHOUT THE WRITTEN APPROVAL OF THE
PROJECT ENGINEER.
15. NATURAL VEGETATION AND SOIL COVER SHALL NOT BE DISTURBED PRIOR TO ACTUAL CONSTRUCTION OF A REQUIRED FACILITY OR IMPROVEMENT. MASS CLEARING OF THE SITE IN ANTICIPATION OF CONSTRUCTION SHALL BE AVOIDED.
16. CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING, MAINTAINING, OR RESTORING ALL MONUMENTS AND MONUMENT REFERENCE MARKS WITHIN THE PROJECT SITE. CONTACT THE CITY OR COUNTY SURVEYOR FOR MONUMENT LOCATIONS AND
CONSTRUCTION DETAILS.
17. EXISTING UTILITY INFORMATION SHOWN IS FOR INFORMATIONAL PURPOSES ONLY. IT IS DERIVED FROM ON-SITE SURVEY AND/OR UTILITY MAPPING PROVIDED TO THE ENGINEER, AND THEREFORE UTILITIES MAY NOT BE LOCATED CORRECTLY, EITHER HORIZONTALLY OR VERTICALLY, AND MAY NOT BE ALL INCLUSIVE. CONTRACTOR IS REQUIRED TO FOLLOW THE PROCEDURE
OUTLINED BELOW:
17.1. CONTRACTOR IS REQUIRED TO LOCATE AND POTHOLE ALL EXISTING UTILITY LINES (BOTH HORIZONTALLY AND VERTICALLY) THAT AFFECT THE PROJECT CONSTRUCTION, EITHER ON-SITE OR OFF-SITE, AND DETERMINE IF THERE ARE ANY CONFLICTS WITH THE DESIGN OF THE SITE AS SHOWN ON THE APPROVED PLANS PRIOR TO ANY CONSTRUCTION. IF IT IS DETERMINED THAT CONFLICTS EXIST BETWEEN EXISTING UTILITIES AND DESIGN UTILITIES (OR ANOTHER ASPECT OF PROPOSED CONSTRUCTION) THE ENGINEER MUST BE NOTIFIED IMMEDIATELY TO CORRECT THE CONFLICTS BEFORE ANY WORK CAN BEGIN.
IF THE CONTRACTOR FAILS TO FOLLOW THIS ABSOLUTE REQUIREMENT AND CONFLICTS ARISE DURING CONSTRUCTION THE
CONTRACTOR WILL BEAR THE SOLE RESPONSIBILITY TO FIX THE CONFLICTS.
17.2. CONTRACTOR IS REQUIRED TO VERIFY THAT PROPER COVER AND PROTECTION OF EXISTING UTILITY LINES IS MAINTAINED OR ATTAINED WITHIN THE DESIGN ONCE VERIFICATION OF THE EXISTING UTILITIES IS COMPLETED AS OUTLINED IN 16.1 ABOVE.
17.3. IN ADDITION TO 16.1 AND 16.2 ABOVE THE CONTRACTOR WILL VERIFY DEPTHS OF UTILITIES IN THE FIELD BY "POTHOLING" A MINIMUM OF 300 FEET AHEAD OF PROPOSED PIPELINE CONSTRUCTION TO AVOID POTENTIAL CONFLICTS WITH DESIGNED
PIPELINE ALIGNMENT AND GRADE AND EXISTING UTILITIES.
17.4. IF A CONFLICT ARISES BETWEEN EXISTING UTILITIES AND DESIGN UTILITIES (OR ANOTHER ASPECT OF PROPOSED CONSTRUCTION) AS DETERMINED UNDER 16.1, 16.2 OR 16.3 THE CONTRACTOR WILL NOTIFY THE ENGINEER IMMEDIATELY TO
RESOLVE THE CONFLICT.
17.5. IF A CONFLICT ARISES BETWEEN EXISTING UTILITIES AND DESIGN UTILITIES (OR ANOTHER ASPECT OF PROPOSED CONSTRUCTION) RESULTING FROM THE CONTRACTOR'S NEGLIGENCE TO IDENTIFY AND/OR “POTHOLE” EXISTING UTILITIES AS REQUIRED IN 16.1, 16.2 AND 16.3 ABOVE, THE CONTRACTOR WILL BE REQUIRED TO RESOLVE THE CONFLICT WITHOUT
ADDITIONAL COST OR CLAIM TO THE OWNER OR ENGINEER.
18. ANY AREA OUTSIDE THE LIMIT OF WORK THAT IS DISTURBED SHALL BE RESTORED TO ITS ORIGINAL CONDITION AT NO COST TO
OWNER.
19. CONSULT ALL OF THE DRAWINGS AND SPECIFICATIONS FOR COORDINATION REQUIREMENTS BEFORE COMMENCING CONSTRUCTION.
20. AT ALL LOCATIONS WHERE EXISTING PAVEMENT ABUTS NEW CONSTRUCTION, THE EDGE OF THE EXISTING PAVEMENT SHALL BE
SAWCUT TO A CLEAN, SMOOTH EDGE.
21. ALL CONSTRUCTION AND MATERIALS SHALL BE IN ACCORDANCE WITH THE MOST RECENT, ADOPTED EDITION OF ADA ACCESSIBILITY
GUIDELINES.
22. CONTRACTOR SHALL, AT THE TIME OF BIDDING AND THROUGHOUT THE PERIOD OF THE CONTRACT, BE LICENSED IN THE STATE OF
UTAH AND SHALL BE BONDABLE FOR AN AMOUNT REQUIRED BY THE OWNER.
23. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE ALL WATER, POWER, SANITARY FACILITIES AND TELEPHONE SERVICES AS
REQUIRED FOR THE CONTRACTOR'S USE DURING CONSTRUCTION.
24. CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY SCHEDULING INSPECTION AND TESTING OF ALL FACILITIES CONSTRUCTED UNDER THIS CONTRACT. ALL TESTING SHALL CONFORM TO THE REGULATORY AGENCY'S STANDARD SPECIFICATIONS. ALL
RE-TESTING AND/OR RE-INSPECTION SHALL BE PAID FOR BY THE CONTRACTOR.
25. IF EXISTING IMPROVEMENTS NEED TO BE DISTURBED AND/OR REMOVED FOR THE PROPER PLACEMENT OF IMPROVEMENTS TO BE CONSTRUCTED BY THESE PLANS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING EXISTING IMPROVEMENTS FROM DAMAGE. COST OF REPLACING OR REPAIRING EXISTING IMPROVEMENTS SHALL BE INCLUDED IN THE UNIT PRICE BID FOR ITEMS REQUIRING REMOVAL AND/OR REPLACEMENT. THERE WILL BE NO EXTRA COST DUE TO THE CONTRACTOR FOR REPLACING OR
REPAIRING EXISTING IMPROVEMENTS.
26. WHENEVER EXISTING FACILITIES ARE REMOVED, DAMAGED, BROKEN, OR CUT IN THE INSTALLATION OF THE WORK COVERED BY THESE PLANS OR SPECIFICATIONS, SAID FACILITIES SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE WITH MATERIALS EQUAL TO OR BETTER THAN THE MATERIALS USED IN THE ORIGINAL EXISTING FACILITIES. THE FINISHED PRODUCT SHALL BE SUBJECT TO
THE APPROVAL OF THE OWNER, THE ENGINEER, AND THE RESPECTIVE REGULATORY AGENCY.
27. CONTRACTOR SHALL MAINTAIN A NEATLY MARKED SET OF FULL-SIZE RECORD DRAWINGS SHOWING THE FINAL LOCATION AND LAYOUT OF ALL STRUCTURES AND OTHER FACILITIES. RECORD DRAWINGS SHALL REFLECT CHANGE ORDERS, ACCOMMODATIONS, AND ADJUSTMENTS TO ALL IMPROVEMENTS CONSTRUCTED. WHERE NECESSARY, SUPPLEMENTAL DRAWINGS SHALL BE PREPARED AND SUBMITTED BY THE CONTRACTOR. PRIOR TO ACCEPTANCE OF THE PROJECT, THE CONTRACTOR SHALL DELIVER TO THE ENGINEER ONE SET OF NEATLY MARKED RECORD DRAWINGS SHOWING THE INFORMATION REQUIRED ABOVE. RECORD DRAWINGS SHALL BE REVIEWED AND THE COMPLETE RECORD DRAWING SET SHALL BE CURRENT WITH ALL CHANGES AND DEVIATIONS REDLINED AS A PRECONDITION TO THE FINAL PROGRESS PAYMENT APPROVAL AND/OR FINAL ACCEPTANCE.
28. WHERE THE PLANS OR SPECIFICATIONS DESCRIBE PORTIONS OF THE WORK IN GENERAL TERMS BUT NOT IN COMPLETE DETAIL, IT IS UNDERSTOOD THAT ONLY THE BEST GENERAL PRACTICE IS TO PREVAIL AND THAT ONLY MATERIALS AND WORKMANSHIP OF THE
FIRST QUALITY ARE TO BE USED.
29. CONTRACTOR SHALL PROVIDE ALL SHORING, BRACING, SLOPING OR OTHER PROVISIONS NECESSARY TO PROTECT WORKMEN FOR ALL AREAS TO BE EXCAVATED TO A DEPTH OF 4' OR MORE. FOR EXCAVATIONS 4 FEET OR MORE IN DEPTH, THE CONTRACTOR SHALL COMPLY WITH INDUSTRIAL COMMISSION OF UTAH SAFETY ORDERS SECTION 68 - EXCAVATIONS AND SECTION 69 - TRENCHES, ALONG
WITH ANY LOCAL CODES OR ORDINANCES.
30. ALL EXISTING GATES AND FENCES TO REMAIN UNLESS OTHERWISE NOTED ON PLANS. PROTECT ALL GATES AND FENCES FROM
DAMAGE.
31. ALL EXISTING TREES ARE TO REMAIN UNLESS OTHERWISE NOTED ON PLANS. PROTECT ALL TREES FROM DAMAGE.
32. ASPHALT MIX DESIGN MUST BE SUBMITTED AND APPROVED BY THE GOVERNING AGENCY PRIOR TO THE PLACEMENT.
33. CONTRACTORS ARE RESPONSIBLE FOR ALL OSHA REQUIREMENTS ON THE PROJECT SITE.
34. A UPDES (UTAH POLLUTANT DISCHARGE ELIMINATION SYSTEM) PERMIT IS REQUIRED FOR ALL CONSTRUCTION ACTIVITIES 1 ACRE OR
MORE AS WELL AS A STORM WATER POLLUTION PREVENTION PLAN.
1. EXISTING UTILITY INFORMATION SHOWN IS FOR INFORMATIONAL PURPOSES ONLY. IT IS DERIVED FROM ON-SITE SURVEY AND MAY NOT BE LOCATED CORRECTLY AND IS NOT ALL INCLUSIVE. CONTRACTOR SHALL FIELD LOCATE ALL UTILITIES
WITHIN THE PROJECT LIMITS BEFORE BEGINNING DEMOLITION/CONSTRUCTION.
2. THERE MAY BE BURIED UTILITIES WITHIN THE LIMITS OF DISTURBANCE THAT ARE NOT SHOWN ON THE PLANS DUE TO LACK OF MAPPING OR RECORD INFORMATION. CONTRACTOR SHALL NOTIFY THE ENGINEER WHEN UNEXPECTED UTILITIES ARE
DISCOVERED.
3. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR LOCATING AND PROTECTING FROM DAMAGE ALL EXISTING UTILITIES AND IMPROVEMENTS WHETHER OR NOT SHOWN ON THESE PLANS. THE FACILITIES AND IMPROVEMENTS ARE BELIEVED TO BE CORRECTLY SHOWN BUT THE CONTRACTOR IS REQUIRED TO SATISFY HIMSELF AS TO THE COMPLETENESS AND ACCURACY OF THE LOCATIONS. ANY CONTRACTOR PERFORMING WORK ON THIS PROJECT SHALL FAMILIARIZE HIMSELF WITH THE SITE AND SHALL BE HELD SOLELY RESPONSIBLE FOR ANY DAMAGE TO EXISTING FACILITIES RESULTING DIRECTLY, OR INDIRECTLY, FROM HIS OPERATIONS, WHETHER OR NOT SAID FACILITIES ARE SHOWN ON THESE PLANS.
1. TRAFFIC CONTROL AND STRIPING TO CONFORM TO THE CURRENT MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES (M.U.T.C.D.).
2. BARRICADING AND DETOURING SHALL BE IN CONFORMANCE WITH THE REQUIREMENTS OF THE CURRENT M.U.T.C.D.
3. NO STREET SHALL BE CLOSED TO TRAFFIC WITHOUT WRITTEN PERMISSION FROM THE APPROPRIATE AGENCY, EXCEPT
WHEN DIRECTED BY LAW ENFORCEMENT OR FIRE OFFICIALS.
4. THE CONTRACTOR SHALL MAKE EVERY EFFORT TO PROVIDE FOR SMOOTH TRAFFIC FLOW AND SAFETY. ACCESS SHALL BE
MAINTAINED FOR ALL PROPERTIES ADJACENT TO THE WORK.
5. DETOURING OPERATIONS FOR A PERIOD OF SIX CONSECUTIVE CALENDAR DAYS, OR MORE, REQUIRE THE INSTALLATION OF TEMPORARY STREET STRIPING AND REMOVAL OF INTERFERING STRIPING BY SANDBLASTING. THE DETOURING STRIPING PLAN OR CONSTRUCTION TRAFFIC CONTROL PLAN MUST BE SUBMITTED TO THE GOVERNING AGENCY FOR REVIEW AND
APPROVAL.
6. ALL TRAFFIC CONTROL DEVICES SHALL BE RESTORED TO THEIR ORIGINAL CONDITION AT THE END OF THE WORK TO THE
SATISFACTION OF THE GOVERNING AGENCY.
7. TRAFFIC CONTROL DEVICES (TCDs) SHALL REMAIN VISIBLE AND OPERATIONAL AT ALL TIMES.
8. ALL PERMANENT TRAFFIC CONTROL DEVICES CALLED FOR HEREON SHALL BE IN PLACE AND IN FINAL POSITION PRIOR TO ALLOWING ANY PUBLIC TRAFFIC ONTO THE PORTIONS OF THE ROAD(S) BEING IMPROVED HEREUNDER, REGARDLESS OF THE STATUS OF COMPLETION OF PAVING OR OTHER OFF-SITE IMPROVEMENTS CALLED FOR BY THESE PLANS.
9. THE CONTRACTOR SHALL PROVIDE BARRICADES, SIGNS, FLASHERS, OTHER EQUIPMENT AND FLAG PERSONS NECESSARY
TO INSURE THE SAFETY OF WORKERS AND VISITORS.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING UTAH TRANSIT AUTHORITY (UTA) IF THE CONSTRUCTION INTERRUPTS OR RELOCATES A BUS STOP OR HAS AN ADVERSE EFFECT ON BUS SERVICE ON THAT STREET TO ARRANGE
FOR TEMPORARY RELOCATION OF STOP.
TRAFFIC CONTROL AND SAFETY NOTES
GRADING AND DRAINAGE NOTES
1. SITE GRADING SHALL BE PERFORMED IN ACCORDANCE WITH THESE PLANS AND SPECIFICATIONS AND THE
RECOMMENDATIONS SET FORTH IN THE GEOTECHNICAL REPORT AND ALL RELATED ADDENDUMS.
2. THE CONTRACTOR SHALL STRIP AND CLEAR THE TOPSOIL, MAJOR ROOTS AND ORGANIC MATERIAL FROM ALL PROPOSED BUILDING AND PAVEMENT AREAS PRIOR TO SITE GRADING. (THE TOPSOIL MAY BE STOCKPILED FOR LATER USE IN
LANDSCAPED AREAS.)
3. THE CONTRACTOR SHALL REMOVE ALL ORGANIC MATERIAL AND OTHER DELETERIOUS MATERIALS PRIOR TO PLACING GRADING FILL OR BASE COURSE. THE AREA SHOULD BE PROOF-ROLLED TO IDENTIFY ANY SOFT AREAS. WHERE SOFT AREAS ARE ENCOUNTERED, THE CONTRACTOR SHALL REMOVE THE SOIL AND REPLACE WITH COMPACTED FILL.
4. ALL DEBRIS PILES AND BERMS SHOULD BE REMOVED AND HAULED AWAY FROM SITE OR USED AS GENERAL FILL IN
LANDSCAPED AREAS.
5. THE CONTRACTOR SHALL CONSTRUCT THE BUILDING PAD TO THESE DESIGN PLANS AS PART OF THE SITE GRADING CONTRACT, AND STRICTLY ADHERE TO THE SITE PREPARATION AND GRADING REQUIREMENTS OUTLINED IN THE
GEOTECHNICAL REPORT.
6. THE CONTRACTOR SHALL GRADE THE PROJECT SITE TO PROVIDE A SMOOTH TRANSITION BETWEEN NEW AND EXISTING
ASPHALT, CURB AND GUTTER, AND ADJOINING SITE IMPROVEMENTS.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE AND DEBRIS ON ADJACENT STREETS WHEN EQUIPMENT IS
TRAVELING THOSE STREETS.
8. THE CONTRACTOR SHALL BE FAMILIAR WITH ALL CONDITIONS AND RECOMMENDATIONS OUTLINED IN THE GEOTECHNICAL REPORT AND TAKE ALL NECESSARY PRECAUTIONS AND RECOMMENDED PROCEDURES TO ASSURE SOUND GRADING
PRACTICES.
9. THE CONTRACTOR SHALL TAKE APPROPRIATE GRADING MEASURES TO DIRECT STORM SURFACE RUNOFF TOWARDS CATCH
BASINS.
10. THE LOCATIONS OF UNDERGROUND FACILITIES SHOWN ON THESE PLANS ARE BASED ON ON-SITE SURVEY. IT SHALL BE THE CONTRACTORS' FULL RESPONSIBILITY TO CONTACT THE VARIOUS UTILITY COMPANIES TO LOCATE THEIR FACILITIES PRIOR TO PROCEEDING WITH CONSTRUCTION. NO ADDITIONAL COMPENSATION SHALL BE PAID TO THE CONTRACTOR FOR
DAMAGE AND REPAIR TO THESE FACILITIES CAUSED BY HIS WORK FORCE.
11. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PERFORM ALL NECESSARY CUTS AND FILLS WITHIN THE LIMITS OF THIS PROJECT AND THE RELATED OFF-SITE WORK, SO AS TO GENERATE THE DESIRED SUBGRADE, FINISH GRADES, AND
SLOPES SHOWN.
12. THE CONTRACTOR IS WARNED THAT AN EARTHWORK BALANCE WAS NOT NECESSARILY THE INTENT OF THIS PROJECT. ANY ADDITIONAL MATERIAL REQUIRED OR LEFTOVER MATERIAL FOLLOWING EARTHWORK OPERATIONS BECOMES THE
RESPONSIBILITY OF THE CONTRACTOR.
13. THE GRADING CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH THE OWNER TO PROVIDE FOR THE REQUIREMENTS OF THE PROJECT STORM WATER POLLUTION PREVENTION PLAN (SWPPP) AND ASSOCIATED PERMIT. ALL CONTRACTOR ACTIVITIES 1 ACRE OR MORE IN SIZE ARE REQUIRED TO PROVIDE A STORM WATER POLLUTION PREVENTION PLAN.
14. ALL CUT AND FILL SLOPES SHALL BE PROTECTED UNTIL EFFECTIVE EROSION CONTROL HAS BEEN ESTABLISHED.
15. THE USE OF POTABLE WATER WITHOUT A SPECIAL PERMIT FOR BUILDING OR CONSTRUCTION PURPOSES INCLUDING CONSOLIDATION OF BACKFILL OR DUST CONTROL IS PROHIBITED. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY
PERMITS FOR CONSTRUCTION WATER FROM GOVERNING AGENCY.
16. THE CONTRACTOR SHALL MAINTAIN THE STREETS, SIDEWALKS, AND ALL OTHER PUBLIC RIGHT-OF-WAYS IN A CLEAN, SAFE AND USABLE CONDITION. ALL SPILLS OF SOIL, ROCK OR CONSTRUCTION DEBRIS SHALL BE PROMPTLY REMOVED FROM THE PUBLICLY-OWNED PROPERTY DURING CONSTRUCTION AND UPON COMPLETION OF THE PROJECT. ALL ADJACENT PROPERTY, PRIVATE OR PUBLIC, SHALL BE MAINTAINED IN A CLEAN, SAFE, AND USABLE CONDITION.
UTILITY NOTES
1. ALL CONSTRUCTION AND MATERIALS SHALL BE IN ACCORDANCE WITH THESE CONTRACT DOCUMENTS, CITY AND STATE
REQUIREMENTS AND THE MOST RECENT EDITIONS OF THE FOLLOWING: THE INTERNATIONAL PLUMBING CODE, UTAH DRINKING WATER REGULATIONS, APWA MANUAL OF STANDARD PLANS AND SPECIFICATIONS. THE CONTRACTOR IS REQUIRED TO ADHERE TO ALL OF THE ABOVE-MENTIONED DOCUMENTS UNLESS OTHERWISE NOTED AND APPROVED BY THE
ENGINEER.
2. CONTRACTOR SHALL COORDINATE LOCATION OF NEW "DRY UTILITIES" WITH THE APPROPRIATE UTILITY COMPANY, INCLUDING BUT NOT LIMITED TO: TELEPHONE & INTERNET SERVICE, GAS SERVICE, CABLE, AND POWER.
3. EXISTING UTILITIES HAVE BEEN SHOWN ON THE PLANS BASED ON ON-SITE SURVEY. PRIOR TO COMMENCING ANY WORK, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO HAVE EACH UTILITY COMPANY LOCATE, IN THE FIELD, THEIR MAIN AND SERVICE LINES. THE CONTRACTOR SHALL NOTIFY BLUE STAKES AT 811 48 HOURS IN ADVANCE OF PERFORMING ANY EXCAVATION WORK. THE CONTRACTOR SHALL RECORD THE BLUE STAKES ORDER NUMBER AND FURNISH ORDER NUMBER TO OWNER AND ENGINEER PRIOR TO ANY EXCAVATION. IT WILL BE THE CONTRACTOR'S SOLE RESPONSIBILITY TO DIRECTLY CONTACT ANY OTHER UTILITY COMPANIES THAT ARE NOT MEMBERS OF BLUE STAKES. IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY TO PROTECT ALL EXISTING UTILITIES SO THAT NO DAMAGE RESULTS TO THEM DURING THE PERFORMANCE OF THIS CONTRACT. ANY REPAIRS NECESSARY TO DAMAGED UTILITIES SHALL BE PAID FOR BY THE CONTRACTOR. THE CONTRACTOR SHALL BE REQUIRED TO COOPERATE WITH OTHER CONTRACTORS AND UTILITY
COMPANIES INSTALLING NEW STRUCTURES, UTILITIES AND SERVICE TO THE PROJECT.
4. CARE SHOULD BE TAKEN IN ALL EXCAVATIONS DUE TO POSSIBLE EXISTENCE OF UNRECORDED UTILITY LINES. EXCAVATION REQUIRED WITHIN PROXIMITY OF EXISTING UTILITY LINES SHALL BE DONE BY HAND. CONTRACTOR SHALL REPAIR ANY DAMAGE TO EXISTING UTILITY LINES OR STRUCTURES INCURRED DURING CONSTRUCTION OPERATIONS AT CONTRACTOR'S
EXPENSE.
5. TRENCH BACKFILL MATERIAL AND COMPACTION TESTS ARE TO BE TAKEN PER APWA STANDARD SPECIFICATIONS (CURRENT EDITION), SECTION 02320 - BACKFILLING TRENCHES, OR AS REQUIRED BY THE GEOTECHNICAL REPORT IF NATIVE MATERIALS ARE USED. NO NATIVE MATERIALS ARE ALLOWED IN THE PIPE ZONE. THE MAXIMUM LIFT FOR BACKFILLING EXCAVATIONS IS
DETERMINED BY THE GEOTECHNICAL RECOMMENDATIONS.
6. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR CONFORMING TO LOCAL AND FEDERAL CODES GOVERNING SHORING AND
BRACING OF EXCAVATIONS AND TRENCHES AND FOR THE PROTECTION OF WORKERS.
7. THE CONTRACTOR IS REQUIRED TO KEEP ALL CONSTRUCTION ACTIVITIES WITHIN THE APPROVED PROJECT LIMITS. THIS INCLUDES, BUT IS NOT LIMITED TO VEHICLE AND EQUIPMENT STAGING, MATERIAL STORAGE AND LIMITS OF TRENCH EXCAVATION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN PERMISSION AND/OR EASEMENTS FROM THE APPROPRIATE GOVERNING ENTITY AND/OR INDIVIDUAL PROPERTY OWNER(S) FOR WORK OR STAGING OUTSIDE OF THE
PROJECT LIMITS.
8. THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING ANY DAMAGE, CAUSED BY ANY CONDITION INCLUDING SETTLEMENT, TO EXISTING UTILITIES FROM WORK PERFORMED AT OR NEAR EXISTING UTILITIES. THE CONTRACTOR SHALL TAKE ALL MEASURES NECESSARY TO PROTECT ALL EXISTING PUBLIC AND PRIVATE ROADWAY AND UTILITY FACILITIES. DAMAGE TO EXISTING FACILITIES CAUSED BY THE CONTRACTOR MUST BE REPAIRED BY THE CONTRACTOR AT HIS/HER EXPENSE TO THE
SATISFACTION OF THE OWNER OF SAID FACILITIES.
9. ALL WATER LINE AND SEWER LINE INSTALLATION AND TESTING TO BE IN ACCORDANCE WITH LOCAL GOVERNING AGENCY'S
STANDARDS AND SPECIFICATIONS.
10. ALL MANHOLES, HYDRANTS, VALVES, CLEANOUT BOXES, CATCH BASINS, METERS, ETC. MUST BE RAISED OR LOWERED TO FINAL GRADE PER APWA (CURRENT EDITION) STANDARDS AND INSPECTOR REQUIREMENTS. CONCRETE COLLARS MUST BE CONSTRUCTED ON ALL MANHOLES, CLEANOUT BOXES, CATCH BASINS, AND VALVES PER APWA STANDARDS. ALL MANHOLE, CATCH BASIN, OR CLEANOUT BOX CONNECTIONS MUST BE MADE WITH THE PIPE CUT FLUSH WITH THE INSIDE OF THE BOX
AND GROUTED OR SEALED.
11. CONTRACTOR SHALL NOT ALLOW ANY GROUNDWATER OR DEBRIS TO ENTER THE NEW OR EXISTING PIPE DURING
CONSTRUCTION.
12. SILT AND DEBRIS ARE TO BE CLEANED OUT OF ALL STORM DRAIN BOXES. CATCH BASINS ARE TO BE MAINTAINED IN A
CLEANED CONDITION AS NEEDED UNTIL AFTER THE FINAL BOND RELEASE INSPECTION.
13. CONTRACTOR SHALL CLEAN ASPHALT, TAR OR OTHER ADHESIVES OFF OF ALL MANHOLE LIDS AND INLET GRATES TO ALLOW
ACCESS.
14. EACH TRENCH SHALL BE EXCAVATED SO THAT THE PIPE CAN BE LAID TO THE ALIGNMENT AND GRADE AS REQUIRED. THE TRENCH WALL SHALL BE SO BRACED THAT THE WORKMEN MAY WORK SAFELY AND EFFICIENTLY. ALL TRENCHES SHALL BE
DRAINED SO THE PIPE LAYING MAY TAKE PLACE IN DEWATERED CONDITIONS.
15. CONTRACTOR SHALL PROVIDE AND MAINTAIN AT ALL TIMES AMPLE MEANS AND DEVICES WITH WHICH TO REMOVE
PROMPTLY AND TO PROPERLY DISPOSE OF ALL WATER ENTERING THE TRENCH EXCAVATION.
16. ALL SEWER LINES AND SEWER SERVICES SHALL HAVE A MINIMUM SEPARATION OF 10 FEET, EDGE TO EDGE, FROM THE WATER LINES. IF A 10 FOOT SEPARATION CAN NOT BE MAINTAINED, CONSTRUCT PER GOVERNING AGENCY'S MINIMUM
SEPARATION STANDARDS.
17. CONTRACTOR SHALL INSTALL THRUST BLOCKING AT ALL…