This is an Amendment of Solicitation/Modification of Contract (SF30) and associated procurement documents for the Nambe Wastewater Treatment Plant Improvements project.
The Indian Health Service Division of Engineering Services (DES) in Seattle issued Solicitation 75H70126R00020 on July 6, 2026, as a 100% Indian Small Business Economic Enterprise (ISBEE) set-aside under NAICS code 237110 (Water and Sewer Line and Related Structures Construction). Amendment A00002, effective July 29, 2026, extends the proposal due date to August 11, 2026 at 2:00 PM PT, provides responses to 49 questions submitted by potential offerors, revises the price schedule in Section B, and updates Section J with revised wastewater treatment facility drawings. The construction project magnitude is anticipated between $1,000,000 and $5,000,000. Performance must begin within 10 days of award and be completed within 365 days. Performance and payment bonds are required within 10 days of award. The revised price schedule includes 15 line items covering mobilization/demobilization, two 25,000-gallon fiberglass reinforced tanks, three wastewater treatment units, 65 linear feet of 8" PVC sewer pipe, 80 linear feet of 2" PVC sewer force main, electrical and controls, one sewer manhole, 600 linear feet of chain link fencing, 150 linear feet of 1" water service line, yard hydrant, storm water pollution prevention plan, gravel cover, electrical service drop, earthwork, and dust control. Offers must acknowledge receipt of all amendments and are subject to 60 days of Government acceptance time. Invoices should be submitted to IHS Albuquerque Area Finance Office.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
SF30 CONTINUATION OF BLOCK NARRATIVE
SUMMARY OF CHANGES
Solicitation Number 75H70126R00020 is hereby amended to address the following:
1. Provide responses to questions submitted (8 pages)
2. Revise Section B to include a revised price schedule (1 page)
3. Extend the proposal due date to 11 August 2026 at 2:00PM. See revised SF1442.
4. Revise Section J to include:
a. B01 Attachment J01 WWT Improve Drawings Revised
NOTICE TO OFFERORS: Offerors must acknowledge receipt of any and all amendments by number and date on their cover letter in their offer or by submitting a signed copy of the SF30. All other terms and conditions remain unchanged.
END OF SUMMARY OF CHANGES
75H70126R00020 Nambe WTP Improvements
RFI Responses No. Question Response A00001 dated 7/17/26 1 Can the government provide a geotechnical report, or soil boring report, the for area that is to be excavated?
Will be helpful to know what we are digging into to reduce unknowns and bid with proper equipment.
IHS does not have a geotechnical survey.
2 Can the government provide detail drawings for pipe bedding, backfill requirements around treatment system, and structures? Special fill is referenced, but specifications are unknown.
For standard pipes and manholes the detailed drawings have been attached from the IHS standard blocks. For the wastewater treatment system, the detailed drawings for this will come from the vendor.
3 The access road appears to be coming through a residential area. Are there any special provisions needed to accommodate them (dust/noise/etc) or established hours for work traffic?
The access road will begin at a cul-de-sac, and public access to the road where the contractor will be working is not anticipated to be necessary. However, dust abatement measures will be required during the work.
5 Will the current livestock storage area near the property be occupied during the project (safety and security reasons)?
The livestock storage area will remain occupied during the project. IHS can reach out to the land owner and see if there is another place the animals can be kept during the project duration.
6 Will the chosen contractor need to bond any roads that could be impacted by the project. Are road closures, or lane reductions anticipated?
No bonding for roads will be required. We do not anticipate any road closures or lane reductions.
7 The project drawings specified PVC pipe for this project.
Would HDPE be an acceptable alternative?
HDPE pipe is an acceptable alternative but please note all alternatives will be addressed post award in the submittals.
8 As referenced in the RFP, we are unable to find the technical provisions. Supplemental Technical provisions are incorporated, but we cannot find Standard Technical Provisions in the RFP, or separate
See attachment J01c included in Amendment 1.
attachment of technical specifications. Screenshot below.
9 Are there any domestic requirements as BABA, AIS, or domestic preferences?
Refer to the solicitation clauses regarding Buy American requirements.
10 Sheet 5 has 305lf of 8” PVC and manholes A2 and A3. In which bid item # does this belong?
Manholes A2 and A3 are existing. Manhole A2A will be installed as part of the scope of the project and is associated with line item 8.
11 Sheets 11&12 have details for a diversion manhole with sluice gates. Which bid item does this belong and where on the plans are these located?
This belongs to bid item 8 and is the proposed manhole A2A. See sheets 5 and 6 of the plans.
12 Do you have any fence details, and there is no posted height for the fence on the plans?
See attachment J01c included in Amendment 1.
A00002 dated 7/29/26 13 Bid Item #2 Calls for 2 (two)- 35,000 Gallon Fiberglass
Reinforced Primary Tank - The statement of work states there are 2 (two) 25,000 gallon settlement tanks.
Removed from bid schedule. See revised price schedule in Section B.
14 Bid Item #3 Calls for 2- (two) 25,000 Gallon Fiberglass Reinforced Primary and Recirculation/Dosing Tank, please clarify
Correct item is two 25,000-gallon tank
15 Bid Item #4 calls for 8 (eight) Waste Water Treatment Units. The plans show 3 units. Please clarify
3 units. See revised price schedule in Section B.
16 Bid Item #16 - Please provide specifications for the Old Lagoon conversion. what size gravel?, how much gravel?
Does the sludge need to be removed from the lagoon?
Does the lagoon need a liner to be a percolation pond and hold up the gravel? Does the bottom of the lagoon need to be compacted to hold the gravel from sinking?
Do both cells of the lagoon require gravel? Does the outline of the lagoons need to be made square much like a standard lagoon?
This item will be removed from project. See revised price schedule in Section B.
17 In our experience, line extension fees are normally by the Owner as they will receive a metered service from PNM and an account. The fees then become part of the total construction budget for the Owner. Is the contractor to include line extension fees in their proposal? The cost of the line extension may be difficult to obtain from PNM in a timely manner.
Line extension fees by owner. Line extension fees should not be included in proposal.
18 The Access Road lacks specification and profile. Will the following specification suffice:?
���������� Subgrade Preparation & Compaction
• Subgrade Excavation: Proof-roll the exposed native soil subgrade using a heavy vibratory roller to identify soft spots or unstable soils.
• Moisture Conditioning: Scarify the top 6 inches of subgrade, moisture-condition to within ±2% of optimum moisture content, and compact to a minimum of 95% Maximum Dry Density (MDD) per ASTM D1557 (Modified Proctor).
Yes. Access road needs to be built to support a loaded septic pump truck.
• Geotextile Separation: Lay a high-survivability geotextile stabilization fabric (such as Mirafi 140N or equivalent) directly over the prepared subgrade to prevent the migration of native silts into the gravel base. [1]
������� Aggregates & Surfacing Materials
• Base Course Layer: Install a minimum 6-inch compacted thickness of Crushed Aggregate Base Course (CABC) conforming to New Mexico Department of Transportation (NMDOT) Class I or Class II specifications.
• Surface Aggregate Layer: Top with a 2-to-3-inch compacted layer of open-graded gravel or driving aggregate to provide a weather-resistant, non-slip surface for maintenance vehicles.
• Final Compaction: Compact the aggregate layers to a minimum of 95% MDD to withstand regular high-wheel loading from utility trucks.
� Drainage & Civil Profile
• Cross Slope: Maintain a 2% crown or uniform cross-slope shedding away from the parallel utility lines to avoid water ponding on the driving surface.
• Utility Parallelism: The roadbed runs directly parallel to the underlying civil utility layout, which features 65 linear feet of 8-inch PVC sewer pipe and 80 linear feet of 2-inch sewer force main.
Heavy equipment routing must preserve the integrity of these deep buried assets.
• Erosion Control: Implement roadside drainage swales lined with rock rip-rap where grades https://urldefense.us/v3/__https:/www.santafecountynm.gov/userfiles/AAEngRpt10b.pdf__;!!Og_tST9LxTiQE1I!oaatcpH3WN___NXld7G9ZsjLOvNAxsjF8-Ost53f7HnFfylwfotT8AB9ps7Q7qYb464Q4MqDQhjgWq6_uSFgO0esTlJhBvf8mwDA2w$ exceed 5% to prevent monsoon runoff from undercutting the gravel shoulders. [1, 2]
19 Drawing 9 of 12 shows an 8 x 10 shed. There are no specifications for this shed. Does the Owner want a metal or wood constructed shed with a metal roof. Does the shed need a floor? Please advise.
A prefab 8x10 shed, metal. 12x14 reinforced, 6”-thick concrete pad required. Rebar to be #3, 18” O.C.
Compacted 6” road base (3/4” crusher fines) to be installed under concrete pad, compacted to 95% standard proctor density.
20 We are assuming that the interconnecting piping between the waste processing units is a pumped waste.
There is no technical specification calling out the required pipe type. Our experience is that the interconnecting piping between the filtration units will be PVC Schedule 80 with solvent weld fittings and flanges. Also, we are assuming service valves at each POC. Please advise.
This is correct.
21 We are assuming that water and land for the construction of the WWT at Lagoon #4 will be provided at no charge. Is this assumption correct? Also please clarify that a backflow and meter must be provided by the contractor for this project.
Lagoon rehab to be removed from project.
Contractor to provide backflow and meter.
22 What size gate will the Owner require in the chain link fence?
14’ to match access road. Install double-leaf swing gate (two 7’ leaves)
23 Is reclamation seeding required? No 24 Since there is no geotechnical report for this site, can all bidders assume compaction can be obtained with native soils and there is no overabundance of subsurface rock/boulders that could inhibit digging?
Correct
25 Please confirm the local TERO percentages No TERO in Nambe 26 Can all spoils be used to balance site, and if spoils from existing lagoons are needed to be trucked offsite, how Spoils can be used if compaction can be attained.
Proctor test required.
https://urldefense.us/v3/__https:/nooksacktribe.org/wp-content/uploads/2025/11/IHS-Application-2016_.pdf__;!!Og_tST9LxTiQE1I!oaatcpH3WN___NXld7G9ZsjLOvNAxsjF8-Ost53f7HnFfylwfotT8AB9ps7Q7qYb464Q4MqDQhjgWq6_uSFgO0esTlJhBvebezNagg$ https://urldefense.us/v3/__https:/sam.gov/workspace/contract/opp/987d19c343194c57a468f3c5a57d635d/view__;!!Og_tST9LxTiQE1I!oaatcpH3WN___NXld7G9ZsjLOvNAxsjF8-Ost53f7HnFfylwfotT8AB9ps7Q7qYb464Q4MqDQhjgWq6_uSFgO0esTlJhBvfimR1rMQ$ will that be handled as it will probably contain sewage (testing, manifesting, etc). Is there a preferred disposal site the tribe/government wishes to use?
If there are extra spoils after site balancing, they can be deposited on/near project site.
27 Please confirm the need, size, area for the access roads to access the existing lagoons
Access road to existing lagoon no longer needed since lagoon will not be rehabbed in this contract.
28 What is the design for the gravel in the existing lagoons?
IS there a plan in case the lagoons are too soft and will just "swallow" the gravel once placed?
No longer part of project.
29 Please confirm location of power source for site, or will we be required to run generators as power lines are underground.
Generators will be required.
30 Can you create a separate line item for dust control See revised price schedule in Section B.
31 There are no bid items for borrow or import. Is all earthwork to be provided from within the project site as a balanced fill or is any import material expected and borrow site to be determined? Please confirm.
Quantities should be close to balanced from sitework.
However Nambe Pueblo does have a borrow pit. It is located past the buffalo range near the water tank
32 It is our understanding at pre-bid meeting that all clear and grubbing material can remain on site. Please confirm.
Correct
33 It was also discussed all staging areas can be done on project site. Please confirm.
Correct.
34 Announcement states 10’ x10’ pad in scope of work, but plans show only a concrete pad for yard hydrant is 3’ x3’.
Is this the same pad? Please confirm.
It is a 10x10 gravel pad with a 3x3 concrete pad around the hydrant. Standard detail shows the gravel as 5x10, but this is incorrect. 10x10 gravel is correct.
35 Bid item 13 - Gravel pad, is 10’ x10’ on plans. Is there any other gravel cover to be included to the project site or access road?
Access road to have gravel cover as referenced in question #18
36 The existing MH-A3 to be converted to a Diversion MH is showing two existing 8” PVC sewer lines coming into existing MH-A3. Also adding 33’ of 8” PVC connected from same MH to the new proposed tanks. This isn’t
Correct. Core for new 8” line to proposed tanks, and install new MH-A2A at elevation shown on existing line clear or consistent with detail on sheet II detail for a new Diversion MH. Is diversion MH to be cored for new 8” PVC discharge to new tanks and existing sewer line continuing to new MH-A2A to remain? Please clarify.
37 Plans show 33’ and 26’ for total of 59’ sewer line. Bid quantity is for 65’? Is there more footage not shown?
Please confirm.
59’ is correct, but 65’ was put on the bid sheet to account for any extra sewer line needed.
38 Plans show 210’ of 1” water service and bid quantity is 150 LF. Please confirm.
210 is correct.
39 On sheet 12, the Yard hydrant detail shows a 3’ x 3’ concrete pad with 10’ x10’ gravel pad around it. The project Bid Announcement states 10’ x10’ concrete pad.
Please confirm.
The detail drawing is correct. 10’x10’ gravel pad with a 3’x3’ concrete pad for the yard hydrant.
40 Is this the same gravel cover on Bid item #13 shown on the yard hydrant detail which includes a10’ x 10’ gravel surround? Are there any other gravel areas expected on the project site or access road?
The gravel is the same throughout.
41 Grading contours on plan do not have a final grade elevation for site or grading for access road. Please confirm Finish grade elevations for site.
Elevations labels added. See revised drawings.
42 Will final grade elevations require any manhole rim elevations to change or modified to accommodate the final grade change? Currently all existing and new MH are at all varying rim elevations. MH-A3 has two different rim elevations on sheet 6. Please confirm.
Correct MH-A3 rim elevation = 6107.50. Drawing corrected.
43 Will the wastewater treatment system be set on top of final grade, and no pad work or grading around I to be required? Please confirm.
Correct. For example, see Orenco AX-MAX brochure:
https://odl.orenco.com/documents/AdvanTexAX- Max_Brochure_Orenco_NBR-ATX-AXM-1.pdf
44 There is no detail or site confirmation of the access road (or option) shown on plans. Will there be any further details (length, grading, width, soil compaction, etc. or
Include with earthwork bid item #14. Access road needs to be built to support a loaded septic pump truck and follow general layout on plans from cul de sac.
https://odl.orenco.com/documents/AdvanTexAX-Max_Brochure_Orenco_NBR-ATX-AXM-1.pdf https://odl.orenco.com/documents/AdvanTexAX-Max_Brochure_Orenco_NBR-ATX-AXM-1.pdf other requirements? Is this work to be included with earthwork bid item #15 or an added bid item? Please clarify.
45 Details on sheets 11 and 12 include both a fiberglass slide gate and aluminum sluice gate detail. Which is to be used in this project? Also are gates and associated rework, i.e. the manhole modifications, sloped benches toward channels, etc. to be completed and to be included in which bid item or scope of work? Please clarify.
Use sluice gate.
46 Bid item #6 includes 80 feet of2” PVC sewer force main.
Do not see this on plan, where is this located or to be installed?
Sheet 9 – 2” FM from secondary tank to treatment pods.
80’ is approximate distance from tank to treatment pods.
Please provide clarification on bid tabulation sheet (Line 2,3,4) as the quantities specified don't match the number of units to be installed.
- OR please describe what goes on what line item.
See revised price schedule in Section B.
48 Can you please give more specifics of the AX-Max Treatment system, Flow Rates, and the sizes/setup that is being asked of the contractors.
Must be able to treat up to 20,000 GPD. The AX-MAX is the preferred system since the tribe already has these systems elsewhere, but contractor must submit for approval.
49 Please provide specificity on the controller units and requirements.
Use manufacturer’s recommendations for required electrical controls for treatment system.
SF30 CONTINUATION OF BLOCK NARRATIVE
SECTION B – SUPPLIES OR SERVICES AND PRICES/COSTS
IMPORTANT INFORMATION:
Under no circumstances will any oral statements made be binding upon the Government unless such statements or agreements are issued in writing by the Contracting Officer.
Only a warranted Contracting Officer acting within their delegated limits has the authority to issue modifications or otherwise change the terms and conditions of this contract. If an individual other than the Contracting Officer attempts to make changes to the terms and conditions of this contract, you shall not proceed within the change and shall immediately notify the Contracting Officer.
B.1. PRICE SCHEDULE
Bid Item Description Units Quantity Unit Cost Total Cost 1 Mobilization/Demobilization LS 1 $ -
2 25,000 Gallon Fiberglass Reinforced Primary and Recirculation/Dosing Tank
EA 2 $ -
3 Wastewater Treatment Units EA 3 $ -
4 8" PVC Sewer Pipe LF 65 $ -
5 2" PVC Sewer Force Main LF 80 $ -
6 Water Reclamation Facility Electrical and Controls
LS 1 $ -
7 Sewer Manhole EA 1 $ - 8 Chain Link Fencing LF 600 $ - 9 1" Water Service Line, incl tee LF 150 $ - 10 Yard Hydrant EA 1 $ -
11 Storm Water Pollution Prevention Plan
LS 1 $ -
12 Gravel Cover LS 1 $ - 13 Electrical Service Drop EA 1 $ -
14 Earthwork LS 1 $ - 15 Dust Control LS 1 $ -
Proposal Total: $ -
(See ).
SOLICITATION, OFFER,
AND AWARD
(Construction, Alteration, or Repair) IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.
9. FOR
INFORMATION CALL:
NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid and "bidder".
SOLICITATION
1. SOLICITATION NUMBER
5. REQUISITION/PURCHASE REQUEST NUMBER
CODE
6. PROJECT NUMBER
8. ADDRESS OFFER TO
4. CONTRACT NUMBER
7. ISSUED BY
10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS (Title, identifying number, date)
11. The contractor shall begin performance within
12a. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?
(If "YES", indicate within how many calendar days after award in Item 12b.)
13. ADDITIONAL SOLICITATION REQUIREMENTS:
a. Sealed offers in original and
b. An offer guarantee
c. All offers are subject to the (1) work requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.
d. Offers providing less than
STANDARD FORM 1442 (REV. 12/2022)
Prescribed by GSA - FAR (48 CFR) 53.236-1(d) calendar days for Government acceptance after the date offers are due will not be considered and will be rejected.
is, is not required.
local time containing offers shall be marked to show the offeror's name and address, the solicitation number, and the date and time offers are due.
(date). If this is a sealed bid solicitation, offers will be publicly opened at that time. Sealed envelopes copies to perform the work required are due at the place specified in Item 8 by (hour) award, YES NO notice to proceed. This performance period is mandatory negotiable.
calendar days and complete it within calendar days after receiving
a. NAME b. TELEPHONE NUMBER (Include area code) (NO COLLECT CALLS)
12b. CALENDAR DAYS
2. TYPE OF SOLICITATION
SEALED BID (IFB)
INVITATION FOR BID
NEGOTIATED (RFP)
REQUEST FOR PROPOSAL
3. DATE ISSUED PAGE OF PAGES
75H70126R00020
Indian Health Service Division of Engineering Services (DES) - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104
Project: Nambe Wastewater Treatment Plant Improvements
Project No: AL 17-A78
See Section L for Proposal Submittal Instructions and Site Visit Information.
This project will be procured as a 100% Indian Small Business Economic Enterprise (ISBEE) set-aside under North American Industry Classification System (NAICS) code 237110, Water and Sewer Line and Related Structures Construction. The associated size standard for this procurement is $45 million.
CONSTRUCTION MAGNITUDE: The magnitude of this construction project is anticipated to be between $1,000,000 and $5,000,000.
Indian Health Service Division of Engineering Services (DES) - Seattle Attn: Taylor Kanthack 701 5th Ave Seattle, WA 98104
Taylor Kanthack taylor.kanthack@ihs.gov 240-478-1501 see box 10
1 52
8/11/2026
2:00PM PT
10 Days after award
Section F.2
7/6/26
AWARD (To be completed by Government)
17. The offeror agrees to perform the work required at the prices specified below in strict accordance with the terms of this solicitation, if this offer is accepted calendar days after the date offers are due. (Insert any number equal to or greater than the minimum requirement by the Government in writing within stated in Item 13d. Failure to insert any number means the offeror accepts the minimum in Item 13d.)
OFFER (Must be fully completed by offeror)
AMOUNTS
18. The offeror agrees to furnish any required performance and payment bonds.
19. ACKNOWLEDGMENT OF AMENDMENTS
(The offeror acknowledges receipt of amendments to the solicitation -- give number and date of each)
AMENDMENT
NUMBER
DATE
CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE
14. NAME AND ADDRESS OF OFFEROR (Include ZIP Code)
CODE FACILITY CODE
15. TELEPHONE NUMBER (Include area code)
16. REMITTANCE ADDRESS (Include only if different than Item 14.)
20a. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN OFFER (Type or print)
21. ITEMS ACCEPTED:
22. AMOUNT
26. ADMINISTERED BY
30a. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED TO SIGN (Type or print)
31c. DATE
STANDARD FORM 1442 (REV. 12/2022) BACK
31b. UNITED STATES OF AMERICA
BY
31a. NAME OF CONTRACTING OFFICER (Type or print)
29. AWARD (Contractor is not required to sign this document.) Your offer on this solicitation is hereby accepted as to the items listed. This award consummates the contract, which consists of (a) the Government solicitation and your offer, and (b) this contract award. No further contractual document is necessary.
30b. SIGNATURE 30c. DATE
28. NEGOTIATED AGREEMENT (Contractor is required to sign this document and return and deliver all items or perform all work requirements identified on this form and any continuation sheets for the consideration stated in this contract. The rights and obligations of the parties to this contract shall be governed by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certifications, and specifications incorporated by reference in or attached to this contract.
copies to issuing office.) Contractor agrees to furnish
24. SUBMIT INVOICES TO ADDRESS SHOWN IN
(4 copies unless otherwise specified)
23. ACCOUNTING AND APPROPRIATION DATA
ITEM
25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO THE UNITED STATES
CODE AT
27. PAYMENT WILL BE MADE BY
10 U.S.C. 3204(a) ( ) 41 U.S.C. 3304(a) ( )
20b. SIGNATURE 20c. OFFER DATE
B.3
Indian Health Service, DES - Seattle 701 5th Ave, Suite 1600 Seattle, WA 98104
IHS Albuquerque Area Attn: Finance Office 4101 Indian School Rd NE Suite 225 Albuquerque, NM 87110-3988
| ADPAA4.tmp |
| END OF SUMMARY OF CHANGES |
| SECTION C – DESCRIPTION/SPECIFICATIONS/STATEMENT OF WORK |
| 1. Project Description |
| 3. Submittals |
| 4. Schedule/Meetings |
| 5. Miscellaneous |
| a. |
| b. |
| c. |
| d. |
| e. |
| f. |
| 6. Payments to the Contractor |
| 7. IHS Personnel |
| 8. Invoice Format |
| 9. Closeout Documents |
| SECTION F – DELIVERIES OR PERFORMANCE |
| ADP6CB2.tmp |
| END OF SUMMARY OF CHANGES |
| ADP4682.tmp |
| END OF SUMMARY OF CHANGES |
| 1. Project Description |
| 3. Submittals |
| 4. Schedule/Meetings |
| 5. Miscellaneous |
| ADPAB4E.tmp |
| Proposals must set forth full, accurate, and complete information as required by this request for proposal (including Gres). The penalty for making false statements in proposals is prescribed in 18 U.S.C. 1001. |
| SECTION B – SUPPLIES OR SERVICES AND PRICES/COSTS |
| SECTION C – DESCRIPTION/SPECIFICATIONS/STATEMENT OF WORK |
| 1. |
| 2. |
| 3. |
| 4. |
| 5. |
| 6. |
| SECTION D – PACKAGING AND MARKING |
| SECTION E – INSPECTION AND ACCEPTANCE |
| SECTION F – DELIVERIES OR PERFORMANCE |
| SECTION G – CONTRACT ADMINISTRATION DATA |
| SECTION H – SPECIAL CONTRACT REQUIREMENTS |
| SECTION I – CONTRACT CLAUSES |
| SECTION J – LIST OF ATTACHMENTS |
| SECTION K – REPRESENTATIONS, CERTIFICATIONS, AND OTHER STATEMENTS OF OFFERORS |
| SECTION L – INSTRUCTIONS, CONDITIONS, & NOTICES TO OFFERORS |
| FACTOR 2: PAST PERFORMANCE |
| SECTION M – EVALUATION FACTORS FOR AWARD |
| FACTOR 2: Past Performance |
| ADP70C9.tmp |
| END OF SUMMARY OF CHANGES |
| ADPC8A0.tmp |
| END OF SUMMARY OF CHANGES |
| SECTION B – SUPPLIES OR SERVICES AND PRICES/COSTS |
| topmostSubform[0]: |
| Page1[0]: |
| AmendmentNo[0]: A00002 |
| Code[0]: |
| Code[1]: |
| AccountingData[0]: |
| A13[0]: |
| C13[0]: |
| D13[0]: |
| NameandTitleSigner[0]: |
| NameandTitleOfficer[0]: Taylor M. Kanthack |
| Description[0]: See continuation page. |
| FacilityCode[0]: |
| Code[2]: |
| IssuedBy[0]: Indian Health Service (IHS) |
Division of Engineering Services (DES) - Seattle 701 5th Ave, Suite 1650 Seattle, WA 98104
| NameandAddress[0]: |
| AdministeredBy[0]: See item 6 |
| ContractIDCode[0]: |
| ReqNumber[0]: |
| AmendmentNo[1]: 75H70126R00020 |
| ProjectNo[0]: |
| Page[0]: 1 |
| Pages[0]: 13 |
| EffectiveDate[0]: 7/29/2026 |
| Dated9B[0]: 7/6/2026 |
| Dated10B[0]: |
| CheckBox9[0]: 1 |
| CheckBox10[0]: Off |
| CheckBox11[0]: 1 |
| CheckBox13A[0]: Off |
| CheckBox13B[0]: Off |
| CheckBox13C[0]: Off |
| CheckBox13D[0]: Off |
| IsNot[0]: 1 |
| Is[0]: Off |
| Extended[0]: 1 |
| NotExtended[0]: Off |
| DateSigned[0]: |
| DateSigned[1]: |
| Copies[0]: |
| CopiesReturned[0]: |
File details come from the government source that posted it. Updated .