8-04 - Plan Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- RFP 26-19454-KM
- Issued by
- Hunt County, Texas
About this file
This is a construction plan drawing document for the Bell Farms Public Improvement District (PID) Playa Lake Retaining Wall Project located in Lubbock County, Texas, prepared by Hugo Reed and Associates, Inc., a Texas-licensed surveying and civil engineering firm. The project involves the removal of an existing stone retaining wall, construction of a new five-foot-wide concrete sidewalk, installation of pedestrian lighting with pole-mounted fixtures, and associated landscape improvements within the limits of Bell Farms Playa Park, Tract A. The construction scope includes site grading and dimension planning, concrete flatwork with 4000 PSI compressive strength specification, installation of stone benches and boulders, new tree plantings (Cedar Elm, Burr Oak, Western Soapberry, and Mexican Sycamore), and modification of the existing irrigation system to accommodate new site elevations and hardscape features. The site plan indicates approximately 0.25 acres of disturbed area with earthwork volumes showing 43 cubic yards of cut and 106 cubic yards of fill, with a net 63 cubic yards of fill to be removed from the lake south of the existing sidewalk. The project is located at 143rd Street adjacent to an existing playground and is subject to Lubbock City stormwater management requirements and TPDES General Permit TXR150000.
The electrical component includes installation of pole-mounted LED lighting fixtures on twelve-foot round steel poles with a timeclock and photocell control system, fed by a new 480/277-volt, three-phase panel designated "HSA" with a 125-ampere main circuit breaker and 30-ampere demand load for exterior lighting and irrigation equipment. All construction materials must comply with City of Lubbock Public Works Engineering Design Standards, including concrete sidewalk specifications requiring light broom finish, accessibility standards with maximum cross-slopes of two percent, and subgrade compaction to ninety-five percent of standard Proctor density as verified through ASTM field density testing. The project requires contractors to obtain City of Lubbock approvals and permits prior to construction, notify One-Call Center for utility locates at least two working days but no more than fourteen days prior to commencing work, and maintain a designated competent person on-site for safety supervision in compliance with OSHA regulations and Texas State Law.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
U G
O R
EE
D
A N
D A
SS
O
C
IA
TE
S, IN
C
BE
LL
F
AR
M S
PI
D
P
LA
YA
P
AR
K
R
ET
AI
N
IN
G
W
AL
L
IM
PR
O
VE
M
EN
T
PR
O
JE
C
T
LU
BB
O C
K C
O U
N
TY
, T
EX
AS
D
AT
E
PR
IN
TS
F O
R
AN
A
D D
IT
IO
N T
O T
H E
C
IT
Y O
F
LU
BB
O
C K, TE
XA
S
LI
C
EN
SE
D
S U
R
VE
YI
N
G F
IR
M
6-
A N
D A
S S
O C
IA
T
E S
IN
C
LA
N
D S
U R
VE
YO
R S
C
IV
IL
E
N G
IN
EE
R S
PH
O
N E:
3-
A
VE
N U
E N
LU
BB
O C
K, T
EX
AS
FA
X:
3-
TE
XA
S
R
EG
IS
TE
R
ED
E N
G
IN
EE
R
IN
G
F
IR
M F
-7
BELL FARMS PID PLAYA PARK
LUBBOCK COUNTY, TEXAS
RETAINING WALL IMPROVEMENT PROJECT
AN ADDITION TO THE CITY OF LUBBOCK,
Ursuline Street
Brownfield Hwy.
US 62-82
Sl id e
R oa d
98th Street
82nd Street
Loop 289
Clovis Hwy. US 84
LUBBOCK LOCATION MAP
NOT TO SCALE
M ilw au ke e Av en ue
U pl an d
A ve nu e
Al co ve
A nu e
Fr an kf or d
Av en ue
City Limits
66th Street
SPUR 327
In le r nu e
19th Street
Q ui ts na ue
Al co nu e
U pl an d
A ve nu e
City Limits
City Limits
4th Street
M ilw au ke ue
Av ue
M .L
. K in g Bl vd
Q ua ke ue
US 84
In di an a
A ve nu e
U ni ve rs ity nu e
In te rs ta te H w y.
66th Street
50th Street
Av
P
Slaton Hwy.82nd Street
City Limits
Erskine
In te rs ta te H ig hw ay
U ni ve rs ity ue
19th Street
34th StreetIn di an a ue
Erskine Street Av
Q
4th Street
Kent Street
City Limits
W oo d Municipal Dr.
M .L
. K in g
Bl vd
19th Street
Lo op
C ity
L im its
Regis Kent Street
Bluefield
C ity
L im its
O liv e
US 82
130th Street
114th Street
146th Street
C ity
L im its
DECEMBER 2025
AutoCAD SHX Text c
AutoCAD SHX Text
PROJECT LOCATION
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
C100.1
BELL FARMS
PID PLAYA
PARK
SITE
DIMENSION
PLAN
N O
R
TH
Site Dimension Notes
UTILITY ONE-CALL NOTE:
GENERAL DIMENSION NOTES:
LEGEND
AutoCAD SHX Text 1 4 3 r d
AutoCAD SHX Text S t r e e t
AutoCAD SHX Text
EXISTING PLAYGROUND
AutoCAD SHX Text
AutoCAD SHX Text
NEW 5' WIDE CONCRETE SIDEWALK
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
SHEET NAME
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text c
AutoCAD SHX Text
FILE PATH:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text O:\Bell Farms\A\Engineering\Drawings\SDIM_BELF_A
AutoCAD SHX Text
2018 - HUGO REED AND ASSOCIATES, INC.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text SIDEWALKS SHOWN ON THIS PLAN SHEET SHALL HAVE A WIDTH OF 5' CONTRACTOR WILL REFER TO ARCHITECT'S PLAN SHEETS FOR DIMENSIONS, DETAILS, SURFACE FINISHED OR SPECIFICATIONS OF ANY SPECIAL FLATWORK IN AMENITY AREAS.
AutoCAD SHX Text CONTRACTOR TO NOTIFY ONE-CALL CENTER BY CALLING 811 OR 800-344-8377 FOR UTILITY LOCATES AT LEAST 2 WORKING DAYS, AND NOT MORE THAN 14 DAYS, PRIOR TO COMMENCING ANY CONSTRUCTION ACTIVITY. MARKS ( PAINT, FLAGS, STAKES, ETC. ) ARE VALID 14 DAYS.
AutoCAD SHX Text REFER TO SITE CIVIL GRADING PLAN DETAIL SHEET FOR DIMENSIONING, CONSTRUCTION DETAILS AND VERTICAL LAYOUT OF INDIVIDUAL PAVING AND HARDSCAPE ITEMS SUCH AS CURBING, WALKWAYS, VALLEY GUTTERS, ISLANDS, DRIVE ENTRANCES, ACCESSIBLE RAMPS, ORNAMENTAL PAVING, PLANTER ISLANDS AND OTHER SPECIFIC HARDSCAPE FEATURES. REFER TO LANDSCAPE PLANS FOR FINAL DISPOSITION, LAYOUT, AND DIMENSIONS OF IRRIGATION, TREES, ORNAMENTAL PLANTINGS, GROUND COVERS, ISLAND OR PLANTER BEDDING AND ANY OTHER LANDSCAPE FEATURES. REFER TO ARCHITECT'S PLANS TO VERIFY THE LAYOUT AND DIMENSIONS OF INTERIOR STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING OR FINISHED CONSTRUCTION. ALSO REFER TO ARCHITECT'S PLANS FOR CONSTRUCTION OF PROPOSED EXTERIOR FEATURES OF BUILDINGS, STRUCTURES, FOOTINGS, RETAINING WALLS, EQUIPMENT, LIGHTING, STEPS, FENCING, SCREENING, HANDRAILS, GUARDRAILS, SIGNAGE OR OTHER ARCHITECTURAL FEATURES.
AutoCAD SHX Text
EXISTING CONCRETE PAVING
AutoCAD SHX Text
EXISTING ASPHALT PAVING
AutoCAD SHX Text
NEW CONCRETE PAVING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROPOSED LIGHT POLE
AutoCAD SHX Text
EXISTING CONTOUR
AutoCAD SHX Text
PROPOSED CONTOUR
AutoCAD SHX Text
EXISTING TREE
AutoCAD SHX Text
PROPOSED TREE
AutoCAD SHX Text 117032
AutoCAD SHX Text
TERRY L. WHITE, II
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text X
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
12/11/2025
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
C300.1
BELL FARMS
PID PLAYA
PARK
SITE GRADING
PLAN
N O
R THSite Grading Notes
FILL MATERIAL AND PLACEMENT REQUIREMENTS:
SITE FILL MATERIAL DENSITY REQUIREMENTS:
EROSION CONTROL NOTE:
GENERAL REGULATORY NOTE:
UTILITY ONE-CALL NOTE:
GENERAL GRADING / PAVING NOTES:
FLATWORK CONSTRUCTION JOINT
FLATWORK EXPANSION JOINT
TYPICAL FLATWORK CROSS-SECTION
FLATWORK ISOLATION JOINT
FLATWORK NOTE
LEGEND
PLAYA LAKE 192 DATA COL MDP 2010 UPDATE:
PLAYA LAKE SYSTEM = SYSTEM K
PLAYA LAKE SUB-BASIN ID = K805
PLAYA LAKE TYPE = TRUE NON-OVERFLOW
NATURAL OVERFLOW ELEVATION = 3195.0 NAVD88
100-YR NATURAL PWSE = 3190.6 NAVD88
500-YR NATURAL PWSE = 3194.0 NAVD88
EARTHWORK VOLUMES SHOWN:
CUT (EXCAVATION) = 43 CY
FILL (EMBANKMENT) = 106 CY (IN-PLACE)
TOTAL DISTURBED AREA AS SHOWN ON THIS PLAN = 0.25 AC
TOTAL SURFACE AREA AT 500-YEAR NATURAL PWSE WITHIN SUBJECT PROPERTY 35.0 ACRES
**NET 63 CY OF FILL...63 CY SHOULD BE REMOVED FROM LAKE SOUTH OF EXISTING SIDEWALK**
A
A
SECTION A-A
AutoCAD SHX Text 1 4 3 r d
AutoCAD SHX Text S t r e e t
AutoCAD SHX Text
EXISTING PLAYGROUND
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW STONE BENCH
AutoCAD SHX Text
NEW STONE BENCH
AutoCAD SHX Text
NEW STONE BOULDERS
AutoCAD SHX Text
NEW STONE BENCH
AutoCAD SHX Text
NEW STONE BENCH
AutoCAD SHX Text
NEW 5' WIDE CONCRETE SIDEWALK
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
LP
AutoCAD SHX Text
REMOVE EXISTING STONE RETAINING WALL
AutoCAD SHX Text
NEW STONE BOULDERS
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
SHEET NAME
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text c
AutoCAD SHX Text
FILE PATH:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text O:\Bell Farms\A\Engineering\Drawings\SGRD_BELF_A
AutoCAD SHX Text
2018 - HUGO REED AND ASSOCIATES, INC.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text FILL MATERIALS ASSOCIATED WITH BUILDINGS / STRUCTURES / RETAINING WALLS AND OTHER
AutoCAD SHX Text ARCHITECTURAL ELEMENTS SEPARATE FROM THE GENERAL SITE CONSTRUCTION WILL CONFORM TO
AutoCAD SHX Text
THE REQUIREMENTS SET FORTH IN THE SOILS ENGINEERING REPORT AND/OR THE ARCHITECT
AutoCAD SHX Text / STRUCTURAL ENGINEERING REQUIREMENTS. SHOULD THERE BE ANY QUESTION REGARDING THE
AutoCAD SHX Text
MATERIAL REQUIREMENTS OF THE FILL MATERIAL, THE MOST STRINGENT REQUIREMENT SHALL
AutoCAD SHX Text
GOVERN.
AutoCAD SHX Text SITE AREAS TO RECEIVE FILL SHALL BE STRIPPED OF SURFACE VEGETATION AND DELETERIOUS
AutoCAD SHX Text
MATERIALS TO A MINIMUM DEPTH OF 3 INCHES BELOW EXISTING GRADE. SUITABLE TOPSOIL
AutoCAD SHX Text MATERIALS THAT ARE STRIPPED SHALL BE STOCKPILED ON-SITE AS DIRECTED BY OWNER. THE
AutoCAD SHX Text
STRIPPED SURFACES SHALL THEN BE SCARIFIED TO A MINIMUM DEPTH OF 6 INCHES AND
AutoCAD SHX Text
COMPACTED IN-PLACE BEFORE THE INITIAL LIFT OF ANY FILL MATERIAL IS PLACED.
AutoCAD SHX Text ALL MATERIAL PLACED AS 'FILL' FOR SITE USE SHALL BE 'CLEAN' EARTHEN MATERIALS FREE OF
AutoCAD SHX Text
DELETERIOUS AMOUNTS OF ORGANIC MATERIAL, LARGE ROCK, DEBRIS, OR OTHER MATERIALS
AutoCAD SHX Text
CONSIDERED CONTAMINANTS.
AutoCAD SHX Text
PRIOR TO PLACEMENT OF ANY FILL MATERIAL, CONTRACTOR SHALL HAVE THE SOIL MOISTURE
AutoCAD SHX Text DENSITY CURVE ESTABLISHED AND ATTERBERG LIMITS DETERMINED FOR USE IN SUBSEQUENT FIELD
AutoCAD SHX Text DENSITY QUALITY CONTROL TESTING. IF THE NATURE OF FILL MATERIAL DEVIATES, EACH MATERIAL
AutoCAD SHX Text SHALL BE TESTED AND CLASSIFIED PRIOR TO USE. ALL FILL MATERIAL PLACED IS SUBJECT TO
AutoCAD SHX Text
THE APPROVAL OF THE OWNER / ENGINEER / AND OR ARCHITECT.
AutoCAD SHX Text
IMPORTED SELECT FILL MATERIAL FOR SITE USE SHALL MEET THE FOLLOWING MINIMUM
AutoCAD SHX Text
REQUIREMENTS
AutoCAD SHX Text
(ASTM D4318, C117, AND D2487; TEX 107-E):
AutoCAD SHX Text
PARTICLE SIZE: MAXIMUM
AutoCAD SHX Text
PLASTICITY INDEX RANGE: MINIMUM
AutoCAD SHX Text
LIQUID LIMIT: MAXIMUM
AutoCAD SHX Text
GRADATION: SUBJECT TO APPROVAL BY ENGINEER AND/OR ARCHITECT.
AutoCAD SHX Text Regardless of final disposition, all fill is subject to the following minimum requirements:
AutoCAD SHX Text Testing shall be performed in accordance with ASTM standards by a commercial testing labora-
AutoCAD SHX Text standard Proctor density in accordance with ASTM D-698. Moisture content for all fill densities
AutoCAD SHX Text inclusion with certified grading plan if record documents becomes necessary.
AutoCAD SHX Text certified grading plan if record documents become necessary.
AutoCAD SHX Text
(1) acre shall have a minimum of three (3) field densities for each six inch (6") depth.
AutoCAD SHX Text Each lift shall have a maximum compacted depth of six inches (6").
AutoCAD SHX Text All fill materials on site shall be compacted to an absolute minimum of ninety-five 95%%%
AutoCAD SHX Text method), ASTM D-1556 (sand cone density method), or ASTM D-2922 (nuclear density method).
AutoCAD SHX Text A minimum of Four (4) field densities shall be taken per acre of fill material and densities shall
AutoCAD SHX Text be taken for each six inch (6") depth, or portion thereof, of succeeding depths of fill material.
AutoCAD SHX Text Each area of fill material less than one half (1/2) acre shall have a minimum of two (2) field
AutoCAD SHX Text densities for each six inch (6") depth, and areas of fill between one half (1/2) acre and one
AutoCAD SHX Text The field densities shall be taken in such a manner as to be a representative sampling of the
AutoCAD SHX Text approximate equal areas of each acre being tested. Testing shall not occur at the same
AutoCAD SHX Text location in succeeding depths, so a representative sampling of the total fill may be obtained.
AutoCAD SHX Text Copies of all test results with location maps shall be furnished to the Owner Engineer for
AutoCAD SHX Text The location of the field density tests shall be indicated upon a map to become a part of a
AutoCAD SHX Text Field densities shall be determined in accordance with ASTM D-2167 ( rubber balloon density
AutoCAD SHX Text (6") depths. The location of tests shall be proportionately spaced to represent six inch (6")
AutoCAD SHX Text tory. ASTM is the American Society for Testing and Materials.
AutoCAD SHX Text a.
AutoCAD SHX Text b.
AutoCAD SHX Text c.
AutoCAD SHX Text d.
AutoCAD SHX Text e.
AutoCAD SHX Text f.
AutoCAD SHX Text g.
AutoCAD SHX Text h.
AutoCAD SHX Text shall be within minus one-percent (-1.0%) to plus two-precent (+2.0%) of optimum.
AutoCAD SHX Text Densification of fill material associated with Buildings/Structures/Retaining Walls and other architectural elements separate from the general site construction will conform to the requirements set forth in the soils engineering report and/or the architect / structural engineering requirements. Should there be any question regarding the density requirements of fill material, the most stringent requirement shall govern.
AutoCAD SHX Text
= 3 INCHES
AutoCAD SHX Text
= 4, MAXIMUM = 20
AutoCAD SHX Text = 35
AutoCAD SHX Text CONTRACTOR TO NOTIFY ONE-CALL CENTER BY CALLING 811 OR 800-344-8377 FOR UTILITY LOCATES AT LEAST 2 WORKING DAYS, AND NOT MORE THAN 14 DAYS, PRIOR TO COMMENCING ANY CONSTRUCTION ACTIVITY. MARKS ( PAINT, FLAGS, STAKES, ETC. ) ARE VALID 14 DAYS.
AutoCAD SHX Text THE CONTRACTOR IS TO OBTAIN ALL APPROVALS AND PERMITS REQUIRED BY THE CITY OF LUBBOCK PRIOR TO COMMENCING PHASES OF CONSTRUCTION THAT REQUIRE SUCH APPROVAL. THE CONTRACTOR IS RESPONSIBLE TO COMPLY WITH APPLICABLE O.S.H.A. REGULATIONS AND TEXAS STATE LAW CONCERNING CONSTRUCTION METHODS. AT ALL TIMES THAT WORK IS PROGRESSING, THE CONTRACTOR SHALL HAVE A DESIGNATED COMPETENT PERSON ON-SITE WHO SHALL BE RESPONSIBLE FOR SUPERVISING THE WORK AND WHOSE DUTY IT WILL BE TO PERFORM REQUIRED SAFETY INSPECTIONS AND TO DIRECT ALL REQUIRED CONSTRUCTION SAFETY ACTIVITIES. MUNICIPAL INFRASTRUCTURE INCLUDING UTILITY MAINS ARE ANTICIPATED TO BE CONSTRUCTED WITH THIS PROJECT. IF NECESSARY, REFER TO PLANS APPROVED AND/OR STAMPED 'FOR CONSTRUCTION' BY THE CITY OF LUBBOCK IF APPLICABLE. REFER TO ARCHITECT'S PLANS FOR ANY SPECIALTY PAVING ITEMS, INTERIOR PAVING, RETAINING WALLS, STEPS, OR ANY OTHER HARDSCAPE ITEMS NOT SPECIFICALLY NOTED IN THE CIVIL SITE PLANS. MATERIALS AND CONSTRUCTION OF ANY PAVING / HARDSCAPE ITEM NOT SPECIFICALLY DELINEATED IN THE CIVIL PLANS SHALL MEET THE ARCHITECT'S REQUIREMENTS AND/OR MANUFACTURER'S SPECIFICATIONS, AND MEET ALL APPLICABLE BUILDING CODES, ORDINANCES, AND REGULATIONS.
AutoCAD SHX Text CONTRACTOR SHALL ENSURE THAT A CITY OF LUBBOCK STORMWATER MANAGEMENT DEPARTMENT CONSTRUCTION SWP3 REVIEW APPLICATION (ORDINANCE NO. 2008-O0095) HAS BEEN SUBMITTED AND APPROVED, AND THAT THE PROPER TPDES GENERAL PERMIT TXR150000 HAS BEEN ISSUED FOR THE PROJECT PRIOR BEGINNING WORK. REFER TO AND PROPERLY CONSTRUCT AND MAINTAIN ALL SWP3 MEASURES SET FORTH IN THE TPDES GENERAL PERMIT AND THE SEPARATE SWP3 PLAN PREPARED BY OTHERS.
AutoCAD SHX Text ALL ELEVATIONS ARE NAVD88. ADD 3200 WHERE NECESSARY TO OBTAIN NAVD88 ELEVATION. SPOT ELEVATIONS WITHOUT DESIGNATION ARE TOP-OF-SIDEWALK ELEVATIONS. PROPOSED CONTOURS SHOWN IN THE PLANS ARE FINISHED GRADE WHETHER TOP-OF-PAVING, TOP-OF-HARDSCAPE, OR AREAS TO BE LANDSCAPED. CONTRACTOR SHALL SALVAGE TOPSOIL FOR FINAL PLACEMENT IN LANDSCAPED AREAS. STORE AS DIRECTED BY OWNER. CROSS-SLOPES FOR SIDEWALKS, FLATWORK OR ACCESSIBLE ROUTES SHALL NOT EXCEED 2%. SLOPES ALONG THE TRAVELED WAY OF ALL SUCH FEATURES SHALL NOT EXCEED 5%. REFER TO LANDSCAPE PLANS FOR FINAL DISPOSITION OF NON-HARDSCAPE AREAS. ALL PAVEMENT SECTIONS SHALL BE CONSTRUCTED PER GEOTECHNICAL REPORT PROVIDED BY OWNER OR AS NOTED ON THE PLANS. ALL MATERIALS TO BE INCORPORATED INTO THE PROJECT SHALL MEET THE APPLICABLE REQUIREMENTS AND BE PLACED IN ACCORDANCE WITH THE PLANS, SPECIFICATIONS, GEOTECHNICAL REPORT, AND LATEST VERSION OF THE CITY OF LUBBOCK PUBLIC WORKS ENGINEERING DESIGN STANDARDS AND SPECIFICATIONS. SHOULD THERE BE ANY QUESTION REGARDING REQUIREMENTS FOR MATERIALS THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.
AutoCAD SHX Text 4000 PSI PCC FLATWORK (w/ 6x6 NO.10 WIRE MESH)
AutoCAD SHX Text 5"
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
ASTM D698
AutoCAD SHX Text
95% STANDARD PROCTOR
AutoCAD SHX Text
SUBGRADE COMPACTED TO
AutoCAD SHX Text 4000 PSI PCC FLATWORK (w/ 6x6 NO.10 WIRE MESH)
AutoCAD SHX Text
WITH PREMOLDED FILLER,
AutoCAD SHX Text
30'-0" O.C. MAX. EACH WAY
AutoCAD SHX Text
BACKER ROD & SEALANT
AutoCAD SHX Text
1/2" EXPANSION JOINT
AutoCAD SHX Text
TOOLED EDGE
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
ASTM D698
AutoCAD SHX Text
95% STANDARD PROCTOR
AutoCAD SHX Text
SUBGRADE COMPACTED TO
AutoCAD SHX Text 4000 PSI PCC FLATWORK (w/ 6x6 NO.10 WIRE MESH)
AutoCAD SHX Text
1/2" WIDTH
AutoCAD SHX Text
1-3/4" DEPTH
AutoCAD SHX Text
CONTRACTOR RESPONSIBLE TO PROTECT ALL ABUTTING STRUCTURES.
AutoCAD SHX Text
BUILDING, STRUCTURE, WALL, CURB, OR EXISTING PAVEMENT.
AutoCAD SHX Text
APPLY CONTINUOUS BEAD OF SILICONE SEALANT ENTIRE JOINT LENGTH.
AutoCAD SHX Text
FULL DEPTH PREFORMED BITUMINOUS JOINT FILLER
AutoCAD SHX Text INCLUDING BUT NOT LIMITED TO BUILDINGS, WALLS, CURBS, STEPS, FOUNDATIONS, OR OTHER PERMANENT STRUCTURES.
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
AT 5' INTERVALS OR AS SHOWN
AutoCAD SHX Text
TOOLED JOINT (1/2" DEEP)
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
ASTM D698
AutoCAD SHX Text
95% STANDARD PROCTOR
AutoCAD SHX Text
SUBGRADE COMPACTED TO
AutoCAD SHX Text 4000 PSI PCC FLATWORK (w/ 6x6 NO.10 WIRE MESH)
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
SUBGRADE COMPACTED TO
AutoCAD SHX Text
95% STANDARD PROCTOR
AutoCAD SHX Text
ASTM D698
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text ALL CONCRETE SIDEWALK AND GENERAL FLATWORK SHALL BE FIBER MESH CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI, 3 TO 5 SLUMP RANGE, AND A 5% (±1%) MAXIMUM AIRENTRAINMENT. ALL SIDEWALK / ACCESS ROUTES SHALL BE CONSTRUCTED WITH A CROSS-SLOPE NO GREATER THAN 1/4" PER FOOT (2%) AND WITH A MAXIMUM LONGITUDINAL SLOPE OF 5%. ALL SIDEWALKS / ACCESS ROUTES TO HAVE A LIGHT BROOM FINISH, 3/8" RADIUS AND TROWEL JOINT EDGES. TEXTURE IN DIRECTION OF NORMAL TRAFFIC. PLACE CURING COMPOUND ON EXPOSED SURFACES IMMEDIATELY AFTER FINISHING IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS. PROVIDE ADDITIONAL CURING METHODS IN HARSH WEATHER AS DIRECTED BY THE ENGINEER. CONCRETE FIBER SHALL BE 100% VIRGIN MONOFILAMENT OR FIBRILLATED POLYPROPYLENE FIBERS SPECIFICALLY MANUFACTURED FOR USE AS CONCRETE REINFORCEMENT AND SO CERTIFIED BY THE MANUFACTURER AND CONTAINING NO REPROCESSED MATERIALS. FIBER PHYSICAL CHARACTERISTICS SHALL BE: SPECIFIC GRAVITY OF 0.91 g/cc, TENSILE STRENGTH OF 70-110 ksi, FIBER LENGTHS OF 1-1/2" TO 2".
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text 5"
AutoCAD SHX Text 5"
AutoCAD SHX Text 4.
AutoCAD SHX Text
EXISTING CONCRETE PAVING
AutoCAD SHX Text
EXISTING ASPHALT PAVING
AutoCAD SHX Text
NEW CONCRETE PAVING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROPOSED LIGHT POLE
AutoCAD SHX Text
EXISTING CONTOUR
AutoCAD SHX Text
PROPOSED CONTOUR
AutoCAD SHX Text
EXISTING TREE
AutoCAD SHX Text
PROPOSED TREE
AutoCAD SHX Text 76.75
AutoCAD SHX Text
PROPOSED SPOT ELEVATION
AutoCAD SHX Text 117032
AutoCAD SHX Text
TERRY L. WHITE, II
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text X
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text 12/11/2025
APPROXIMATE LOCATION OF CUT (63 CY)
N O R T H 0' 20' 40'
EL:3194.09'
N:7232100.31
E:943718.44
EL:3194.65'
N:7232184.06
E:943500.86
EL:3193.99'
N:7232095.93
E:943715.59
EL:3194.55'
N:7232180.57
E:943496.32
S t
Existing Pine Tree
Existing Shade Tree
New Shade Tree
Existing Concrete
PLAN LEGEND
Natural Turfgrasss - restored & updated irrigation
Existing Playground
New Concrete Walk
Existing Stone Bench
New Stone Bench
Sandstone Boulders
Area Lights re: Electrical Sheets
Existing Steel Bench
New Steel Bench
Existing Trash Receptacle
New Trash Receptacle
SHEET NUMBER
SHEET NAME
NO. DATE DESCRIPTION
c
DRAWN BY: JSH
LA-1.0
BELL FARMS PID
RETAINING WALL
PROJECT
SITE
PLAN
CONSTRUCTION
DRAWING
H U G O
R E E D
A N D
A S S O C I A T E S
I N C
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
PRAIRIE WORKSHOP
L A N D S C A P E A R C H I T E C T U R E w w w . p r a i r i e w o r k s h o p . c o m
806-773-1508 TEXAS REGISTERED FIRM #1285
SCALE:
1/LA-1.0
1" = 20'-0" Site Plan
E
R
A
T
T
J
A
E
S
G
I
S
S
E
R
T
X
T
E
E
F
O
R
A
S
E
T
T
C
C
I
H
G
D
O
E
S
S
H
D
N
A
D
L
N
S
P
E
A
C
O
A
10.29.2025
EXISTING PLAYGROUND.
EXISTING WALK
EXISTING WALK
EL:3194.09'
N:7232100.31
E:943718.44
EL:3194.65'
N:7232184.06
E:943500.86
EL:3193.99'
N:7232095.93
E:943715.59
EL:3194.55'
N:7232180.57
E:943496.32
S
CE
BO
BO
WS
CE
MS
CE
Existing Pine Tree
Existing Shade Tree
New Shade Tree
PLAN LEGEND
Existing Turf
Replace/Repair Turf after re-grading
Cedar Elm
BO Burr Oak
WS Western Soapberry
MS Mexican Sycamore
Sandstone Boulder Tree Wells
'Celebration' Bermuda sod
SHEET NUMBER
SHEET NAME
NO. DATE DESCRIPTION
c
DRAWN BY: JSH
C O P Y W R I T E
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
PRAIRIE WORKSHOP
L A N D S C A P E A R C H I T E C T U R E w w w . p r a i r i e w o r k s h o p . c o m
806-773-1508 TEXAS REGISTERED FIRM #1285
SCALE:
1/LA-2.0
1" = 20'-0" Planting Plan
E
R
A
T
T
J
A
E
S
G
I
S
S
E
R
T
X
T
E
E
F
O
R
A
S
E
T
T
C
C
I
H
G
D
O
E
S
S
H
D
N
A
D
L
N
S
P
E
A
C
O
A
10.29.2025
EXISTING PLAYGROUND.
EXISTING WALK
EXISTING WALK
BELL FARMS PID
RETAINING WALL
PROJECT
PLANTING PLAN
LA-2.0
CONSTRUCTION
DRAWING
A
B
B
B
Existing Pine Tree
Existing Shade Tree
New Shade Tree
PLAN LEGEND
Existing Irrigation Spray Head (PGP Rotor)
Relocated Irrigation Head (PGP Rotor)
Sandstone Boulder Tree Wells
A - Vertical Adjustment B - Horizontal Adjustment
Existing Tree Spray Head (pop up VAN)
New Tree Spray Head (pop up VAN)
SHEET NUMBER
SHEET NAME
NO. DATE DESCRIPTION
c
DRAWN BY: JSH
C O P Y W R I T E
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
PRAIRIE WORKSHOP
L A N D S C A P E A R C H I T E C T U R E w w w . p r a i r i e w o r k s h o p . c o m
806-773-1508 TEXAS REGISTERED FIRM #1285
SCALE:
1/LA-3.0
1" = 20'-0" Irrigation Plan
E
R
A
T
T
J
A
E
S
G
I
S
S
E
R
T
X
T
E
E
F
O
R
A
S
E
T
T
C
C
I
H
G
D
O
E
S
S
H
D
N
A
D
L
N
S
P
E
A
C
O
A
10.29.2025
EXISTING PLAYGROUND.
EXISTING WALK
EXISTING WALK
BELL FARMS PID
RETAINING WALL
PROJECT
IRRIGATION PLAN
LA-3.0
The scope of work includes modification of the existing irrigation system. Existing turf rotors, tree spray heads and lateral lines shall be adjusted to accomodate the site grading, sidewalks, benches and trees.
The existing irrigation system consists of multiple zones controlled by electric valves. The system is feed by two wells. At the controller, reference zone #'s 18-22 (turf) & #55 (trees)
TREE PLANTING
NOT TO SCALE
FOR B&B MATERIAL, CUT AND REMOVE TOP 1/3 OF BURLAP
FROM ROOT BALL OR FOR CONTAINER MATERIAL, REMOVE
CONTAINER AND SCARIFY SIDES OF ROOTBALL.
SET ROOT FLARE 1" ABOVE FINISHED GRADE
2.5 X DIA. ROOTBALL
MULCH AN AREA 3X THE DIA. OF THE ROOTBALL AS SPEC'D.
NOTE: AFTER TREE HOLE IS EXCAVATED AND 8 HRS.
PRIOR TO PLANTING, FILL HOLE WITH WATER AND ALLOW
TO INFILTRATE COMPLETELY. IF WATER HAS NOT DRAINED
WITHIN 6 HRS. PREPARE DRAINAGE IMPROVEMENTS
HAND WATER TREES AND SHRUBS IMMEDIATELY AFTER PLANTING
WITH A WATER HOSE TO COMPLETELY SATURATE BACKFILL MATERIAL
AND SETTLE ALL VOIDS. DO NOT TAMP.
BACKFILL WITH EXCAVATED MATERIAL FROM TREE PIT
**DO NOT BUILD WATERING RINGS**
STAKE TREES ONLY WHEN NECESSARY
UNDISTURBED SOIL
ENLARGED STAKING DETAIL
STONE TREE WELL
NOT TO SCALE2
PIPE & WIRE TRENCHING
MAINLINE, LATERAL,
AND WIRING IN
THE SAME TRENCH
MAINLINE LATERAL WIRING IN
CONDUIT
RUN WIRING BENEATH
AND BESIDE MAINLINE.
TAPE AND BUNDLE AT
10-FOOT INTERVALS.
ALL SOLVENT WELD
PLASTIC PIPING TO
BE SNAKED IN
TRENCH AS SHOWN.
TIE A 24-INCH LOOP IN
ALL WIRING AT CHANGES
OF DIRECTION OF 30°
OR GREATER. UNTIE
AFTER ALL CONNECTIONS
HAVE BEEN MADE.
NOTES:
1. SLEEVE BELOW ALL HARDSCAPE ELEMENTS WITH CLASS 200 PVC TWICE THE
DIAMETER OF THE PIPE OR WIRE BUNDLE WITHIN.
2. FOR PIPE AND WIRE BURIAL DEPTHS SEE SPECIFICATIONS.
PLAN VIEW
WIRE W/O CONDUIT
PIPE PIPE
SECTION VIEW
NOT TO SCALE
18"
24"
NOT TO SCALE
6 4" POP-UP SPRAY HEAD FOR TREES 5
SWING ASSEMBLY:
RAIN BIRD MODEL SA 6050
PVC LATERAL PIPE
PVC SCH 40 TEE OR ELL5
1 FINISH GRADE/TOP OF MULCH
RAIN BIRD 1804 WITH 8' VAN
POP-UP SPRAY SPRINKLER:
SECTION VIEW
MATERIAL
ADJACENT
NEW SIDEWALK
5 FT. LONG LEUDERS STONE SLAB (SET LEVEL, TO SEATING HT.
APPROX. 17-19" ABOVE GRADE)
FIBER BOARD
#57 STONE BASE - COMPACTED24" Scarborough Litter Receptacle (30g) by Landscape Forms
Scarborough Bench (72" / backed with 1 center arm)
33"
24 1/2"Ø
33 3/4"
17 3/4"
27 3/4"
72 "
27 1/4 "
SURFACE MOUNT
Ø 8" OPENING
LIFT AND TURN LID
TO EMPTY
LOCK
SURFACE MOUNT
4 SITE FURNISHINGS
NOT TO SCALE
SECTION VIEW
SANDSTONE BOULDERS STACKED IN HORSESHOE
SHAPE AROUND EXISTING TREE FOR ROOT ZONE
PROTECTION IN NEW GRADED AREAS.
3 STONE BENCH
NOT TO SCALE
STEEL TUBING
Note: powdercoat color = 'stormcloud'
SHEET NUMBER
SHEET NAME
NO. DATE DESCRIPTION
c
DRAWN BY: JSH
C O P Y W R I T E
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
PRAIRIE WORKSHOP
L A N D S C A P E A R C H I T E C T U R E w w w . p r a i r i e w o r k s h o p . c o m
806-773-1508 TEXAS REGISTERED FIRM #1285
E
R
A
T
T
J
A
E
S
G
I
S
S
E
R
T
X
T
E
E
F
O
R
A
S
E
T
T
C
C
I
H
G
D
O
E
S
S
H
D
N
A
D
L
N
S
P
E
A
C
O
A
10.29.2025
BELL FARMS PID
RETAINING WALL
PROJECT
LANDSCAPE DETAILS
LA-4.0
BRANCH CIRCUIT AND SERVICE CONDUCTOR SIZING SCHEDULE
EQUIPMENT
GROUNDING
CONDUCTOR(S)
(AWG/kcmil)
F20
BRANCH
CIRCUIT/FEEDER
IDENTIFICATION
OVERCURRENT
DEVICE
PHASE AND NEUTRAL
CONDUCTORS
(AWG/kcmil)
1/2"12
CONDUIT
10F25 25 10
10F30 30
8F35 35
8F40 40
1/2"
1/2"
1"
1"
8F45 45 1"
8F50 50
6F60 60
4F70 70
4F80 80
1"
1"
1-1/4"
1-1/4"
2F90 90 1-1/4"
2F100 100 1-1/4"8
1/0F125 125 2"6
1/0F150 150 2"6
2/0F175 175 2"6
3/0F200 200 2"6
4/0F225 225 2-1/2"4
250 kcmilF250 250 2-1/2"4
350 kcmilF300 300 3"4
500 kcmilF350 350 4"2
(2) 3/0F400 400 (2) 2-1/2"(2) 2
(2) 4/0F450 450 (2) 2-1/2"(2) 2
(2) 250 kcmilF500 500 (2) 2-1/2"(2) 2
(2) 350 kcmilF600 600 (2) 3"(2) 1/0
(2) 500 kcmilF700 700 (2) 4"(2) 1/0
(3) 300 kcmilF800 800 (3) 3"(3) 1/0
(3) 400 kcmilF1000 1000 (3) 3"(3) 2/0
(4) 350 kcmilF1200 1200 (4) 3"(4) 3/0
(5) 400 kcmilF1600 1600 (5) 3"(5) 4/0
(6) 400 kcmilF2000 2000 (6) 3"(6) 250 kcmil
(7) 500 kcmilF2500 2500 (7) 4"(7) 350 kcmil
(8) 500 kcmilF3000 3000 (8) 4"(8) 400 kcmil
(11) 500 kcmilF4000 4000 (11) 4"(11) 500 kcmil
NOTES:
1. WHERE BRANCH CIRCUIT OR FEEDER IS NOT DESIGNATED ON THE DRAWINGS, BRANCH CIRCUIT
OR FEEDER SHALL BE SIZED TO MATCH THE OVERCURRENT DEVICE LISTED ABOVE.
2. GROUNDING ELECTRODE CONDUCTORS FOR SEPARATELY DERIVED SYSTEMS SHALL BE SELECTED
BASED ON THE SECONDARY FEEDER OVERCURRENT DEVICE RATING.
GROUNDING
ELECTRODE
CONDUCTOR
(AWG/kcmil)
1/0
1/0
1/0
1/0
2/0
2/0
2/0
3/0
3/0
3/0
3/0
3/0
3/0
3/0
ELECTRICAL LEGEND
A
LPA-1
A
LPA-1
A
LPA-1
A
LPA-1
A
LPA-1
A1
LPA-1
A
LPA-1
A
LPA-1
E
SS
E
LPA-1
LPA-1
LPA-1
LPA-1
LPA-1,3
30A
LPA-1
LPA-1
GFI
LPA-1
WP
LPA-1
EWC
LPA-1
LPA-1
LPA-1
X
X
E
DESCRIPTIONSYMBOL
LIGHTING FIXTURE - TYPE & CIRCUIT NOTED
LIGHTING
LIGHTING FIXTURE WITH BATTERY BACK-UP - TYPE & CIRCUIT NOTED
LIGHTING FIXTURE - TYPE & CIRCUIT NOTED
WALL WASHER - TYPE & CIRCUIT NOTED
WALL MOUNTED LIGHTING FIXTURE - TYPE & CIRCUIT NOTED
CEILING MOUNTED EXIT SIGN - TYPE NOTED - DIRECTIONAL ARROWS INDICATED
WALL MOUNTED EXIT SIGN - TYPE NOTED - DIRECTIONAL ARROWS INDICATED
EMERGENCY LIGHTING FIXTURE - TYPE & CIRCUIT NOTED
FLOOD LIGHT - TYPE & CIRCUIT NOTED
POLE MOUNTED LIGHTING FIXTURE - TYPE & CIRCUIT NOTED
GROUND MOUNTED BOLLARD LIGHT - TYPE & CIRCUIT NOTED
LIGHTING FIXTURE WITH BATTERY BACKUP - TYPE & CIRCUIT NOTED
EXISTING LIGHT FIXTURE TO REMAIN
EXISTING LIGHT FIXTURE TO BE REMOVED
EXISTING LIGHT FIXTURE TO REMAIN
EXISTING LIGHT FIXTURE TO BE REMOVED
EXISTING EXIT LIGHT FIXTURE TO REMAIN
EXISTING EXIT LIGHT FIXTURE TO BE REMOVED
JUNCTION BOX
PULLBOX
MOTOR LOCATION
LIGHTING CONTACTOR
DISCONNECT SWITCH - CIRCUIT NOTED
COMBINATION MOTOR STARTER/DISCONNECT SWITCH - CIRCUIT NOTED
TIMECLOCK
DESCRIPTIONSYMBOL
POWER
THERMOSTAT LOCATION
SURFACE MOUNTED LIGHTING AND APPLIANCE PANELBOARD
FLUSH MOUNTED LIGHTING AND APPLIANCE PANELBOARD
PUSHBUTTON
START/STOP PUSHBUTTON
EXISTING JUNCTION BOX TO REMAIN
EXISTING JUNCTION BOX TO BE REMOVED
SPST WALL SWITCH
3-WAY WALL SWITCH
4-WAY WALL SWITCH
SPST WALL SWITCH WITH PILOT LIGHT
KEY OPERATED SPST WALL SWITCH
WALL MOUNTED DIMMER SWITCH
WALL MOUNTED OCCUPANCY SENSOR - OPTIONS (M2) TWO POLE
DESCRIPTIONSYMBOL
WIRING DEVICES
WALL MOUNTED COMBINATION OCCUPANCY SENSOR/DIMMER
WALL MOUNTED VOLUME CONTROL SWITCH
CEILING MOUNTED OCCUPANCY SENSOR - OPTIONS (H) HIGH BAY, (S) SYSTEM
DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W, GROUNDING - CIRCUIT NOTED
DUPLEX RECEPTACLE ON EMERGENCY POWER
RECEPTACLE - 125/250V, 3P, 3W - AMP RATING AND CIRCUIT NOTED
DOUBLE DUPLEX RECEPTACLE - 20A, 125V, 2P, 3W, GROUNDING - CIRCUIT NOTED
DUPLEX RECEPTACLE WITH GFI - CIRCUIT NOTED
DUPLEX RECEPTACLE WITH WEATHER-PROOF COVER - CIRCUIT NOTED
DUPLEX RECEPTACLE WITH GFI SERVING ELECTRIC WATER COOLER - CIRCUIT NOTED
FLOOR MOUNTED DUPLEX RECEPTACLE - CIRCUIT NOTED
FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE - CIRCUIT NOTED
CEILING MOUNTED DUPLEX RECEPTACLE - CIRCUIT NOTED
OCCUPANCY SENSOR POWER PACK - OPTIONS (D) DIMMING, (E) UL 924 EMERGENCY
RECEPTACLE - 250V, 4P, 4W - AMP RATING AND CIRCUIT NOTED
WALL MOUNTED LOW VOLTAGE SWITCH - NO. OF BUTTONS / ZONES NOTED
A
LPA-1
A1
LPA-1
E
LPA-1,3,5
60A
J
P
T
T
FLOOR MOUNTED JUNCTION BOXJ
J
J
P
K
D
M
MD
V
L2
OS
H
OWNER FURNISHED CONTRACTOR INSTALLED
DIAMETER
DATA COLLECTION PANEL
DISTRIBUTION
DRAWINGS
DOWN
ELECTRIC DRINKING FOUNTAIN
EMPTY CONDUIT
EXHAUST FAN
EQUIPMENT
ELECTRIC WATER COOLER
EXHAUST
CENTRAL PROCESSING UNIT
CONDUCTOR
CIRCUIT
CLOSED CIRCUIT TELEVISION
CIRCUIT BREAKER
AMPERE(S)
ABOVE
ABOVE COUNTER
AIR CONDITIONING
AMPERE INTERRUPTING CAPACITY
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTOMATIC TRANSFER SWITCH
AIR HANDLING UNIT
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
EXPLOSION PROOF
EXISTING
FIRE ALARM
FOOTCANDLES
FAN COIL UNIT
FLUORESCENT
FULL NEUTRAL
FEET, FOOT
GALVANIZED
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT INTERRUPTER
GROUND
GALVANIZED RIGID STEEL
HIGH INTENSITY DISCHARGE
HORSEPOWER
HAND OFF AUTOMATIC
HIGH PRESSURE SODIUM
HEATING/VENTILATING/AIR CONDITIONING
DIA
DCP
DIST
DWGS
DN
EDF
EC
EF
EQMT
EWC
EXH
CPU
COND
CKT
CCTV
CB
A
ABV
AC
A/C
AIC
AFF
AFG
ATS
AHU
BFF
BFG
BLDG
C
EXP
EXTG
F/A
FC
FCU
FLUOR
FN
FT
GALV
GFCI
GFI
GND
GRD
HID
HP
HOA
HPS
HVAC
HERTZHZ
MECHANICAL
MAIN DISTRIBUTION PANEL
MOUNTING HEIGHT
MAIN LUGS ONLY
MINIMUM
MERCURY VAPOR
MOUNTING
NON APPLICABLE
NORMALLY CLOSED
NON FUSED
NORMALLY OPEN
MOTOR CONTROL CENTER
MAXIMUM
MANHOLE
LOW PRESSURE SODIUM
POUND
INTERCOM
INSIDE DIAMETER
INTERMEDIATE STEEL CONDUIT
INCHES
INCANDESCENT
ISOLATED GROUND
JUNCTION BOX
KILOVOLT AMPERE
KILOVOLT
KILOVOLT AMPERE REACTIVE
KILOWATT
KILOWATT HOUR
NIGHT LIGHT
ON CENTER
OVERHEAD
POLE
PUBLIC ADDRESS
PUSHBUTTON
PRIVATE BUILDING EXCHANGE
PULL CHAIN
PHOTOCELL
POWER DISTRIBUTION PANEL
PANELBOARD
POUNDS PER SQUARE INCH
POWER
SECURITY
SOLID NEUTRAL
MECH
MDP
MH
MLO
MIN
MV
MTG
NA
NC
NF
NO
MCC
MAX
M
LPS
LB
IC
ID
IMC
IN
INC
IG
JB
KVA
KV
KVAR
KW
KWH
NL
OC
OFCI
OH
P
PA
PB
PBX
PC
P/C
PDP
PNL
PSI
PWR
S
SN
SQUARE FOOTSQFT
SWITCHSW
SWITCHBOARDSWBD
TIME CLOCKTC
TELEPHONETELE
THERMOSTATTSTAT
TELEVISIONTV
UNIT HEATERUH
UNLESS OTHERWISE NOTEDUON
UNDERGROUND PRIMARY ELECTRICUPE
VOLT(S)V
VAPOR PROOFVP
WIREW
WEATHERPROOFWP
TRANSFORMERXFMR
TRANSPONDERXPD
IMPEDANCEZ
ONE POLE1P
TWO POLE2P
THREE POLE3P
PHASEØ
WIRELESS ACCESS POINTWAP
ABBREVIATION DESCRIPTION
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
PP
DE
CEILING MOUNTED DAY LIGHTING SENSOR - OPTIONS (S) SYSTEMDS
LPA-1
USB
DUPLEX RECEPTACLE WITH TWO USB CHARGING STATIONS - CIRCUIT NOTED
S
LPA-1
SIMPLEX RECEPTACLE - 125V, 2P, 3W, GROUNDING - AMP RATING AND CIRCUIT
NOTED
30A
KILOVOLT AMPERE CAPACITIVEKVAC
TAMPER RESISTANTTP
1.01 GENERAL:
A. All electrical installation shall be performed in accordance with the National Electrical Code and all local codes and ordinances.
1.02 CONDUITS:
A. All conduits used outdoors or in wet location shall be rigid steel conduit with factory made steel threaded couplings and bushings or Liquidtight Flexible Metal Conduit with factory made connectors. All liquidtight flexible metal conduit shall not exceed 4 feet in length.
B. All underground conduit shall be rigid steel or underground plastic Type 40 heavy wall high impact PVC conduit with fittings conforming to Nema Publications TC2 and TC3 and U.L. listed for direct burial.
C. All conduit in all other locations shall be electrical metallic conduit (EMT) with steel compression-type box connectors and couplings or flexible metal conduit with factory made connectors. All flexible metal conduit shall not exceed 4 feet in length.
1.03 ELECTRICAL BOXES:
A. All outlet boxes shall be galvanized sheet steel, or cast iron in wet locations and U.L. listed.
B. All pullboxes and junction boxes shall be sheet steel or cast iron in wet locations and U.L. listed.
C. Outlet boxes, pullboxes and junction boxes used outdoors or in wet locations shall be U.L. listed for wet locations and be provided with watertight seals and covers.
1.04 CONDUCTORS:
A. All wiring shall be copper type THHN stranded if larger than No. 10 and solid for No. 10 and smaller. Wire size should not be used smaller than No. 12 unless used for low voltage control wiring.
1.05 OVERCURRENT PROTECTIVE DEVICES:
A. All new circuit breakers shall be Square D or equivalent bolt-on circuit breakers.
1.06 LIGHTING:
A. All lighting fixtures shall bear the label of Underwriter's Laboratories, Inc. Submit for review manufacturer's catalog data and drawings on all light fixtures with separate sheets for each proposed fixture clearly labeled.
B. Provide all labor, material, and equipment necessary for and incidental to the complete lighting system as shown on the drawings.
1.07 EXTERIOR LIGHTING CONTROLS
A. ELECTRONIC TIME SWITCHES
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a) Cooper Industries, Inc.
b) Intermatic, Inc.
c) Invensys Controls.
d) Leviton Mfg. Company Inc.
e) NSi Industries LLC; TORK Products.
f) Tyco Electronics; ALR Brand.Electronic
2. Time Switches: Solid state, programmable, with alphanumeric display; complying with UL 917.
3. Astronomic Time: Al channels.
4. Automatic daylight savings time changeover.
C. LIGHTING CONTACTOR
1. Manufacturers: Switches shall be ASCO 917 or approved equivalent.
1.08 ELECTRICAL SERVICE:
A. Provide all labor, material and equipment for the complete electrical service from the Power Company service point to the service entrance equipment. Coordinate all electrical service requirements with Power Company. Include all service utility costs from the Power Company in the contractor’s final bid number.
B. Furnish and install service entrance conductors in conduit from the panel enclosure, underground to the service pedestal.
Leave sufficient slack in the conductors at the transformer to facilitate connections by Power Company.
C. The Power Company shall provide and install a power service pedestal. Provide and install a reinforced concrete pad for the transformer of size and configuration as directed by Power Company.
D. All metering instruments shall be furnished by the Power Company and installed by the Electrical Contractor. Provide meter bases and/or instrument cabinets as indicated on the electrical riser diagram
ELECTRICAL SPECIFICATIONS
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
SHEET NUMBER
SHEET NAME
NO. DATE DESCRIPTION
DRAWN BY:
BELL FARMS PID
RETAINING WALL
PROJECT
CONSTRUCTION
DOCUMENTS
BRW
E001
ELECTRICAL
LEGEND &
SCHEDULES
REESE WRIGHT
79805
S
TA
ET OF TE
AX
S
P R O
FESS IONAL ENG
IN
E
E R
R
EG I S TERED
12/11/25
BELOW SLAB CONDUIT DETAIL
NO SCALE
NOTE: THE ABOVE DETAIL SHALL APPLY WHEREVER PVC CONDUIT IS USED
UNDERGROUND OR BELOW FLOOR IN LIEU OF RIGID THREADED GALVANIZED CONDUIT.
THE ELBOW SHALL BE RIGID GALVANIZED CONDUIT.
RIGID THREADED
GALVANIZED CONDUIT
FINISHED FLOOR
CONCRETE SLAB
SAND
CARLON PVC TYPE 40
HEAVY WALL CONDUIT
WITH GROUND WIRE
GALVANIZED STEEL TO
CARLON CONDUIT
ADAPTER
M
IN
DIRECT BURIED CONDUIT DETAIL
NO SCALE
NOTE: THE ABOVE DETAIL SHALL APPLY WHEREVER PVC CONDUIT IS USED
UNDERGROUND OR BELOW FLOOR IN LIEU OF RIGID THREADED GALVANIZED CONDUIT.
THE ELBOW SHALL BE RIGID GALVANIZED CONDUIT.
RIGID THREADED
GALVANIZED CONDUIT
GROUND LEVEL - GRADE
CARLON PVC TYPE 40
HEAVY WALL CONDUIT
GALVANIZED STEEL
TO CARLON CONDUIT
ADAPTER
12" WIDE PLASTIC
UNDERGROUND BURIAL
WARNING TAPE
8"
22"
CL
PANELBOARD IDENTIFICATION DETAIL
NO SCALE
NOTE: PROVIDE LABELING FOR NEW AND EXISTING
PANELBOARDS.
PANEL NAME
PHENOLIC NAMEPLATE WITH 1/4" LETTERS INSCRIBED
AS INDICATED. PROVIDE WHITE LABELS WITH BLACK
LETTERS FOR NORMAL SYSTEM PANELS AND RED
LABELS WITH WHITE LETTERS FOR EMERGENCY AND
ESSENTIAL SYSTEM PANELS.
WARNING:WARNING: POTENTIAL ARC FLASH HAZARD.
APPROPRIATE PPE AND TOOLS
REQUIRED WHEN WORKING
ON THIS EQUIPMENT.
PANEL "DPB"
480/277 VOLTS 3 PHASE
NORMAL BRANCH
FED BY SWITCHBOARD 'SBA'
PANEL VOLTAGE AND PHASE
POWER SYSTEM (HOSPITAL ONLY):
NORMAL BRANCH
CRITICAL BRANCH
LIFE SAFETY BRANCH
EQUIPMENT BRANCH
SOURCE OF POWER TO PANEL
WIRE COLOR CODES:
PHASE A - NEUTRAL -
PHASE B - GROUND -
PHASE C -
A LEGEND OF THE WIRE COLOR CODES SHALL BE
INSTALLED ON THE COVER OF EACH
PANELBOARD. COLOR CODES SHALL COMPLY
WITH NEC.
FOR DISTRIBUTION PANELS, PROVIDE PERMANENT PHENOLIC
NAMEPLATE WITH 1/4" LETTERS INSCRIBED WITH LOAD NAME
NEXT TO EACH CIRCUIT BREAKER. PROVIDE WHITE LABELS WITH
BLACK LETTERS FOR NORMAL SYSTEM FEEDERS AND RED
LABELS WITH WHITE LETTERS FOR EMERGENCY AND ESSENTIAL
SYSTEM FEEDERS.
BONDING JUMPER - SAME SIZE AS EQUIPMENT
GROUNDING CONDUCTOR
PANELBOARD EQUIPMENT GROUND
BUS BONDED TO CABINET
EQUIPMENT GROUNDING CONDUCTOR
INSTALLED WITH FEEDER
FEEDER CONDUIT
LOCKNUT (NOT SHOWN)
INSULATED THROAT GROUNDING
BUSHING
PANELBOARD BONDING DETAIL
NO SCALE
NEUTRAL BUS
MAIN BONDING
JUMPER
BOND TO CABINET
MAIN SERVICE
EQUIPMENT
NEUTRAL CONDUCTOR
INSULATED THROAT
GROUNDING BUSHING
(TYPICAL)
SERVICE ENTRANCE
EXOTHERMIC WELD
CONNECTION
THERMOWELD #CR-1 WITH
#M-8422 MOLD AND SIZE 32
CARTRIDGE
PVC COVER
3/4" x 10' COPPERCLAD STEEL
GROUND ROD, INSTALL OUTSIDE
BUILDING EXPOSED TO RAINFALL
#6 CU IN 1/2" CONDUIT
EXOTHERMIC WELD
CONNECTION
THERMOWELD #CS-6.
VERIFY ADDITIONAL
REQUIREMENTS AT
JOBSITE
1/2" MINIMUM RE-BAR IN
CONCRETE FOOTING IN
DIRECT CONTACT WITH
EARTH
EXOTHERMIC WELD CONNECTION
THERMOWELD #CRE-2. VERIFY
ADDITIONAL REQUIREMENTS AT JOBSITE
EXOTHERMIC WELD CONNECTION
THERMOWELD #CC-6. VERIFY
ADDITIONAL REQUIREMENTS AT JOBSITE
STRUCTURAL
STEEL
SERVICE GROUNDING DETAIL
NO SCALE
NOTE: INSTALL GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH THE NEC
ARTICLE 250. GROUNDING ELECTRODE CONDUCTOR SIZE SHALL BE AS INDICATED ON
THE ELECTRICAL RISER DIAGRAM. BONDING JUMPERS SHALL BE THE SAME SIZE AS
THE GROUNDING CONDUCTORS.
PANEL
"HSA"
ELECTRICAL RISER DIAGRAM
NO SCALE
T
F100
M
M
NEW
EXISTING
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
SHEET NUMBER
SHEET NAME
NO. DATE DESCRIPTION
DRAWN BY:
BELL FARMS PID
RETAINING WALL
PROJECT
CONSTRUCTION
DOCUMENTS
BRW
E002
ELECTRICAL
DETAILS
REESE WRIGHT
79805
S
TA
ET OF TE
AX
S
P R O
FESS IONAL ENG
IN
E
E R
R
EG I S TERED
12/11/25
TYPE VOLTAGE MOUNTING MANUFACTURER MODEL NO. LAMPS
DELIVERED
LUMENS INPUT WATTS NOTES
A 480 POLE INVUE MSA-SA1B-830-U-5MQ-BK-MS/DIM-L20 LED 5000 44 VA 1
LIGHT FIXTURE SCHEDULE
1 PROVIDE WITH A 12’ ROUND STEEL POLE IN FINISH TO MATCH THE FIXTURE.
LIGHT FIXTURE NOTES
A ALL SUBSTITUTED LIGHT FIXTURES ARE SUBJECT TO APPROVAL BASED ON PERFORMANCE, CONSTRUCTION, SHAPE, OVERALL DIMENSIONS, AND AESTHETIC LOOK BASED ON THE STANDARD SET IN THE SPECIFIED FIXTURE. THE ENGINEER AND THE ARCHITECT RESERVE THE RIGHT TO REJECT ANY FIXTURE BASED ON ONE OR MULTIPLE FEATURES LISTED ABOVE. PRIOR APPROVAL WILL NOT BE GRANTED FOR ANY SUBSTITUTE FIXTURE TYPE. ALL SUBSITUTE FIXTURE TYPES WILL BE SUBJECT TO APPROVAL BY THE ENGINEER OR ARCHITECT.
LIGHT FIXTURE GENERAL NOTES
A VERIFY THE EXACT LOCATION OF ALL ELECTRICAL EQUIPMENT AT THE SITE.
B VERIFY ALL POWER COMPANY REQUIREMENTS WITH THE POWER COMPANY PRIOR TO BID. INCLUDE ALL POWER
COMPANY SERVICES COSTS IN THE ELECTRICAL BID NUMBER.
C VERIFY ALL ELECTRICAL SERVICE METERING REQUIREMENTS WITH THE POWER COMPANY. PROVIDE ALL LABOR AND MATERIALS NECESSARY TO PROVIDE THE METERING CONNECTIONS REQUIRED BY THE POWER COMPANY.
D WHERE FEEDER SIZES ARE NOT INDICATED, FEEDER SHALL MATCH THE ASSOCIATED OVERCURRENT PROTECTIVE
DEVICE AS INDICATED ON THE BRANCH CIRCUIT AND SERVICE CONDUCTOR SIZING SCHEDULE.
GENERAL NOTES
NOTES INDICATED BY " "
1 EXISTING 480/277 V UTILITY TRANSFORMER TO REMAIN AS EXISTING.
2 EXISTING FEEDER TO REMAIN.
3 EXISTING 60A-3P DISCONNECT SWITCH SERVING EXISTING IRRIGATION EQUIPMENT TO BE REMOVED. EXTEND AND RECONNECT EXISTING FEEDER TO NEW 60A-3P CIRCUIT BREAKER IN NEW PANEL “HSA”. RECONNECT AS EXISTING.
4 NEMA 4X STAINLESS STEEL ENCLOSURE WITH HINGED LOCKABLE DOOR, HOFFMAN WATERSHED OR EQUAL. SIZE AS
REQUIRED TO HOUSE EQUIPMENT INDICATED.
5 ANGLED STEEL SUPPORT STRUCTURE TO SUPPORT ENCLOSURE. ANCHOR STRUCTURE IN NEW CONCRETE PAD.
6 4" CONCRETE SLAB EXTEND 6" BEYOND THE ENCLOSURE DIMENSION.
7 PHOTOCELL MOUNTED ON TOP OF ENCLOSURE.
8 #1/0 GR. IN 1" CONDUIT TO GROUND ROD AND PAD REBAR.
9 CONTACTOR "C1". 30A-6P. CONTROL WITH TIMECLOCK AND PHOTOCELL AS DIRECTED BY THE OWNER.
10 EXISTING 480/277V, 3 PHASE SECONDARY SERVICE PEDESTAL TO REMAIN. VERIFY EXACT LOCATION AND EXISTING
CONDITIONS AT THE JOBSITE.
11 EXISTING DIRECT METER BASE TO BE RE-USED TO SERVE NEW PANEL “HPA”. COORDINATE ALL WORK WITH THE POWER
COMPANY.
1. EXTEND AND RECONNECT EXISTING FEEDER AS EXISTING.
2. ROUTE CIRCUIT THROUGH CONTACTOR "C1". PROVIDE #10 WIRING.
Notes:
Total Est. Demand: 30 A
Total Conn.: 37 A
Total Est. Demand: 24544 VA
EXTERIOR LIGHTING 572 VA 100.00% 572 VA Total Conn. Load: 30544 VA
EXISTING LOAD 30000 VA 80.00% 24000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 37 A 37 A 36 A
Total Load: 10272 VA 10272 VA 10000 VA
17 SPACE ONLY -- 1 -- -- 1 -- SPACE ONLY 18
15 SPACE ONLY -- 1 -- -- 1 -- SPACE ONLY 16
13 SPACE ONLY -- 1 -- -- 1 -- SPACE ONLY 14
11 SPACE ONLY -- 1 -- 10000 12
9 SPACE ONLY -- 1 -- 10000 10
7 SPACE ONLY -- 1 -- 10000
1 3 60 A EXISTING IRRIGATION EQUIP.
5 SPACE ONLY -- 1 -- -- 1 -- SPACE ONLY 6
3 286 0 4
EXTERIOR LIGHTING 20 A 2 2
286 0
2 20 A SPARE
CKT Circuit Description Trip Poles Notes
A B C A B C
Notes Poles Trip Circuit Description CKT
Notes:
Panel Space: 18
Enclosure: Type 1 inside Type 4X MCB Rating: 125 A
Mounting: Surface Wires: 4 Mains Rating: 125 A
Supply From: UTILITY TRANSFORMER Phases: 3 Mains Type: MCB
Volts: 480/277 Wye A.I.C. Rating: 14000
PANEL: "HSA"
1 4 3 r d
S t r e e t
APPROX. 450'
A
A
A
A
A
A
AA
A
A
A
A
A
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
HSA 1,3
CONCRETE BASE DETAIL
NO SCALE
BEARING DIMENSION TO BE
VERIFIED WITH
MANUFACTURER
HANDHOLE
GROUND LUG
1" MINIMUM NON-SHRINK
GROUT 2/WEEP HOLE
LEVELING NUT
AND WASHER
ANCHOR BOLTS BY
MANUFACTURER
GRADE
STUB AND CAP
ONE SPARE
CONDUIT AT EACH
POLE
4-#6 REINFORCEMENT
BARS VERTICAL
2'-0" DIA.
RIGID STEEL CONDUIT
PVC
CONDUIT
V E
R
IF
Y
60º ANGLE
STUB CONDUIT 6" ABOVE
FOOTING
ANCHOR BOLT
COVER
18" DIA #4 ROUND TIES
AT 12" O.C.
3000 PSI CONCRETE
NOTE: CONCRETE AND REINFORCEMENT BY GENERAL CONTRACTOR.
USE MANUFACTURER'S TEMPLATE TO POSITION ANCHOR BOLTS.
TYPICAL FOR FIXTURE TYPE(S) "??"
F O
R P
O L E
H E
IG
H
T
O
R L
E S
S
F O
R P
O L E
H E
IG
H
T G
R E
A T
E R
T H
A N
TEXAS LICENSED SURVEYING FIRM 100676-00
AND ASSOCIATES, INC.
LAND SURVEYORS
CIVIL ENGINEERS
PHONE: 806 / 763-5642
1601 AVENUE N
LUBBOCK, TEXAS 79401
FAX: 806 / 763-3891TEXAS REGISTERED ENGINEERING FIRM F-760
SHEET NUMBER
SHEET NAME
NO. DATE DESCRIPTION
DRAWN BY:
BELL FARMS PID
RETAINING WALL
PROJECT
CONSTRUCTION
DOCUMENTS
BRW
E101
Electrical Site Plan
REESE WRIGHT
79805
S
TA
ET OF TE
AX
S
P R O
FESS IONAL ENG
IN
E
E R
R
EG I S TERED
12/11/25
GENERAL NOTES
A IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR, SUB-CONTRACTORS, MANUFACTURERS AND SUPPLIERS TO ADHERE TO THE REQUIREMENTS OF THE FOLLOWING GENERAL NOTES. IF CONFLICT OCCURS, CONTACT A/E PRIOR TO
COMMENCEMENT OF WORK.
B EVERY EFFORT HAS BEEN MADE TO MAKE THESE DOCUMENTS CONCISE AND COORDINATED, TO DEFINE WORK IN THE MOST LOGICAL PLACE AND TO ELIMINATE REDUNDANCY. THE SCOPE OF WORK IS DEFINED THROUGHOUT THE ENTIRE SET OF DRAWINGS & SPECIFICATIONS AND IS NOT LIMITED TO JUST ONE SERIES OF DRAWINGS OR DIVISION OF SPECIFICATIONS.
REVIEW THE ENTIRE SET OF CONTRACT DOCUMENTS TO DETERMINE EACH CONTRACTOR'S SCOPE OF WORK. NO ADDITIONAL COST SHALL BE INCURRED BY THE OWNER FOR CONTRACTOR'S FAILURE TO UNDERSTAND THE FULL SCOPE OF
WORK. IF CONFLICT OCCURS, CONTACT A/E PRIOR TO COMMENCEMENT OF WORK.
C VERIFY THE EXACT LOCATION OF ALL EXISTING AND NEW UTILITIES AT THE SITE WITH THE UTILITY COMPANIES.
NOTES INDICATED BY "Ο"
1 APPROXIMATE LOCATION OF EXISTING TRANSFORMER, SECONDARY SERVICE PEDESTAL, AND NEW EQUIPMENT RACK.
VERIFY EXACT LOCATION AT THE JOBSITE. REFER TO THE ELECTRICAL RISER DIAGRAM.
NORTH
SCALE: 1" = 20'-0"
ELECTRICAL SITE PLAN
| Sheets and Views |
| -- COVER |
| C100.1 SITE DIMENSION PLAN |
| C300.1 SITE GRADING PLAN |
File details come from the government source that posted it. Updated .