751/21267. JAG; Wolf Lake SFH - Electrical Dist. Upgrades
Solicitation number
RFQ - 171 - 220000000395
Issued by
Kent County, Muskegon City, Michigan

About this file

This document is Addendum No. 2 for the Wolf Lake Fish Hatchery - Electrical Distribution Upgrades project, File #751.21267.JAG, issued by the State of Michigan. The addendum provides clarifications and responses to questions regarding the project, including requirements for the temporary power generator, medium voltage cable sizes, transformer pad replacements, and usage of precast concrete vaults or pads.

The related state and local contract opportunity is for the Wolf Lake SFH - Electrical Dist. Upgrades project, Contract #751/21267.JAG, located in Kent County and Muskegon City, Michigan. The project involves electrical distribution upgrades, and all questions should be emailed to Joel Gordon. Bid attachments must be uploaded to SIGMA VSS, and the deadline for submission is 2:00 p.m. COVID-19 precautions may require bidders to wear masks when attending meetings.

View the file

Other files

File Type Posted
Mich Spec 21267.pdf PDF
Drawings 21267.pdf PDF
751.21267.JAG _Addendum No 1.pdf PDF
Advertisement 21267.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1601 E. CÉSAR E. CHÁVEZ AVENUE, LANSING, MI 48906

PHONE: (517) 487-2511

FAX: (517) 487-2544

ADDENDUM NO. 2

Date: 06/27/22 Project Name: Wolf Lake Fish Hatchery – Electrical Distribution Upgrades File # 751.21267.JAG Unit Code # 4290

This Addendum is issued for the purpose of modifying and/or clarifying the original Contract Documents and shall take precedence over them.

All work included herein shall be in accordance with the original drawings and specifications except as specifically noted herein. All incidental items required to provide the following modifications shall be included even though not specifically described.

This addendum is being sent to all bidders receiving plans and specifications. Receipt of this Addendum shall be noted on the Bid Summary in the appropriate location.

Clarification and Questions:

A1.1 Temporary Power Clarification: Contractor shall provide a generator capable of running

(1) 100HP motor during required outages.

A1.2 Question: The spec calls out 24.9kV and 14.9kV both. Please confirm that it is 24.9kV.

Response: 24,920V.

A1.3 Question: Both expulsion and current limiting fuses are in the spec, which ones are wanted? Response: Current limiting fuses.

A1.4 Question: Surge arrestors. They mention disconnect and elbow mounted. They should be disconnect mounted on the incoming line side, correct? Response: Correct.

A1.5 Question: Please confirm the existing MV cable sizes for proper lineup sizing. Response:

(3) #4/0 25kV MV-105 cables.

A1.6 Question: Please confirm that replacement on the existing pads is the intent for the one-for-one transformer replacements or if new pads are required? Response: Provide all new concrete pad(s).

A1.7 Question: Will a new pad or vault be required when replacing existing MV switch S4 with new MV switch S5? Response: Contractor shall provide new concrete pad as required for the installation of the new switch.

ADDENDUM NO. 1

A1.8 Question: Are we using the pre-cast concrete vault detail shown on E-8.0 under all new MV switchgear locations or will some use the concrete pad detail? Response: Contractor shall provide precast concrete or concrete pad.

A1.9 Question: Can a fiberglass box pad be used in lieu of a precast concrete vault or concrete pad? Response: Contractor shall provide precast concrete or concrete pad.

End of Addendum #2