Questions and Answers.pdf
PDF 65 KB Posted
- Attached to
- Fire Alarm and Sprinkler System Service GIMC
- Solicitation number
- 75H71025Q00244
About this file
This Questions and Answers document provides clarification for the Gallup Indian Medical Center (GIMC) Fire Alarm and Sprinkler System Service solicitation (75H71025Q00244). The document addresses key inquiries from potential bidders, including the scope of work, system inventory, and submission requirements. Specific details include confirmation that the project involves testing fire alarm systems, fire sprinkler risers (wet, dry, anti-freeze, pre-action), fire pumps, and backflow preventers, with a requirement to comply with Joint Commission and National Fire Protection Association (NFPA) standards.
Bidders are directed to reference two attachments (Devices GIMC and Statement of Work) for comprehensive system details, and are instructed to submit an email proposal with a capability statement and quote. The current fire alarm system is monitored via phone lines, and no existing deficiencies were noted. Interested vendors must include the solicitation number 75H71025Q00244 in the email subject line when submitting their proposal. Past inspection reports will not be released, as they are maintained in-house by the department.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Sol_75H71025Q00244_Amd_0001.pdf | ||
| Devices GIMC .xlsx | XLSX spreadsheet | |
| Statement of Work.pdf | ||
| Sol_75H71025Q00244.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers
1. Can you please give me a full inventory of all items to be tested under this solicitation? I will need the quantity of Fire Alarm Systems (and devices tied to each system), Fire Sprinkler Risers (To Include wet, dry, anti freeze, pre-action), Fire Pumps & Backflow Preventers.
See attachment labeled Devices GIMC.
2. Verify the scope and volume of systems to be serviced
The scope is spelled out on the attachment labeled Statement of Work. Volume of systems see Devices GIMC.
3. Understand any recurring deficiencies or special conditions
No deficiencies at this time.
4. Ensure compliance with Joint Commission and NFPA standards
Compliance needs to meet in accordance with the Joint Commission and National Fire Protection Association. In order for the hospital to be accredited it has to meet those standards.
5. Can you also tell me if this fire alarm is currently being monitored? If so, is it using phone lines for monitoring, or a cell/radio dialer?
Alarm system is being monitored via phone lines.
6. Is email submission of our bid proposal acceptable?
An email submission with capability statement and quote reflecting the requirements needed in the Statement of Work. Please use 75H71025Q00244 in the subject line.
7. Past inspection reports?
Inspection reports are kept in-house. No release from the department.