75H71220R00032 Reponse to Questions.docx

DOCX document 13 KB Posted

Attached to
PIMC Pathology Dept. HVAC Repair
Solicitation number
75H71220R00032
Issued by

View the file

Other files

File Type Posted
path_duct.pdf PDF
Pict_4.jpg JPG image
Pict_1.jpg JPG image
Pict_2.jpg JPG image
Pict_3.jpg JPG image
255SP01-Layout2.pdf PDF
Solicitation Attach C. Wage Determination AZ20200031.pdf PDF
Solicitation Attach B. Provisions and Clauses.docx DOCX document
Solicitation Attach D. Appendix B-ASHRAE_Chart_HVAC_Life_Expectancy.pdf PDF
Solicitation Attach A. intro.docx DOCX document
Solicitation Attach D. Appendix A-Old design from 2006.pdf PDF
Solicitation Attach D. Performance Scope of Work.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

75H71220R00032

Response to Questions:

1. Is the Pathology lab at PIMC the type that requires a minimum humidity range?

PIMC wants 60% maximum humidity, so a sensor is needed for discharge air (inside humidity is already in place and is for feedback/control). Options for reheat of air to the room is a separate reversed compressor (for heat) or electric heat strips. The maximum amps for this system is 200 amps, the service is 208 V 3 phase.

2. Could you please give us an idea of what the existing exhaust fan capacity is and a mechanical plan layout of the facility?

We have multiple exhaust fans, about up to 5,000 CFM exhaust, but the main 3,000 CFM has pressure controls for flow to keep the building negative at 0.01 inches water column.